HomeMy WebLinkAboutExhibit3_Floor_Plans_Set_PACCARPACCAR - KENWORTH
R&D BUILDING OFFICE REMODEL
485 HOUSER WAY N.
RENTON, WA 98057
DESIGN DEVELOPMENT
INDEX OF DRAWINGS
01/12/2023
PROJECT LOCATION PROJECT TEAM
PROJECT INFORMATION © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:34 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
COVER SHEET
G0.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL.ARCHITECTURAL.
OP1.1 ORIENTATION PLAN
AD1.1 LEVEL 1 - DEMOLITION PLAN
AD1.2 LEVEL 2 - DEMOLITION PLAN
AD3.1 LEVEL 1 - REFLECTED CEILING DEMOLITION PLAN
AD3.2 LEVEL 2 - REFLECTED CEILING DEMOLITION PLAN
AD4.1 EXTERIOR ELEVATIONS DEMOLITION
A1.1 LEVEL 1 - FLOOR PLAN
A1.2 LEVEL 2 - FLOOR PLAN
A1.3 ROOF PLAN
A2.1 ENLARGED FLOOR PLANS
A3.1 LEVEL 1 - REFLECTED CEILING PLAN
A3.2 LEVEL 2 - REFLECTED CEILING PLAN
A4.1 EXTERIOR ELEVATIONS
A5.1 BUILDING SECTIONS
A5.2 BUILDING SECTIONS
A7.1 STAIR VIEWS
A7.2 STAIR VIEWS
A7.3 ELEVATOR VIEWS
A8.1 PARTITION TYPES
A8.2 DOOR & WINDOW FRAME TYPE AND SCHEDULE
A8.3 ROOM FINISH SCHEDULE
A9.1 EXTERIOR DETAILS
A9.2 CEILING DETAILS
A9.3 GENERAL BUILDING DETAILS
A9.4 DOOR AND WINDOW DETAILS
A10.1 INTERIOR ELEVATIONS
.GENERAL.
G0.1 COVER SHEET
G0.2 GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
G0.3 ARCHITECTURAL SITE PLAN
.STRUCTURAL.
S0.1 GENERAL STRUCTURAL NOTES
S0.2 GENERAL STRUCTURAL NOTES & SPECIAL INSPECTIONS
S0.3 GENERAL STRUCTURAL NOTES, SYMBOLS AND ABBREVIATIONS
S1.1 FOUNDATION PLAN
S1.2 LEVEL 2 - FRAMING PLAN
S1.3 LEVEL 3 - ROOF FRAMING PLAN
S3.1 CONCRETE DETAILS
S4.1 MASONRY DETAILS
S5.1 STEEL DETAILS
S5.2 STEEL DETAILS
.ELECTRICAL.
E0.1 ELECTRICAL SYMBOLS, ABBREVIATIONS & NOTES
ED1.1 LEVEL 01 - ELECTRICAL DEMOLITION PLAN
ED1.2 LEVEL 02 - ELECTRICAL DEMOLITION PLAN
E1.1 LEVEL 01 - LIGHTING PLAN
E1.2 LEVEL 02 - LIGHTING PLAN
E2.1 LEVEL 01 - POWER PLAN
E2.2 LEVEL 02 - POWER PLAN
E3.1 LEVEL 01 - SPECIAL SYSTEMS PLAN
E3.2 LEVEL 02 - SPECIAL SYSTEMS PLAN
E5.1 ELECTRICAL ONE-LINE DIAGRAMS
E7.1 ELECTRICAL SCHEDULES
.CODE.
CP0.1 BUILDING CODE ANALYSIS
CP1.1 CODE PLANS
CLIENT KENWORTH TRUCK CO.
485 HOUSER WAY N,
RENTON, WA 98057
RYAN REED
DIRECTOR OF RESEARCH DEVELOPMENT
425-254-6046
RYAN.REED@PACCAR.COM
ARCHITECT DLR GROUP
51 UNIVERSITY ST #600
SEATTLE, WA 98101
MICHAEL VANDER PLOEG
206-461-6033
MVANDERPLOEG@DLRGROUP.COM
STRUCTURAL ENGINEER DLR GROUP
51 UNIVERSITY ST #600
SEATTLE, WA 98101
CHRISTIE HASENKAMP
402-972-4085
CHASENKAMP@DLRGROUP.COM
PROJECT ADDRESS:
485 HOUSER WAY N.
RENTON, WA 98057
AREA OF WORK
SCOPE OF WORK:
11,411 SF OF INTERIOR RENOVATION INCLUDING ADDITION OF 2ND LEVEL
FOR OFFICE SPACE + 732 SF ADDITION OF EXTERIOR DECK.
BUILDING OWNER: PACCAR INC.
750 HOUSER WAY N,
RENTON, WA 98057
PROJECT SIZE: 11,192 SF (INTERIOR) + 732 SF (EXTERIOR DECK)
CONSTRUCTION TYPE: V-N
ZONING: INDUSTRIAL HEAVY (IH)
OCCUPANCY TYPE: FI, B, S
FULLY SPRINKLERED: YES
NUMBER OF STORIES: TWO + EXTERIOR DECK
PARCEL #: 7223000010
LEGAL DESCRIPTION:
RENTON FARM ACREAGE ADD BLOCKS 1-2-5-6 TGW VACATED
STS ADJ LESS P C R R/W LESS ST OF RENTON FARM ACREAGE
ADD TGW BLOCKS 4-5-13 TGW VACATED STS & ALLEY OF CAR
WORKS ADD TO RENTON TGW PORTION OF SE 1/4 OF SW 1/4 OF
SECTION 08-23-05 LY ELY OF GARDEN AVE & NLY OF CAR WORKS
ADD TO RENTON TGW VACATED STS & ALLEYS ADJ TGW
PORTION OF W 1/2 OF SE 1/4 LY WLY OF PC R R/W & N OF CAR
WORKS ADD TO RENTON TGW VACATED STS ADJ LESS PORTION
DEEDED TO PACCAR INC UNDER RECORDING NO 9003091494
APPLICABLE CODES:
(2018 EDITIONS W/ RENTON AND WA STATE AMENDMENTS)
• INTERNATIONAL BUILDING CODE (IBC)
• INTERNATIONAL EXISTING BUILDING CODE (IEBC)
• INTERNATIONAL FIRE CODE (IFC)
• UNIFORM PLUMBING CODE (UPC)
• INTERNATIONAL MECHANICAL CODE (IMC)
• WASHINGTON STATE ENERGY CODE
• NATIONAL ELECTRICAL CODE (NFPA 70)
LIST OF DEFERRED PERMITS:
- MECHANICAL
- ELECTRICAL
- PLUMBING
- FIRE PROTECTION
ELECTRICAL ENGINEER DLR GROUP
51 UNIVERSITY ST #600
SEATTLE, WA 98101
SEAN AVERY
206-461-6046
SAVERY@DLRGROUP.COM
MECHANICAL ENGINEER DLR GROUP
51 UNIVERSITY ST #600
SEATTLE, WA 98101
DAN LUZIUS
206-461-6090
DLUZIUS@DLRGROUP.COM
.INTERIORS.
