HomeMy WebLinkAbout0931.1PRIMARY POWER HANDHOLE EQUAL
TO PIPE INC #55400 W/ 550-13 COVER.
NEW PRIMARY METERING CABINET
BY PUGET POWER. LEAVE
SUFFICIENT CABLE IN METERING
CAB. FOR TERMINATION BY
PUGET POWER.
EXISTING POWER POLE
REMOVE EXIST. TRANSFORMERS
CONNECT TO NEW MTR CAB
JI
FUTURE 75 KVA TRANSFORMER
PRIMARY CONDUCTORS TO BE INSTALLED BY CONTRACTOR.
1/0 AL, 15KV X-LINK POLY W/ CONCENTRIC NEUTRAL AND
OUTER JACKET EXTRUSION. CABLE TO MEET PUGET POWER
SPECS AND STANDARDS OF INSULATION. COORDINATE
CABLE MARKINGS WITH PUGET POWER.
NEW 500KVA TRANSFORMER
2-3"C, 3-500MCM + 1#4/0 THWN
FOR SUPPLY TO ENGINE/GENERATOR /e/ REMOVE AND DISPOSE EXIST.
BUILDING AND SYSTEM (BY OTHERS) a/// POWER POLE
ee
I
EXIST POWER SUPPLY CONDUIT
,// ABANDON
e eI
ee
e/e
e,
e
FUTURE SUPPLY e///
TO E/G BLDG I e
(BY OTHERS) eeI
I
ee
Ie
/e
/e
ee
I /
e, I
/ /I
/
'/ //
i
EXIST. METERING CABINET
REMOVE AND DISPOSE
EXISTING MOUNT
OLIVET RESERVOIR
ELECTRICAL SITE PLAN
1 "=5'-O" APPROX
EXIST. DRAIN LINE (TYPICAL)
(2) 3" CONDUIT FOR POWER SUPPLY
(TYPICAL)
METER VAULT
(2) 1" CONDUIT, 24" BELOW GRADE -
REMOVE AND DISPOSE.
ALTITUDE VALVE VAULT WITH
CATHODIC PROTECTION SYSTEM INSIDE.
RELOCATE EXIST. CATHODIC PROTECTION
SYSTEM TO EXIST PUMP STATION
-SEE ELECTRICAL PLAN
EXISTING WATERLINE (TYPICAL)
r d
10 CITY OF RENTON DEPARTMENT OF PUBLIC WORKS
MOUNT OLIVET PUMP STATION REHABILITATION
��W I
11 -5.20
1410 MARKET STREET ELECTRICAL SITE PLAN
P.O. BOX 1180
KIRKLAND, WASH. 98033
0 j 2 FILE ENGR. RE`/IEWED SCALE DATE PLOT SHEET
20s 827 6400 1 FUTURE XFMR DRE DRE 7 1 88
ORIGINAL SCALE (INCHES) Engineering 2os 453 0241 MOP DRE RHH 1"=5'-0" JULY 01, 1988 5 4 9
NO. REVISION BY REVIEW DATE