HomeMy WebLinkAboutWWP2703626.8CMU ANCHORS SHALL BE HILTI HY-150 ADHESIVE ANCHORS FOR USE IN GROUTED CMU CELLS OR HILTI HIT-HY 20 HYBRID ADHESIVE ANCHORS FOR USE IN UNGROUTED CMU CELLS. WHERE SIZE IS CALLED OUT ON THE DRAWINGS, PROVIDE MINIMUM EMBEDMENT DEPTHS AS SHOWN ON THE FOLLOWING TABLES. PROVIDE MINIMUM EDGE DISTANCES AND SPACING AS SHOWN ON THE FOLLOWING TABLES UNLESS SPECIFICALLY DETAILED OTHERWISE. INSTALL ANCHORS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. NOTIFY OWNER 24 HOURS IN ADVANCE OF INSTALLATION OF ALL ANCHORS. WHERE SIZE IS NOT CALLED OUT. ANCHOR SHALL BE SELECTED BASED ON DESIGN LOADS.IF THE MINIMUM EDGE DISTANCE AND/OR MINIMUM SPACING CAN NOT BE ACHIEVED, REFER TO PRODUCT INFORMATION FOR REDUCTION IN ALLOWABLE LOADS. HILTI HY-150 - 316 STAINLESS STEEL THREADED ROD DIAMETER OF ROD (INCHES) 3/8 1/2 5/8 MINIMUM EMBEDMENT DEPTH (INCHES) 31/2 41/4 5 MINIMUM CONCRETE THICKNESS (INCHES) 51/4 6 3/8 71/2 MINIMUM EDGE DISTANCE (INCHES) 51/4 61/2 71/2 MINIMUM ANCHOR SPACING (INCHES) 7 81/2 10 ALLOWABLE TENSION LOAD CAPACITY (POUNDS) 2,540 3,690 4,920 ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) 1,875 3,335 5,060 HILTI HY 20 - STAINLESS STEEL THREADED ROD DIAMETER OF ROD (INCHES) 1/4" 5/16" 3/8" 1/2" MINIMUM EDGE DISTANCE (INCHES) 12" 12" 12" 12" MINIMUM ANCHOR SPACING (INCHES) (1) ANCHOR PER BLOCK CELL ALLOWABLE TENSION LOAD CAPACITY (POUNDS) 255 370 525 525 ALLOWABLE SHEAR LOAD CAPACITY (POUNDS) 340 505 790 1,230 FORCES ARE DETERMINED BY THE FOLLOWING FORMULA: (PS/ P ) + (Vs/ V ) = 1 WHERE: t t P = Applied Service Tension Load P t= Allowable Service Tension Load ALLOWABLE LOADS FOR ANCHORS V s = Applied Service Shear Load SUBJECTED TO COMBINED SHEAR AND V t = Allowable Service Shear Load TENSION CMU ANCHOR �2 NOTE: SEE MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND DIMENSIONS. CAST -IN -PLACE CONCRETE, ROUGHEN FLOOR 3" MIN. BEYOND UNDER PAD PRIOR TO POURING PAD. PROVIDE EQUIPMENT BOLTS, TYP. 44 W1.4xW1.4 WWM AT TOP FACE WITH 1%" #4 DOWELS, EACH CLEAR COVER CORNER AND 18" O.C.. 3" EMBEDMENT INTO FLOOR �4' CHAMFER, ALL OUTER EDGES CAST -IN -PLACE CONCRETE ��x ,worm.. �:x 4" UNLESS �.x FLOOR, REINF. PER PLAN ° •..: OTHERWISE NOTED Or EQUIPMENT PAD TYPICAL BAR DETAILING AT FOOTING CORNER CMU DOWELS TO MATCH WALL VERTS. EXTEND 2'-0" INTO CMU WALL CMU WALL #5 @ 12" O.C., MIN. 2 /2" PJF, TYP. UNO FLOOR SLAB FOOTING INSULATION �\ 1r #5 DOWELS @ 12" O.C., ALTERNATE HOOKS ^ ° 24" ° (3) #5 vj • 8" 1'-6" TYPICAL FOOTING SPREAD FOOTING 1" = 1'-0" �— DOOR �2° PJF EXTERIOR SLAB EXTEND CONCRETE FLOOR ACROSS THRESHOLD HOLD FOOTING DOWN 2 LAYERS OF 30# i p-• BUILDING PAPER J ' SPREAD FOOTING I-- 1'-6" --�I DOOR THRESHOLD sot 1"= 1,-�u #3 @ 12" O.C., EACH WAY, CENTER OF SLAB. CAST -IN -PLACE CONCRETE r- LANDING. SLOPE AWAY 4" PJF FROM DOOR AT 2% MIN. PROPOSED :... ... , 411 GRADE 3'-8" CONCRETE FLOOR NOTE: ENTRANCE LANDING, WIDTH EQUAL TO DOOR WIDTH PLUS 3" EACH SIDE, OR AS NOTED. TYPICAL ENTRANCE LANDING DETAIL 08 NOT TO SCALE `Sr DOUBLE 2x8 PRESSURE TREATED HEADER, CONTINUOUS WITH "0 J-BOLTS AT 32" O.C. IN GROUTED VERTICAL CELLS. BOLT LENGTH AS NECESSARY FOR 6" EMBEDMENT. 