Loading...
HomeMy WebLinkAboutWWP2703640.4LLJ Q Z W H U z W O W U V z z W I� O O 1 0 U J Q W FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR COMPRESSION TYPE SUCH AS CI OW MEDALLION: M N. H 929, MUFII FIR SUPER CENIURION 200, AND WATERLILS PACER W'TH 6" MECHANICAL JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING TWO 2-1/2" HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR, 4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS STEEL CABLE. 1-1/4" PENTAGON OPERATING NUFIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT KF1IY-MOORF/PRESFRVATIVTF PAINT No. 5780-563 ')TM ACRYI IC CI OSS, SAFFTY YFI I OW OR APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED. MIN '8" TO 20" BEHIND BACK OF CURB OR 12" BEHIND BACK OF 3° SIDFWA.LK THAT IS AC,,ACFNT TO CURB �4.875" x 5" STORZ /- TWO PIECE CAST IRON VALVE BCX WITH LUG 5'x5'xF." THICK CONCRFTF PAD AROUND / TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO. / HYDRANT. FINISH TO MATCH SIDEWALK. STANDARD 8" TOP SECTION WITH REGULAR BASE 0M7 i EXPANSION OINT AT / SECTION LENGTH TO FIT. VALVE NUT EXTENSION , BACK OF SIDEWALK AS REQUIRED. Z CONCRETE SIDEWALK RAISED PAVEMENT MARKER TYPE 88-A /rOR PLANTING STRIP / STIMSONITE TWO --WAY BLUE REFLECTIVE 36" MIN COVER CONCRETE BLOCKING CONCRETE THRUST BLOCK \ MAIN LINE TEE, WITH 6" FLANGE SIDE OUT -ET, 6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT 1, v-6" DUCTILE IRON PIPE, C =MENT LINED, LENGTH TO FIT 2-3/4" COR-TEN STEE_ T E ROD-_. 1F, x 8 x 4 MININUM J 1 /2 YARD OF 1-1/4" WASHED DRAIN ROCK uRETE BEARING 1' ABOVE BOOT FLANGE. PLACE 8 MIL flOCK UNDER HYDRANT PCLYE-HY_ENE FILM AROUND TOP AND SIDES OF GRAVEL. FIRE HYDRANT ASSEMBLY ✓LEVEL ALL GROJP<D LEVEL ALL GROUND MIN 3' RADIUS -- MIN 3' RADIUS Y ` \' ONE MAN ROCK 6" CONCRETE PAD L 6" COINER PAC CUT FI LL HYDRANT LOCATION N CUT OR FILL f� STD. PLAN - 310.1 P BLIC WORKS FIRE HYDRANT ASSEMBLY DEPARTMENT ;A1,C;f I ,'C 10 A A PLAN VIEW WATER > VALVE BOX LID WITH EARS IN DIRECTICN OF 2" SQUARE WATER MAIN AND WORD ✓ OPERATING NUT "WATER" CAST INTO IT 12" MIN ; 1B" MAX., 4' (ONCRETF Ol_AR FOR VALVES IN PAVED AREAS / 4-1/4" DIA. 12" 118 MIN. THICKNESS SEE DETAIL- ��- 2 PIECE CAST IRON VALVE / BOX, RICH-SEATTLE TYPE OR OLYMPIC FOUNDRY STEEL 1 -LENGTH LENGTH AS REQUIRED 1,/8" MIN. THICKNESS - 2-1/4" INSID'= MEASU <EMENT 2-1/4" DEPTH SECTION A -A VALVE OPERATING NUT EXTENSION VALVE ')P=RATION NUT EX-ENS!ON NOTE: FXTFNSIONS ARE RFQUIRFD WHFN VAI_VF NUT IS MORE THAN THREE (3) FEET BELOW FINISHED GRADE. EXTENSIONS ARE TC, BE A MINIMUM OF ONE (1) FOOT LONG. ONLY ONE EXTENSION TO BE UPER VALVE.SED E NOTE: ALL EXTENSIONS ARE TO BE MADE CF STEEL, SIZED AS NOTED, AND PAINTED WITH TWO COATS OF META'_ PAINT. VA'-VE MARKER NOTES: VA'-VE MARKERS S'-A'I-L BE EQUAL TO CARSON!TE UTILITY MARKER VA'-VE MARKER POST TO BE USED FOR ALL MAIN LINE VALVES OUTSIDE PAVED AREAS 3„ MIN. i WIDTH �- WHITE POST -_I 62" 24"I VALVE MARKER POST �'. PUT3t,IC" WORKS VALVE BOX, MARKER & OPERATING STD. PLAN - 330.1 _ 1>t,PAR('hIk v'L' NUT EXTENSION I MARCH 2010 5-364004 A PORTION OF SEC. 4, TWP. 23 N., RGE. E., W.M., KING COUNTY WASHINGTON - i I 11--1 / 4° BEND 22 1 /2° BEND 45° BEND CAP TEE 90° BEND -4PJST a PFA N S)H4P FEET (SEE NOTES) FOR HORIZONTA'_ AND DOWNWARD VERTICAL BENDS OMPACT SAND COMPACT SAND Rc GRAVEL. 