HomeMy WebLinkAboutWTR2703554.2CONCRETE BLOCKING SIZING PROCEDURE A. GENERAL THE AMOUNT OF CONCRETE REQUIRED TO ANCHOR HORIZONTAL BENDS, TEES, AND DEAD ENDS DEPENDS ON THE STRENGTH OF THE SOIL. THE METHODS OF PLACING CONCRETE TO KEEP THE JOINT ACCESSIBLE IS SHOWN IN FIGURE 1, THE AREA IN SQUARE FEET OF CONCRETE WHICH MUST BEAR AGAINST THE SIDE OF THE TRENCH IS FOUND BY DIVIDING THE THRUST IN POUNDS SHOWN IN TABLE 1 BY THE SAFE BEARING LOAD OF THE SOIL AS SHOWN IN TABLE 2. B. CRITERIA 1. THE SIZING PROCEDURE IS FOR HORIZONTAL OR DOWNWARD THRUST ONLY. 2. HEIGHT OF THE THRUST BLOCK MUST BE EQUAL TO OR LESS THAN 1/2 THE DEPTH FROM THE GROUND SURFACE -0 THE BLOCK BASE. 3. THE THRUST BLOCK BEARING FACE IS APPROXIMATELY RECTANGULAR. 4. THE CONCRETE BLOCKING SHALL BE AS PER APWA SPECIFICATION 74-2.14. C. SYMBOLS D = OUTSIDE DIAMETER OF PIPE IN FEET T = THRUST IN POUNDS AT THE FITTING (TABLE 1) SBL = SAFE BEARING LOAD IN POUNDS/SQ. FT. (TABLE 2) H = DEPTH OF TRENCH IN FEET W = WIDTH OF TRENCH IN FEET A = AREA OF CONCRETE WHICH MUST BEAR AGAINST THE SIDE OF THE TRENCH IN SO. FT. HM = MAXIMUM HEIGHT OF THE THRUST BLOCK IN FEET DC = DEPTH OF THE CONCRETE THRUST BLOCK TO BEARING SURFACE IN FEET LM = MAXIMUM LENGTH OF THE THRUST BLOCK IN FEET GROUND SURFACE h �d Hm h - 2 + BLOCK BASE DC W D. CALCULATION EQUATIONS 1. Area of Concrete (A) = Thrust (In Pounds = T Safe Bearing Load (In Pounds/Sq. Ft.) SBL 2. Maximum Height of Thrust Block (Hm) = Depth of Trench in Feet = h 2 2 (Width of Trench in Feet) - 3. Depth of Concrete Thrust Block = (Outside Diameter of Pipe in Feet) - W-d 2 2 4. Maximum Length of Thrust Block (Lm) - Area of Concrete = A Maximum Height Hm 5. Required Amount of Concrete (Cu. Yd.) = (Height x Depth x Length) x 0.03704 - (Hm x Lm x Dc) x 0.03704 E. EXAMPLE 1. Problem: Calculation of the amount of concrete required to block a 90` bend in an 8" C.I. water main; the normal operating pressure in the pipe will be 65 psi and the soil condition in the area indicates sand and gravel. 2. Solution: - Maximum testing pressure (See Table 1) = 300 psi. - Outside diameter of 8" pipe = 9.05 in. = 9.05/' 2 - Go to Table 1: The testing pressure of 300 psi, we see that the thrust on a 90' bend is 21,360 pounds. CAP TEE 22-1/2' 45' BEND - Go to Table 2: Table 2 gives the safe bearing load for sand and gravel: 3,000 lbs./sq. ft. - Go to Figure 1: figure 1 indicates the position of the concrete for blocking the 90' bend. - Go to the specifications of the project and find depth of trench (h) = 4 feet - Width of trench (W) = 3 feet With the above assembled information, we proceed to the final calculations: - Area of Concrete (A) = Thrust = 21,360 = 7.12 sq ft. Safe Bearing Load 3,000 Depth of Trench in Feet - Maximum Height of Thrust Block (Hm) _ _ h _ 4 _ 2 - 2 - 2 - 2.0 ft. Depth