HomeMy WebLinkAbout1748.1GEN ER A L IE :
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS AND THESE PLANS.
2. THE LOCATIONS OF FEATURES SHOWN ARE
APPROXIMATE AND SHALL BE VERIFIED IN THE
FIELD BY THE CONTRACTOR AS NECESSARY.
3. INSTALL ALL STREET LIGHTING MATERIALS
SHOWN ON THE PLANS, EXCEPT AS NOTED.
ALL MATERIALS SHALL BE NEW AND OF THE
BEST AVAILABLE GRADE OR QUALITY, EXCEPT
AS NOTED.
4. THE CONTRACTOR SHALL SUBMIT A REQUEST TO
THE CITY OF RENTON FOR MATERIALS APPROVAL
AT THE EARLIEST POSSIBLE DATE.
5. ALL WORK SHALL BE CONSISTENT WITH UTILITY
AGENCY REQUIREMENTS. THE CONTRACTOR SHALL
CONTACT ,ALL PERTINENT UTILITY AGENCIES 48
HOURS BEFORE COMMENCING WORK, AND SHALL
COORDINATE THE WORK WITH THE UTILITIES
THROUGHOUT THE PROJECT.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ANY DAMAGE TO EXISTING UTILITIES. THE
CONTRACTOR SHALL NOTIFY THE AFFECTED
UTILITY COMPANY AND THE CITY IMMEDIATELY
UPON DAMAGE.
J7.1
,4 n12x {3' u
N GO'd5•Jf' E
01 1°
7. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON
TRAFFIC ENGINEERING DIVISION (PHONE 235-2620)
FOR INSPECTION PURPOSES, 24 HOURS BEFORE
COMMENCING WORK. NO WORK SHALL BE COVERED
UNTIL IT HAS BEEN EXAMINED BY THE ENGINEER.
8. THE CONTRACTOR SHALL INSPECT EACH STREET LIGHTING
STANDARD INCLUDING WIRING, CONNECTIONS AND LUMINAIRE,
AND REPAIR ALL DEFECTIVE WIRING AND CONNECTIONS
PRIOR TO ENERGIZING SYSTEM. OTHER DEFECTS SHALL BE
BROUGHT TO THE ATTEN110N OF THE CITY OF RENTON
TRAFFIC ENGINEERING DIVISION FOR RECTIFICATION PRIOR
TO ENERGIZATION OF THE SYSTEM.
X ;�S' 3.
SNS
i
F
00
a
RECOMMENDED
FOR APPROVAL
7- Fcj
-t -7 $9
m
o� \
9+00
� 12+00
1
x
14+00
13+00
11+0t.7<,
10+00 11+
FLAG N C TE :
PROVIDE NEW SERVICE WIRING TO EXISTING STREET
LIGHTING CONTACTOR CABINET. PROVIDE NEW CONCRETE
BASE AND INSTALL SERVICE RACEWAY. PROVIDE NEW
GROUND ROD & NEW GROUNDING ELECTRODE CONDUCTOR.
RECONNECT ALL EXISTING WIRING.
CONNECT TO PSP&L 50 KVA 120/240 VOLT, 1 PHASE,
3 WIRE PAD MOUNTED TRANSFORMER.
REMOVE EXISTING TEMPORARY METER, ENCLOSED
BREAKERS, WIRING, AND SUPPORT STRUCTURE NEAR
STREET LIGHTING CONTACTOR CABINET.
,
VERIFY EXACT LOCATION OF BURIED SEWER, STORM, AND
WATER UTILITIES PRIOR TO INSTALLATION OF RACEWAY.
LEGEND
®' -� EXISTING LIGHTING STANDARD AND NO. SYMBOL
( KIM EKG 401, 250 WATT )
— — PVC CONDUIT. SEE WIRING SCHEDULE
® STREET LIGHT CONTACTOR CABINET
® TYPE 1 JUNCTION BOX (EXISTING)
TYPE 2 JUNCTION BOX
T� UTILITY CO. PAD MOUNTED SERVICE TRANSFORMER
WIRE SCHEDULE SYMBOL
FLAG NOTE SYMBOL
SCALE I "=40'
17Vk
Sparling & Associates, Inc.
ELECTRICAL ENGINEERS
1920 Eastlake Avenue East
Seattle, Washington 98102
(206) 324-1555