A11.1 INTEROR DETAILS
A12.1 LEVEL 1 - FINISH PLAN
A12.2 LEVEL 2 - FINISH PLAN
A13.1 LEVEL 1 - FF&E PLAN
A13.2 LEVEL 2 - FF&E PLAN
LUA23-000230 Exhibit 3
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
GENERAL SYMBOLS
???
?
?
???
SIM
???
?
?
???
?
???
?
ROOM NAME
???
XXX-XX
DETAIL NUMBER
SHEET NUMBER
CROSS REFERENCE
WALL SECTION
SIMILAR OR TYPICAL
REFERENCE
DETAIL REFERENCE
BUILDING SECTION
SHEET NOTE
COLUMN GRID LINE
ROOM NUMBER/NAME
REVISION NUMBER
EARTH
GRAVEL
SAND
CONCRETE
PRECAST CONCRETE
STEEL
STONE
CONCRETE MASONRY UNIT
BRICK VENEER
LEVEL XX
XXX'-XX"LEVEL ELEVATION
GYM FLOOR
WOOD
(CONTINUOUS BLOCKING)
WOOD
(NON-CONTINUOUS BLOCKING)
WOOD (TRIM/FINISH)
GLASS
SHINGLES
PLYWOOD (LARGE SCALE)
GYPSUM WALL BOARD
BLANKET INSULATION
RIGID INSULATION
SPRAY FOAM INSULATION
MINERAL WOOL INSULATION
PROTECTION BOARD
CARPET (LARGE SCALE)
ACOUSTIC TILE (LARGE SCALE)
TILE (LARGE SCALE)
?REFERENCE KEYNOTE
XX A4.XX
BUILDING ELEVATION
A12.X
XX
XX XX
XX
INTERIOR ELEVATION
100'-0"
TYP FF EL=
100'-0"
FINISH FLOOR
ELEVATION
SPOT ELEVATION
X
PROPERTY LINE
LOT LINE
EASMENT LINE
BUILDING LINE, EXISTING
BUILDING LINE, NEW W/DOOR
OPENING AND STRUCTURAL STOOP
PRIMARY CONTOUR, EXISTING
PRIMARY CONTOUR, NEW
SECONDARY CONTOUR, EXISTING
SECONDARY CONTOUR, NEW
SLOPE, PAVEMENT
DRAINAGE DITCH OR SWALE
STREET CENTERLINE
CURB, THICKENED EDGE
CURB, EXISTING
CURB, NEW
PAVING CONTRACTION JOINT
PAVING KEYED CONSTRUCTION JOINT
PAVING TIED CONSTRUCTION JOINT
PAVING EXPANSION JOINT
FENCE, SECURITY
FENCE, BARBED WIRE
FENCE, CHAIN LINK
FENCE, WOOD
SEED LIMIT
SOD LIMIT
FOUNDATION DRAIN, NON-PERFORATED
FOUNDATION DRAIN, PERFORATED
SUBDRAIN, PERFORATED
SANITARY SEWER
FORCE MAIN
WATER
FIRE
GAS
HIGH PRESSURE STEAM
MEDIUM PRESSURE STEAM
LOW PRESSURE STEAM
UNDERGROUND ELEC/TELEPHONE
OVERHEAD POWER
LAWN SPRINKLER HOT LINE
LAWN SPRINKLER LATERAL
100
100
99
99
1% SLOPE
DOWN
KCJ
KCT
EJ
xx xx xx xx
x x x x
FD
S
FM
W
F
G
HPS
MPS
LPS
UGE/UGT
OHP
HOT
LAT
AREA INLET
CURB INLET
MANHOLE
HEAD WALL
FLARED END
CLEAN OUT
CAP
THRUST BLOCK
VALVE
POST INDICATOR VALVE
REDUCER
FIRE HYDRANT
POWER POLE
LIGHT POLE
TELEPHONE MANHOLE
TELEPHONE BOX
SPRINKLER HEAD, 360°
SPRINKLER HEAD, 270°
SPRINKLER HEAD, 180°
SPRINKLER HEAD, 90°
QUICK COUPLING
TREE, EXISTING DECIDUOUS
TREE, EXISTING CONIFER
SHADE TREE
ORNAMENTAL TREE
DECIDUOUS TREE
SHRUB
CLIPPED SHRUB
X'
X"
QC
FH
PIV
CO
SITE SYMBOLS
FD
PSD
GENERAL NOTES
A. GENERAL NOTES APPLY TO ALL SHEETS.
B. DIMENSIONS ARE ACTUAL AND ARE TO FACE OF STUDS, FACE
OF CONCRETE WALLS, FACE OF CMU WALLS, FACE OF FRAMES,
OR CENTERLINE OF COLUMNS, UNLESS NOTED OTHERWISE.
C. THE OWNER SHALL FURNISH AND INSTALL THE FOLLOWING
ITEMS: 1.???, 2. ???
D. INCLUDE ALL OWNER-FURNISHED AND INSTALLED ITEMS AND
OWNER-FURNISHED AND CONTRACTOR-INSTALLED ITEMS IN
THE CONSTRUCTION SCHEDULE, AND SHALL COORDINATE
WITH THE OWNER TO ACCOMMODATE THESE ITEMS.
E. COORDINATE ALL MECHANICAL CHASE SIZES WITH THE
MECHANICAL CONTRACTOR.
F. ARCHITECTURAL FINISH FLOOR ELEVATION 0'-0" EQUALS
ACTUAL SITE REFERENCE ELEVATION OF FINISH FLOOR ?????
FEET.
G. SEE SHEET XX.X FOR LOCATION OF WALLS OF FIRE-
RESISTANCE-RATED CONSTRUCTION. ALL WALLS OF FIRE-
RESISTANCE-RATED CONSTRUCTION SHALL EXTEND TO
UNDERSIDE OF FLOOR OR ROOF DECK ABOVE.
H. ALL PENETRATIONS THROUGH WALLS SHALL BE SEALED WITH
PENETRATION FIRE STOPPING MATERIAL AS REQUIRED TO
ACHIEVE THE RESPECTIVE FIRE-RESISTANCE RATING AND
SMOKE STOPPAGE. SEE SPECIFICATION SECTION 078413.
I. COORDINATE WITH MECHANICAL AND ELECTRICAL
CONTRACTORS THE SIZE AND LOCATION OF EQUIPMENT PADS
SHOWN ON PLANS.
J. FIRE-RESISTANCE-RATED ENCLOSURES AROUND ALL STEEL
COLUMNS SHALL BE CONTINUOUS FROM FLOOR TO UNDERSIDE
OF FLOOR OR ROOF DECK ABOVE FOR EACH LEVEL.
K. WORK: ALL ASPECTS OF THE WORK AND ITEMS NOT
SPECIFICALLY MENTIONED, BUT NECESSARY TO MAKE A
COMPLETE WORKING INSTALLATION, SHALL BE INCLUDED AND
INDICATED IN THE CONTRACTOR'S BID.
L. GENERAL SHEET NOTES ONLY APPLY TO PARTICULAR
DRAWING OR SERIES OF DRAWINGS.
M. NO ASBESTOS OR PCB CONTAINING MATERIALS SHALL BE USED
ON THIS PROJECT.
N. DO NOT SCALE DRAWINGS. DIMENSIONS NOTED PREVAIL.
NOTIFY ARCHITECT IN CASE OF DISCREPANCY.
O. HORIZONTAL AND VERTICAL DIMENSIONS ARE MINIMUM
DIMENSIONS. CLEARANCES ARE GIVEN TO FINISH SURFACES.
