HomeMy WebLinkAboutExh_03_Plan_Drawings223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
3/15/2023 4:56:11 PM
102987.00
1601 LIND AVE SW
RENTON WA 98057
CONDITIONAL USE PERMIT
UW DLMP CENTRAL LABS TI
UW DLMP
Exhibit 3
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
GENERAL NOTES
1. DRAWINGS HAVE BEEN PREPARED ON AN ORIGINAL SHEET SIZE OF 36" x 48".
2. HORIZONTAL DIMENSIONS SHOWN INDICATE FACE OF CONCRETE, FACE OF SHEATHING, CENTERLINE
OF COLUMN GRIDLINE, OR FACE OF FINISH (INTERIOR), UNLESS OTHERWISE NOTED. VERTICAL
DIMENSIONS INDICATE TOP OF SLAB, TOP OF SUBFLOOR, UNLESS OTHERWISE NOTED.
3. THESE DRAWINGS ARE THE EXCLUSIVE PROPERTY OF NBBJ AND HAVE BEEN PREPARED FOR USE IN
THE EXECUTION OF THE ENCLOSED PROJECT. USE OR REPRODUCTION FOR ANY OTHER PURPOSE
WITHOUT THE WRITTEN PERMISSION OF NBBJ IS PROHIBITED.
PROJECT NARRATIVE
THE UNIVERSITY OF WASHINGTON DEPARTMENT OF LABORATORY MEDICINE AND PATHOLOGY IS PROPOSING TO
CONSOLIDATE THE MAJORITY OF THEIR NON-EMERGENCY TESTING FACILITIES INTO AN OFF-SITE LOCATION AT AN
EXISTING OFFICE BUILDING LOCATED AT 1601 LIND AVE SW, RENTON, WA 98057 (APN 3340404006). ADDITIONAL
MEDICINE TESTING LAB FACILITIES, SUPPORT OFFICES AND AMENITIES WOULD OCCUPY THE REMAINING FLOORS
(2-5). LEVEL 1 IS CURRENTLY OCCUPIED BY UW DLMP BUT WILL BE REVISED TO MEET THE NEW PROGRAM. THE
CURRENT SIZE OF THE TESTING LAB IS APPROXIMATELY 15,240 SF OF LEVEL 1. THE ENTIRE BUILDING IS LEASED BY
THE UNIVERSITY OF WASHINGTON. NOTE THE UPPER FLOORS OF THE BUILDING ARE PREDOMINANTLY VACANT
OFFICE SPACE.
RENOVATIONS TO THE INTERIOR OF BUILDING WILL BE REQUIRED TO SUPPORT THE TECHNICAL EQUIPMENT AND
LAYOUT TO SUPPORT THE WORKFLOW. NEW FINISHES, CEILINGS, INTERIOR PARTITIONS, AND DOORS (INCLUDING
CARD ACCESS SECURITY) WILL BE REQUIRED, IN ADDITION TO NEW ELECTRICAL, DATA, MECHANICAL EQUIPMENT,
AND NEW SINKS (HAND-WASH AND LAB USE). NEW AIR HANDLING UNITS TO PROVIDE 100% OUTSIDE AIR FOR LAB
SAFETY IS REQUIRED AND WILL BE LOCATED ON THE UPPER ROOF. ADDITIONAL MECHANICAL SCREENING WILL BE
REQUIRED. RESTROOMS TO BE ADDED OR MODIFIED TO SUPPORT CURRENT STANDARDS. NEW SCREENING MAY BE
REQUIRED FOR EXPANDED GENERATOR YARD LOCATED AT GRADE. NO TREES OR LANDSCAPE PLANNED TO BE
REMOVED AS PART OF THIS PROJECT.
THIS TESTING LAB WILL CONTAIN EQUIPMENT TO PERFORM SEVERAL TESTS ON SAMPLES THAT ARE COLLECTED IN
OTHER LOCATIONS AND COURIERED TO THE FACILITY USING SMALL COURIER VEHICLES INCLUDING CARS AND
SMALL PANEL TRUCKS (I.E., FEDEX). PATIENTS REQUIRING TESTING ARE NOT EXPECTED TO VISIT THE SITE.
THE EXPECTED HOURS OF OPERATION WILL BE 24/7. APPROXIMATELY A TOTAL OF 600 - 750 FULL TIME STAFF WILL
BE EMPLOYED (300-375 DAY, 180-225 EVENING & 120-150 NIGHT SHIFTS).
THE 5.29-ACRE SITE IS LOCATED IN THE COMMERCIAL OFFICE (CO) ZONE, URBAN DESIGN DISTRICT ‘D’, AND THE
EMPLOYMENT AREA COMPREHENSIVE PLAN LAND USE DESIGNATION. THE ADJACENT PROPERTIES ARE CO AND IM
(MEDIUM INDUSTRIAL). THE CURRENT USE OF LEVEL 1 IS A MEDICAL TESTING LAB, AND THE REMAINDER OF THE
BUILDING IS OFFICE USE. THE PROPOSED USE FOR THE ENTIRE BUILDING IS A MEDICAL TESTING LAB.
“LABORATORIES: RESEARCH, DEVELOPMENT, AND TESTING” ARE SPECIFIED AS AD (ADMINISTRATIVE CONDITIONAL
USE) UNDER THE CO ZONING DESIGNATION.
LEGAL DESCRIPTION
LEGAL DESCRIPTION:
PARCEL A:
LOT 2, CITY OF RENTON SHORT PLAT NUMBER 431-79, ALSO KNOWN AS VALLEY OFFICE & INDUSTRIAL PARK –
SUBDIVISION NO. 1, RECORDED UNDER RECORDING NUMBER 8002269013, IN KING COUNTY, WASHINGTON;
EXCEPT THOSE PORTIONS THEREOF CONVEYED TO THE CITY OF RENTON FOR STREET PURPOSED BY DEEDS
RECORDED UNDER RECORDING NUMBERS 8007070464, 8008200077 AND 8202160354.
KING COUNTY DEPARTMENT OF ASSESSMENTS LEGAL:
HILLMANS EARLINGTON GARDENS #1 LOT 2 LESS ST - CITY OF RENTON SP #431-79 REC #8002269013 SD SP DAF - ALL
OF VAC BLKS 24 & 31 & VAC VALENTINE AVE BET SD BLKS OF SD SUBD LY S OF S MGN OF SW 16TH ST LESS STS
PARCEL NUMBER: 334040-4006
GENERAL PROJECT INFORMATION
THE PROPOSED PROJECT IS FOR TENANT IMPROVEMENTS OF AN EXISTING OFFICE BUILDING TO SUPPORT
TECHNICAL EQUIPMENT AND LABORATORY WORKFLOW. THE PROPOSAL INCLUDES A CHANGE OF USE TO
LABORATORIES: TESTING AND RESEARCH FOR FLOORS 2 THROUGH 5. CURRENTLY FLOOR 1 IS A LABORATORY
USE. TENANT IMPROVEMENT SCOPE INCLUDES THE ENTIRE 2ND, 3RD, 4TH AND 5TH FLOORS AS WELL AS ROOFTOP
ALTERATIONS INCLUDING STRUCTURAL AND MECHANICAL ENHANCEMENTS. THE ENTIRE 1ST FLOOR WILL BE A
TENANT IMPROVEMENT COMPLETED IN PHASES PER THE CLIENT. NEW FINISHES, CEILINGS, INTERIOR PARTITIONS,
AND DOORS (INCLUDING ACCESS SECURITY) WILL BE REQUIRED, IN ADDITION TO NEW ELECTRICAL, DATA,
MECHANICAL EQUIPMENT, AND NEW SINKS (HAND-WASH AND LAB USE). NEW AIR HANDLING UNITS TO PROVIDE
100% OUTSIDE AIR FOR LAB SAFETY IS REQUIRED AND WILL BE LOCATED ON THE UPPER ROOF. NEW
TRANSFORMERS AND GENERATORS WILL ALSO BE PROVIDED.
THE BUILDING IS NOT CLASSIFIED AS A HIGH-RISE AND THE HIGHEST OCCUPIED LEVEL IS LESS THAN 75’ABOVE THE
LOWEST LEVEL OF FIRE DEPARTMENT ACCESS. A NEW MECHANICAL/ PLUMBING PENTHOUSE IS PROPOSED TO
SUPPORT NEW MECHANICAL AND PLUMBING NEEDS.
WORK INCLUDES:
• STRUCTURAL MODIFICATIONS FOR STRENGTHENING FLOOR AREAS TO MEET VIBRATION REQUIREMENTS,
SUPPORT NEW EQUIPMENT AND SHAFT PENETRATIONS.
• DEMOLITION OF NON-STRUCTURAL PARTITIONS AND FINISHES.
• MECHANICAL, ELECTRICAL, PLUMBING AND FIRE SAFETY SYSTEMS TO SUPPORT PROPOSED USE
• NEW SERVICE ELEVATOR TO SUPPORT THE LAB FUNCTIONS.
