HomeMy WebLinkAboutWWP2703625.10General Structural Notes 300 BAD" - ` SIGN GENERAL DESIGN CRITERIA: CONCRETE DESIGN: CMU DESIGN: GEOTECHNICAL PARAMETERS: MINIMUM FROST DEPTH MAXIMUM NET BEARING OTHER LOADING PARAMETERS: RISK CATEGORY: WIND DESIGN: ENCLOSURE CLASSIFICATION PROCEDURE USED: SNOW LOAD: OTHER DESIGN VALUES USED: CONCRETE: TIMBER: GLULAM: ASCE 7-10 & IBC 2012 ACI 318-11 ACI 530-11 18" 2,000 PSF STATIC FOR FOOTINGS AT GRADE II (NON -ESSENTIAL FACILITY) 110 MPH BASIC WIND SPEED, EXPOSURE C ENCLOSED BUILDING SIMPLIFIED ENVELOPE PROCEDURE 25 PSF, IS=1.0 4000 PSI WITH 60,000 PSI REINFORCING DFL #2 OR BETTER 24F-V4 DF/DF 100 PSF CRITERIA ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (2012 EDITION). SPECIAL INSPECTIONS, TESTS AND OBSERVATIONS SPECIAL INSPECTIONS AND TESTS SHALL INCLUDE THE FOLLOWING. REFER TO IBC SECTION 1704 AND 1707 FOR DETAILS. 1. SPECIAL INSPECTIONS BY THE GEOTECHNICAL ENGINEER INCLUDING: A. SITE EXCAVATION AND GRADING B. PLACEMENT OF STRUCTURAL FILL AND SOIL COMPACTION C. VERIFICATION OF SOIL -BEARING CAPACITY 2. CONCRETE PLACEMENT AT CONCRETE CONSTRUCTION: CONTINUOUS, SEE ALSO SECTION 1704.4. 3. REINFORCEMENT AT CONCRETE CONSTRUCTION: PERIODIC, SEE ALSO SECTION 1704.4. 4. WOOD -FRAMED LATERAL -FORCE RESISTING SYSTEM: PERIODIC, SEE ALSO SECTION 1707.3. 5. TESTING OF CONCRETE FOR SPECIFIED COMPRESSIVE STRENGTH (FC), AIR CONTENT AND SLUMP. SEE IBC TABLE 1704.4, 6. STRUCTURAL OBSERVATION IN ACCORDANCE WITH IBC 1709 SHALL BE PROVIDED. 7. VERIFICATION OF SPECIFIED COMPRESSIVE STRENGTH (FM) OF MASONRY PRIOR TO CONSTRUCTION AND EVERY 5,000 SQUARE FEET DURING CONSTRUCTION.. SEE IBC TABLE 1708.1.4. GENERAL 1. LINES SHOWN ON DRAWINGS MAY BE ASSOCIATED WITH CAD MODELING AND MAY NOT REPRESENT REQUIRED OR ALLOWED JOINTS. SEE DETAILS FOR CLARIFICATION ON REQUIRED AND ALLOWED JOINTS. 2. NOT ALL PENETRATIONS MAY BE SHOWN ON PLANS, CONTRACTOR SHALL COORDINATE SIZE AND LOCATION OF STRUCTURE PENETRATIONS WITH MECHANICAL SHEETS, MFR AND ORIENTATION PLAN. 3. GROUNDWATER MAY BE ENCOUNTERED DURING CONSTRUCTION OF THE STRUCTURES. THE CONTRACTOR SHALL PROVIDE THE NECESSARY SHORING AND DEWATERING FOR THE CONSTRUCTION OF THE STRUCTURES. 