GC TO VERIFY ALL CLEARANCES. NOTIFY ARCHITECT IN CASE
OF DISCREPANCY.
ARCHITECTURAL SYMBOLS
XX/ A11.X
?
XX. X. XX
CASEWORK ELEVATION
DOOR NUMBER
EXTERIOR WINDOW /
CURTAIN WALL NUMBER
WALL TYPE
A110
A124
XX/ A11.X XXXX
XX
XX
APC-1
9' -0"
CEILING TYPE
CEILING HEIGHT CEILING TYPE
INTERIOR WINDOW
NUMBER
MR EWC
(ACC)
EWC URINAL URINAL
(ACC)
HD
(ACC)
PTD/R
(ACC)
LAV LAV TTD SD
WC
(ACC)
WC
(ACC)
SND SCD SNV
RH
(ACC)
RH SH(ACC)
ELEVATION 1
SH(ACC)
ELEVATION 2
BCS
**T.O. TABLE IN OPEN
POSITION
MBH US SSS
2009 ICC/A117.1 - 604,609 2009 ICC/A117.1 - 308 2009 ICC/A117.1 - 308
2009 ICC/a117.1 - 604.8 2009 ICC/A117.1 - 608 2009 ICC/A117.1 - 308.2.1 2009 ICC/A117.1 - 603.4
2009 ICC/A117.1 - 308 2009 ICC/A117.1 - 606.3 2009 ICC/A117.1 - 604.7 2009 ICC/A117.1 - 308
2009 ICC/A117.1 - 3082009 ICC/A117.1 - 605.2
2009 ICC/A117.1 - 602.5
KNEE AND TOE CLEARANCE - REFER TO 306
2009 ICC/A117.1 - 603.3
ADULT MOUNTING HEIGHTS
TO B.O.40" MAXTO SPOUT36" MAX27" MIN38" MIN43" MAX2' - 0"17" MAXT.O. CONTROLS44" MIN - 48" MAXT.O. CONTROLS48" MAX34" MAX27" MIN8" MIN
11" MIN 9" MIN34" MAX27" MIN9" MINTO DISPENSER15" MIN TO 48" MAXT.O. CONTROLS44" MIN - 48" MAXFLOOR MOUNTED WC
59" MIN AT
WALL HUNG WC
56" MIN AT
12" MAX42" MIN
C TO REAR WALL
41" MAX - 39" MIN
LGB-3
GB-2
GB-1
T.O. GRAB BAR33" MIN - 36" MAX7" TO 9"1' - 6"B.O. GRAB BAR41" MAX - 39" MIN18" MIN48" MAX60" MIN
1' - 6"
12" MIN 24" MIN
36" MIN
1' - 6"T.O. GRAB BAR33" MIN - 36" MAX2' - 4"T.O. DISPENSER48" MAXCONTROLS44" T.O.1' - 6" 1' - 6"
15" MAX
3' - 0"B.O. CONTROLS34" MINT.O. CONTROLS48" MAX5' - 9"48" MAX1' - 6" 1' - 6"19" MAX17" MIN3' - 0"T.O. CONTROLS44" MAX**34" MAX6' - 0"48" MAX40" MIN15" MINT.O. SPOUTREFLECTINGSURFACE© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:35 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
GENERAL NOTES,
SYMBOLS AND
ABBREVIATIONS
G0.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELA/E ARCHITECT/ENGINEER
AB AIR BARRIER
ABS ASBESTOS
ACC ADA ACCESSIBLE
ACR ACRYLIC
ACT ACOUSTIC CEILING TILE
AD ACCESS DOOR
ADJ ADJUSTABLE
ADJT ADJACENT
ADMIN ADMINISTRATION
AEC AUTOMATED EXTERNAL DEFIBRILLATORS
AL ALUMINUM
ALUM ALUMINUM
AP ACCESS PANEL
APC ACOUSTIC PANEL CEILING
ASPH ASPHALT
AUTO AUTOMATIC
AVG AVERAGE
AWP ACOUSTIC WALL PANEL
B.O. BOTTOM OF
BCS BABY CHANGING STATION
BD BOARD
BLK BLOCK
BLKG BLOCKING
BLKHD BULKHEAD
BM(S) BEAM(S)
BOT BOTTOM
BRDG BRIDGING
BRG BEARING
BRKT BRACKET
BT BATHTUB
BTWN BETWEEN
CAB CABINET
CBD CHALKBOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CLEAR FLOAT GLASS
CI CAST IRON
CIG CLEAR INSULATING GLASS
CIP CAST IN PLACE
CJ CONTROL JOINT
CJA CONTROL JOINT ABOVE
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COM COMMON
COMB COMBINATION
COMM COMMUNICATIONS
COMPR COMPRESSIBLE
CONF CONFERENCE
CONFIG CONFIGURATION
CORR CORRIDOR
CP COVER PLATE
CPT CARPET
CR CHAIR RAIL
CS COUNTERSINK
CSTJ CONSTRUCTION JOINT
CSWK CASEWORK
CT CERAMIC TILE
CTG CLEAR TEMPERED FLOAT GLASS
CTIG CLEAR TEMPERED INSULATING GLASS
CU COPPER
CU COMBINATION UNIT
CV CONDOM VENDOR
CY CUBIC YARD
CYL CYLINDER
DB DECIBEL
DBL DOUBLE
DC DUST COLLECTOR
DEPR DEPRESS(ION)(ED)
DEPT DEPARTMENT
DET DETENTION
DF DRINKING FOUNTAIN
DG DOOR GRILLE
DIAG DIAGONAL
DPFG DAMPROOFING
DR DOOR
DSN DOWNSPOUT NOZZLE
DW DISHWASHER
DWL(S) DOWEL(S)
DWR DRAWER
EB EXPANSION BOLT
EE EACH END
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE WASH SHOWER
EFF EFFICIENCY
EJ EXPANSION JOINT
ELAS ELASTOMERIC
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENTR ENTRANCE
ERF EPOXY RESIN FLOORING
EUI ENERGY USE INTENSITY
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXP EXPANSION
EXP EXPOSED
F FABRIC
F.O. FACE OF
FAB FABRICATE(D)
FB FACE BRICK
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIX FIXTURE
FLASH FLASHING
FLEX FLEXIBLE
FLG FLOORING
FLM FULL LENGTH MIRROR
FLUOR FLUORESCENT
FO FINISH OPENING
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FP FIREPROOFING
FR FIRE RESISTANT
FRP FIBERGLASS REINFORCED PANEL
FRT FIRE RESISTANCE TREATED
FS FLOOR SINK
FSS FOLDING SHOWER SEAT
FTG FOOTING
FVC FIRE VALVE CABINET
FWC FABRIC WALL COVERING
G GROUT
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GD GARBAGE DISPOSAL
GEN GENERAL
GFA GROSS FLOOR AREA
GL GLUE LAMINATED
GL GLASS
GMP GUARANTEED MAXIMUM PRICE
GR GUARD RAIL
GR GRADE
GRS GALVANIZED RIGID STEEL
GWB GYPSUM WALL BOARD
GYP GYPSUM
HC HOLLOW CORE
HD HAND DRYER
HDF HIGH DENSITY FIBERBOARD
HDR HEADER
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HR HOUR
HR HANDRAIL
HS HARDWARE SET
HSS HOLLOW STRUCTURAL SHAPE
HVAC HEATING VENTILATING AND AIR CONDITIONING
IAW IN ACCORDANCE WITH
ID INSIDE DIAMETER
IF INSIDE FACE
IIP INSULATED INFILL PANEL GLASS
IJ ISOLATION JOINT
IJS IN JOIST SPACE
INC INCLUDE(ING)
INSUL INSULATION
JAN JANITOR
JBE JOIST BEARING ELEVATION
JCT JUNCTION
JFB JOINT FILLER BOARD
JST JOIST
JT JOINT
KCJ KEYED CONSTRUCTION JOINT
KD KNOCKDOWN
KH KITCHEN HOOD
KIT KITCHEN
L ANGLE
LAB LABORATORY
LAM LAMINATED
LAV LAVATORY
LBR LUMBER
LDG LOADING
LF LINEAR FOOT
LG LENGTH (LONG)
