HomeMy WebLinkAboutWWP2703628.10MOTOR CONTROL CENTER, 48OV, 30, 4W, 600A BUS, 42 KAIC WITHSTAND.
LIGHTING FIXTURE SCHEDULE
MANUFACTURER
* LAMP
TYPE
DESCRIPTION
NAME CATALOG NO.
QTY. CATALOG NO.
REMARKS
Al
METAL HALIDE OUTDOOR AREA SECURITY LIGHT, 120 VAC, (1)
METAL HALIDE
- 10OW METAL HALIDE LAMP, MOUNT TOP OF FIXTURE 12"
LITHONIA
TDD 100ML 120 M2
1
100 WATT
BELOW TOP OF POLE. U.L. LISTED FOR WET LOCATIONS.
* NUMBER OF LAMPS PER FIXTURE
ELECTRICAL EQUIPMENT AND INSTRUMENTATION SCHEDULE
ITEM
DESCRIPTION
MANUFACTURER
MODEL NO.
A
O
SERVICE ENTRANCE DISCONNECT SWITCH - NEMA 3R, HEAVY
DUTY SERVICE RATED, 100% RATED CIRCUIT BREAKER, 100-AMP,
HDL 26100C WITH
600VOLT, 18,000 AMP INTERRUPTING RATING.
SQUARE D
ENCLOSURE OR EQUAL
4
MANUAL TRANSFER SWITCH - NEMA 3R, DOUBLE THROW,
MODEL DTU363RB
NON -FUSED SAFETY SWITCH, 60OV, 100-AMP.
SQUARE D
OR EQUAL
4
GENERATOR RECEPTACLE - 100A, 480 VOLT, 4-POLE, 3-WIRE,
APPLETON
MODEL ADR1034 W/
THREADED CAP, WEATHER PROOF.
MODEL AJA100 ANGEL
ADAPTER OR EQUAL
4D
NOT USED THIS PLAN
0
FLOAT SWITCH - SEE DETAIL ON DWG NO. E07
SEE
SEE SPECIFICATIONS
SPECIFICATIONS
FO
LEVEL TRANSMITTER
SEE SPECIFICATIONS
SEE
SPECIFICATIONS
4G
CHECK VALVE LIMIT SWITCHES - CONTRACTOR SHALL SELECT
HEAVY DUTY
ACTUATOR LEVER ARM BEST SUITED FOR MOUNTING
SQUARE D
TYPE C, CLASS
CONFIGURATION. SEE DETAIL ON DWG NO. E07.
9007 OR EQUAL
0
NOT USED THIS PLAN
KO
VAULT FLOOD SWITCH - N.O. REED TYPE FLOAT SWITCH, 20
OMEGA MODEL
LVN-20 OR
EQUAL
VA. SEE DWG NO. E07 FOR DETAIL.
4
NOT USED THIS PLAN
O
INTRUSION ALARM SWITCH - CONTRACTOR SHALL SELECT
HEAVY DUTY
ACTUATOR LEVER ARM BEST SUITED FOR MOUNTING
SQUARE D
TYPE C, CLASS
CONFIGURATION. WIRE SWITCHES IN SERIES.
9007 OR EQUAL
PROPOSED PAD -MOUNT
TRANSFORMER BY UTILITY
PROPOSED UNDERGROUND
PRIMARY SERVICE PER 4
SERVING UTILITY
REQUIREMENTS.