PROJECT NAME: UW DLMP CENTRAL LABS
PROJECT SITE ADDRESS: 1601 LIND AVE SW, RENTON WA 98057
ZONING: COMMERCIAL OFFICE (CO)
SITE FEATURES: FLOOD HAZARD AREA (100 YEAR)
CURRENT USES (EXISTING BUILDING):
LABORATORIES: RESEARCH, DEVELOPMENT AND TESTING - LEVEL 1
OFFICE - LEVELS 2-5
PROPOSED USES:
PRINCIPLE USE: LABORATORIES: RESEARCH, DEVELOPMENT AND TESTING - LEVELS 1-5
ACCESSORY USE: OFFICE, GENERAL
PARCEL NO: 3340404006
FLOOR AREA (EXISTING) 197,446 SF APPROX
LOT AREA: 230,430 SF (5.29 AC)
PROJECT AREA OF WORK:
GROUND FLOOR: 39,888 SF
SECOND FLOOR: 38,332 SF
THIRD FLOOR: 38,332 SF
FOURTH FLOOR: 38,332 SF
FIFTH FLOOR: 38,332 SF
ROOF: 2,460 SF MECHANICAL PENTHOUSE & STRUCTURAL / MECHANICAL UPGRADES
TOTAL AREA OF WORK: 195,676 SF
GENERAL PROJECT DESCRIPTION
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:11 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
SHEET INDEX,
GENERAL
INFORMATION &
CODE SUMMARY
GI002-A2
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
DRAWING INDEX
SHEET # SHEET NAME
00-GENERAL
GI001 COVER SHEET
GI002-A2 SHEET INDEX, GENERAL INFORMATION & CODE SUMMARY
GI004 LAND USE SUMMARY & NEIGHBORHOOD DETAIL MAP
GI005 LANDSCAPE DIAGRAM
00-GENERAL: 4
06-STRUCTURAL
S107 GENERATOR YARD PLAN AND DETAILS
06-STRUCTURAL: 1
07-ARCHITECTURAL
AS101-A2 ARCHITECTURAL SITE PLAN
AS102 ARCHITECTURAL SITE PLANS - ENLARGED
AE001 ARCHITECTURAL NOTES AND SYMBOLS
AD102-A1 F2 ARCHITECTURAL DEMOLITION PLAN
AD103-A1 F3 ARCHITECTURAL DEMOLITION PLAN
AD104-A1 F4 ARCHITECTURAL DEMOLITION PLAN
AD105-A1 F5 ARCHITECTURAL DEMOLITION PLAN
AD106 ROOF ARCHITECTURAL DEMOLITION PLAN
AE101-A1 F1 FLOOR PLAN
AE102 F2 FLOOR PLAN
AE103 F3 FLOOR PLAN
AE104 F4 FLOOR PLAN
AE105 F5 FLOOR PLAN
AE106 R1 ROOF PLAN
AE201 EXTERIOR ELEVATIONS
AE202 EXTERIOR ELEVATIONS
07-ARCHITECTURAL: 16
TOTAL SHEETS: 21
INCLUDES WRITE-UP AND OTHER SUPPORT FUNCTIONS WITHIN LAB CONTROL AREA
APPROXIMATE LABORATORY GROSS FLOOR AREA
F1 19,631 SF
F2 27,283 SF
F3 27,283 SF
F4 27,283 SF
F5 12,515 SF
113,997 SF
COMPLIANCE PATH: ENERGY MODELING OR PRESCRIPTIVE - TBD
ENERGY CODE
SEISMIC DESIGN CATEGORY:D IBC 1613.3.5
RISK CATEGORY:II IBC T1604.5
STRUCTURAL
A, H-3 20'
GROUP B, S, SPRINKLERED:50' IBC 1020.4
• WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS REQUIRED
CORRIDOR MAXIMUM DEAD END (IBC)
H-3 150' (SPRINKLERED)
B 300' (SPRINKLERED)
A, S-1 250' (SPRINKLERED)
OCCUPANCY MAXIMUM TRAVEL DISTANCE
(SPRINKLERED)
IBC T1017.2
EXIT ACCESS TRAVEL DISTANCE (IBC)
GROUP S 29 100' (SPRINKLERED)
H-3 3 25' (SPRINKLERED)
GROUP B 49 100' (SPRINKLERED)
GROUP A, M 49 75' (SPRINKLERED)
OCCUPANCY
GROUP
MAXIMUM
OCCUPANT LOAD
MAXIMUM
COMMON PATH OF
TRAVEL
(SPRINKLERED)
IBC T1006.2.1
SPACES WITH SINGLE EXIT (IBC)
OTHER EGRESS COMPONENTS: 0.2" / OCCUPANT IBC 1005.3.2
STAIRWAYS: 0.3" / OCCUPANT IBC 1005.3.1
EGRESS WIDTH FACTORS (IBC)
OUTDOOR AREAS 15 NET IBC 1004.7
LOCKER ROOMS 50 GROSS
EXERCISE ROOMS 50 GROSS
BUSINESS AREAS 150 GROSS
ASSEMBLY - UNCONCENTRATED 15 NET
STORAGE / MECHANICAL 300 GROSS
FUNCTION OF SPACE:OCCUPANT LOAD
FACTOR:
IBC T1004.5
OCCUPANT LOAD FACTORS (IBC)
MEANS OF EGRESS
MAXIMUM FLOOR AREA PER
EXTINGUISHER:
11,250 SF
IBC T906.3(1)
FIRE EXTINGUISHER TYPE / SIZE: 4A-80B:C
HAZARD CLASS: ORDINARY HAZARD - TBD NFPA 10
PORTABLE FIRE EXTINGUISHERS (IBC)
YES: NFPA 13 IBC 903
AUTOMATIC SPRINKLER SYSTEM (IBC)
FIRE PROTECTION
GROUPS A, B, H, S DOC FF-1 OR CLASS II (SPRINKLERED)
EXCEPTIONS: WOOD, VINYL, LINOLEUM, TERRAZZO, RESILIENT FLOORING THAT ARE NOT
COMPRISED OF FIBERS IBC 804.1
INTERIOR FLOOR FINISH REQUIREMENTS (IBC)
SET-OUT CONSTRUCTION CLASS A MATERIALS IBC 803.15.2
• NOT REQUIRED IF CONCEALED SPACE IS
CUSTRUCTED OF NONCOMBUSTIBLE MATERIALS
FURRED CONSTRUCTION FIREBLOCKED AT 8' O.C. BOTH DIRECTIONS IBC 803.15.1.1
S CLASS C CLASS C CLASS C
H CLASS B CLASS B CLASS C
B CLASS B CLASS C CLASS C
A CLASS B CLASS B CLASS C
OCCUPANCY (SPRINKLERED) EXIT
ENCLOSURES
CORRIDORS ROOMS AND
SPACES
IBC T803.13
INTERIOR WALL AND CEILING FINISH REQUIREMENTS (IBC)
SMOKE PARTITION ELEVATOR LOBBY NONRATED 710 / 3006.1
H-3 | A OCCUPANCY SEPARATION 2 HOUR 707 / 508.4
H-3 | B OCCUPANCY SEPARATION 1 HOUR 707 / 508.4
HORIZONTAL EXIT 2 HOUR 707 / 1026.1
EXIT PASSAGEWAYS 2 HOUR 707 / 1024.3
FIRE BARRIER SHAFTS / STAIR ENCLOSURE 2 HOUR 707 / 713 / 1023.1
TYPE: LOCATION: FIRE RATING: IBC
INTERIOR PARTITIONS (IBC)
PENTHOUSE 20' OR MORE NONRATED IBC 1510.2.4
30' OR MORE NONRATED
FIRE SEPARATION DISTANCE: FIRE RATING:
EXTERIOR WALL FIRE RESISTANCE RATINGS (IBC)IBC T602
ROOFS 1 HOURS
FLOORS 2 HOURS
• NOT LESS THAN RATING REQUIRED
BY OTHER SECTIONS OF THE CODE
INTERIOR NONBEARING WALLS 0 HOURS
• WHERE SUPPORTING ROOF ONLY 1 HOURS
INTERIOR BEARING WALLS 2 HOURS
EXTERIOR BEARING WALLS 2 HOURS
• WHERE SUPPORTING ROOF ONLY 1 HOURS
PRIMARY STRUCTURAL FRAME 2 HOURS
FIRE RESISTANCE RATINGS FOR BUILDING ELEMENTS (IBC)
TYPE I-B (TYPE
II-FR)
IBC T601
FIRE RESISTIVE CONSTRUCTION
BUILDING AREA 199,500.00 UNLIMITED 201,487 IBC 506
ROOF PENTHOUSE UNLIMITED 1,987
LEVEL 5 39,903.00 UNLIMITED NO CHANGE
LEVEL 4 39,903.00 UNLIMITED NO CHANGE
LEVEL 3 39,903.00 UNLIMITED NO CHANGE
LEVEL 2 39,903.00 UNLIMITED NO CHANGE
LEVEL 1 39,888 UNLIMITED NO CHANGE IBC T506.2
FLOOR AREAS (SQUARE FEET)
STORIES 5 STORIES 12 STORIES IBC T504.4
HEIGHT ±77'-8" EXISTING 180'-0"IBC T504.3
EXISTING ALLOWABLE PROPOSED
ALLOWABLE HEIGHT AND AREA (IBC)
YES: NFPA 13 - SEE FIRE PROTECTION SECTION
SPRINKLERED BUILDING
TYPE I-B (TYPE II-FR)IBC 602, T601
CONSTRUCTION TYPE (IBC)
ALTERATIONS COMPLY WITH IBC FOR NEW CONSTRUCTION 503.1
PRESCRIPTIVE COMPLIANCE
TOILET ROOMS - FULLY ACCESSIBLE (EXCEPT F4)
ALL RESTROOM FINISHES TO BE REPLACED AND MADE
ACCESSIBLE. NEW SINGLE-USER RESTROOMS TO BE...
305.8.10-11
PROPOSED IMPROVEMENTS TO MEET 20% RULE 305.7
ALTERATIONS AFFECTING PRIMARY FUNCTION - YES 305.7
COMPLETE CHANGE OF OCCUPANCY - YES 305.4.2
ACCESSIBILITY
NO INCREASE IN DESIGN LIVE LOAD ON EXISTING
BUILDING
303
STRUCTURAL DESIGN
H-3 ACCESSORY HIGH-HAZARD
IBC 307.1
S-1 STORAGE, MODERATE HAZARD IBC 311.2
B BUSINESS IBC 304.1
A-3 ASSEMBLY - GENERAL
IBC 303.4
OCCUPANCY GROUPS (PER IBC)
PRESCRIPTIVE 301.3
COMPLIANCE METHOD
PROJECT SCOPE ALTERATIONS 301.2, 301.3
• REFERENCES
ARE IEBC UNO
SUBJECT:PROJECT SPECIFIC:REFERENCE:
2016 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
2016 NFPA 13 STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2014 NFPA 70 NATIONAL ELECTRICAL CODE
2018 UNIFORM PLUMBING CODE - WA STATE AMENDMENTS, WAC 51-56 & 51-57
2018 INTERNATIONAL MECHANICAL CODE - WA STATE AMENDMENTS, WAC 51-52
2018 WASHINGTON STATE ENERGY CODE (WSEC)
2018 INTERNATIONAL FIRE CODE - WA STATE AMENDMENTS, WAC 51-54A
2018 INTERNATIONAL BUILDING CODE - WA STATE AMENDMENTS, WAC 51-50
2018 INTERNATIONAL EXISTING BUILDING CODE - WA STATE AMENDMENTS, WAC 51-50-480000
APPLICABLE CODES AND STANDARDS
JURISDICTION: CITY OF RENTON WA
BUILDING CODE SUMMARY
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
PROJECT SITE
CURRENT USES:
LABORATORIES:RESEARCH, DEVELOPMENT AND TESTING
OFFICES, GENERAL
PROPERTY LINE
PROPERTY LINEPROPERTY LINEPROPERTY LINELIND AVE SWVACANT (COMMERCIAL)
UTILITY, PUBLIC
DAYCARE CENTER (VACANT)
SW 16TH ST
I-405
SW 19TH STRAYMOND AVE SWEAST VALLEY RD1000'-0" RADIUS FROM PROJECT SITE
R 1 0 0 0 ' - 0 "HWY 167SENECA AVE SWMAPLE AVE SWTAYLOR AVE SWOFFICE PARK
WAREHOUSE
OFFICE BUILDINGOFFICE BUILDING
VACANT (INDUSTRIAL)
* STORAGE BUILDING
USE NOT LISTED
* OFFICE BUILDING
USE NOT LISTED
* STORAGE
USE NOT LISTED
* VACANT
WAREHOUSE
NOTE: PRESENT USES SHOWN ARE FROM COR MAPS DATA
SERVICE BUILDING
PARKING (COMMERCIAL LOT)
HIGH TECH / HIGH FLEX
WAREHOUSE
WAREHOUSE
ROW / UTILITY, ROAD
INDUSTRIAL (LIGHT)
VACANT (INDUSTRIAL)
VACANT (INDUSTRIAL)
WAREHOUSE
OFFICE BUILDING
TAVERN / LOUNGE
INDUSTRIAL
(GEN PURPOSE)
OFFICE BUILDING OFFICE BUILDING
OFFICE BUILDING
VACANT (COMMERCIAL)
VACANT (COMMERCIAL)
VACANT (COMMERCIAL)
HOTEL / MOTEL
HOTEL / MOTEL HOTEL / MOTEL
HOTEL / MOTEL
OFFICE BUILDING GOVERNMENTAL SERVICE VACANT (COMMERCIAL)VACANT (COMMERCIAL)
WAREHOUSEWAREHOUSEVACANT
(COMMERCI
AL)RI
VER
/
CREEK
/
STREAMOFFICE PARK
VACANT (INDUSTRIAL)VACANT(INDUSTRIAL)CHURCH /WELFARE /RELIG SRVCVACANT(INDUSTRIAL)VACANT(INDUSTRIAL)OFFICE BUILDING
AUTO SHOWROOM & LOT
WAREHOUSE
AUTO SHOWROOM & LOT
VACANT (COMMERCIAL)SR 167I-405
I-5PROJECT
LOCATION
VICINITY LOCATION MAP
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:14 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
LAND USE
SUMMARY &
NEIGHBORHOOD
DETAIL MAP
GI004
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1" = 100'-0"A2 NEIGHBORHOOD DETAIL MAP
NOT APPLICABLE - PROJECT IS NOT RESIDENTIAL OR MIXED USE
SPECIAL DEVELOPMENT STANDARDS:
SHORELINE MASTER PROGRAM REGULATIONS NOT APPLICABLE 4-3-090
ENVIRONMENTAL REVIEW:
CHANGE OF USE IN A BUILDING OVER 4,000 SQUARE FEET WOULD REQUIRE ENVIRONMENTAL REVIEW IN ACCORDANCE WITH THE STATE
ENVIRONMENTAL POLICY ACT WAC 197-11-800. IN ADDITION, CRITICAL AREAS ARE PRESENT ON THE SUBJECT SITE.