LG LAMINATED GLASS
LIN LINEAR
LINO LINOLEUM
LKR LOCKER
LOC LOCATION
LONG LONGITUDINAL
LSC LIFE SAFETY CODE
LTG LIGHTING
LV LOUVER
LVT LUXURY VINYL TILE
MAG MAGNETIC
MAINT MAINTENANCE
MAN MANUAL
MAS MASONRY
MATL MATERIAL
MB MOP BASIN
MBD MARKER BOARD
MBH MOP/BROOM HOLDER
MC MEDICINE CABINET
MEMB MEMBRANE
MH MANHOLE
MR/S MIRROR WITH SHELF
MTD MOUNTED
MTG MOUNTING
MUL MULLION
NC NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NOM NOMINAL
O to O OUT TO OUT
OA OVERALL
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OPPOSITE HAND
OPG(S) OPENING(S)
OSHA OPERATIONAL SAFETY AND HEALTH ADMINISTRATION
OTB OPEN TO BELOW
OVFL OVERFLOW
P PAINT
PAN B PANIC BOLT
PB PARTICLE BOARD
PC PRECAST CONCRETE
PCD PAPER CUP DISPENSER
PCT PORCELAIN CERAMIC TILE
PD PANIC DEVICE
PERF PERFORATED
PERP PERPENDICULAR
PG PATTERN GLASS
PIC PORTABLE INSTRUMENT CONNECTION
PIG PATTERN INSULATING GLASS
PL PLATE
PL PROPERTY LINE
PL PLASTIC LAMINATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PR PAIR
PREFAB PREFABRICATED
PROJ PROJECT(OR) (ION)
PS PROJECTION SCREEN
PT POINT
PT POINT OF TANGENCY
PTD PAPER TOWEL DISPENSER
PTD/R COMBINATION TOWEL DISPENSER/RECEPTACLE
PTN PARTITION
PVC POLYVINYL CHLORIDE
PWL SOUND POWER LEVEL
QT QUARRY TILE
QTR RND QUARTER ROUND
R RISER
RAD RADIUS
RB RUBBER BASE
RC REMOTE CONTROL
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REM REMOVABLE
RESIL RESILIENT
RF RESILIENT FLOORING
RF RUBBER FLOOR
RFM RECESSED FLOOR MAT
RH ROBE HOOK
RI&C ROUGH IN AND CONNECT
S SINK
SAT SPRAYED ACOUSTIC TREATMENT
SAW SOUND ABSORBING WALL UNITS
SB SPLASH BLOCK
SC SOLID CORE
SC SHOWER CURTAIN
SCD SEAT COVER DISPENSER
SCH SHOWER CURTAIN HOOK
SCR SHOWER CURTAIN ROD
SCT STRUCTURAL CLAY TILE
SD SOAP DISPENSER
SECY SECRETARY
SF SQUARE FEET
SG SPANDREL GLASS
SGL SINGLE
SH SHOWER
SHM SECURITY HOLLOW METAL
SLNT SEALANT
SM SHEET METAL
SND SANITARY NAPKIN DISPOSAL
SNV SANITARY NAPKIN VENDOR
SPL SOUND PRESSURE LEVEL
SQ SQUARE
SS SOLID SURFACE
SSA STORM SHELTER AREA
SSS STAINLESS STEEL SHELF
SST STAINLESS STEEL
ST STONE
ST STAIR
STAG'D STAGGERED
STC SOUND TRANSMISSION CLASS
STGR STRINGER
SUBFL SUBFLOOR
SURF SURFACE
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
T TREAD
T&G TONGUE AND GROOVE
T.O. TOP OF
TAN TANGENT
TB TOWEL BAR
TBD TACK BOARD
TCP TOILET COMPARTMENT PARTITION
TERR TERRAZZO
TFG TINTED FLOAT GLASS
TG TEMPERED GLASS
TH THRESHOLD
THK THICK(NESS)
TI TENANT IMPROVEMENT
TIG TINTED INSULATING GLASS
TMR TILT MIRROR UNIT
TOIL TOILET
TOP TOP OF PAVING
TRANS TRANSVERSE
TT TERRAZZO TILE
TTD TOILET TISSUE DISPENSER
TTG TINTED TEMPERED FLOAT GLASS
TTIG TINTED TEMPERED INSULATING GLASS
TW TACK WALL
UL UNDERWRITERS LABORATORIES
UR URINAL
US UTILITY SHELF
UTIL UTILITY
VB VAPOR BARRIER
VB VINYL BASE
VCB VENTED COVE BASE
VF VINYL FLOOR
VOC VOLITILE ORGANIC COMPOUND
VOL VOLUME
VP VENEER PLASTER
VT VINYL TILE
VWC VINYL WALL COVERING
W WIDE
WB WALL BASE
WC WATER CLOSET
WC WALL COVERING
WCL WATER CLOSET/LAVATORY COMBINATION
WD WOOD
WDF WOOD FLOORING
WDW WINDOW
WG POLISHED WIRE GLASS
WI WROUGHT IRON
WOM WALK OFF MAT
WR WASTE RECEPTACLE
WRB WEATHER RESISTANT BARRIER
WW WARM WHITE
WWF WELDED WIRE FABRIC
YD YARD
ABBREVIATIONS
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:36 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ARCHITECTURAL
SITE PLAN
G0.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1" = 30'-0"
SITE PLAN
PARCEL #: 7223000010
LEGAL DESCRIPTION:
RENTON FARM ACREAGE ADD BLOCKS 1-2-5-6 TGW VACATED STS ADJ
LESS P C R R/W LESS ST OF RENTON FARM ACREAGE ADD TGW BLOCKS
4-5-13 TGW VACATED STS & ALLEY OF CAR WORKS ADD TO RENTON TGW
PORTION OF SE 1/4 OF SW 1/4 OF SECTION 08-23-05 LY ELY OF GARDEN
AVE & NLY OF CAR WORKS ADD TO RENTON TGW VACATED STS &
ALLEYS ADJ TGW PORTION OF W 1/2 OF SE 1/4 LY WLY OF PC R R/W & N
OF CAR WORKS ADD TO RENTON TGW VACATED STS ADJ LESS PORTION
DEEDED TO PACCAR INC UNDER RECORDING NO 9003091494
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
LEGEND - OCCUPANCY GROUP PLANS
SINGLE USE OCCUPANCY GROUP TAG
- TAG USED TO INDICATE OCCUPANCY GROUP
AND GROSS BUILDING AREA PER STORY IN SF
MIXED-USE OCCUPANCY GROUP TAG
- TAG USED FOR SEPARATED, NON-
SEPARATED, AND ACCESSORY USES
ACC
150 SF
X-X Y-Y
150 SF
X-X
ASSIGNED OCCUPANCY GROUP
OPTIONS:
SEP = SEPARATED
NON = NON-SEPARATED
ACC = ACCESSORY
PRIMARY OCCUPANCY GROUP
FOR NON OR ACC OCCUPANCIES
GROSS BUILDING AREA
PER STORY IN SF
B ASSEMBLY
B OFFICE
F-1 FACTORY
S-2
OCCUPANCY GROUP PATTERNS
7212 SF
F-1
5458 SF
B-OFFICE
9897 SF
S-2
270 SF
B
B OCCUPANCY
OVER F-1 OCCUPANCY
231 SF
B-ASSEMBLY
752 SF
B-ASSEMBLY
5474 SF
B-OFFICE
285 SF
B-ASSEMBLY
688 SF
DECK
PROJECT DATA AND CODE ANALYSIS
CONSTRUCTION TYPE:
V-N
OCCUPANCY CLASSIFICATION:
• BUSINESS GROUP B
• FACTORY GROUP F1
• STORAGE GROUP S2
FIRE ALARM:
SPRINKLER INFORMATION:
BUILDING FULLY SPRINKLERED
SEPARATED OCCUPANCIES:
NO SEPARATION IS REQUIRED BETWEEN GROUP B AND F1, AND 1 HOUR SEPARATION
IS REQUIRED BETWEEN GROUP B AND S2 WHEN BOTH ARE PROTECTED BY AUTOMATIC
SPRINKLER SYSTEMS.