4. PROVIDE 6" MINIMUM PVC WATERSTOPS AT BELOW GRADE AND WATER HOLDING CONSTRUCTION JOINTS TYP., UNLESS NOTED OTHERWISE. PROVIDE MIN 1" CLR BETWEEN REINFORCING AND WATERSTOPS, 5. ALL DIMENSIONS SHALL BE COORDINATED AND VERIFIED BY THE EQUIPMENT MANUFACTURER PRIOR TO ANY CONCRETE CONSTRUCTION. DIMENSIONS AND ELEVATIONS SHOWN MAY REQUIRE ADJUSTMENT FOR SPECIFIC EQUIPMENT USED. REINFORCED CONCRETE REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS) IN ACCORDANCE WITH ACI 315-99 AND 318-11. LAP ALL REINFORCEMENTS IN ACCORDANCE WITH THE "REINFORCING SPLICE AND DEVELOPMENT LENGTH SCHEDULE" - SEE THIS SHEET. PROVIDE CORNER BARS AT ALL WALL INTERSECTIONS PER DETAIL 306. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT UNLESS SPECIFICALLY DETAILED OR APPROVED BY THE ENGINEER. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED: FOOTINGS AND OTHER UNFORMED SURFACES CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH, ....3', FORMED SURFACES EXPOSED TO EARTH (WALLS BELOW GRADE), WATER OR WEATHER (#6 BARS OR LARGER).. 2" COLUMN TIES OR SPIRALS AND BEAM STIRRUPS... ...... 2" SLABS AND WALLS (DRY) 1 1/2" CONCRETE ANCHORS USE HILTI HIT -RE 500-SD CONCRETE ANCHORS AS SPECIFIED AND INSTALLED PER DETAIL 303 UNLESS OTHERWISE CALLED OUT ON PLANS. ABBREVIATIONS: AL - ALUMINUM CHK-CHECKERED CL - CENTERLINE CLR - CLEAR EA - EACH EF - EACH FACE EW - EACH WAY FB - FLAT BAR HORZ - HORIZONTAL LLV - LONG LEG VERTICAL O.C. - ON CENTER PL - PLATE RB - ROUND BAR RST - REINFORCING STEEL SST - STAINLESS STEEL T&B - TOP AND BOTTOM VERT - VERTICAL MINIMUM STRAIGHT DEVELOPMENT LENGTHS (�d+ 1 TENSION BARS BAR SIZE TOP BARS OTHER BARS # 3 19" 1511 # 4 25" 19" # 5 31" 24" # 6 37" 29" # 7 54" 42" # 8 62" 48" # 9 70" 54" # 10 79" 61" MINIMUM EMBEDMENT LENGTHS (4) U FOR STANDARD END HOOKS BAR SIZE ALL BARS # 3 6" # 4 7" # 5 9" # 6 10" # 7 12" # 8 14" # 9 15" # 10 17" MINIMUM LAP SPLICE LENGTHS (g$ u TENSION BARS CLASS B BAR SIZE TOP BARS OTHER BARS # 3 25" 19" # 4 33" 25" # 5 41" 31" # 6 49" 37" # 7 71" 54" # 8 81" 62" # 9 91" 70" # 10 103" 79" 1. SIDE COVER EQUAL TO OR GREATER THAN 2-1/2". 2. END COVER FOR 900 HOOKS MUST BE EQUAL TO OR GREATER THAN 2". -�- "TOP BARS" ARE HORIZONTAL BARS WITH MORE THAN 12" DEPTH OF CONCRETE CAST BELOW THEM. IF CLEAR CONCRETE COVER IS LESS THAN 2x THE DIAMETER OF THE BAR OR THE CENTER -TO -CENTER SPACING IS LESS THAN (4) BAR DIAMETERS, THEN VALUES SHALL BE INCREASED BY 43%. REINFORCEMENT SPLICE AND 30 DEVELOPMENT LENGTH SCHEDULE SEE DETAIL 403 FOR CMU ANCHORS CONCRETE ANCHORS SHALL BE HILTI HIT -RE 500-SD ADHESIVE ANCHORS AS SPECIFIED. WHERE SIZE IS CALLED OUT ON THE DRAWINGS, PROVIDE MINIMUM EMBEDMENT DEPTHS AS SHOWN ON THE FOLLOWING TABLES. PROVIDE MINIMUM EDGE DISTANCES AND SPACING AS SHOWN ON THE