AN ENVIRONMENTAL CHECKLIST HAS BEEN SUBMITTED WITH THE LAND USE APPLICATION.
PROPOSALS AND OTHER ALTERATIONS SHALL NOT REDUCE THE EFFECTIVE BASE FLOOD
STORAGE VOLUME OF THE FLOODPLAIN
ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS SHALL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE, OR LATERAL
MOVEMENT OF THE STRUCTURE RESULTING FROM HYDRODYNAMIC AND HYDROSTATIC LOADS INCLUDING THE EFFECTS OF BUOYANCY.
PROPOSED EMERGENCY GENERATORS, FUEL TANKS AND UTILITY TRANSFORMERS WILL BE ANCHORED TO HOUSEKEEPING PADS
SITE IS MAPPED WITH HIGH SEISMIC HAZARD AREAS, AND SPECIAL FLOOD HAZARD AREA (100 YEAR FLOOD) FEMA ZONE –AE 4-3-050
CRITICAL AREAS:
REFUSE AND RECYCLING: SECTION IS APPLICABLE TO "NEW" DEVELOPMENT, HOWEVER EXISTING DEVELOPMENT IS UNDERSIZED AND DOES NOT
MEET MINIMUM STANDARDS BY THIS SECTION AND WILL BE EXPANDED IN NON LANDSCAPED AREA.
OTHER NONRESIDENTIAL DEVELOPMENTS – MINIMUM SIZE:
A MINIMUM OF 3 SF PER 1,000 SF OF BUILDING GROSS FLOOR AREA SHALL BE PROVIDED FOR RECYCLABLES DEPOSIT AREAS
A MINIMUM OF 6 SF PER 1,000 SF OF BUILDING GROSS FLOOR AREA SHALL BE PROVIDED FOR REFUSE DEPOSIT AREAS.
GROSS BUILDING AREA (KING COUNTY ASSESOR): 200,680 GSF
200,680 SF / 1,000 SF = 200.68
RECYCLABLES 200.68 x 3 = 602 SF
REFUSE: 200.68 x 6 = 1,204 SF
TOTAL AREA REQUIRED = 1,806 SF
EXISTING 319 SF + PROPOSED ADDITIONAL 1,487 SF = 1,806 SF TOTAL AREA
4-4-090
DUMPSTER / RECYCLING COLLECTION AREA:
NO CHANGES PROPOSED. NO ADJACENT OR ABUTTING RESIDENTIAL ZONES TO RESTRICT LOCATION.
LOADING DOCKS:
NO SIGNS PROPOSED AT THIS TIME. FUTURE SIGNAGE TBD AND UNDER SEPARATE PERMIT FOLLOWING 4-4-100 SIGN REGULATIONS 4-4-100
SIGNS:
NO CHANGES PROPOSED. PEDESTRIAN CONNECTIONS FROM PRIMARY ENTRANCE TO STREET ARE EXISTING
PEDESTRIAN ACCESS:
BICYCLE PARKING STANDARDS:
FOR LABORATORIES, RESERVED AREA FOR RACKS SHALL BE PROVIDED WITH A MINIMUM AREA OF 2'x6'x7' CLEAR HEIGHT FOR EACH BICYCLE.
5' OF MANUEVERING AREA BETWEEN ROWS SHALL BE PROVIDED.
BICYCLE PARKING SHALL BE SECURE EXTENDED USE AND SHALL PROTECT THE ENTIRE BICYCLE AND ITS COMPONENTS AND ACCESSORIES
FROM THEFT AND WEATHER.
NUMBER OF BICYCLE PARKING SPACES REQUIRED:
THE NUMBER OF BICYCLE PARKING SPACES SHALL BE EQUAL 10% OF THE NUMBER OF REQUIRED OFF-STREET VEHICLE PARKING SPACES.
198 x .10 = (19.8) 20 BICYCLE PARKING SPACES
197,446 NET FLOOR AREA (KC ASSESSOR) / 1,000 SF = 198
198 X 1.0 = 198 STALL MINIMUM
198 X 1.5 = 297 STALL MAXIMUM
NUMBER OF EXISTING STALLS EXCEED MAXIMUM, REFER TO SITE PLAN FOR PROPOSED AREAS OF REDUCTION, INCLUDING REFUSE/RECYCLING
EXPANSION AND MANUEVERING SPACE
PROVIDED 299 STALLS + 16 ACCESSIBLE STALLS (6% OVER MAXIMUM)
LABORATORIES REQUIRE A MINIMUM OF 1 SPACE UP TO A MAXIMUM 1.5 PER 1,000 SF OF NET FLOOR AREA 4-4-080
PARKING AND LOADING:
REFUSE AND RECYCLING: GARBAGE DUMPSTERS, REFUSE COMPACTOR AREAS, AND RECYCLING COLLECTION AREAS MUST BE FENCED OR
SCREENED.
4-4-090
GENERAL SCREENING: PROPOSED GENERATOR ELECTRICAL UTILITY YARD EXPANSION SHALL BE SCREENED FROM PUBLIC VIEW.
ROOF-TOP EQUIPMENT: PROPOSED EXPANSION OF ROOF-TOP MECHANICAL YARD SHALL BE SCREENED FROM PUBLIC VIEW. IF STRUCTURAL
ANALYSIS OF EXISTING ROOF STRUCTURE IS DETERMINED TO NOT BE ABLE TO SAFELY SUPPORT THE REQUIRED SCREENING EQUIPMENT TO BE
PAINTED A COLOR TO BE DETERMINED WITH APPROVAL.
LOADING, REPAIR, MAINTENANCE AND WORK AREAS: NO SCREENING REQUIRED
OUTDOOR STORAGE: NO OUTDOOR STORAGE PROPOSED
4-4-095
SCREENING:
NO CHANGE PROPOSED. EXISTING BUILDING IS BELOW MAXIMUM HEIGHT OF 250 FT
HEIGHT:
LANDSCAPING REQUIREMENTS ARE APPLICABLE DUE TO A CHANGE OF USE THAT REQUIRE IMPROVMENTS EQUAL TO OR GREATER THAN 50% OF
ASSESSED PROPERTY VALUATION
NO CHANGES PROPOSED. LANDSCAPED AREAS AND TREES TO BE MAINTAINED.4-4-070
LANDSCAPING:
CLEAR VISION AREA: NO STRUCTURES PROPOSED IN CLEAR VISION AREA
NO CHANGES PROPOSED. EXISTING BUILDING MEET MINIMUM FRONT YARD SETBACK OF 20'
NO MAXIMUM FRONT SETBACK REQUIRED. NO SIDE OR REAR YARD SETBACKS REQUIRED
SETBACKS:
NO RESIDENTIAL PROPOSED & LOT DOES NOT ABUT ANY LOTS DESIGNATED AS RESIDENTIAL
DENSITY:
65% MAXIMUM LOT COVERAGE FOR BUILDINGS: NO CHANGE PROPOSED, EXISTING BUILDING LOT COVERAGE IS ± 17.5%
LOT COVERAGE:
MINIMUM LOT SIZE: NO CHANGE PROPOSED, EXISTING LOT EXCEEDS 25,000 SF MINIMUM
LOT DIMENSIONS:
DEVELOPMENT STANDARDS FOR COMMERCIAL ZONING CO DESIGNATION:4-2-120B
LABORATORIES: RESEARCH, DEVELOPMENT AND TESTING - PERMITTED AS CONDITIONAL USE - ADMINISTRATIVE
OFFICES - PERMITTED
4-2-060
PERMITTED USES:
COMMERCIAL OFFICE (CO)
URBAN DESIGN DISTRICT ‘D’, AND THE EMPLOYMENT AREA COMPREHENSIVE PLAN LAND USE DESIGNATION
4-2-010
ZONING DISTRICT & DESIGNATIONS:
PARCEL A:
LOT 2, CITY OF RENTON SHORT PLAT NUMBER 431-79, ALSO KNOWN AS VALLEY OFFICE & INDUSTRIAL PARK – SUBDIVISION NO. 1, RECORDED
UNDER RECORDING NUMBER 8002269013, IN KING COUNTY, WASHINGTON;
EXCEPT THOSE PORTIONS THEREOF CONVEYED TO THE CITY OF RENTON FOR STREET PURPOSED BY DEEDS RECORDED UNDER RECORDING
NUMBERS 8007070464, 8008200077 AND 8202160354.
KING COUNTY DEPARTMENT OF ASSESSMENTS LEGAL:
HILLMANS EARLINGTON GARDENS #1 LOT 2 LESS ST - CITY OF RENTON SP #431-79 REC #8002269013 SD SP DAF - ALL OF VAC BLKS 24 & 31 & VAC
VALENTINE AVE BET SD BLKS OF SD SUBD LY S OF S MGN OF SW 16TH ST LESS STS
LEGAL DESCRIPTION:
1601 LIND AVE SW
RENTON WA 98057
PARCEL NO: 3340404006
SITE ADDRESS & PARCEL:
LAND USE SUMMARY
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
11 P.S.
13 P.S.
F L O OD Z O NE "X "
F L O OD Z O NE "A E"
F
L
OOD
Z
ONE
"AE
"
F
L
OOD
Z
ONE
"
X
"
OWNER:
PROVIDENCE HEALTH SYSTEMO/H EO/H E O/H E O/H E
LIND AVE. SWS.W. 16TH STREET
10.4'45.0'800707046480070704648007070464
8008200077
40'45'
40'45'
N89°34'32"E
32.54'
N89°34'32"E 412.79'S01°19'23"W403.71'N89°49'54"W 502.07'
S01°22'05"W
5.00'
APPROXIMATE
FLOOD ZONE
BOUNDRY PER
FEMA FLOOD MAP
(21)(21)
(22)
(23)
(2 2)
(2 2 )
(22)
(22)(23)(23)(23)(23)(24)(23)(23)(24)(24)(23)(22)(24)(24)(23)(2 2 )
(2 2 )(22)(24)(
2
4
)(24)(22)
(22)(23)(23)(22)(24)(21)(24)(23)
(22)
(26)
(26)(22)(22)
(22)
(2 1 )(25)(25)(25)(25)(25)(25)(20)(20)(25)(2 5 )
(2 5 )(25)(25)ID #85
ID #150
2"DEC
(TYP.)