APPLICABLE CODES:
(2018 EDITIONS W/ RENTON AND WA STATE AMENDMENTS)
• INTERNATIONAL BUILDING CODE (IBC)
• INTERNATIONAL EXISTING BUILDING CODE (IEBC)
• INTERNATIONAL FIRE CODE (IFC)
• UNIFORM PLUMBING CODE (UPC)
• INTERNATIONAL MECHANICAL CODE (IMC)
• WASHINGTON STATE ENERGY CODE
• NATIONAL ELECTRICAL CODE (NFPA 70)
BUILDING EXISTING INFORMATION
EXITS OR ACCESS TO EXITS REQUIRED PER STORY (IBC TABLE 1006.3.2 & 1006.3.3):
FIRST FLOOR:
GROUP B: REQUIRED - 2
PROVIDED - 4
GROUP F1: REQUIRED - 2
PROVIDED - 3
GROUP S2:REQUIRED - 2
PROVIDED - 3
SECOND FLOOR:
GROUP B: REQUIRED - 2
PROVIDED - 3
DECK:
REQUIRED: 1
PROVIDED: 1
EXIT EGRESS CAPACITY (IBC 1005.3):
LEVEL 2 STAIR WAY WIDTH
51 OCC X 0.3 = 15.3" WIDTH REQUIRED, 95" PROVIDED,
DISTRIBUTED BETWEEN 2 STAIRS
CODE MINIMUM OF 44" STAIR WIDTH PROVIDED PER IBC 1011.2
LEVEL 1 OTHER EGRESS COMPONENT WIDTH
235 OCC X 0.2 = 47" WIDTH REQUIRED, 396" PROVIDED
COMMON PATH OF TRAVEL (IBC TABLE 1006.2.1):
MAXIMUM ALLOWABLE (B OCCUPANCY): 100' WITH SPRINKLER SYSTEM
MAXIMUM ALLOWABLE (F1 OCCUPANCY): 100' WITH SPRINKLER SYSTEM
MAXIMUM ALLOWABLE (S2 OCCUPANCY): 100' WITH SPRINKLER SYSTEM
EXIT ACCESS TRAVEL DISTANCE (IBC TABLE 1017.2):
MAXIMUM ALLOWABLE (B OCCUPANCY): 300' WITH SPRINKLER SYSTEM
MAXIMUM ALLOWABLE (F1 OCCUPANCY): 250' WITH SPRINKLER SYSTEM
MAXIMUM ALLOWABLE (S2 OCCUPANCY): 400' WITH SPRINKLER SYSTEM
PLUMBING FIXTURE COUNT (IBC 2902.1)
WATER CLOSETS
MALE:
38 OCC. @ B-OFFICE = 1:25 FOR FIRST 50, 1:50 REMAINDER EXCEEDING 50
62 OCC.: @ B-ASSEMBLY = 1:125
67 OCC.: @ F1/S2 = 1:100
TOTAL REQUIRED: 4
TOTAL PROVIDED: 4
FEMALE:
38 OCC. @ B-OFFICE = 1:25 FOR FIRST 50, 1:50 REMAINDER EXCEEDING 50
62 OCC.: @ B-ASSEMBLY = 1: 65
67 OCC.: @ F1/S2 = 1:100
TOTAL REQUIRED: 4
TOTAL PROVIDED: 4
LAVATORIES
MALE:
38 OCC. @ B-OFFICE = 1:40 FOR FIRST 80, 1:80 REMAINDER EXCEEDING 80
64 OCC.: @ B-ASSEMBLY = 1:200
67 OCC.: @ F1/S2 = 1:100
TOTAL REQUIRED: 3
TOTAL PROVIDED: 4
FEMALE:
38 OCC. @ B-OFFICE = 1:40 FOR FIRST 80, 1:80 REMAINDER EXCEEDING 80
64 OCC.: @ B-ASSEMBLY = 1:200
67 OCC.: @ F1/S2 = 1:100
TOTAL REQUIRED: 3
TOTAL PROVIDED: 3
DRINKING FOUNTAIN
76 OCC. @ B-OFFICE = 1:100 = 0.76
128 OCC.: @ B-ASSEMBLY = 1:500 = 0.26
37 OCC.: @ F1 = 1:400 = 0.1
95 OCC.: @ S2 = 1:1000 = 0.1
TOTAL REQUIRED: 2
TOTAL PROVIDED: 2
SERVICE SINK
TOTAL REQUIRED: 4?© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:25 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
BUILDING CODE
ANALYSIS
CP0.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELGROSS AREA SCHEDULE
LEVEL NAME
OCCUPANCY
GROUP AREA
LEVEL 01 F-1 7,212 SF
LEVEL 01 B 5,458 SF
LEVEL 01 S-2 9,897 SF
LEVEL 01 B 270 SF
LEVEL 01 A-2 231 SF
LEVEL 01 A-2 752 SF
LEVEL 02 B 5,474 SF
LEVEL 02 A-2 285 SF
DECK A-2 688 SF
Grand total 30,267 SF
NSCALE:1/16" = 1'-0"
OCCUPANCY GROUP, LEVEL 1NSCALE:1/16" = 1'-0"
OCCUPANCY GROUP, LEVEL 2NSCALE:1/16" = 1'-0"
OCCUPANCY GROUP, DECK
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
PRESENTATION
108
MODELING
ROOM
107
WOOD SHOP
104
PREPARATION
AREA
101
TOOL ROOM
103
ROUTER ROOM
105
TRUCK BAYS
126
MACHINE
SHOP
127
WAREHOUSE
128
7161 SF
200 SF/OCC37 OCC
F-1
5506 SF
150 SF/OCC40 OCC
B-OFFICE
9897 SF
add space function
100 SF/OCC95 OCC
S-2
724 SF
B-ASSEMBLY
210 SF
B-ASSEMBLY
1808"3536"0.21808"3536"0.2 1808" 3536"0.2
1802"836"0.2
34' COMMON PATH OF TRAVEL
92' EXIT ACCESS TRAVEL DISTANCE 107' EXIT ACCESS TRAVEL DISTANCE15 Net SF
100 Gross SF
120 Gross SF
150 Gross SF
200 Gross SF
OCCUPANT LOAD FACTORS
LEGEND - CODE FLOOR PLANS
SEPARATION LEGEND
0
1"0
0"0.15OCCUPANT LOAD TAG (GROSS)
PD
XX MIN - DOOR FIRE RATING
HOURLY RATING
0 = 0 HOUR
5 = 1/2 HOUR
1 = 1 HOUR
2 = 2 HOUR
3 = 3 HOUR
4 = 4 HOUR
SP = SMOKE PARTITION
Space Function
XXXX SF
XXX SF/OCCXXX OCC
Area name
G
REQUIRED WIDTH FOR OCCUPANT LOAD (INCHES)
REQUIRED OCCUPANT LOAD
CAPACITY OF EGRESS COMPONENT (WIDTH IN INCHES)
CAPACITY OF EGRESS COMPONENT (OCCUPANTS)
LOAD FACTOR (INCHES/OCCUPANT)