45' & ND 90 45' BEND 1 t% 1TTIN OR CAP OR '_UG & 22 '/2' BEND "-EC CAP OR PLUG & 22 1 TC BEND BENE ry 4" I ! 4.2 4', i 29 2.1 2.1 1, l2 16 1.6 I-11 In E" 1 13.3 1 9.4 9.4 8 6.7 4.i 4.7 1.9 5,0 3.5 3.5 _ .4 u 8" 123.31 16.7 16.7 - . 1 : 113 8.4 8,4 3A 8.8 6.3 6. 3 - --~ 1. S 12" 153,01 37.5 37.5 1 5.D 26 5 18.8 18.8 7,5 20.0 1a.0 4.E 5.6 c AREAS CALCULATED ON 300 PSI TEST PRESSURE. 3'-0" MIN. COVER FCR WATERMAIN LESS THAN 12'. 4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER MAX. HEIGHT OF THRUST 3LOCK (FT) - 0.5 x DEPTH OF TRENCH MIN_ HEIGHT OF THRUST BLOCK (F-) = O.D. PIPE + 1.0' TRUST BLOCK BE, REA REFERS TO - ICE OF BOCK MI IN SQUARE FEET NOTES: i. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND FOR SOIL TYPES DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER. 2- ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND. 3. ALL POURED THRJST BLOCKS SHALL. BE BACKFILLED AFTER MIN. 1 DAv, PRESSURE TESTING SHALL CCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH. 4. ALL BLOCKING Sh+ALL 3E CONCRETE CL 5 i1-1/2 ;. 5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA POSSIB_E, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOAT BOLTS OR GLANDS REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED. I CONCRETE BLOCKING FOR STD. PLAN - 330.2 . PC FHIC WORKS I HORIZONTAL AND DOWNWARD - - �� D7,PARr141\�VERTICAL BENDS c}� I rel all skyjMMP►.I FINISHED GRADE E-EVATICN L COVER (10 :NCH DIAMETER AND UNDER) \.'J. C) FR: 12-INCH DIAMETER AND OVER) NEW 'WATER MAIN POLYFIG VFRTICAI CROSS FOR POI_YPIGS ING STATION: TEVPORARY 2" GALVANIZED PIPE AND 2." GATE VALVE INSTALL 2" PLUG ON TOP BLIND FLAB ;,.;F / AFTER REMOVAL OF POLYPIG SIZE OF VERTICAL CROSS SHALL BE THE SAME AS SIZE OF MAIN LINE VERTICAL CROSS (MJ X FL) ONE BLIND FLANGE ON TOP OF CROSS WITH 2" TAP & 2" TEMPORARY BLOW -OFF ASSEMBLI' (REMOVE BLOW -OFF ASSEMBLY AND INSTALL 2" PLUG AFTER REMOVAL OF CLEANING "POLY -PIG") ONE B'-IND FLANGE ON BOTTOM OF ;ROSS ONE PLUG (MJ) ON END OF CROSS CONCRETE BLOCKING ALL DEBRIS AND POLYPIGS SHALL BE REMOVED FROM SUM? OF VERTICAL CROSS BEFORE DISINFECTION OF NEW WATER MAIN PL L_WORKS POLY PIG STATION FOR CLEANING OF STD. PLAN - 300.6_ DP BAR 'e1 NT WATER MAINS z 120 VOLT ELECTRICAL OUTLET FOR -, HEAT TAPE. INS TALL HEAT TAPE a> FOR FREEZE PROTECTON CENTER BACKFLOV'J LJ ao REDUCED PRESSURE ENCLOSURE a �BACKFLOW ASSEMBLY -�{I o (RPBA) \� 13„ MIN. ` !! 