6"DEC
ID #101
4"DEC
4"DEC
6"DEC
ID #96
8"DEC
6"DEC2"DEC
8"DEC
6"DEC6"DEC6"DEC6"DEC6"DEC8"DEC
8"DEC ID #1 ID #2 ID #3 ID #4
ID #5
ID #6
4"DEC
6"DEC
6"DEC
ID #104
ID #103
ID #98
4"DEC2"DECID #48ID #137 4"DEC
ID #130
ID #131 ID #132
ID #7 ID #8 ID #9 ID #10 ID #11 ID #12 ID #13
ID #14
ID #15
ID #16 ID #17 ID #18
ID #19
ID #20
ID #21
ID #22
ID #23
ID #24
ID #25
ID #26
ID #27
ID #28
ID #29
ID #30
ID #31
ID #32
ID #33ID #34ID #35ID #36ID #37ID #38ID #39
ID #40
ID #41
ID #42
ID #52
ID #53ID #54ID #55ID #57
ID #58
ID #59
ID #60
ID #61
ID #62
ID #63
ID #64
ID #65
ID #66
ID #67
ID #68
ID #69
ID #70
ID #71
ID #72
ID #73
ID #74 ID #75 ID #76 ID #77
ID #78
ID #79 ID #80 ID #81
ID #83
ID #82
ID #84
ID #86
ID #87
ID #126
ID #88
ID #89
ID #90
ID #91
ID #92
ID #93
ID #95
4"CON
ID #116
ID #117
ID #149ID #148ID #147ID #146
ID #145
ID #144ID #133
ID #135
ID #134
ID #136
ID #127
ID #128
ID #129
ID #138 ID #139 ID #141 ID #142 ID #143
ID #51
ID #97
ID #115
ID #114
ID #106
ID #107
ID #102
ID #99
ID #100
ID #113
ID #108
ID #109 ID #110
ID #112
ID #111 ID #118ID #119ID #121ID #125ID #124ID #122ID #153ID #47ID #46ID #151ID #50ID #123ID #120ID #43
ID #44
ID #45
ID #15239' DWY30' DWY 6'CONC. WALK
6'CONC. WALK
6'CONC. WALKD
D
D
D
D
S
D
D
D
D
21.65
19.6
3
19.94
19.44
19.30
25.08
22.65
N89°34'32"E 1027.81'N01°19'23"EN01°20'40"E460.23'PROJECT SITE: 1601 LIND AVE SW
PARCEL NO: 3340404006
FLOOR NET AREA (EXISTING): 197,446 SF APPROX
LOT AREA: 229,238 SF (5.263 AC)
PRIMARY ENTRANCE
ENTRANCE / EXIT
ENTRANCE / EXIT
ENTRANCE / EXIT105'-0"PROPERTY LINENOTE:
• ALL LANDSCAPING AND TREES ARE EXISTING AND WILL BE RETAINED, NO PROPOSED CHANGES
• LANDSCAPE DIAGRAM TO DEMONSTRATE COMPLIANCE WITH SITE PLAN REVIEW CRITERIA FOR
CONDITIONAL USE PERMIT
1,487 SF
EXISTING FFE = 25.01'
77'-3"19'-3"46'-6"6'-4"6'-0"12'-8"6'-0"6'-4"5'-0"13'-0"FEMA BASE FLOOD ELEVATION = 20'
GENERATOR
GENERATOR 12'-10"10'-0"EXISTING LANDSCAPE MEETS STREET FRONTAGE LANDSCAPING
REQUIRED ALONG PUBLIC STREET (RMC 4-4-070 F.1)
EXISTING STREET TREES,
REFER TO TREE RETENTION
AUDIT FOR SIZE AND SPECIES
EXISTING PERIMETER PARKING LOT &
STREET TREES, REFER TO TREE
RETENTION AUDIT FOR SIZE AND SPECIES
14,360 SF
INTERIOR PARKING LOT LANDSCAPE
AREA
3
4
2
1
5
6
7
8
9
10
11
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
29 30 31 32 33 34 35 36
43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59
37 38 39 40 41 42
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83
85 84 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103
104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120
121 122 123 124 125 126 127 128
181
182
183
184
185
186
187
188
189
239
238
240
241
242
243
244
245
246
167
168
169
170
171
172
173
174
175
176
177
178
179
180
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
280281282283284285286287288289290291
304 303 302 301
298 297 296 295 294 293 292
247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279
305306
308
307
309310
311312
314 313
315
300 299
HATCHED AREA: 10 STALLS
RESERVED FOR COURIER/ VENDOR
12'-10"
EXISTING PERIMETER PARKING LOT
LANDSCAPING AT LEAST 10' IN WIDTH
484'-10" STREET FRONTAGE
443'-6" STREET FRONTAGELAYOUT LEGEND
EXISTING INTERIOR PARKING
LOT LANDSCAPING
EXISTING LANDSCAPING AREA
EXISTING DECIDUOUS TREES
(REFER TO ARBORIST REPORT)
EXISTING CONIFEROUS TREES
(REFER TO ARBORIST REPORT)
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:16 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
LANDSCAPE
DIAGRAM
GI005
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
A1 LANDSCAPE DIAGRAM
INTERIOR PARKING LOT LANDSCAPING RMC 4-4-070 H.5.b
MINIMUM 1 SHRUB PER 20 SF OF LANDSCAPED
AREA
14,360 SF / 20 = 664 SHRUBS REQUIRED
EXISTING MATURE SHRUBS COVER MAJORITY
OF INTERIOR PARKING LOT LANDSCAPED AREA
INTERIOR PARKING LOT LANDSCAPING RMC 4-4-070 H.5.a MINIMUM 1 TREE FOR EVERY 6 PARKING STALLS
TOTAL OF 315 PARKING STALLS
315 / 6 = 53 TREES REQUIRED
±60 EXISTING
PERIMETER PARKING LOT LANDSCAPING RMC 4-4-070 H.4.b
MINIMUM 1 SHRUB PER 20 SF OF LANDSCAPED
AREA
EXISTING MATURE SHRUBS COVER MAJORITY
OF PERIMETER PARKING LOT LANDSCAPED
AREA
PERIMETER PARKING LOT LANDSCAPING RMC 4-4-070 H.4.a
MINIMUM 1 TREE PER 30 LINEAL FT OF STREET
FRONTAGE
TOTAL OF 928' - 4" OF STREET FRONTAGE
928.3 / 30 = 31
±54 EXISTING
MINIMUM AMOUNT OF INTERIOR PARKING LOT
LANDSCAPING RMC 4-4-070 F.6.b
MINIMUM LANDSCAPE AREA REQUIRED:
100 OR MORE PARKING STALLS @ 35SF/
PARKING SPACE
TOTAL OF 315 PARKING STALLS
315 X 35 = 11,025 SF REQUIRED
14,360 SF EXISTING
ALL LANDSCAPING AND TREES ARE EXISTING AND WILL BE RETAINED, NO PROPOSED CHANGES
PARKING LOT LANDSCAPE REQUIREMENTS
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
2
B
C
D
1
1
2
3
3
9
S107
REINFORCING PER
PLAN
COMPACTED SUBGRADE
5/8" MINUS CRUSHED
ROCK CAPILLARY BREAK
MATERIAL
/3 S107
GENERATOR PER PLAN AND
ELECTRICAL DRAWINGS
GENERATOR BASE RAIL
ANCHOR GENERATOR TO SLAB
WITH STAINLESS STEEL
EXPANSION ANCHORS AT
MFR'S REQUIRED LOCATIONS
4' - 0"2' - 0"TOP OF WALL
15' -0"
CAP AT TOP OF WALL PER ARCH.
BOND BEAM AT GRADE, TOP OF
WALL, AND 48" OC. BETWEEN,
REINFORCE WITH (2) #5
(2) #6 AT 16" OC.
HOOKED DOWELS TO MATCH WALL VERTS.
THICKENED SLAB AT EDGE OF
GENERATOR YARD
SLAB ON GRADE PER PLAN, EXTEND
REINFORCING INTO THICKENED SLAB
REINFORCE BOTTOM OF THICKENED
SLAB WITH (5) #6 LONG AND #4 AT
32" TRANSVERSE
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
LAB CONSULTING MANAGER:
STRUCTURAL ENGINEER:
MEP:
LAB PLANNING:
REVISIONS
MARK DATE DESCRIPTIONB
SHEET OF 250
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
NOT FOR
CONSTRUCTION
3/7/2023 3:32:33 PMAutodesk Docs://102987.00 - UW DLMP R22/STRU_UW DLMP_TI.rvt102987.00
JT
GENERATOR
YARD PLAN AND
DETAILS
S107
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 13, 223
SCALE: 3/16" = 1'-0"7 STRUCTURAL PLAN - GENERATOR YARD
1 8" SLAB ON GRADE WITH #4 AT 16" OC. EACH WAY, TOP AND
BOTTOM. PROVIDE THICKENED SLAB AT EDGE PER SECTION
REFERENCED ON PLAN.
2 12" REINFORCED AND SLOID GROUTED CMU WALL. REINFORCE
WITH (2) #6 AT 16" OC. AND BOND BEAMS WITH (2) #5 AT GRADE,
TOP OF WALL, AND 48" OC. BETWEEN. TOP OF WALL EQUALS
15'-0" ABOVE SLAB.
3 GENERATOR PER ELECTRICAL DRAWINGS. ANCHOR TO SLAB PER
DETAIL
KEYNOTES:GENERAL NOTES:
A. SEE ARCHITECTURAL AND / OR SITE DRAWINGS FOR
DIMENSIONS NOT SHOWN.
B. APPROXIMATE GENERATOR PAD ELEVATIO EQUALLS 24.75'.
SCALE: 1" = 1'-0"4 TYP. SLAB ON GRADE
SCALE: 1" = 1'-0"3 GENERATOR ANCHORAGE
SCALE: 1" = 1'-0"9 MASONRY WALL SECTION
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
F L O OD Z O NE "X "
F L O OD Z O NE "A E"
F
L
OOD
Z
ONE
"AE
"
F
L
OOD
Z
ONE
"
X
"
OWNER:
PROVIDENCE HEALTH SYSTEMO/H EO/H E O/H E O/H E
LIND AVE. SWS.W. 16TH STREET
10.4'45.0'800707046480070704648007070464
8008200077
40'45'
40'45'
N89°34'32"E
32.54'
N89°34'32"E 412.79'S01°19'23"W403.71'N89°49'54"W 502.07'
S01°22'05"W
5.00'20.0'20.0'
FRONT SETBACK
SIDE SETBACK
CONC WALK IS
1.32' OUTSIDE
EASEMENT
APPROXIMATE
FLOOD ZONE
BOUNDRY PER
FEMA FLOOD MAP
(21)(21)
(22)
(23)
(2 2)
(2 2 )
(22)
(22)(23)(23)(23)(23)(24)(23)(23)(24)(24)(23)(22)(24)(24)(23)(2 2 )
(2 2 )(22)(24)(
2
4
)
(24)(24)(22)
(22)(23)(23)(22)(24)(21)(24)(23)
(22)
(26)
(26)(22)(22)
(22)
(2 1 )(25)(25)(25)(25)(25)(25)(20)(20)(25)(2 5 )
(2 5 )(25)(25)ID #85
ID #150
2"DEC
(TYP.)