FOLLOWING TABLES UNLESS SPECIFICALLY DETAILED OTHERWISE. INSTALL CONCRETE ANCHORS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. NOTIFY OWNER 24 HOURS IN ADVANCE OF INSTALLATION OF ALL ANCHORS. WHERE SIZE IS NOT CALLED OUT, ANCHOR SHALL BE SELECTED BASED ON DESIGN LOADS. IF THE MINIMUM EDGE DISTANCE AND/OR MINIMUM SPACING CAN NOT BE ACHIEVED, REFER TO PRODUCT INFORMATION FOR REDUCTION IN ALLOWABLE LOADS. 316 STAINLESS STEEL THREADED ROD DIAMETER OF ROD (INCHES) 3/8 1/2 5/8 3/4 MINIMUM EMBEDMENT DEPTH (INCHES) 31/2 41/4 5 6 5/8 MINIMUM CONCRETE THICKNESS (INCHES) 51/4 61/2 71/2 10 MINIMUM EDGE DISTANCE (INCHES) 51/4 61/2 71/2 10 MINIMUM ANCHOR SPACING (INCHES) 7 81/2 10 131/4 ALLOWABLE TENSION LOAD CAPACITY (POUNDS) 3,105 4,371 5,535 8,274 ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) 2,519 5,440 7,195 10,757 GRADE 60 REBAR REBAR SIZE #5 #6 #7 #8 MINIMUM EMBEDMENT DEPTH (INCHES) 5 7 71/2 8 MINIMUM CONCRETE THICKNESS (INCHES) 71/2 101/2 11 1/4 12 MINIMUM EDGE DISTANCE (INCHES) 71/2 101/2 11 1/4 12 MINIMUM ANCHOR SPACING (INCHES) 10 14 15 16 ALLOWABLE TENSION LOAD CAPACITY (POUNDS) 5,535 8,783 9,968 11,201 ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) 7,195 11,418 12,959 14,562 CONCRETE ANCHOR 302 TYP NOTE: SEE MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND DIMENSIONS. 3" MIN. BEYOND EQUIPMENT BOLTS, TYP. #4 DOWELS, EACH CORNER AND 18" O.C., 3" EMBEDMENT INTO FLOOR CAST -IN -PLACE CONCRETE FLOOR, REINF. PER PLAN CAST -IN -PLACE CONCRETE, ROUGHEN FLOOR UNDER PAD PRIOR TO POURING PAD. PROVIDE 44 W1 AxW1.4 WWM AT TOP FACE WITH 1%" CLEAR COVER 1 i �x�w�x�•��1{ •' , ► • r Y EQUIPMENT PAD 04 (2) #5 MIN IN GROUTED (1) #5 EACH SIDE OPENING, FU._, HEIGHT, TYP. � 10.00 TOP OF WALL INTERIOR FACE OF ALL CMU BLOCKS TO BE SMOOTH FACE 4.00' 'qLJBOND BEAM #5 VERTICAL RST @ 24" O.C. MAX. FILL ALL REINFORCED CELLS WITH GROUT. DO NOT GROUT UNREINFORCED CELLS. oil 3/4" CHAMFER, ALL OUTER EDGES 3.5" UNLESS OTHERWISE NOTED BOND BEAM CONCRETE FLOOR - LINTEL BLOCK OPENING GREATER THAN k 24" IN EITHER DIRECTION I r 1VP1`. %OIVIIU OPENING 402 NOT TO SCALE S01 DOUBLE 2x8 PRESSURE TREATED HEADER, CONTINUOUS WITH 5/"0 J-BOLTS AT 32" O.C. --- IN GROUTED VERTICAL CELLS, BOLT LENGTH AS NECESSARY FOR 6" • EMBEDMENT. BOND BEAM, TOP COURSE 8"x8"x16" SPLIT -FACE CMU BLOCK, PROVIDE WEATHERPROOF AND ANTI -GRAFFITI COATING ON EXTERIOR. PROVIDE SMOOTH FACE BLOCKS WHERE LIGHTS AND EQUIPMENT ARE PROPOSED ON WALLS CMU WALL INSULATION. ALL ♦ WALL CMU BLOCK TO BE GROUTED SOLID AS SPECIFIED. • BOND BEAM WITH #5 CONTINUOUS, LAP JOINTS 24" MINIMUM (TYPICAL) CMU WALL NOT TO SCALE REVISED TO CONFORM TO CONSTRUCTION RECORDS ! a RH2 ENGINEERIN INC. D #5 DOWELS AT 24" O.C., TYPICAL, TO MATCH LOCATIONS OF VERTICALLY REINFORCED CELLS OF CMU WALL ABOVE. CONCRETE STEM WALL S 362510 *r, n 11" n r' VCDT q CMU WALL INTERSECTION / CORNER 1" - lr_orr CMU ANCHORS SHALL BE HILTI HY-150 ADHESIVE ANCHORS FOR USE IN GROUTED CMU CELLS OR HILTI HIT-HY 20 HYBRID ADHESIVE ANCHORS FOR USE IN UNGROUTED CMU CELLS. o� WHERE SIZE IS CALLED OUT ON THE DRAWINGS, PROVIDE MINIMUM EMBEDMENT DEPTHS AS SHOWN ON THE FOLLOWING TABLES. PROVIDE MINIMUM EDGE DISTANCES AND SPACING AS r SHOWN ON THE FOLLOWING TABLES UNLESS SPECIFICALLY DETAILED OTHERWISE oil r� INSTALL ANCHORS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, NOTIFY OWNER 24 HOURS IN ADVANCE OF INSTALLATION OF ALL ANCHORS. WHERE SIZE IS NOT CALLED OUT, ANCHOR SHALL BE SELECTED BASED ON DESIGN LOADS.IF THE MINIMUM EDGE DISTANCE AND/OR MINIMUM SPACING CAN NOT BE ACHIEVED, REFER TO 9 PRODUCT INFORMATION FOR REDUCTION IN ALLOWABLE LOADS, HILTI HY-150 - 316 STAINLESS STEEL THREADED ROD Z DIAMETER OF ROD (INCHES) 3/8 112 5/8 MINIMUM EMBEDMENT DEPTH (INCHES) 31/2 41/4 5 MINIMUM CONCRETE THICKNESS (INCHES) 51/4 6 3/8 71/2 0 MINIMUM EDGE DISTANCE (INCHES) 51/4 61/2 71/2 0 Cn MINIMUM ANCHOR SPACING (INCHES) 7 81/2 10 a Z O ALLOWABLE TENSION LOAD CAPACITY (POUNDS) 2,540 3,690 4,920 0 a CA ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) 1,875 3,335 5,060 Q j w w Lill TI LIV 01A @TAIAII C@@ [`TCCI "rUnCAMOM Mf%r% U /W�. li DIAMETER OF ROD (INCHES) MINIMUM EDGE DISTANCE (INCHES) MINIMUM ANCHOR SPACING (INCHES) ALLOWABLE TENSION LOAD CAPACITY (POUNDS) ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) FORCES ARE DETERMINED BY THE FOLLOWING FORMULA: (Ps /Pt )+ (Vs /Vt) = 1 ALLOWABLE LOADS FOR ANCHORS SUBJECTED TO COMBINED SHEAR AND TENSION 1 /4" 5/16" 3/8" 1 /2" 1 ,, I rn N C:) 12" 12" 12" 12" (1) ANCHOR PER BLOCK CELL 255 370 525 525 0 340 505 790 1,230 U � WHERE: Ps _ Applied Service Tension Load I z P - Allowable Service Tension Load Vt = Applied Service Shear Load V t = Allowable Service Shear Load CMU ANCHOR 404 TYP M d w Q 0 w co Cn J W 0 0 Z J • • I07wn W W m 0 z SCALE: SHOWN i„ 2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" DWG N0 SHEET No.: S02 12 21 Z L Z m m z m m 0 D D 0 to i Cn aZ m 0 im z m Cn 0 D m o ❑ m ma °C D c m5 m