3" MIN. / INSULATED ENCLOSURE \ 3" MIN. "HOT BOX" OR EQUAL 3/8" X 4" ANCHOR- BO'_TS PER MANUFACTURER \ 3" MIN. CONCRETE SLAB z UNION I �- FINISHED N \ GRADE FINISHED C,xAD I x71w't'7T w't GO DRAIN ' z j SEE NOTE 4 6" MINIMUM > I N­- SLEEVE FREE DRAINING / (TYP GRAVEL z s CONN=CT TO N WATER METER IMMED'ATELY ADJACENT TO RPBA �� \ FLOW INSTALLED VU/ APP'D. OWNERS ELECTRICAL PANEL. FRONT VIEW MATERIAL PLR 'UPC DIRECT BURIAL OR IN RIGID METER SIDE (SIZE AS REQ.) CCNDOIT PER ELECTRICAL SIDE VIEW' PERMIT REQUIREMENTS. NOTES: 1. ALL REDUCED PRESSURE BACKFLOW ASSEMBLIES (RPBA's; MUST BE LISTED ON -ATEST LIST OF "BACKFLOW PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASINGTON DEPARTMENT OF HEALTH. 2 THE OWNER/A?PL'CANT MJST OBTAIN A SEPARATE CITY OF RENTON PLUMBING 'HERMIT FOR THE INSPECTON OF THE INSTALLATION 0= THE RPBA AND PIPING. THE OWNER SHALL FURNISH, I'�STA.LL AND MAINTAIN THE RPBA AND ALL PIPING AND .APPURTENANCES SHOWN ON THIS PLAN. 3. THE RPBA. MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL_ INSTALLATION, AFTER REPAIRS AND ANNUA'-LY TI-EREA=TER AT OWNER'S EXPENSE. A COPY OF THE TEST REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON `NATER L-ILITY ENGINEERING DEPT., ATTN: WATER UTIL'-Y CROSS -CONNECTION CONTROL SPECIALSIT, FAX NO. 425-430-7241, 4. DRAIN SHALL BE SIZED IN ACCORDANCE WITH AWWA CROSS CONNECTION CON`'ROL MANUAL JIANDARDS 3" DRAIN FOR 1" OR SMAIJ FR RPBA's, 4" DRAIN FOR 1.5" TO 2" RPBA.'s, 6" FOR .3" RPBA'-. 5. RPBA AND ENCLOSURE SHA;_L B� LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE WATER METER. 'S PUBLIC WORKS REDUCED PRESSURE BACKFLOW STD. PLAN - 350.2 DEPARTMENT ASSEMBLY IN HOT BOX •�,N„Tp'� MARCH 2010 SURVEYED: DESIGNED: J. KELLY DRAWN: TDS CHECKED: D. NASON BY DATE APPR APPROVED: D. GAVIN SCALE AS NOTED ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY VERTICAL: NAVD 1908 HORIZONTAL NAD 1983/1991 DATU M REGISTEP, SHALL BE TOUCH READ PIT LID 4" POST INDICATOR VALVE (TR-PL) AND BE ':INTELLIGENT COMMUNICATION (MJxMJ) ?AINTED BLUE ENCODER TYPE (ICE). METER MUST READ !N CU. FT. \ J- 2-3/4" SHACKLE RCDS PER CITY OF RENTON SPECIFICATIONS 4" CIO' BEND (MJ) 4" 9C' BEND (MJ) \ - ----- - - - i-'NSTALL IN TES- PORT A 2"x2" -- TEE (MJx:=L) t2" �, '3 LF 4" D.I BRASS NIPPLE WITH w / GATE VALVE (FLxMJ) o 7' 0" ---� / A 2° RESILIENT z � V - .. SEATED BRASS C . / --- E ATE (/ LADDER WITH �--� VALVE AND 2" P_UG. z ( w �f-" g/ LADDER BARS , 2, 4' 4' FL.NL ADAPTOR PER OSHA 4" FLxMJ ADAPIUR 4° or 6" C.I. :... . ..:... TO SUi_DING FLOW ..