6"DEC
ID #101
4"DEC
4"DEC
6"DEC
ID #96
8"DEC
6"DEC2"DEC
8"DEC
6"DEC6"DEC6"DEC6"DEC6"DEC8"DEC
8"DEC ID #1 ID #2 ID #3 ID #4
ID #5
ID #6
4"DEC
6"DEC
6"DEC
ID #104
ID #103
ID #98
4"DEC2"DECID #48ID #137 4"DEC
ID #130
ID #131 ID #132
ID #7 ID #8 ID #9 ID #10 ID #11 ID #12 ID #13
ID #14
ID #15
ID #16 ID #17 ID #18
ID #19
ID #20
ID #21
ID #22
ID #23
ID #24
ID #25
ID #26
ID #27
ID #28
ID #29
ID #30
ID #31
ID #32
ID #33ID #34ID #35ID #36ID #37ID #38ID #39
ID #40
ID #41
ID #42
ID #52
ID #53ID #54ID #55ID #57
ID #58
ID #59
ID #60
ID #61
ID #62
ID #63
ID #64
ID #65
ID #66
ID #67
ID #68
ID #69
ID #70
ID #71
ID #72
ID #73
ID #74 ID #75 ID #76 ID #77
ID #78
ID #79 ID #80 ID #81
ID #83
ID #82
ID #84
ID #86
ID #87
ID #126
ID #88
ID #89
ID #90
ID #91
ID #92
ID #93
ID #95
4"CON
ID #116
ID #117
ID #149ID #148ID #147ID #146
ID #145
ID #144ID #133
ID #135
ID #134
ID #136
ID #127
ID #128
ID #129
ID #138 ID #139 ID #141 ID #142 ID #143
ID #51
ID #97
ID #115
ID #114
ID #106
ID #107
ID #102
ID #99
ID #100
ID #113
ID #108
ID #109 ID #110
ID #112
ID #111 ID #118ID #119ID #121ID #125ID #124ID #122ID #153ID #47ID #46ID #151ID #50ID #123ID #120ID #43
ID #44
ID #45
ID #152CROSSWALKYELLOWSTRIPESTOP
BAR
LOADING DOCK STRIPE
ENTRANCE
SIGN "RIGHTTURN ONLY""BUS STOP"
"RIGHT TURN ONLY""NO RACINGZONE"""NOTRESSPASSING""FAA" SIGN
"15 MIN
PARKING"
HANDICAP PARKING
"H/C""VAN POOL""H/C"
"BUS STOP"
"BUS STOP""FLOOD
EVAC. ROUTE"
(6) "H/C
PARKING"
SIGNS
STREET
SIGN
"NO TRESPASSING"
SIGN
"CCTV
SURVEILANCE"
"VISITOR/ BUILDING
ENGINEER PARKING ONLY"
CRW
CRW CRW39' DWY30' DWY 6'CONC. WALK
6'CONC. WALK
6'CONC. WALKSPEED
BUMP
SPEED
BUMP
SPEED BUMP17 P.S.24 P.S
20 P.S.
17 P.S.17 P.S.
8 P.S.
21 P.S
16 P.S.
14 P.S.
16 P.S.
17 P.S.
16 P.S.
9 P.S.
7 P.S.
12 P.S.
13 P.S.11 P.S."MAIL
TRUCK
PARKING
ONLY"
33 P.S.
NO
PARKING
18 P.S.
2 P.S.
2 P.S.
D
D
D
D
D
S
D
D
D
D
23.06
21.65
21.23
21.3
0
21.2
9
23.48
19.6
3
19.94
19.44
19.30
25.08
22.65
23.51
23.67
23.53
N89°34'32"E 1027.81'N01°19'23"EN01°20'40"E460.23'PROJECT SITE: 1601 LIND AVE SW
CURRENT USES (EXISTING BUILDING):
LABORATORIES: RESEARCH, DEVELOPMENT AND TESTING - LEVEL 1
OFFICES, GENERAL - LEVELS 1-5
PROPOSED USES:
PRINCIPLE USE: LABORATORIES: RESEARCH, DEVELOPMENT AND TESTING - LEVELS 1-5
ACCESSORY USE: OFFICE, GENERAL - LEVELS 1-5
PARCEL NO: 3340404006
FLOOR NET AREA (EXISTING): 197,446 SF APPROX
LOT AREA: 229,238 SF (5.263 AC)
PRIMARY ENTRANCE
ENTRANCE / EXIT
ENTRANCE / EXIT
ENTRANCE / EXIT
EXISTING GENERATOR w/ FUEL TANK REMOVED
EXISTING GENERATOR REMOVED
EXISTING FUEL TANK REMOVED
EXISTING ELECTRICAL
TRANSFORMER REMOVED
EXISTING FENCE ENCLOSURE
PROPERTY LINEEXISTING REFUSE, COMPOST &
RECYLCING LOCATION
NOTE: ALL INFORMATION ON SITE PLAN REQUIRES VERIFICATION
319 SF
1,487 SF
PROPOSED ADDITIONAL REFUSE
& RECYLCING LOCATION WITH 6'
FENCE ENCLOSURE (4-4-090.C9)
EXISTING FFE = 25.01'
(11 BIKES)
HATCHED AREA: 10 STALLS
RESERVED FOR COURIER/ VENDOR
20 LOCKABLE BIKE LOCKERS.
12 SINGLE & 4 DOUBLE UNITS
AS102
A5
FEMA BASE FLOOD ELEVATION = 20'
AS102
A2
GENERATOR
GENERATOR
3
4
2
1
5
6
7
8
9
10
11
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
29 30 31 32 33 34 35 36
43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59
37 38 39 40 41 42
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83
85 84 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103
104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120
121 122 123 124 125 126 127 128
181
182
183
184
185
186
187
188
189
239
238
240
241
242
243
244
245
246
167
168
169
170
171
172
173
174
175
176
177
178
179
180
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
280281282283284285286287288289290291
304 303 302 301
298 297 296 295 294 293 292
247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279
305306
308
307
309310
311312
314 313
315
300 299
PSE SUB-STATION
PARKING LOT
(COMMERCIAL)
77'-3"19'-3"46'-6"6'-4"6'-0"12'-8"6'-0"6'-4"5'-0"13'-0"37'-0"
24'-1"183'-2"250'-4"223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:09 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
ARCHITECTURAL
SITE PLAN
AS101-A2
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1" = 20'-0"A1 ARCHITECTURAL SITE PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DN
D
22.10
22.24
22.8322.42
22.24
23.02
22.6322.61
23.15
23.06
2
3.6
8
23.58
23.51
23.14
23.17
22.90
22.88
22.91
22.75
23.38
22.29 2
2.8
6
2
5.10
24.64
24.77
24.95
26.51
23.44
2
3.4
6
24.86
2
4.7
2
26.47
2
4.4
6
2
4.5
8
26.43
22.94
22.55
22.30
2
2.8
2
24.50
25.00
2
4.3
0
23.31
N01°20'40"E460.23'11 P.S.
13 P.S.F
L
OOD
Z
ONE
"AE
"
F
L
OOD
Z
ONE
"
X
"
(23)
(22)(23)(2 1 )6"DEC6"DEC8"DEC
8"DEC ID #1 ID #2 ID #3 ID #4
SPEED BUMPNO
PARKING
18 P.S.
AE201 A1
2
A
D
E
F
1
B
C
PUBLIC UTILITIES EASEMENT
PUBLIC UTILITIES EASEMENTPUBLIC UTILITIES EASEMENTEASEMENT
PUBLIC UTILITIES
PSE EASEMENT
PSE EASEMENTPSE EASEMENT48" CORRUGATED
METAL PIPE
EXISTING CATCH BASIN
48" CORRUGATED PIPE
(25')(24')
(23')
(24'
)
(22'
)
(23'
)
(24')
(25')
(23')
TO COMBUSTIBLE
10'-0" CLEAR
TO COMBUSTIBLE10'-0" CLEAR10" WATER MAIN
10" WATER MAIN
3'-0" CLEAR TO
NON-COMBUSTIBLE
MAIN
ELECTRICAL
ROOM
NON-COMBUSTIBLE
RECLADDING6'-0"4'-1 1/8"4'-1"7'-4 5/8"
GENERATOR & FUEL TANK
GENERATOR & FUEL TANK
FUEL FILL STATION
3'-6"3'-4"8'-0"8'-0"3'-4"4'-0"
4'-4 5/8"MTS 1 MTS 2
34'-9 7/8"32'-1 3/8"EXISTING REFUSE, COMPOST &
RECYLCING LOCATION - NO
PROPOSED CHANGES
319 SF
1,487 SF
PROPOSED ADDITIONAL REFUSE
& RECYLCING LOCATION WITH 6'
FENCE ENCLOSURE (4-4-090.C9)
HATCHED AREA: 10 STALLS
RESERVED FOR COURIER/ VENDOR
20 LOCKABLE BIKE LOCKERS.
12 SINGLE & 4 DOUBLE UNITS
77'-3"19'-3"46'-6"310 309
307
308
306 305
279
RESTRIPE AREA FOR
NO PARKING
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:11 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
ARCHITECTURAL
SITE PLANS -
ENLARGED
AS102
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A5 ARCHITECTURAL SITE PLAN -ELECTRICAL YARD
1/8" = 1'-0"A2 ARCHITECTURAL SITE PLAN -REFUSE/RECYCLE
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
B B
C C
36,681 SF
AREA OF WORK
ALL GYPSUM BOARD AT PERIMETER
EXTERIOR WALLS TO REMAIN, TYP
EXISTING GYPSUM BOARD FIRE-PROOFING
COLUMN ENCLOSURES TO REMAIN AT ALL
COLUMNS U.O.N., TYP
DEMOLITION PLAN NOTES
1. ALL INFORMATION SHOWN ON DRAWINGS RELATIVE TO
EXISTING CONDITIONS IS GIVEN AS THE BEST PRESENT
KNOWLEDGE BUT WITHOUT GUARANTEES OF ACCURACY.
FIELD VERIFY ALL CONDITIONS.
2. IN GENERAL, THE FULL EXTENT OF THIS WORK INCLUDES
ALL DEMOLITION NECESSARY FOR THE INSTALLATION OF
NEW CONSTRUCTION UNDER SEPARATE PERMIT(S).
DEMOLITION DRAWINGS ONLY SHOW THE GENERAL
SCOPE OF DEMOLITION.
3. REMOVE ALL NON-STRUCTURAL PARTITIONS, FLOORING,
BASE MATERIALS, CASEWORK AND FINISHES IN AREA OF
WORK.
4. REMOVE ALL CEILINGS AND LIGHTING THROUGHOUT
AREA OF WORK.
5. REMOVE MECHANICAL, ELECTRICAL , DATA AND
PLUMBING ASSOCIATED WITH DEMOLITION OF
PARTITIONS AND CEILINGS IN AREA OF WORK.
6. EXISTING MECHANICAL, PLUMBING AND ELECTRICAL
SERVICES WHICH SERVE OTHER EXISTING OCCUPIED
AREAS MUST REMAIN AND SHALL BE PROTECTED DURING
THE CONSTRUCTION.
7. ALL RAIN LEADERS TO REMAIN IN PLACE
8. COORDINATE DEMOLITION OUTSIDE THE PROJECT AREA
TO THE POINT OF CONNECTION FOR MECHANICAL,
ELECTRICAL, DATA AND PLUMBING.
9. EXISTING GYPSUM BOARD FIRE-PROOFING COLUMN
ENCLOSURES TO REMAIN AT ALL COLUMNS U.O.N.
10. ALL PERIMETER GYPSUM BOARD FINISH TO REMAIN AT
EXTERIOR WALLS
11. SALVAGE EXIT SIGNS, FIRE EXTINGUISHERS AND
CABINETS AND SIGNAGE IF PRESENT FOR REUSE AND
REINSTALLATION.
DEMOLITION LEGEND
ELEMENTS TO BE DEMOLISHED OR REMOVED
AREA NOT IN SCOPE
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:44 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F2
ARCHITECTURAL
DEMOLITION
PLAN
AD102-A1
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F2 DEMOLITION PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
B B
C C
36,681 SF
AREA OF WORK
ALL GYPSUM BOARD AT
PERIMETER EXTERIOR
WALLS TO REMAIN, TYP
EXISTING GYPSUM BOARD FIRE-PROOFING
COLUMN ENCLOSURES TO REMAIN AT ALL
COLUMNS U.O.N., TYP
DEMOLITION PLAN NOTES
1. ALL INFORMATION SHOWN ON DRAWINGS RELATIVE TO
EXISTING CONDITIONS IS GIVEN AS THE BEST PRESENT
KNOWLEDGE BUT WITHOUT GUARANTEES OF ACCURACY.
FIELD VERIFY ALL CONDITIONS.