- WHEN LOAD FACTOR TRIANGLE IS FILLED - THIS IS TOTAL EXIT FROM LEVEL
DOOR TAG
- PANIC DEVICE
OCCUPANT LOAD TAG (NET)
- THIS LOAD DOES NOT EXTEND BEYOND THIS SPACE
- SEE PATTERN FOR APPLIED LOAD FACTOR
- SELECT FUNCTION OF SPACE FOR AREA
- INPUT OCCUPANT LOAD
- SELECT FUNCTION OF SPACE FOR AREA
- INPUT CALCULATED OCCUPANT LOAD
MAX TRAVEL = Length
XXXX SF
###
XXX
EXIT ACCESS TRAVEL DISTANCE
FIRE AND SMOKE SEPARATION TYPES
= CORRIDOR (CYAN)
= EXTERIOR WALL (PURPLE)
= FIRE WALL (BLUE)
= FIRE BARRIER (RED)
= FIRE PARTITION (MAGENTA)
= SMOKE PARTITION (GREEN)
= SMOKE BARRIER (GREEN)
= VERTICAL SHAFT (ORANGE)
= VERTICAL EXIT ENCLOSURE (ORANGE)
= EXIT PASSAGEWAY (YELLOW)
EXIT TAG
- CUMULATIVE OCCUPANT LOAD
- EGRESS CAPACITY
AREA (SF)
ROOM NUMBER
OCCUPANT LOAD
EXIT SIGN
COMMON PATH OF EGRESS TRAVEL DISTANCE
MAX CP = Length
1/3 DIAG = X'-X"
MAX DIAG DIM = X'-X"MAX OVERALL DIAGONAL DIM OF AREA SERVED
DISTANCE = X'-X"
MIN SEPARATION MIN EXIT SEPARATION
C
EW
XP
FB
FW
SB
FP
SP
VS
VX
5343 SF
B-OFFICE
270 SF
B-ASSEMBLY
1576" 1747"0.3
160
6"17
48"0.31804" 1736"0.2
28' COMMON PATH OF TRAVEL
146' DISTANCE TO FIRST FLOOR EXIT
197' DISTANCE TO FIRST FLOOR EXIT
688 SF
DECK16815"4951"0.3
4' - 10 1/2"© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:27 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
CODE PLANS
CP1.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/16" = 1'-0"
CODE PLAN, LEVEL 1
OCCUPANT LOAD TABLE - LEVEL 1
AREA NAME FUNCTION OF SPACE AREA GROSS/NET OLF
OCCUPANT
LOAD
B-ASSEMBLY 210 SF net 15 14
B-ASSEMBLY 724 SF net 15 49
B-OFFICE 5,506 SF gross 150 40
F-1 7,161 SF gross 200 37
S-2 add space function 9,897 SF gross 100 95
GRAND TOTAL: 5 235NSCALE:1/16" = 1'-0"
CODE PLAN, LEVEL 2NSCALE:1/8" = 1'-0"
CODE PLAN, DECK
OCCUPANT LOAD TABLE - DECK
LEVEL AREA NAME FUNCTION OF SPACE AREA GROSS/NET OLF
OCCUPANT
LOAD
688 SF
DECK DECK 688 SF net 15 46
GRAND TOTAL 46
OCCUPANT LOAD TABLE - LEVEL 2
AREA NAME FUNCTION OF SPACE AREA GROSS/NET OLF
OCCUPANT
LOAD
B-ASSEMBLY 270 SF net 15 15
B-OFFICE 5,343 SF gross 150 36
GRAND TOTAL: 2 51
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.UP
UP
UP
REF.
DN
DN
DN
DN
PN Q R SMLK
1
2
3
4
HGFEDCBA
0.2
0.1
0.3
J
NIC NIC
1.6
2.2
2.8
3.4
PN Q R SMLK
1
2
3
4
HGFEDCBA
0.2
0.1
0.3
J
NIC
NIC
1.6
2.2
2.8
3.4 © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
R&D BLDG
OVERALL
1/13/2023 5:16:40 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ORIENTATION
PLAN
OP1.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/16" = 1'-0"
ORIENTATION PLAN, LEVEL 01
NSCALE:1/16" = 1'-0"
ORIENTATION PLAN, LEVEL 02
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
UP
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. REFERENCE A4.1 FOR NEW OPENING.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.
SHEET NOTES#
NMLK
1
2
3
4
HGFEDC
AD4.1
0.2
0.1
0.3
1
AD1.1
5AMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
PRESENTATION
108
MODELING
ROOM
107
WOOD SHOP
104
TRUCK BAYS
126
MACHINE
SHOP
127
J
AD4.1
2
1.6
2.2
2.8
3.4
SEE ELEVATION
FOR DIMENSIONS. 26' - 0 3/4"K
4
J
11
3.4
EXISTING PARTITION TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING ACOUSTIC CEILING
SYSTEM TO BE DEMOLISHED
DEMOLITION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)© DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:18 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -
DEMOLITION
PLAN
AD1.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL1 COUNTER TOPS, FINISHES, AND LIGHT FIXTURES
TO BE UPDATED IN EXISTING RESTROOMS.
LAYOUT TO REMAIN UNCHANGED.
2 NEW WALL OPENING TO BE CREATED IN EXISTING
SHEER WALL. SEE STRUCTURAL FOR MORE
INFORMATION.
3 DEMO SHEET NOTE 3
NSCALE:1/8" = 1'-0"
DEMOLITION PLAN, LEVEL 1
SCALE:1/4" = 1'-0"AD1.1
5A ENLARGED DEMOLITION PLAN, LEVEL 1 - RESTROOMS
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. REFERENCE A4.1 FOR NEW OPENING.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.