10.00, TOP OF WALL BOND BEAM, TOP COURSE 8 00' 8"x8"x16" SPLIT -FACE CMU BLOCK, PROVIDE BOND BEAM WEATHERPROOF AND ANTI -GRAFFITI COATING ON EXTERIOR. PROVIDE SMOOTH �-' FACE BLOCKS WHERE LIGHTS AND EQUIPMENT ARE PROPOSED ON WALLS CMU WALL INSULATION. ALL WALL CMU BLOCK TO BE GROUTED SOLID AS SPECIFIED, INTERIOR FACE OF ALL CMU BLOCKS TO BE SMOOTH FACE BOND BEAM WITH #5 CONTINUOUS, 4.00' �- - LAP JOINTS 24" MINIMUM (TYPICAL) "LJBOND BEAM #5 VERTICAL RST @ 32" O.C. MAX. TIE RST TO DOWELS IN FLOOR, FILL ALL REINFORCED CELLS WITH GROUT. DO NOT GROUT #5 DOWELS AT 32" O.C., TYPICAL, TO UNREINFORCED CELLS. f MATCH LOCATIONS OF VERTICALLY REINFORCED CELLS OF CMU WALL ABOVE. BOND BEAM 0.00' BOND BEAM . . o a a s � n t> CONCRETE FLOOR -j a CONCRETE STEM ._ a= WALL CMU WALL 402 NOT TO SCALE S01 ROOFING PLYWOOD ROOF DECK ANCHOR TRUSS TO 1" AIR _ TOP PLATE PER PLAN GAP, MIN. FULL DEPTH VENTED EAVE BLOCKING aw- 12 4r, n'101r n r \/CDT BOND BEAM REINF, #5 CORNER BARS AT ALL 54" BOND BEAM LOCATIONS AT WALL CORNERS CMU WALL CMU WALL INTERSECTION / CORNER 40 ,„ S01 1'-0" VENTILATION BAFFLE, INSTALL TO KEEP INSULATION AWAY FROM EAVE VENTS FLASHING WITH (2) #5 MIN IN GROUTED LINTEL BLOCK -,,,,DRIP EDGE CELLS, TYP. I R-30 KRAFT PAPER FACED BATT ^ INSULATION ON ALL CEILING 1"x6" CEDAR FASCIA TRUSS SURFACES, INSTALL WITH KRAFT -- - - — - OVER NAILER FACED SIDE OF INSULATION I -- SOFFIT FACING INTERIOR OF BUILDING. PRESSURE TREATED J WITH VENT -- 2"x4" NAILER r I I FINISH CEILING WITH ONE LAYER DOOR - -- OPENING 1"x4" CEDAR TRIM, GREATER THAN - s 1"x2"CEDAR TRIM, j CONTINUOUS, TYP. OF 5/" GYPSUM WALLBOARD, 24'" IN EITHER CONTINUOUS, TYP. FINISH SMOOTH AND PAINT WHITE. J_. DIRECTION ATTACH TRUSS TO SILL CONTINUOUS TRIM PLATE WITH SIMPSON HOLD ' DOWN ANCHOR PER PLAN CMU WALL/TRUSS CONNECTIONS 501 (1) #5 EACH SIDE OF OPENING, FULL HEIGHT, TYP. TYPICAL CMU OPENING 401 NOT TO SCALE S01 RIDGE VENT, PROVIDE END CAPS PER MANUFACTURER'S SPECIFICATIONS �1 3" MIN I METAL ROOFING ­1 1/ / OOF TRUSS 2X FLAT PLYWOOD BLOCKING, TYP DECKING RIDGE VENT DETAIL 502 NOT TO SCALE S01 REVISED TO CONFORM TO CONSTRUCTION RECORDS zy RH2 &NEERING INC. DATE u H. WA �_ 1s727 R8c t s'tEg$� l roNAL SIGNED: 01118113 SIGNED: 01118113 W J Q ui W � Q J 4 cj V z w cc O J ul 0 ~ Q .ftft Lift 4i � H Q W � JW z J ,ER PLANNERS RH2 ENGIMFF'a!NW' !Nf - '.ttp: /'Wwv& aL_ SHOWN 0 1" 2" DRAWING IS NOT TO SCALE IF BAR IS NOT 2" LONG PLOT: 1 DWG N6 ENGINEER: DEB S02 REVIEWED MM DATE. Nov 11, 2014 O� CLIENT: REN JOB NO. 112-023 T270 FILENAME LIND—D—S02,DWG m � >z L m �c� Z mf C y ECG = u "z m z m m 0 D I0' D n O m 0 O goo °M =�Cf) ;W D 'ACm � C G �_ M° � � rz z m 0 D Y Z C m m �z zN A 1 �D W zz D n 0 O X o 0 D C Cn