Utility Specifications
Sanitary Sewer Notes and Specifications
THESE NOTES SHALL. APPEAR ON PROJECTS FOR THE WASTEWATER UTILITY.
1. All work and work material shall be in conformance with the standards and specifications'
of the City of Renton Planning/Building/Public Works Department and the latest edition
of the WSDOT/APWA. Standards and Specifications, as approved and modified by the
City of Renton in the Renton Standard Plans & Specifications. A set of approved plans
shall be kept on site at all times during construction.
2. The hours of work in the street right of way shall be per' City specifications an weekdays
unless otherwise approved in writing by the Planning/Building/Public Works Department.
An approved traffic control plan must be obtained prior to beginning any work within
public right of way.
3. All locations of existing utilities shown are approximate and it shall be the contractor's
responsibility to verify the true and correct location so as to avoid damage or
disturbance.
4. A pre-cor0 „ ion conference and a 24 hour notice shall be required prior to starting
new cony- 1, on. It shall be the contractors responsibility to secure all necessary
permits p ; _3t to starting construction. (Inspection will be accomplished by a
representative of the City of Renton.) It shall be the contractors responsibility to notify
the Public Works inspector 24 hours in advance of backfilling all construction.
I
5. Contractor is solely responsible for the means, methods and sequences of construction
and for the safety of workers and others on the construction site.
6. It shall be the responsibility of the contractor to obtain street use and any other related
permits prior to any construction.
7. Plans approved by the City of Renton, Public Works Department shall take precedence
over all other plans.
i
8. A copy of these approved plans must be on the job site whenever construction is in
progress.
I
9. The contractor shall provide the City of Renton with an as -built drawing of the sanitary
sewer system, which has been stamped and signed by a licensed professional engineer
or licensed professional surveyor.
10. Backfill shall be placed equally on both sides of the pipe in layers with a loose average
depth of 6 inches, maximum depth of 8 inches, thoroughly tamping each layer to 95
percent of maximum density. These compacted layers must extend for one pipe
diameter on each side of the pipe or to the side of the trench. Materials to complete the
fill over pipe shall be the same as described.
11.Open cut road crossings for utility trenches on existing traveled roadway shall be
backfilled with crushed rock and mechanically compacted unless otherwise approved by
12. Datum for Vertical Control shall be North American Vertical Datum 1988 Meters, and for
Horizontal Control shall be North American Datum 1983/1991 Meters unless otherwise
approved by the City of Renton Public Works Department. Reference benchmark and
elevations are noted on the plans.
13. All disturbed areas shall be seeded and mulched or otherwise stabilized to the
satisfaction of the Departrnent for the prevention of on -site erosion after the completion
of construction.
14. All pipe and appurtenances shall be laid on a properly prepared foundation in
accordance with the standards and specifications of the City of Renton
Planning/BuildingjPublic Works Department and the latest edition of the WSDOT/APWA
Standards and Specifications, as approved and modified by the City of Renton in the
Renton Standard Plans & Specifications. This shall include necessary leveling of the
trench bottom or the bop of the foundation material, as well as placement and
compaction of required bedding material, to uniform grade so that the entire length of
the pipe will be supported on a uniformly dense, unyielding base. Pipe bedding shall be
pea gravel 6 inches above and below the pipe.
15. Sanitary sewer pipe shall be polyvinyl chloride (PVC) rubber gasketed ASTM D 3034,
SDR 35, or ductile iron class 50, unless otherwise approved by the Wastewater Utility.
16. In unimproved areas, manhole to extend minimum 6 inches and maximum 12 inches
above finished grade or must have minimum 2' diameter concrete ring poured at grade.
In paved area, cover must slope in all directions to match paving.
7' 1
NOT TO SCALE
MANHOLE FRAME AND COVER
SEE STD. PLAN 401
ADJUSTMENT RINGS (2" MIN.)
SEE NOTE 6
MORTAR JOINT(S) (3/8" MIN.)
SEE NOTE 5
CONE (ECCENTRIC)
RUBBER GASKETED JOINTS IN
ACCORDANCE WITH ASTM C-443
STEPS - POLYPROPYLENE STEPS
SHALL BE INCLUDED
CONCRETE RISER BY PIPE INC.,
OR APPROVED EQUAL.
