HomeMy WebLinkAboutWWP2703557.4NORTH
GENERAL NOTES:
A. PROTECT EXISTING SHRUBBERY AND TREES UNLESS
OTHERWISE INDICATED.
U
w
Q
z
w
J_
LL
0 10, 20' 40'
RECORD DRAWING
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED
IN PART ON INFORMATION PROVIDED BY OTHERS
THIS DRAWING WAS PREPARED ONLY FOR THE
PROJECT AND SITE SPECIFICALLY IDENTIFIED
110%
HEREON AND IS NOT TO BE USED ELSEWHERE
CoAla
Date 288 ho 12
By
.�
DEMOLITION PLAN
SCALE: 1" = 20'
FILE: 8453-SRV.dwg
B. PROTECT UNDERGROUND UTILITIES UNLESS OTHERWISE
INDICATED.
C. DEMOLITION OF ASPHALT FOR NEW PIPE NOT SHOWN FOR
CLARITY. SEE DWGS C-03 AND C-05 FOR DETAILS.
KEY NOTES:
PHASE 1 DEMOLITION -
(APPLICABLE PRIOR TO LIFT STATION CONSTRUCTION)
1 REMOVE EXISTING TREE, CURBING, AND LANDSCAPED STUB -OUT.
2 REMOVE ASPHALT OCCUPIED BY FOUR EXISTING PARKING
SPACES TO FACE OF CURB AND ADDITIONAL AS REQUIRED TO
FACILITATE INSTALLATION OF WET WELL AND OTHER SITE
APPURTENANCES.
OREMOVE EXISTING CURB. PROTECT SHRUBBERY EAST OF CURB.
PHASE 2 DEMOLITION
APPLICABLE AFTER LIFT STATION CONSTRUCTION AND TESTIN
ODECOMMISSION EXISTING LIFT STATION. REMOVE TOP 2 FEET OF
STEEL STRUCTURE. DRILL MINIMUM 30 1-INCH DIAMETER HOLES
THROUGH FLOOR AND BASE SLAB OF STRUCTURE, EVENLY
SPACE. FILL STRUCTURE TO 2 FEET BELOW EXIST GRADE WITH
DRAIN ROCK PER CITY NEW SECTION 9-03.20. BACKFILL AND
RESTORE TO MATCH EXISTING.
<s>
REMOVE EXISTING CONTROL PANEL AND ANTENNA. SALVAGE
TELEMETRY PANEL AND DELIVER TO CITY MAINTENANCE SHOPS.
SEE ELECT DWGS FOR ANTENNA DETAILS.
OPLUG
AND ABANDON EXISTING 4-INCH DIAMETER FORCE MAIN TO
POINT OF CONNECTION WITH NEW SSFM. SEE DWG C-03, SITE AND
PIPING PLAN FOR POINT OF CONNECTION LOCATION.
O7
PLUG PIPES FEEDING EXISTING LIFT STATION. FILL AND CHANNEL
MANHOLE PER DETAIL 1/ C-06.
OPROTECT
ROOT ZONE OF EXISTING TREE. EXCAVATE IN AREA OF
ROOT ZONE PER WSDOT SECTION 8-03.3(2).
OREMOVE
CURB AS REQUIRED FOR INSTALLATION OF UTILITY.
10
REMOVE CONCRETE HOIST PAD.
11
TEMPORARILY PLUG 8-INCH SS DURING DEMOLITION OF EXISTING
LIFT STATION. COORDINATE WITH CITY FOR PARK RESTROOM
FACILITIES CLOSURE. REFER TO SUB -SECTION 10.01500 FOR
ADDITIONAL REQUIREMENTS.
12
REMOVE EXISTING UTILITY METER AND TRANSFER SWITCH
CABINET, CONCRETE PAD, AND CONDUIT. BACKFILL AND RESTORE
TO MATCH EXIST.
t
V,
S=355704
/� &c - 3557 0 