HomeMy WebLinkAbout0931.1PRIMARY POWER HANDHOLE EQUAL TO PIPE INC #55400 W/ 550-13 COVER. NEW PRIMARY METERING CABINET BY PUGET POWER. LEAVE SUFFICIENT CABLE IN METERING CAB. FOR TERMINATION BY PUGET POWER. EXISTING POWER POLE REMOVE EXIST. TRANSFORMERS CONNECT TO NEW MTR CAB JI FUTURE 75 KVA TRANSFORMER PRIMARY CONDUCTORS TO BE INSTALLED BY CONTRACTOR. 1/0 AL, 15KV X-LINK POLY W/ CONCENTRIC NEUTRAL AND OUTER JACKET EXTRUSION. CABLE TO MEET PUGET POWER SPECS AND STANDARDS OF INSULATION. COORDINATE CABLE MARKINGS WITH PUGET POWER. NEW 500KVA TRANSFORMER 2-3"C, 3-500MCM + 1#4/0 THWN FOR SUPPLY TO ENGINE/GENERATOR /e/ REMOVE AND DISPOSE EXIST. BUILDING AND SYSTEM (BY OTHERS) a/// POWER POLE ee I EXIST POWER SUPPLY CONDUIT ,// ABANDON e eI ee e/e e, e FUTURE SUPPLY e/// TO E/G BLDG I e (BY OTHERS) eeI I ee Ie /e /e ee I / e, I / /I / '/ // i EXIST. METERING CABINET REMOVE AND DISPOSE EXISTING MOUNT OLIVET RESERVOIR ELECTRICAL SITE PLAN 1 "=5'-O" APPROX EXIST. DRAIN LINE (TYPICAL) (2) 3" CONDUIT FOR POWER SUPPLY (TYPICAL) METER VAULT (2) 1" CONDUIT, 24" BELOW GRADE - REMOVE AND DISPOSE. ALTITUDE VALVE VAULT WITH CATHODIC PROTECTION SYSTEM INSIDE. RELOCATE EXIST. CATHODIC PROTECTION SYSTEM TO EXIST PUMP STATION -SEE ELECTRICAL PLAN EXISTING WATERLINE (TYPICAL) r d 10 CITY OF RENTON DEPARTMENT OF PUBLIC WORKS MOUNT OLIVET PUMP STATION REHABILITATION ��W I 11 -5.20 1410 MARKET STREET ELECTRICAL SITE PLAN P.O. BOX 1180 KIRKLAND, WASH. 98033 0 j 2 FILE ENGR. RE`/IEWED SCALE DATE PLOT SHEET 20s 827 6400 1 FUTURE XFMR DRE DRE 7 1 88 ORIGINAL SCALE (INCHES) Engineering 2os 453 0241 MOP DRE RHH 1"=5'-0" JULY 01, 1988 5 4 9 NO. REVISION BY REVIEW DATE