2. IN GENERAL, THE FULL EXTENT OF THIS WORK INCLUDES
ALL DEMOLITION NECESSARY FOR THE INSTALLATION OF
NEW CONSTRUCTION UNDER SEPARATE PERMIT(S).
DEMOLITION DRAWINGS ONLY SHOW THE GENERAL
SCOPE OF DEMOLITION.
3. REMOVE ALL NON-STRUCTURAL PARTITIONS, FLOORING,
BASE MATERIALS, CASEWORK AND FINISHES IN AREA OF
WORK.
4. REMOVE ALL CEILINGS AND LIGHTING THROUGHOUT
AREA OF WORK.
5. REMOVE MECHANICAL, ELECTRICAL , DATA AND
PLUMBING ASSOCIATED WITH DEMOLITION OF
PARTITIONS AND CEILINGS IN AREA OF WORK.
6. EXISTING MECHANICAL, PLUMBING AND ELECTRICAL
SERVICES WHICH SERVE OTHER EXISTING OCCUPIED
AREAS MUST REMAIN AND SHALL BE PROTECTED DURING
THE CONSTRUCTION.
7. ALL RAIN LEADERS TO REMAIN IN PLACE
8. COORDINATE DEMOLITION OUTSIDE THE PROJECT AREA
TO THE POINT OF CONNECTION FOR MECHANICAL,
ELECTRICAL, DATA AND PLUMBING.
9. EXISTING GYPSUM BOARD FIRE-PROOFING COLUMN
ENCLOSURES TO REMAIN AT ALL COLUMNS U.O.N.
10. ALL PERIMETER GYPSUM BOARD FINISH TO REMAIN AT
EXTERIOR WALLS
11. SALVAGE EXIT SIGNS, FIRE EXTINGUISHERS AND
CABINETS AND SIGNAGE IF PRESENT FOR REUSE AND
REINSTALLATION.
DEMOLITION LEGEND
ELEMENTS TO BE DEMOLISHED OR REMOVED
AREA NOT IN SCOPE
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:46 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F3
ARCHITECTURAL
DEMOLITION
PLAN
AD103-A1
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F3 DEMOLITION PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
B B
C C
36,681 SF
AREA OF WORK
ALL GYPSUM BOARD AT PERIMETER
EXTERIOR WALLS TO REMAIN, TYP
EXISTING GYPSUM BOARD FIRE-PROOFING
COLUMN ENCLOSURES TO REMAIN AT ALL
COLUMNS U.O.N., TYP
DEMOLITION PLAN NOTES
1. ALL INFORMATION SHOWN ON DRAWINGS RELATIVE TO
EXISTING CONDITIONS IS GIVEN AS THE BEST PRESENT
KNOWLEDGE BUT WITHOUT GUARANTEES OF ACCURACY.
FIELD VERIFY ALL CONDITIONS.
2. IN GENERAL, THE FULL EXTENT OF THIS WORK INCLUDES
ALL DEMOLITION NECESSARY FOR THE INSTALLATION OF
NEW CONSTRUCTION UNDER SEPARATE PERMIT(S).
DEMOLITION DRAWINGS ONLY SHOW THE GENERAL
SCOPE OF DEMOLITION.
3. REMOVE ALL NON-STRUCTURAL PARTITIONS, FLOORING,
BASE MATERIALS, CASEWORK AND FINISHES IN AREA OF
WORK.
4. REMOVE ALL CEILINGS AND LIGHTING THROUGHOUT
AREA OF WORK.
5. REMOVE MECHANICAL, ELECTRICAL , DATA AND
PLUMBING ASSOCIATED WITH DEMOLITION OF
PARTITIONS AND CEILINGS IN AREA OF WORK.
6. EXISTING MECHANICAL, PLUMBING AND ELECTRICAL
SERVICES WHICH SERVE OTHER EXISTING OCCUPIED
AREAS MUST REMAIN AND SHALL BE PROTECTED DURING
THE CONSTRUCTION.
7. ALL RAIN LEADERS TO REMAIN IN PLACE
8. COORDINATE DEMOLITION OUTSIDE THE PROJECT AREA
TO THE POINT OF CONNECTION FOR MECHANICAL,
ELECTRICAL, DATA AND PLUMBING.
9. EXISTING GYPSUM BOARD FIRE-PROOFING COLUMN
ENCLOSURES TO REMAIN AT ALL COLUMNS U.O.N.
10. ALL PERIMETER GYPSUM BOARD FINISH TO REMAIN AT
EXTERIOR WALLS
11. SALVAGE EXIT SIGNS, FIRE EXTINGUISHERS AND
CABINETS AND SIGNAGE IF PRESENT FOR REUSE AND
REINSTALLATION.
DEMOLITION LEGEND
ELEMENTS TO BE DEMOLISHED OR REMOVED
AREA NOT IN SCOPE
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:47 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F4
ARCHITECTURAL
DEMOLITION
PLAN
AD104-A1
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F4 DEMOLITION PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
B B
C C
36,681 SF
AREA OF WORK
ALL GYPSUM BOARD AT PERIMETER
EXTERIOR WALLS TO REMAIN, TYP
EXISTING GYPSUM BOARD FIRE-PROOFING
COLUMN ENCLOSURES TO REMAIN AT ALL
COLUMNS U.O.N., TYP
DEMOLITION PLAN NOTES
1. ALL INFORMATION SHOWN ON DRAWINGS RELATIVE TO
EXISTING CONDITIONS IS GIVEN AS THE BEST PRESENT
KNOWLEDGE BUT WITHOUT GUARANTEES OF ACCURACY.
FIELD VERIFY ALL CONDITIONS.
2. IN GENERAL, THE FULL EXTENT OF THIS WORK INCLUDES
ALL DEMOLITION NECESSARY FOR THE INSTALLATION OF
NEW CONSTRUCTION UNDER SEPARATE PERMIT(S).
DEMOLITION DRAWINGS ONLY SHOW THE GENERAL
SCOPE OF DEMOLITION.
3. REMOVE ALL NON-STRUCTURAL PARTITIONS, FLOORING,
BASE MATERIALS, CASEWORK AND FINISHES IN AREA OF
WORK.
4. REMOVE ALL CEILINGS AND LIGHTING THROUGHOUT
AREA OF WORK.
5. REMOVE MECHANICAL, ELECTRICAL , DATA AND
PLUMBING ASSOCIATED WITH DEMOLITION OF
PARTITIONS AND CEILINGS IN AREA OF WORK.
6. EXISTING MECHANICAL, PLUMBING AND ELECTRICAL
SERVICES WHICH SERVE OTHER EXISTING OCCUPIED
AREAS MUST REMAIN AND SHALL BE PROTECTED DURING
THE CONSTRUCTION.
7. ALL RAIN LEADERS TO REMAIN IN PLACE
8. COORDINATE DEMOLITION OUTSIDE THE PROJECT AREA
TO THE POINT OF CONNECTION FOR MECHANICAL,
ELECTRICAL, DATA AND PLUMBING.
9. EXISTING GYPSUM BOARD FIRE-PROOFING COLUMN
ENCLOSURES TO REMAIN AT ALL COLUMNS U.O.N.
10. ALL PERIMETER GYPSUM BOARD FINISH TO REMAIN AT
EXTERIOR WALLS
11. SALVAGE EXIT SIGNS, FIRE EXTINGUISHERS AND
CABINETS AND SIGNAGE IF PRESENT FOR REUSE AND
REINSTALLATION.
DEMOLITION LEGEND
ELEMENTS TO BE DEMOLISHED OR REMOVED
AREA NOT IN SCOPE
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:49 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F5
ARCHITECTURAL
DEMOLITION
PLAN
AD105-A1
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F5 DEMOLITION PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DN
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
EXISTING MECHANICAL SCREEN &
SUPPORT STRUCTURE TO BE REMOVED
MECHANICAL EQUIPMENT AND
CURBS TO BE REMOVED, TYP.
REMOVE ELEVATOR
HOISTWAY RELIEF VENTS
HATCHED AREA OF ROOF DEMOLITION
FOR MECHANICAL SHAFTS, TYP.
REMOVE SATELLITE DISHES AND
OTHER MISCELLANEOUS
EXTRANEOUS EQUIPMENT, TYPICAL
B B
C C
DEMOLITION PLAN NOTES
1. IN GENERAL, THE FULL EXTENT OF THIS WORK INCLUDES
ALL DEMOLITION NECESSARY FOR THE INSTALLATION OF
NEW CONSTRUCTION. DEMOLITION DRAWINGS ONLY
SHOW THE GENERAL SCOPE OF DEMOLITION.
COORDINATE DEMOLITION OUTSIDE THE PROJECT AREA
TO THE POINT OF CONNECTION FOR MECHANICAL,
ELECTRICAL AND PLUMBING.
2. EXISTING MECHANICAL, PLUMBING AND ELECTRICAL
SERVICES WHICH SERVE OTHER EXISTING OCCUPIED
AREAS MUST REMAIN AND SHALL BE PROTECTED DURING
THE CONSTRUCTION.
3. REMOVE ALL CEILINGS AND LIGHTING THROUGHOUT
AREA OF WORK.
4. EXISTING GYPSUM BOARD FIRE-PROOFING COLUMN
ENCLOSURES TO REMAIN AT ALL COLUMNS U.O.N.
5. RESTROOMS: DEMOLISH ALL FIXTURES, TOILET
PARTITIONS, FINISHES AND ACCESSORIES. ROUGH
PLUMBING TO REMAIN
6. STAIRWELLS: DEMO ALL GUARDRAILS, FINISHES &
LIGHTINGROOF DEMOLITION NOTES
1. DEMOLISH EXISTING MEP TO MEET PROGRAM
REQUIREMENTS.
DEMOLITION LEGEND
ELEMENTS TO BE DEMOLISHED OR REMOVED
NEW FLOOR OR ROOF OPENINGS
EQUIPMENT TO BE REMOVED
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:51 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
ROOF
ARCHITECTURAL
DEMOLITION
PLAN
AD106
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 R1 DEMOLITION PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
ALUMINUM
CONCRETE
GLASS
RIGID INSULATION
BRICK IN SECTION
CONCRETE MASONRY UNIT
EARTH
GYPSUM / PLASTER
STEEL
STONE
BATT INSULATION
PRECAST
GRAVEL
SAND
WOOD - SOLID
PLYWOOD
BRICK
CULTURED STONE
EXTERIOR COMPOSITE PANEL
BLOCKING
SHIM
GRASS
MATERIAL LEGEND
SYMBOLOGY LEGEND
BUILDING SECTION
NUMBER
SHEET ON WHICH
SECTION IS DRAWN
SHEET NUMBER SEQUENCE
AE 1 01
SHEET NUMBER
SHEET TYPE
DISCIPLINE
EL: +10'-0"
SPOT ELEVATION
LEVEL DATUM
MATCHLINE REFERENCECENTERLINE SYMBOL
PARTITION TAG -
WITH STC
CEILING TAG
REVISION CALLOUT
AND CLOUD
CODED NOTE TAG
WINDOW TAG
DOOR TAG
FURNITURE TAG
FINISH TAG
ROOM TAG
NORTH ARROW
GRID BUBBLES
VIEW TITLE
VIEW TITLE ON SHEET
NUMBER ON SHEET
EXISTING GRID BUBBLES
SCALE
GRAPHIC SCALE
ELEVATION REFERENCE INTERIOR ELEVATION REFERENCE
BUILDING SECTION WALL SECTION
DETAIL SECTION
NUMBER
DETAIL SECTION
ALIGN SYMBOL
INDICATES SIMILAR
OR OPPOSITE HAND
CONDITION
PLAN
NORTH
0'8'16'32'64'
SCALE: 1/16" = 1'-0"
#
##
#
A101
A1
A101
A1 REF
A1REF
A1 REF
A1 REFA101
A1 SIM
SHEET ON WHICH
DETAIL IS DRAWN
101000
1
ALIGN
1
WALL SECTION
NUMBER
SHEET ON WHICH
SECTION IS DRAWN
/MATCHLINE SEE: 1 A101
A1
A101
SIM A1
A101
SIM
DETAIL CALLOUT
SHEET ON WHICH
DETAIL IS DRAWN
A101
A1 SIM
DETAIL SECTION
NUMBER
A
NAME
ELEVATION
CPT-01
ACP-1
1' -0" A.F.F.