UTILITY POWER
12470 - 480/277 - VOLT. 30
POWER CONDUIT AND CONDUCTOR SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE
(QUANTITY)
CONDUCTORS
P1
UTILITY TRANSFORMER
SERVICE ENTRANCE DISCONNECT
1 1/4"
(3) -
#3, (1)
- #3 N
P2
MAIN DISCONNECT
UTILITY METER
1 1/4"
(3) -
#3, (1)
- #3 N, (1)
- #8 GRID
43
UTILITY METER
MANUAL TRANSFER SWITCH, "MTS"
1 1/4"
(3) -
#3, (1)
- #3 N, (1)
- #8 GRID
44
STANDBY GENERATOR RECEPTACLE
MANUAL TRANSFER SWITCH, "MTS"
1 1/4"
(3) -
#3, (1)
- #3 N, (1)
- #8 GRD
P5
BELOW "MTS"
STUB & CAP (FUTURE EG SET)
1 1/4"
NYLON PULL CORD
P6
LIGHTING PANEL, "L"
SITE LIGHT
3/4"
(2) -
#12, (1)
- #12 GRD
P7
MANUAL TRANSFER SWITCH, "MTS"
MOTOR CONTROL CENTER, "MCC"
1 1/4"
(3) -
#3, (1)
- #3 N, (1)
- #8 GRID
P8
MOTOR CONTROL CENTER, "MCC"
MOTOR SPLICE HANDHOLE
1"
(3) -
#10, (1)
- #10 GRD,
MOTOR SENSOR CABLE
_P�
MOTOR CONTROL CENTER, "MCC"
MOTOR SPLICE HANDHOLE
1"
(3) -
#10, (1)
- #10 GRD,
MOTOR SENSOR CABLE
P DO
MOTOR SPLICE HANDHOLE
PUMP NO. 1, P-1
2"
PUMP
MOTOR
CABLES
CP11
MOTOR SPLICE HANDHOLE
PUMP NO. 2, P-2
2"
PUMP
MOTOR
CABLES
P4
TELEMETRY PANEL, "RTU"
LIGHTING PANEL, "L"
3/4"
(2) -
#12, (1)
- #12 GRID
P1 j
LIGHTING PANEL, "L"
STUB & CAP
3/4"
3/8"
NYLON
PULL CORD
P:p14
LIGHTING PANEL, "L"
STUB & CAP
3/4"
3/8"
NYLON
PULL CORD
P�.P15
LIGHTING PANEL, "L"
DEDICATED SUMP PUMP RECEPTACLE
3/4"
(2) -
#12, (1)
- #12 GRD
P��4
LIGHTING PANEL, "L"
OUTDOOR RECEPTACLE
3/4"
(2) -
#12, (1)
- #12 GRD
CON
OL CONDUIT AND CONDUCTOR SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE
(QUANTITY)
CONDUCTORS
U
WETWELL FLOATS
FLOAT/LEVEL TRANSMITTER SPLICE HANDHOLE
2"
MANUFACTURER FLOAT CABLES
C2
VALVE LIMIT SWITCHES
VALVE VAULT JUNCTION BOX
3/4"
(2) -
#14, (1)
- #14 GRD
C3
VALVE VAULT FLOOD SWITCH
VALVE VAULT JUNCTION BOX
3/4"
(2) -
#14, (1)
- #14 GRD
C4
FLOAT/LEVEL TRANSMITTER SPLICE
HANDHOLE
TELEMETRY PANEL, "RTU"
1"
(6) -
#14, (1)
- #14 GRD
Q'�5
BUILDING INTRUSION ALARM SWITCH
TELEMETRY PANEL, "RTU"
3/4"
(2) -
#14, (1)
- #14 GRD
(: D6
OVERFLOW LEVEL FLOAT
FLOAT/LEVEL TRANSMITTER SPLICE HANDHOLE
1"
MANUFACTURER'S
FLOAT CABLES
C7 F
BELOW "MTS"
STUB & CAP (FUTURE EG SET)
3/4"
3/8"
NYLON
PULL CORD
C8
TELEMETRY PANEL, "RTU"
STUB & CAP (FUTURE EG SET)
3/4"
3/8"
NYLON
PULL CORD
C9
VALVE VAULT JUNCTION BOX
TELEMETRY PANEL, "RTU"
3/4"
(8) -
#14, (1)
- #14 GRD
C1O
TELEMETRY PANEL, "RTU"
MOTOR CONTROL CENTER, "MCC"
1 1/4"
(30)
- #14,
(1) - #14 GRID
411/
INTRUSION DISABLE SWITCH
TELEMETRY PANEL, "RTU"
3/4"
(2) -
#14, (1)
- #14 GRD
C12
VALVE VAULT INTRUSION SWITCH
VALVE VAULT JUNCTION BOX
3/4"
(2) -
#14, (1)
- #14 GRD
C`4
"MCC" DOOR INTRUSION SWITCH
TELEMETRY PANEL, "RTU"
3/4"
(2) -
#14, (1)
- #14 GRD
INSTRUMENTATION CONDUIT AND CONDUCTOR SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE
(QUANTITY)
CONDUCTORS
J 4
TELEMETRY PANEL, "RTU"
STUB & CAP (FUTURE FLOW METER)
1 1/2"
3/8"
NYLON
PULL CORD
J2
TELEMETRY PANEL, "RTU"
ANTENNA
2"
ANTENNA CABLE
J3
I WETWELL LEVEL TRANSMITTER
FLOAT/LEVEL TRANSMITTER SPLICE HANDHOLE
3/4"
MANUFACTURER'S LEVEL TRANSMITTER CABLE
J4
FLOAT/LEVEL TRANSMITTER SPLICE
HANDHOLE
TELEMETRY PANEL, "RTU"
3/4"
(1) 2-CONDUCTOR
SHIELDED
CABLE
P3
0/3
I I
0%
IT"
MTS 3
u I
CP 7
ONE -LINE DIAGRAM
NO SCALE
ELECTRICAL NOTES
1�
1. PROPOSED MAIN REVENUE METERING. METER BASE AND
ENCLOSURE BY CONTRACTOR PER SERVING UTILITY REQUIREMENTS.
METER BY PUGET SOUND ENERGY.