LADDER -POLYPROPYLENE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIZE - 'E'
CONCRETE SHELF
PRECAST BASE SECTION
OR CAST IN SHELF.
'A'
B,
'C'
'D'
48" MH
48"
6" MIN.
5"MIN
24" MIN.
21" I.D.
54" MH
54'
8" MIN.
5.5" MIN.
24' MIN.
24" I.D.
60" MH
60"
8" MIN.
6" MIN.
42" MIN.
30" I.D.
NOTES:
1. STEPS TO BE POLYPROPYLENE SAFETY STEPS.
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASTING SHALL BE PER STD. PLAN 401.
4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, BRICKS AND CASTING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED WITH A COMBINATION OF
ADJUSTMENT RINGS, BRICKS AND MORTAR QNLY, BRICKS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1 /2 BOND. THE USE OF SHIMS IS pgoHIEMTEp,
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING,
COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC-AROSHIELD OR
APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE WITH ASTM C-443.
9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE.
10. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR-N-SEAL BOOTS OR
APPROVED EQUAL.
11. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6' AND A MAXIMUM OF 12'
ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS, COVER MUST SLOPE IN ALL. DIRECTIONS TO MATCH PAVING.
� PUBLtc woRxs am. PLAN- 400•1
DEPARTMENT * ' STANDARD SANITARY MANHOLE
SEPTEMBER 2011
PROPERTY LINE
i
FUTURE
6" BUILDING SEWER PIPE BUILDING SEWER
W
Z 2"x 4" STUD MARKING POST PAINTED
TEE WITH 6" SIDE OUTLET 6"X6"X6' WYE WHITE WITH THE WORD 'SEWER" STENCILED
SURFACE CLEANOUT WITH CAST IRON RING & COVER IN 3" HIGH BLACK LETTERS AND6 HARE
WRAPPED AROUND THE STUD AND
IL (EAST JORDAN IRON WORKS
0 2975 OR APPROVED EQUAL, EXTENDED TO THE TOP OF THE STUD.
a_ SPECIFY 'SEWER" ON LID,
6" SIDE SEWER AND BUN+ nIN�g SEE STD. PLAN 403.1 FOR
INSTALLATION)
ACCEPTABLE PROCEDURES FOR SIDE SEWER CONNECTIONS TO MAIN
LINES ARE AS FOLLOWS:
A. VITRIFIED CLAY MAIN - CUT IN A NEW TEE USING FLEXIBLE
COUPLINGS (FERNCO OR APPROVED EQUAL).
B. CONCRETE MAIN - CORE -DRILLED WITH A ROMAC SADDLE (OR
APPROVED EQUAL).
C. PVC MAIN - CORE -DRILLED WITH A ROMAC SADDLE (OR APPROVED
EQUAL) OR CUT IN A NEW TEE USING MC40 COUPLINGS.
D. DUCTILE IRON MAIN - CORE -DRILLED WITH A ROMAC SADDLE (OR
APPROVED EQUAL)
E. MANHOLE CONNECTION - ALL CONNECTIONS TO MANHOLES SHALL BE
AT MANUFACTURED KNOCK -OUTS OR THE
STRUCTURE SHALL BE CORE -DRILLED.
60" ALLOWABLE MAX.
FOR CAST IRON PIPE
OR DUCTILE IRON PIPE.
1:3:5 MIX
CONCRETE
BLOCKING
`- 6" SIDE OUTLET TEE
SEWER
6" MIN. MAIN
CONCRETE BLOCKING ANGLE
OF TEE AT MAIN OVER 25
E FVAnOr,I
NOTE:
UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEWER SHALL HAVE
A MINIMUM 2.5' COVER AT PROPERTY LINE OR 3-5 LOWER
THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER.
