HomeMy WebLinkAboutWWP2703557.5GENERAL NOTES: W Q z W J_ U- RECORD DRAWING THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED IN PART ON INFORMATION PROVIDED BY OTHERS THIS DRAWING WAS PREPARED ONLY FOR THE PROJECT AND SITE SPECIFICALLY IDENTIFIED HEREON AND IS NOT TO BE USED ELSEWHERE c� Date 288 /20 12 By 4, EM015 � TYP _s d I.E. 8" (NE)=16.14 I.E. CTR CHAN = 16.53 8" Ss 2 PROFILE C-06 AS -BUILT AS -BUILT PHOTO PHOTO 8" SS 3 1 C-06 / B-01 / AS -BUILT 3/4" W / PHOTO / i (TYP) SfTE AND PIPING PLAN SCALE: 1" = 20' FILE: 8235B-010-100.dwg A. MAINTAIN OPERATION OF EXISTING LIFT STATION DURING CONSTRUCTION OF NEW LIFT STATION. B. INSTALL 4" SSFM AND 8" SS PIPE PER WSDOT STANDARD SPECIFICATIONS. BACKFILL WITH GRAVEL BORROW PER WSDOT SECTION 9-03.14(1). C. RESTORE AC PAVEMENT PER DET 1/C-05. D. BACKFILL AROUND STRUCTURES WITH GRAVEL BACKFILL FOR WALLS OR CONTROLLED DENSITY FILL PER WSDOT STANDARD SPECIFICATIONS. E. PROTECT EXISTING SHRUBBERY AND TREES UNLESS OTHERWISE INDICATED. KEY NOTES: 1� POINT OF CONNECTION. LOCATION IS APPROXIMATE. CITY PROVIDED POTHOLE DATA ON AUGUST 3, 2010 INDICATE 3'-5" FROM GRADE TO TOP OF PIPE. NEW SSFM SHALL SLOPE UPWARDS TO POINT OF CONNECTION. 2OWATERLINE AND SERVICE METER TO BE SUPPLIED AND INSTALLED BY CITY: SEE SPECIFICATION SUB -SECTION 10.01110 FOR ADDITIONAL REQUIREMENTS. OSEE PROFILE FOR SSMH AND WET WELL CONNECTION AND COUPLING DETAILS. OPROVIDE NEW UTILITY METER AND TRANSFER SWITCH CABINET. PROVIDE CONDUIT FROM UTILITY METER AND TRANSFER CABINET TO NEW LIFT STATION CONTROL PANEL. CONNECT TO EXIST UTILITY TRANSFORMER. SUPPORT ON EQUIPMENT SLAB PER TYP DET S300. SEE ELECT DWGS FOR FURTHER DETAILS. < AC PAVEMENT RESTORATION LIMITS. SAW CUT MIN 1'-0" BEYOND EDGE OF TRENCH UNLESS OTHERWISE INDICATED. S=355705 �k-9.(:-::>',