NMLK
1
2
3
4
HGFEDC
AD4.1
0.2
0.1
0.3
1B/ A2.1
1B
1
MATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
MECH
MEZZANINE
M201
J
AD4.1
2
A2.1
2C
2B
A2.1
3B
3C
2
6' - 7 1/4"12' - 10"26' - 9 5/8"29' - 7 1/4"48' - 11 3/8"SEE ELEVATION
FOR DIMENSIONS
AND REFER TO
STRUCTURAL FOR
REINFORCEMENT.
1.6
2.2
2.8
3.4
A10.11D
A10.1
1E
EXISTING PARTITION TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING ACOUSTIC CEILING
SYSTEM TO BE DEMOLISHED
DEMOLITION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
SHEET NOTES#© DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:18 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -
DEMOLITION
PLAN
AD1.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
DEMOLITION PLAN, LEVEL 2
1 COUNTER TOPS, FINISHES, AND LIGHT FIXTURES
TO BE UPDATED IN EXISTING RESTROOMS.
LAYOUT TO REMAIN UNCHANGED.
2 NEW WALL OPENING TO BE CREATED IN EXISTING
SHEER WALL. SEE STRUCTURAL FOR MORE
INFORMATION.
3 DEMO SHEET NOTE 3
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
NMLK
1
2
3
4
HGFEDC
AD4.1
0.2
0.1
0.3
1
MATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
PRESENTATION
108
MODELING
ROOM
107
WOOD SHOP
104
TRUCK BAYS
126
MACHINE
SHOP
127
J
AD4.1
2
1.6
2.2
2.8
3.4
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. REFERENCE A4.1 FOR NEW OPENING.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.
EXISTING PARTITION TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING ACOUSTIC CEILING
SYSTEM TO BE DEMOLISHED
DEMOLITION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)© DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:19 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -
REFLECTED
CEILING
DEMOLITION
PLAN
AD3.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
DEMOLITION REFLECTED CEILING PLAN, LEVEL 1
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
NMLK
1
2
3
4
HGFEDC
AD4.1
0.2
0.1
0.3
1
A4.1
3A
MECH
MEZZANINE
M201
J
A4.1
1A
DE4.1
2
DE4.1
1
AD4.1
2
1.6
2.2
2.8
3.4
A10.11D
A10.1
1E
EXISTING PARTITION TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING ACOUSTIC CEILING
SYSTEM TO BE DEMOLISHED
DEMOLITION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. REFERENCE A4.1 FOR NEW OPENING.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.© DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:21 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -
REFLECTED
CEILING
DEMOLITION
PLAN
AD3.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
DEMOLITION REFLECTED CEILING PLAN, LEVEL 2
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
P NQRS M L K J H
Level 01
0"
Level 02
16' - 0"
T.O. PANEL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WNDW OPENING
25' - 0"
B.O. WNDW OPENING
20' - 0"
ROOF BEARING
32' - 8"
J.5
Exist Mezz
13' - 0"
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
P NQRS M L K H
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
J
2' - 6"4' - 0"6"3' - 4"1' - 2"1' - 4" 6' - 0"
3' - 4"1' - 4"7' - 4"EXISTING CANOPY TO
BE REMOVED.
2' - 4 3/8"8' - 0"3' - 9 1/4"8' - 0"
2' - 1 5/8"3' - 0" 6' - 0"
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
NMLKJHGFEDC
Level 01
0"
Level 02
16' - 0"
T.O. PANEL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WNDW OPENING
25' - 0"
B.O. WNDW OPENING
20' - 0"
ROOF BEARING
32' - 8"
J.5
Exist Mezz
13' - 0"
C.3 NMLKJHGFEDC
Level 01
0' - 0"
T.O. PANEL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WNDW OPENING
25' - 0"
B.O. WNDW OPENING
20' - 0"
ROOF LEVEL 03
32' - 8"
LEVEL 02
16' - 0"
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
NMLKHGFEDC
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
J
3' - 4" 8' - 11 1/4"7' - 4"4' - 10" 2' - 7" 2' - 3" 4' - 10"7' - 7" 4' - 10"1' - 10" 4' - 10"6' - 6"2' - 6"6' - 6"2' - 6"6' - 6"2' - 6"DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. REFERENCE A4.1 FOR NEW OPENING.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:21 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
EXTERIOR
ELEVATIONS
DEMOLITION
AD4.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE: 1/8" = 1'-0"AD4.1
1 DEMOLITION ELEVATION - WEST
SCALE:1/8" = 1'-0"AD4.1
2 DEMOLITION ELEVATION - EAST
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
UP
REF.UP
UP
UP
UP
SHEET NOTES#
GENERAL ARCHITECTURAL NOTES
1. ALL INTERIOR CMU WALLS SHALL BE 8 INCHES NOMINAL
THICKNESS, UNLESS NOTED OTHERWISE.
2. PARTITION TYPES ARE DESIGNATED ON FLOOR PLANS
THUS: SEE SHEET A8.1 FOR TYPES. ALL INTERIOR
PARTITIONS ARE TYPE SA.3.20 UNLESS NOTED OTHERWISE.
3. ALL MASONRY WALLS AND INTERIOR STUD WALLS SHALL
EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECK ABOVE
UNLESS NOTED OTHERWISE, PER PARTITION TYPE.
4. PROVISIONS ARE MADE AT ALL FULL HEIGHT NON-BEARING
WALLS FOR 1-INCH VERTICAL MOVEMENT OF THE BUILDING
STRUCTURE WITHOUT TRANSFER OF COMPRESSIVE LOADS TO
WALL. FILL IRREGULARITIES BETWEEN TOP OF WALL AND DECK
ABOVE WITH MINERAL WOOL INSULATION OR FIRE STOPPING
MATERIALS AS REQUIRED TO MEET FIRE RATING OF
RESPECTIVE WALLS. SEE DETAILS ON SHEET XX.X.
5. SEE STRUCTURAL DRAWINGS FOR BRACING OF NON-LOAD
BEARING MASONRY WALLS.
6. FURNISH AND INSTALL FIRE-TREATED WOOD BLOCKING OR
METAL BACKING PLATE IN METAL STUD PARTITIONS FOR THE
PROPER ANCHORAGE OF ALL WALL ATTACHED ITEMS; I.E.
TOILET ACCESSORIES, CASEWORK, MILLWORK, WALL-
MOUNTED FIXTURES, DOOR STOPS, AUDIO VISUAL BRACKETS,
AND OTHER WALL ATTACHED ITEMS.
7. GYPSUM BOARD SURFACES SHALL BE ISOLATED WITH
CONTROL JOINTS WHERE SHOWN ON DRAWINGS AND AS
DESCRIBED IN THE SPECIFICATIONS.
8. MASONRY CONTROL JOINTS (CJ) AND CONTROL JOINTS ABOVE
(CJA) SHALL BE LOCATED AS SHOWN ON THE FLOOR PLAN AND
BUILDING ELEVATIONS, AND WHERE LARGE PLUMBING VENTS
OR RISERS OCCUR IN SINGLE WYTHE MASONRY WALLS, AND
WHERE MASONRY WALLS BEARING ON THE CONCRETE FLOOR
SLAB ABUT MASONRY WALLS BEARING ON CONCRETE
FOOTINGS OR AS INDICATED ON DRAWINGS.