of Concrete Thrust Block (Dc) Width of Trench in Feet (W) - Outside Diameter of PIN (d - = - 3 0.75 1.13 ft. 2 - 2 Area of Concrete - Maximum Length of Thrust Block (Lm) _ Height of Concrete = A = 7.12 = 3.56 ft. Hm 2.0 - Required Amount of Concrete = (Height x Depth x Length) x 0.03704 _ (Hm x Lm x Dc) x 0.03704 2.0 x 3.56 x 1.13) x 0.03704 = 0.30 cu. yd. TABLE 1 Size Pressure PSI Thrust at Fittings in Pounds Tees 90° 45' 22-1 /2" 11-1 /4" Dead Ends Bend Bend Bend Bend 3" 300 2,120 3,000 1,630 830 430 4" 300 3,780 5,370 2,910 1,470 750 6" 300 8,500 12,000 6,510 3,320 1,700 8" 300 15,100 21,360 11,550 5,880 3,020 10" 275 21,620 30,570 16,540 8,430 4,330 12" 250 33,930 48,000 25,950 13,260 6,780 14" 250 46,200 65,370 35,340 18,030 9,240 16" 225 45,250 64,000 34,620 17,650 9,050 18" 200 50,900 72,000 38,940 19,860 10,180 20" 200 62,840 88,900 48,080 24,520 12,560 24" 200 90,480 127,980 69,200 35,320 18,100 30" 200 141,370 199,960 108,150 55,140 28,280 36" 200 203,580 287,950 155,740 79,400 40,720 TABLE 2 Safe Bearing Loads in Lb./Sq. Ft. The safe bearing loads given in the following table are for horizontal thrusts when the depth of cover over the pipe exceeds 2 feet. Safe Bearing Load SOIL Lb. per So. Ft. *Muck, peat, etc. 0 Soft Clay 1,000 Sand 2,000 Sand and Gravel 3,000 Sand and Gravel Cemented with Clay 4,000 Hard Shale 10,000 *In muck or peat, all thrusts shall be restrained by piles or tie rods to solid foundations or by removal of muck or peat and replacement with ballast of sufficient stability to resist thrusts. FIGURE 1 NOTE: FOR CONVEX VERTICAL BENDS BLOCKING SEE APWA STANDARD PLAN NO. 73. 90' BEND 3/4" SQUARES AS INDICATED - RAISE-1 /2" WIDE BORDER 10" 9„ 8-3/4" 5/8" 1- 1/4" 1/2" -1 2" 3 4" _T 8" N CAST IRON RING AND COVER 2'- 0 " CONCRETE CLASS 3000 12"o FIBER JOINT PACKING 45° (1/8) BEND z EJE „A„ nC DClll IIDCfI WOOD BLOCKING CASING DETAIL A PIPE SIZES B CASING SIZES CASING WALL THICKNESS 6" 12" 1/4" 8" 16" 1/4" 10" 20" 1/4" 12" 24" 1/4" 14" 28" 1/4" 16" 32" 1/4" NOTE: NYLON PIPE SPACERS MAY BE USED IN LIEU OF WOOD BLOCKING SECTION A -A )NC. END SEAL EX CPLG. SING PIPE "B" 0 STD. STEEL PIPE "B" STD. WALL STEEL CASING PIPE PIPE FLANGE STAINLESS STEEL BAND AS SPECIFIED FOR EACH LENGTH OF BLOCKING MAX. SPACING 8 FEET. WOOD BLOCKING SHALL BE CONTINUOUS EXCEPT AT JOINTS NTS NTS Clean Out 3 Pipe Casing 7 NTS 10 Blocking Sizing Procedure 1 1 0 W=355402 C. �r. 14 ���sS7pNAL *Z)ID Z O H Q O JZ Oce W =OzN V Z w o to Q a m =Zf; 00 =~sue ZOoW UJ O O H N Q J c.i NO. DATE REVISION 12/11/09 PERMIT SET SHFFT TITI.F UTILITY DETAILS 12 C090125-02 JOB NO.: SSN DRAWN: DARDS SLG CHECKED: 4/12/10 DATE: SHEET NUMBER: C6ml Z 0- 0 G\ Q o� M ry) O ' t' `r CL re) O 00 Z I J.J w Z Q7 Z I J.J J u Q Z Q J Q O LLJ � M V D can - o LU w °� Z Q N Z J Z O M W Q L.0 Z Lu LU Z J Z O V O Z