A1 VIEW TITLE
1/8" = 1'-0"
A1
A101
SIMOPP
ROOM NAME
38-999
B 1 6 45
202M
HW D
Extra ShelfCASEWORK TAG
FIXTURE AND EQUIPMENT TAG
00000
PARTITION TAG -
NO STC
B 1 6
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:52 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
ARCHITECTURAL
NOTES AND
SYMBOLS
AE001
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
(E) EXISTING
(N) NEW
(R) REUSED, RELOCATED
@ AT
ACC ACCESSIBLE
ACP ACOUSTIC CEILING PANEL(S)
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE, ALTERATION
BLDG BUILDING
BOT BOTTOM
BW BOTTOM OF WALL
CG CORNER GUARD
CH COAT HOOK
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT(S)
CTR CENTER
CU CUBIC
DEG DEGREE
DIAG DIAGONAL
DIAM DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DW DISHWASHER
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR, ELEVATION
EQ EQUAL
EXT EXTERIOR
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH
FLR FLOORLINE, FLOOR
FO FACE OF
FS FLOOR SINK
FT FOOT, FEET
GA GAUGE
GB GRAB BAR
GFRP GLASS FIBER REINFORCED PLASTIC
GL GLASS
GLI GLASS (INTERIOR)
GLU-LAM GLUE LAMINATED
GYP BD GYPSUM BOARD
HB HOSE BIB
HD HAND DRYER
HEX HEXAGONAL
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING VENTILATION AND AIR
CONDITIONING
ID INSIDE DIAMETER
IGU INSULATED GLASS UNIT
IN INCH
INT INTERIOR
J-BOX JUNCTION BOX
JT JOINT
LF LINEAR FOOT
MAX MAXIMUM
MIN MINIMUM
MO MASONRY OPENING
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
ABBREVIATIONS
PL PLATE, PROPERTY LINE
PT POINT
R RADIUS, RISER
RD ROOF DRAIN
REV REVISION
RO ROUGH OPENING
SF SQUARE FEET
SIM SIMILAR
SQ SQUARE
SSG STRUCTURAL SEALANT GLAZED
STD STANDARD
T TOP
TO TOP OF
TOC TOP OF CURB, TOP OF CONCRETE
TOS TOP OF STEEL, TOP OF SLAB
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
WT WEIGHT
YD YARD
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
ELEC.
PANEL
ELEC.
PANEL
ELEC.
PANEL
LAB 3
PANTHERS & ARCH
VESTIBULE
HALLWAY
OPEN
OFFICE
BF
W/R
OFFICE1
OFFICE
2
STORAGE
SPACE
MAIN
ELECTRICAL
HALLWAY
FITNESS
RESTROOM
4
RESTROOM
3
HALLWAY
LAB
HALLWAY
POST-PCR
ROOM
LOBBY
SPACE
SERVICE ACCESS
HALLWAY
LAB 4
ALINITY
LAB
HALLWAY
OFFICE
STORAGE
LOADING
SPACE
LAB 2
COBAS
LAB
CORRIDOR
LAB
HALLWAY
LOADING
DOCK
LAB
CORRIDOR
STORAGE
SPACE
ACCESSIONING
HALLWAY
OFFICE
OFFICELAB
CORRIDOR
STORAGE
LUNCH
ROOM
FREEZER
STORAGE
EXISTING
COMM ROOM
COMM.
ROOM STAIRS
2
RESTROOM
2
RESTROOM
1
STAIRS
1
ENGINEER'S
OFFICE
SPRINKLER
ROOM
ELEVATOR
LOBBY
VESTIBULE
LUNCH ROOM
BACKROOM
VESTIBULE
SUPERVISOR'S
OFFICE
COMM
ROOM
LAB
HALLWAY
SERVICE ACCESS
HALLWAY
CONFERENCE
ROOM
COMM RM
HALLWAY
UTILITY UTILITY
ACCESSIONING
PROBLEM
RESOLUTION
MECH.
LAB 5
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING RAMP
115
100
HW1
102
103
105
106
104
107
HW2
108
109B
109A
129
HW5
HW7
111
101
HW4A
112
HW8
113
114
LD-2
116
HW10
HW12
LD-1
HW9
120
HW13
138
139
HW13
121
122
124
127
140
ST-2
134
133 130
ST-1
132
131
136
135
HW3
HW6
123
HW14
118
137
HW11
HW4B
128
HW15
119B 119A
EXISTING TO REMAIN
117
118A
141
110
LINE OF EXISTING CANOPY
DN
UP
DN
DN
DN
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"-1'-6"0"
0"
DN
DN
(9) BIKE RACKS
FIRE PUMP &
RISER ROOM
B B
C C
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:53 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F1 FLOOR PLAN
AE101-A1
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F1 FLOOR PLAN FOR REFERENCE ONLY
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
UP
DN
DN
UP
AE202
D1
AE201
D1
AE201 A1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
A2
AE301
A2
AE301
AE202A1
D1
AE301
D1
AE301
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
2-HOUR RATED
GLASS
2-HOUR RATED
GLASS
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
B B
C C
ELEVATOR #1
SERVICE
ELEVATOR
ELEVATOR #2
ELEVATOR #3
CUSTODIAL
ELEVATOR
VESTIBULE
PLUMBING AND
GAS STORAGE
RESTROOM
RESTROOM
MECHANICAL
SHAFT
STORAGEMECHANICAL
SHAFT
STAIR A
STAIR B
SHAFT
SHAFT
SHAFTSHAFT
SAMPLE
RECEIVING
STORAGE
SERVICE
ELEVATOR ELECTRICAL
ROOM
PLUMBING
RISER
ELECTRICAL
RISER
MECH SHAFTMECH SHAFT
ELEVATOR
VESTIBULE HAZARDOUS
MATERIAL
STORAGE SAMPLE
RECIEVING
LOCKERS /
COATS
LOCKERS /
COATS
STORAGEAUTOCLAVE &
GLASS WASH ELECTRICAL
ROOM
PLUMBING
RISER
ELECTRICAL
RISER
MECH SHAFTMECH SHAFT IDF LOCKERS /
COATS
LOCKERS /
COATS
CONTROL AREA
3
CONTROL AREA
2
PHONE PHONE
TOUCHDOWNS
HUDDLE FOCUS FOCUS
BREAK /
PANTRY
RESTROOM
RESPITE
MOTHER'S
HUDDLE
HUDDLE
HUDDLE FOCUS FOCUS
CONTROL AREA
1
SERVICE
CORRIDOR
FLOOR PLAN GENERAL NOTES
1. RESTROOMS: NEW COUNTERS, FIXTURES, TOILET
PARTITIONS, FINISHES AND ACCESSORIES.
2. STAIRWELLS: NEW PAINT, FINISHES, LIGHTING &
GUARDRAILS (CODE COMPLIANT)
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:54 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F2 FLOOR PLAN
AE102
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F2 FLOOR PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DNUP
DN UP
AE202
D1
AE201
D1
AE201 A1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"A2
AE301
A2
AE301
AE202A1
D1
AE301
D1
AE301
2-HOUR RATED
GLASS
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
B B
C C
2-HOUR RATED
GLASS
ELEVATOR #1
SERVICE
ELEVATOR
ELEVATOR #2
ELEVATOR #3
CUSTODIAL
ELEVATOR
VESTIBULE
PLUMBING AND
GAS STORAGE
RESTROOM
RESTROOM
MECHANICAL
SHAFT
STORAGEMECHANICAL
SHAFT
STAIR A
STAIR B
SHAFT
SHAFT
SHAFTSHAFT
STORAGE
SERVICE
ELEVATOR ELECTRICAL
ROOM
PLUMBING
RISER
ELECTRICAL
RISER
MECH SHAFTMECH SHAFT
ELEVATOR
VESTIBULE HAZARDOUS
MATERIAL
STORAGE SAMPLE
RECIEVING
LOCKERS /
COATS
LOCKERS /
COATS
STORAGEAUTOCLAVE &
GLASS WASH ELECTRICAL
ROOM
PLUMBING
RISER
ELECTRICAL
RISER
MECH SHAFTMECH SHAFT IDF LOCKERS /
COATS
LOCKERS /
COATS
SAMPLE
RECEIVING
PHONE PHONEHUDDLE FOCUS FOCUS
HUDDLE
HUDDLE
RESPITE
RESTROOM
MOTHER'S
BREAK /
PANTRY
TOUCHDOWNS
FOCUSFOCUSHUDDLE
CONTROL AREA
1
CONTROL AREA
2
SERVICE
CORRIDOR
FLOOR PLAN GENERAL NOTES
1. RESTROOMS: NEW COUNTERS, FIXTURES, TOILET
PARTITIONS, FINISHES AND ACCESSORIES.
2. STAIRWELLS: NEW PAINT, FINISHES, LIGHTING &
GUARDRAILS (CODE COMPLIANT)
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:55 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F3 FLOOR PLAN
AE103
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F3 FLOOR PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DNUP
DN UP
AE202
D1
AE201
D1
AE201 A1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"A2
AE301
A2
AE301
AE202A1
D1
AE301
D1
AE301
2-HOUR RATED
GLASS
MECHANICAL
SHAFT ABOVE
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
B B
C C
2-HOUR RATED
GLASS
ELEVATOR #1
SERVICE
ELEVATOR
ELEVATOR #2
ELEVATOR #3
CUSTODIAL
ELEVATOR
VESTIBULE
PLUMBING AND
GAS STORAGE
RESTROOM
RESTROOM
MECHANICAL
SHAFT
STORAGEMECHANICAL
SHAFT
STAIR A
STAIR B
SHAFT
SHAFT
SHAFTSHAFT
CONTROL AREA
1
CONTROL AREA
2
MECH SHAFT LOCKERS /
COATS AUTOCLAVE &
GLASS WASH
ELECTRICAL
ROOM IDF
SAMPLE
RECEIVING STORAGE LOCKERS /
COATS MECH SHAFT
ELECTRICAL
RISER
PLUMBING
RISER
MECH SHAFT LOCKERS /
COATS
SERVICE
ELEVATOR ELEVATOR
VESTIBULE
PLUMBING
RISER
ELECTRICAL
RISER
ELECTRICAL
ROOM
HAZARDOUS
MATERIAL
STORAGE SAMPLE
RECIEVING
STORAGE LOCKERS /
COATS MECH SHAFT
FOCUS FOCUSHUDDLE
TOUCHDOWNS
FOCUSFOCUSHUDDLE
HUDDLE
HUDDLE
RESPITE
RESTROOM
MOTHER'S
TOUCHDOWNSSERVICE
CORRIDOR
BREAK /
PANTRY
FLOOR PLAN GENERAL NOTES
1. RESTROOMS: NEW COUNTERS, FIXTURES, TOILET
PARTITIONS, FINISHES AND ACCESSORIES.