2. PROPOSED SERVICE ENTRANCE DISCONNECT SWITCH.
3. PROPOSED MANUAL TRANSFER SWITCH. LEAVE ADEQUATE ROOM
FOR THE INSTALLATION OF A AUTOMATIC TRANSFER SWITCH THAT
WILL REPLACE THE MTS IN THE FUTURE. THE FUTURE ATS
ENCLOSURE DIMENSIONS ARE 40"H X 30"W.
4�
4. PROPOSED MOTOR CONTROL CENTER. NEMA 3R OUTER
ENCLOSURE WITH NEMA 1 INNER ENCLOSURES FOR EQUIPMENT.
5. WATERPROOF SPLICE. SEE DETAIL ON DWG NO. E06 (TYPICAL).
6
6. (2) - 5/8" X 8' COPPER GROUND RODS SPACED APART AS
SHOWN ON DWG NO. E04.
4�
7. SEE DWG NO. E08 FOR CONTROL LOGIC DIAGRAMS.
8�RENTON
8. PROPOSED GENERATOR RECEPTACLE. COORDINATE WITH CITY OF
UTILITIES FOR CORRECT PHASING OF GENERATOR
RECEPTACLE CONNECTIONS.
I ✓ NEUTRALI
I
I
GND BUS
SERVICE ENTRANCE
DISCONNECT SWITCH
S/N
#6 MIN.
130/3
// TM
0
SPD
0
GND BUS
POWER
MONITORING
PMR
PHASE MONITOR
RELAY
#6
BOND TO PIPE
IN VALVE VAULT
GROUNDING
NO SCALE
/ 15/2
T1A
ww
O
PROPOSED WET WE
#6
CONCRETE
REBAR MAT
4 UFER
CONNECTION
PANEL SCHEDULE L Al
NO.
L
LOCATION:
SERVING:
MCC
PUMP STATION
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
240/120
VOLTS 3 WIRE
CIRCUIT DESCRIPTION
KVA
AMP
AMP
KVA
CIRCUIT DESCRIPTION
OUTDOOR RECEPTACLES
0.54
20
20
0.28
POLE LIGHTING
VALVE VAULT SUMP PUMP RECEPTACLE
1.20
20
20
-
SPARE
SHELTER LIGHTS
0.08
20
20
-
SPARE
TELEMETRY PANEL
0.50
20
20
-
SPARE
SPARE
-
20
20
-
SPARE
SPARE
-
20
-
-
SPACE
SPARE
-
20
-
-
SPACE
SPACE
-
-
MANSPACE
-
-
2P
-
CONNECTION LOAD:
2.60 KVA 10.83
AMPS
DEMAND: LIGHTING AND CONTROL LOAD
DEMAND LOAD:
2.06 KVA 8.58 AMPS
1MCP MCP
OSED A
IHOLE E06
PROPOSED
SEAL -OFF,
TYPICAL
'LASTIC BUSHING AT
:ONDUIT, TYPICAL.
G �� i4
16727
CISTV,V' 1
`SIONAL
SIGNED. 05123112
K MILL
�F WASfj`
O
38613
`�:eCISTEg>V
ti
ONAL
SIGNED. 05123112
\N'r%
Z
Zo
O
Q
�Wr �
CC
U.
wAft
0 ".j
CC
Uj
m
0
Z
Q
Q
0
Q
0 cn
W W
z�
J 0
W
W =
Z V
0cn
J
Q
V
CC
F_
U
W
W
ENGINEERS
PLANNERS
RH2 ENGINEERING, INC.
http://www.rh2.com
mailbox&h2.com 1.800.720.8052
BELLINGHAM 36o.676.u..
454 West Horton Road
BOTHELL 425.951.L
22722 29th Drive SE, Suite 210
EAST
WENATCHEE S09.886.29oc.
300 Simon Street, Suite 5
RICHLAND S09.946.S 181
114 Columbia Point Drive, Suite C
SILVERDALE 36o.876.7960
2021 NW Mhyre Rd, Suite 107
TACOMA 2S3.272.3OS9
621 Pacific Avenue Suite 104
SCALE: SHOWN
0 1" 2"
DRAWING IS NOT TO SCALE
IF BAR IS NOT 2" LONG
RECORD DRAWING PLOT: 1 DWG NO.
REVISED TO CONFORM ENGINEER: CCA E03
S=3628 10 TO CON TRUCTIOP RECORDS
REVIEWED: MLM d,4� 04/25/12 DATE: Jul 15, 2013 sNEE.°.
RH2 RING INC. DATE CLIENT: REN O
REVISED TO CONFORM TO CONSTRUCTION RECORDS AHF EH 04/25/13 JOB NO.: 112-033 17
N0. REVISION BY REVIEW DATE FILENAME: LIBHS-D-EO2.DWG
r