� EPDXY NON SHRINK j\ / GROUT y2'-4" 4" TEE (MJxFL) WELDED S"EEL COLLAR -------! , GTY PRIVATE TOUCH READ PIT LID SENSOR MOUNTED CN - -� PIPING PIPING STEEL PLATE COVER THROUGH 2" CIA. DRI'._LED HOLE IN COVER. LOCATE HO-E 2)�' DEADMAN BLOCK FROM EDGE OF PIT LID AND RIBS. / 4' TEE J REQUIRED WITH (FL) SHACKLING TO TEE PRECAST CONCRETE VAULT WITH 2 3"x3" HINGED STEEL PLATE COVER OUTSIDE DIMENSiCINS 4-8"x7'-0 (EQUAL TO PIPE INC, OR LTILITY VAULT WITH SENSUS MODE' �20R RADIO 577L B, 2 �x3' DIAMOND PLATE CCORS) READ PIT SET SENSOR MOUNTED CN STEEL PLATE TAG PIECE CAST IRON VALVE BOX, 6".4" OR 3" GATE VALVE (FLxFL) I COVCR T IRDUGII 2" DIA, EQUAL TO OLYMPIC FOUNDRY CO. NDN-RISING STEM WITH HAND WHEEL � � DRI_LEC HOLE IN COVER / STANDARI 8" IOP SF.CUON, WI-IP EQUAL TO MUELLER CO.A-2380-6. J REGULAR BASE SECTION LENGTH TO =I- 6" OR 4" (FLxPE) CEMENT LINED DUCTILE IRON PIPE CLASS 52 3'-6" LONG WITH COLLAR 2)" FROM P.E. EQUAL IU IHDSf. SUPPLIED BY NACII TIC / VALVE NUT EXTENSION 1= REQUIRED WATER WORKS CO. INC. r"" 4 (DWG Bkc6-/FACE 8090) I \ ✓ 6", 4" OR 3" SATE VALVE (FLxMJ) EQUAL TO MUF(LFIR CO.A-2:580-70. .r TO BUILDING -�- FLOW I 12" AROUND AL I CITY PRIVATE s- 2" -� PIPING PIPING -'.,- 6" OR 4" PExPE CEMENT -- - - - - LINED DUC-ILE IRON PIPE c \ CLASS 52. LENGTH TO FIT. 6",4" OR 3" COMPOUND WATER METER (FL) J 11\ EQUAL TO SENSUS SRII CCMPOUND METER WITH \ TOUCHREAD PITUD I.C.E. REGISTER & SENSOR / WITH 4 WHEEL HIGH RESOLUTION (100 CUBIC ADJUSTABLE STEEL L- 6" OR 4" FLEXIBLE FLANGED FE_I; REG ,IEk FJ3 3" MET-R, REDUCE Al PIPE SUPPORT CDJI I.iNC ADAPTOR, ROMAC METER WITH 4"X3" FLxF_ CONCENTR'C STANCHION BOLTED OR APPROVED EQUAL. REDUC=R. TO FLOOR GENERAL. NOTES: ALL MEF=RS AND BACKFLOW PREVENIION DEVICE COM3INATIONS ARE NOT SHOWN OR INCLUDED IN THE STANDARD DETAIL DRAWINGS. F YOUR PARTICULAR COMBINATION IS NOT SHOWN, AN APPROVED DRAWING WILL BE REQUIRED BY THE UTILITY ENGINEERING DEPT. FOR ITS INSTALLATION. THE PRINCIPAL REQUIREMENTS REGARDING VAULT SIZING ARE THE LENGTH OF FITTINGS OR THEIR CLEARANCE FROM THE VAULT WA'_LS. (:WHICH CLEARANCE SHALL BE A MINIMUM OF 12" FROM THE ENDS AND THE SIDE CLEARANCE SHOULD BE AS TYP CALLY SHOWN ON THE `VARIOUS STANDARD CETAILS,'. NOTE: DEADMAN BLOCK SHALL BE DESIGNED AND INSTALLED SO IT BEARS AGAINST SUFFICIENT UND STURBED EARTH SO AS TO SUPPORT THE DESIGNED THRUST. PUBLIC WORKS 3", 4" & 6" COMPOUND DOMESTIC STD. PLAN - 320.4 N . DEPARTMENT WATER METER ASSEMBLY MARCH 2010 - CITY OF RENTON Planning/Building/Public Works Dept -712 Civil Engineers � S. Structural Engineers WA `�G og S81,1,G j Landscape Architects Community Planners (.? Land Surveyors Neighbors �cl IST S'IONAL NOTICE TACOMA • SEATTLE PROFESSIONAL SEX � AND SIGNATURE PUBUCATION OF E 2215 North 30th Street, Suite 300, Tacoma, WA 98403 INS DOWLENT DOES NOT DEROGATE FROM RESERVED OWNERSHIP RIGHTS IN IT. THIS DOCUMENT IS FOR USE 253.383.2422 TEL ONLY FOR THE PRO,ECT IDENTIFED IN THE TITLE BLOCK AND IS NOT TO BE USED FOR REPAIR, RI)KIDE OR 1200 Sixth Avenue, Suite 1620, Seattle, WA 98101 ADDITION TO THAT PROJECT OR FOR ANY OTHER PRO' 206.267.2425 TEL DATE: - EARLY CHILDHOOD LEARNING CENTER 6-22-2012 RENTON SCHOOL DISTRICT FIE.DE10m: PAGE -- DRAWING NO: SANITARY SEWER AND WATER DETAILS C8.4B SHEET: OF: 50 52 tt n zx 0 zx xo CD r 1 N 0 z 7� t EMEEMEEME