2. STAIRWELLS: NEW PAINT, FINISHES, LIGHTING &
GUARDRAILS (CODE COMPLIANT)
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:57 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F4 FLOOR PLAN
AE104
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F4 FLOOR PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DN
DN UP
AE202
D1
AE201
D1
AE201 A1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
A2
AE301
A2
AE301
AE202A1
CUSTODIAL
ELEVATOR
VESTIBULE
PLUMBING AND
GAS STORAGE
RESTROOM
RESTROOM
MECHANICAL
SHAFT
STORAGE
STAIR A
STAIR B
SHAFT SHAFT
SHAFT
FOCUS PHONE PHONE
HUDDLE
FOCUS
CLINICAL
DEVELOPMENT
LAB - CONTROL
AREA 2
D1
AE301
D1
AE301
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"SHAFT
MECHANICAL
SHAFT
SERVER ROOM
MECHANICAL
SHAFT
UP
2-HOUR RATED
GLASS
FOLDING GLASS WALL/
DOOR SYSTEM
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
EXISTING SHIP
LADDER TO ROOF
MLSP TRAINING
- CONTROL
AREA 1
B B
C C
BUILDING
MANAGEMENT
MECH
SHAFT TECH SUPPORT STORAGEELECTRICAL
ROOM
ELEVATOR
VESTIBULE
PLUMBING
RISER
ELECTRICAL
RISER
2-HOUR RATED
GLASS
OFFICE
MECH SHAFT
HUDDLE FOCUS
SERVICE
ELEVATOR
TECH STORAGE
REPLACE ELEVATOR VESTIBULE DOORS
WITH NEW GLASS SMOKE CONTROL
DOORS WITH KEY CARD ACCESS
MECH SHAFT LOCKERS /
COATS
ELECTRICAL
ROOM IDF
SAMPLE
RECEIVING
STORAGE
LOCKERS /
COATS MECH SHAFT
ELECTRICAL
RISER
PLUMBING
RISER
RESPITE HUDDLE
HUDDLE
RESTROOM
SERVICE
CORRIDOR
FLOOR PLAN GENERAL NOTES
1. RESTROOMS: NEW COUNTERS, FIXTURES, TOILET
PARTITIONS, FINISHES AND ACCESSORIES.
2. STAIRWELLS: NEW PAINT, FINISHES, LIGHTING &
GUARDRAILS (CODE COMPLIANT)
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:55:58 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
F5 FLOOR PLAN
AE105
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 F5 FLOOR PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DN
AE202
D1
AE201
D1
AE201 A1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A A
D D
E E
F F
G G
H H
1
1
A2
AE301
A2
AE301
AE202A1
HOISTWAY RELIEF
VENT SHAFTS
MECHANCIAL
PENTHOUSE
D1
AE301
D1
AE301
22'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"72'-0"28'-0"24'-0"24'-0"24'-0"STAIR B
MECHANICAL
YARD
MECHANICAL SCREEN
NEW MECHANICAL PENTHOUSE. EXTERIOR
WALL FINISH TO BE METAL BOX-BEAM.
B B
C C
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 5:05:19 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
R1 ROOF PLAN
AE106
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"A1 R1 ROOF PLAN
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
F1
0' - 0"
F2
19' - 6"
F3
33' - 6"
F4
47' - 6"
F5
61' - 6"
23456789 1
T.O. PARAPET
77' - 8"
EXTENTS OF EXISTING EQUIPMENT SCREEN TO BE REMOVED
PENTHOUSE ROOF
86' - 9 1/2"
NEW ELEVATOR HOISTWAY RELIEF VENT
METAL BOX-RIB EQUIPMENT SCREEN
AND STRUCTURAL SUPPORTS
NEW CMU GENERATOR
SCREEN WALL
F1
0' - 0"
F2
19' - 6"
F3
33' - 6"
F4
47' - 6"
F5
61' - 6"
A D E F G H
T.O. PARAPET
77' - 8"
METAL BOX-RIB EQUIPMENT SCREEN
AND STRUCTURAL SUPPORTSEXTENTS OF EXISTING EQUIPMENT SCREEN TO BE REMOVED
EXISTING EQUIPMENT SCREEN
PENTHOUSE ROOF
86' - 9 1/2"
F1.5
10' - 3 7/8"
EXISTING FENCE
B C
NEW CMU GENERATOR
SCREEN WALL
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 5:29:39 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
EXTERIOR
ELEVATIONS
AE201
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"D1 NORTH ELEVATION
1/8" = 1'-0"A1 WEST ELEVATION
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
F1
0' - 0"
F2
19' - 6"
F3
33' - 6"
F4
47' - 6"
F5
61' - 6"
2 3 4 5 6 7 8 91
T.O. PARAPET
77' - 8"
EXISTING EQUIPMENT SCREEN
PENTHOUSE ROOF
86' - 9 1/2"
F1.5
10' - 3 7/8"
METAL BOX-RIB EQUIPMENT SCREEN
AND STRUCTURAL SUPPORTS
F1
0' - 0"
F2
19' - 6"
F3
33' - 6"
F4
47' - 6"
F5
61' - 6"
ADEFGH
T.O. PARAPET
77' - 8"
PENTHOUSE ROOF
86' - 9 1/2"
F1.5
10' - 3 7/8"
METAL BOX-RIB EQUIPMENT SCREEN
AND STRUCTURAL SUPPORTS
BC
223 YALE AVENUE NORTH
SEATTLE, WASHINGTON 98109
PHONE 206 223 5555
www.nbbj.com
PROJECT NUMBER
PROJECT ARCHITECT
SHEET NAME
SHEET NUMBER
PROJECT MANAGER:
STRUCTURAL ENGINEER:
MEP:
REVISIONS
MARK DATE DESCRIPTIONB
1 2
A
C
D
E
3 4 5 6
1 2 3 4 5 6
F
B
A
C
D
E
F
CBRE
1420 5TH AVE, SUITE 1700
SEATTLE, WA 98101
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
WSP USA
1001 FOURTH AVE., SUITE 3100
SEATTLE, WA 98154
LAB CONSULTING MANAGER:
WESTLAKE CONSULTING GROUP
2825 EASTLAKE AVE. E, SUITE 350
SEATTLE WA 98102
LAB PLANNING:
WSP USA
3340 PEACHTREE ROAD NE, SUITE 2400
ATLANTA, GA. 30326
3/15/2023 4:56:05 PMAutodesk Docs://102987.00 - UW DLMP R22/ARCH_UW DLMP_TI.rvt102987.00
S.LAZEN
EXTERIOR
ELEVATIONS
AE202
UW DLMP
CENTRAL LABS TI
CONDITIONAL
USE PERMIT
MARCH 16, 2023
1/8" = 1'-0"D1 SOUTH ELEVATION
1/8" = 1'-0"A1 EAST ELEVATION
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
UNIVERSITY OF WASHINGTONPROJECT TEAMARCHITECTURALDRAWING LIST - CONDITIONAL USE PERMIT SUBMISSIONA-00A-01A-02A-02.1A-02.2A-02.3A-04A-05A-05.1A-06A-07A-08OWNERUW REAL ESTATEUNIVERSITY OF WASHINGTONUNIVERSITY FACILITIES BUILDING3988 JEFFERSON RD NEBOX 352210CONTACT: BEN NEWTONPH.206-221-0958E-MAIL: BENEWTON@UW.EDUARCHITECT CHERNOFF THOMPSON ARCHITECTS#110 - 1281 WEST GEORGIA ST.VANCOUVER, BC, CANADA V6E 3J5CONTACT: NAOMI GROSSPH.604-669-9460E-MAIL: NAOMI.G@CTA.BC.CA MECHANICALINTEGRITY ENERGY SERVICES, CO.ELECTRICAL 14405 SE 36TH STREET, SUITE 210BELLEVUE, WA 98006CONTACT: MIKE DEAN / ADAM LYONSPH.206 228-7229E-MAIL: MIKED@IESINNOVATES.COM1602 RAYMOND AVE SW, RENTON, WAPROJECT #43005.1- RAYMOND RENOCOVER SHEETPROJECT DATA / CODESITE PLANSITE PLANFLOOD PLAIN MAPNEIGHBOURHOOD DETAIL MAPDEMOLITION PLANRENOVATION PLANRENOVATION PLAN - BF W/R & KITCHENETTEREFLECTED CEILING PLANEXTERIOR ELEVATIONSBUILDING SECTIONSDocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
UNIVERSITY OF WASHINGTON RAYMOND RENO1602 RAYMOND AVENUE SWRENTON, WADocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
BIKE LOCKERS
STOP SIGN/
STREET SIGN
MECH.
EQUIP.
LIGHT
POLE
LIGHTPOLELIGHTPOLELIGHTPOLELIGHT
POLE
CONCRETE PATHWAY
CONCRETE PATHWAYLIGHT
POLE
1602 RAYMOND
AVENUE SOUTHWEST
MOVABLE
GATE
LIGHT
POLE
LETTER BOX
POLE
MANHOLE
FIRE
HYDRANT
LIGHT POLEBIKE LOCKERSBIKE LOCKERSBIKE LOCKERS
··
BIKE LOCKERS
STOP SIGN/STREET SIGN
MECH.EQUIP.
LIGHTPOLE
LIGHTPOLELI
GHTPOLELIG
HTPOLELIGHTPOLE CONCRETE PATHWAY
CONCRETE PATHWAY
LIGHTPOLE
1602 RAYMOND
AVENUE SOUTHWEST
MOVABLEGATELIGHTPOLE
LETTER BOX
POLE
MANHOLE
FIREHYDRANT
LIGHT POLE
·
·
DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
BIKE LOCKERSSTOP SIGN/STREET SIGNMECH.EQUIP.LIGHTPOLELIGHTPOLELIGHTPOLELIGHTPOLELIGHTPOLECONCRETE PATHWAYCONCRETE PATHWAYLIGHTPOLE1602 RAYMONDAVENUE SOUTHWESTMOVABLEGATELIGHTPOLELETTER BOXPOLEMANHOLEFIREHYDRANTLIGHT POLE··DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
LIGHT POLEFIREHYDRANTMANHOLEPOLERAISEDFLOWERBEDRAISEDFLOWERBEDLETTER BOXLIGHTPOLEMOVABLEGATE1602 RAYMONDAVENUE SOUTHWESTCOVEREDSHEDCOVEREDSHEDPLAYSTRUCTUREPLAYSTRUCTURELIGHTPOLEPLAYSTRUCTURECONCRETE PATHWAYCONCRETE PATHWAYLIGHTPOLELIGHTPOLELIGHTPOLELIGHTPOLEGRASSLIGHTPOLEMECH.EQUIP.STOP SIGN/STREET SIGNDocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
LIGHT POLEFIREHYDRANTMANHOLEPOLERAISEDFLOWERBEDRAISEDFLOWERBEDLETTER BOXLIGHTPOLEMOVABLEGATE1602 RAYMONDAVENUE SOUTHWESTCOVEREDSHEDCOVEREDSHEDPLAYSTRUCTUREPLAYSTRUCTURELIGHTPOLEPLAYSTRUCTURECONCRETE PATHWAYCONCRETE PATHWAYLIGHTPOLELIGHTPOLELIGHTPOLELIGHTPOLEGRASSLIGHTPOLEMECH.EQUIP.STOP SIGN/STREET SIGNDocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
MECHANICALJAN.ALARM BTN.101DocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
DUCT EQUIPMENT:WALL MOUNTEDEQUIPMENT:EQUIPMENT:FREESTANDINGTABLESFROM 1601 LINDCASEWORKFROM 1601 LINDDocuSign Envelope ID: 05F46813-3C21-46CD-8D74-95403BA85B11
BF W/R
55 sf
W/R
36 sf
KITCHENETTE
SINK (LAB 5)
BREAK ROOM
101 sf
SINK (LAB 5)