MAIN
OG ot�G
L✓� 2% MIN SLOPE
HORIZONTAL
��� Y v PUBLIC WORKS STANDARD SIDE SEWER STD. PLAN - 406.1
* DEPARTMENT INSTALLATION
`; ,j, o (SEWER MAIN TO PROPERTY LINE) SEPTEMBER 2011
BEDDING MATERIAL FOR
SANITARY SEWER PIPE
(SEE NOTE 6) -----\
FOUNDATION LEVEL
a
BEDDING FOR SANITARY SEWER PIPE
NOTES
1. PROVIDE UNIFORM SUPPORT UNDER BARREL.
2. HAND TAMP UNDER HAUNCHES_
3. COMPACT BEDDING MATERIAL TO 95% MAX. DENSITY EXCEPT DIRECTLY
OVER PIPE. HAND TAMP ONLY.
4. SF- _-1VATION AND PREPARATION OF TRENCH" IN THE SANITARY
:TION OF THE STANDARD SPECIFICATIONS FOR TRENCH
WIDTH "W" AND TRENCHING OPTIONS. THE PIPE ZONE WILL BE THE
ACTUAL TRENCH WIDTH.
5. TRENCH BACKFILL SHALL CONFORM TO "BACKFILLING" IN THE SANITARY
SEWER SECTION OF THE STANDARD SPECIFICATIONS, EXCEPT THAT
ROCKS OR LUMPS LARGER THAN 1" PER FOOT OF PIPE DIAMETER
SHALL NOT BE USED IN THE BACKFILL MATERIAL.
6. PIPE ZONE MATERIAL SHALL BE "GRAVEL BACKFILL FOR DRAINS" AS
SPECIFIED IN THE AGGREGATES SECTION OF THE STANDARD
SPECIFICATIONS.
7. PIPE MUST BE ANCHORED IN SUCH A MANNER AS TO ENSURE FLOW
LINE IS MAINTAINED.
ZY
PUBLIC WORKS PIPE BEDDING STD. PLAN - 405
DEPARTMENT FOR SANITARY SEWERS
MARCH 2O08
BOLTHOLES - 3 PLCS
EQUALLY SPACED 120"
APART (IN 23 1/16' (586nro)
DIA B.C. (SEE DETAIL)
_00�
RENTON
SEWER
w� w ur
COVER & FRAME
PLAN VIEW
25' DIA.
C635nn1 1'
3/4' r C25nM7
119nnl __.Ij.LL1LL
8 2 lf2'
C222mm2NhnI 164nrtl
TYP
COVER SECTION VIEW
26 1/2' DIA
C673nn1
25 1/4' DIA
C641nn1 1 1/16'
NEOPRENE
(Erin) p 27r,n3
NEOPRENE GASKET
C15j nn]
5/8' 23 3/8' DIA CL OPEN
116nnl 1594mml
27 5/16' DIA
C694nn1
34 1/8' DIA
roe -7 I _
COVER BOTTOM VIEW
BL_T SOC. (ALLEN HEAD)
5/8'-11 X 1.5 SS
RUBBER WASHER
EON BOLTING DETAIL
1/4'
I tail 1 1/16'
[27nn1
13nnl
1/8,
IR3nnl
GASKET GROOVE DETAIL
nn NOTES:
FRAME SECTION VIEW 1. ALL COVERS SHALL BE LOCKING I..ID PER EAST
JORDAN IRON WORKS INC. No. 3717C1 OR EQUAL.
2. USE FRAME AND COVER FOR STORM (SPECIFY
"DRAIN" ON COVER), SANITARY (SPECIFY
"SEWER"), OR WATER (SPECIFY "WATER").
PUBLIC WORKSNTD. PLAN - 401
��'�►1 DEPARTMENT MANHOLE FRAME AND COVER
i DECEMBER�2O��
4
LUA 07-140-SHPLI 1C.
C
v
0
V
`8
a
I
4-1
W�
3"
rw�
v
2j
WU)
Q
0
J
�
I
1��
�h
L.
N
Q.
S=366302J
Q- CL FQ-
or_
C,
947(3 �
�.rsT�� � z
SIONAL.�� < Q z
ct Cn
RECOMMENDED
FOR APPROVAL
BY DATE ,,5'
B DATE N
0
BY DATE N
BY DATE
X M
m 04 Sr-
:2 C)
BY DATE W0C
irl
rn
z�
Zm
�
m
ww ,,
�v
z�
rm >
x
W