9. EXTEND FURRING CHANNELS AND GYPSUM BOARD UP 4
INCHES ABOVE FINISHED CEILING ON CMU WALLS.
10. SCRIBE GYPSUM WALL BOARD OF WALLS AND PARTITIONS TO
IRREGULARITIES OF DECK ABOVE. SEAL TIGHTLY AROUND ALL
PENETRATIONS.
11. PROVIDE SEISMIC BRACING FOR SUSPENDED CEILINGS OR AS
SHOWN ON THE DRAWINGS.
XX. X. XX
NMLK
1
2
3
4
HGFEDC
1E
A5.2
0.2
0.1
1C
A5.2
0.3MATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
A4.1
3A
A2.1
4A
A7.2
5A
A7.1
2A
A7.1
5A
A7.3
3D
1A
A5.1
1A
A5.2
PRESENTATION
108 A10.13A
6' - 8 3/8" 4' - 11 1/4" 5' - 2 3/8" 10' - 2"
10"
4' - 2"1194"
MODELING
ROOM
107
WOOD SHOP
104
TRUCK BAYS
126
MACHINE
SHOP
127
DASHED LINE INDICATES
EDGE OF CANOPY ABOVE
120A120B
121A 121B121CE112AJ
CLOS
118
A4.1
1A
MED CONF
119
STAIR 1
S101
SHARED
OFFICE
120
ELEC
121
LIFT
L101
LARGE CONF
110
CIRCULATION
117
CIRCULATION
111
WOMEN
113
MEN
115
VEST.
114
VEST.
116
LUNCH ROOM
122
JANITOR
123
STORAGE
129
TOOL ROOM
125
STAIR 3
S103
STAIR 4
S104
A10.1 1A1B
STAIR 2
S102 1C/ A10.1MA. 12. 00
MA. 8. 00
SA. 3. 20
SA. 3. 10
SA. 8. 10
SA. 6. 20
SA. 3. 30
1.6
2.2
2.8
3.44' - 8 1/4"11' - 4 7/8"6' - 5 1/4"5' - 7 3/4"6"13' - 5 3/8"3' - 4"5' - 8 3/4"6' - 2 3/4" 13' - 5 1/4"5 1/2"6 5/8"3' - 10"E108A
107A
PN Q R SMLK
1
0.2
0.1
1E
A5.1
0.3MATCHLINE - NEW SCOPEMATCHLINE - EXIST
A4.1
3A
A7.2
5A
1C
A5.1
DASHED LINE INDICATES
EDGE OF CANOPY ABOVE
121B121CJ
ELEC
121
STAIR 4
S104
MA. 12. 00
3' - 4"
CONSTRUCTION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
PLAN KEYED NOTENO
NEW PARTITION
EXISTING PARTITION TO REMAIN
FIRE EXTINGUISHER CABINETFEC
DIMENSION / LEADERS
3' - 6"
ALIGN FACES
PARTITIONS CENTERED ON MULLION
CORNER GUARDSCG © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 5:15:35 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -FLOOR
PLAN
A1.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL1 LARGE FORMAT PLOTTER
2 PLAN SHEET NOTE 2
3 PLAN SHEET NOTE 3
NSCALE:1/8" = 1'-0"
FLOOR PLAN, LEVEL 1NSCALE:1/8" = 1'-0"
FLOOR PLAN, LEVEL 1 - DECK & CANOPY
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.
DN
DN
DN
DN
DN
DN
NMLK
1
2
3
4
HGFEDC
1E
A5.2
0.2
0.1
1E
A5.1
1C
A5.2
0.3
MOTHER
211
OFFICE
215
STUDIO
213
OFFICE
214
MED CONF
212
MICROKITCHEN
209
VR SPACE
210
TOILET
208
TOILET
207
OFFICE
206
OFFICE
205
STUDIO
200
OFFICE
202
OFFICE
203
PHONE
201
LIFT
L201
PRINT
204
A4.1
3A
A2.1
3A
A2.1
1A
A7.2
5C
A7.1
1A
A7.1
4A
A7.3
2D
1A
A5.1
1A
A5.2
1C
A5.1
PRESENTATION
108
A10.13A
ACCESS
DOOR
4"
4"2' - 8 3/4"8' - 0" 4' - 4" 8' - 0" 4' - 4" 8' - 0" 6' - 4" 6' - 4"1' - 4"A115
A116
A118
5' - 2 1/2" 8' - 0" 4' - 3 1/4" 8' - 0" 4' - 2 3/8" 8' - 0" 1' - 6 5/8"
1' - 0"
A145
A112 A113 A114
7' - 11"4"4"TRUCK BAYS
126STAIR 1
S201
STAIR 2
S202
MECH
MEZZANINE
M201
STAIR 4
S204
TS TS
"FLOOR PLAN, DECK"
REF SHT. A1.2
215214212211207
208
206205
201202203MATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
J
A4.1
1A
SA. 3. 20
SA. 3. 10
SA. 3. 20 SA. 3. 20
SA. 3. 10
MA. 12. 00
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 10
SA. 3. 10
TYP FF
EL = 16' -0"
SA. 3. 20
SA. 3. 20
SA. 3. 20SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 3. 20
SA. 6. 20
SA. 3. 20
SA. 6. 20
SA. 6. 20
SA. 6. 20
SA. 3. 10
1.6
2.2
2.8
3.4
10' - 6 3/8" 19' - 8 1/4" 7 3/8"5' - 3 1/4" 8' - 6" 2' - 5 7/8"26' - 6 5/8"14' - 0 3/8"5"1' - 11"1' - 2" 8' - 6 3/4"
4"11' - 7 1/4" 11' - 8 7/8" 15' - 4"
17' - 11 1/8"2' - 4 5/8"7' - 8"3' - 3"3' - 0 3/8" 7' - 5 1/2"11' - 7 3/4"6' - 5 3/4"7' - 0"
1A
A9.1
1C
A9.1
A10.11D
A10.1
1E
1D
A9.3
1
PN Q R SMLK
1
0.2
0.1
1E
A5.1
0.3
A4.1
3A
A7.2
5D 1C
A5.1
GATE
4' - 4"
DECK
301 MATCHLINE - NEW SCOPEMATCHLINE - EXIST
J
1A
A9.1
1C
A9.1
A10.11D
GENERAL ARCHITECTURAL NOTES
1. ALL INTERIOR CMU WALLS SHALL BE 8 INCHES NOMINAL
THICKNESS, UNLESS NOTED OTHERWISE.
2. PARTITION TYPES ARE DESIGNATED ON FLOOR PLANS
THUS: SEE SHEET A8.1 FOR TYPES. ALL INTERIOR
PARTITIONS ARE TYPE SA.3.20 UNLESS NOTED OTHERWISE.
3. ALL MASONRY WALLS AND INTERIOR STUD WALLS SHALL
EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECK ABOVE
UNLESS NOTED OTHERWISE, PER PARTITION TYPE.
4. PROVISIONS ARE MADE AT ALL FULL HEIGHT NON-BEARING
WALLS FOR 1-INCH VERTICAL MOVEMENT OF THE BUILDING
STRUCTURE WITHOUT TRANSFER OF COMPRESSIVE LOADS TO
WALL. FILL IRREGULARITIES BETWEEN TOP OF WALL AND DECK
ABOVE WITH MINERAL WOOL INSULATION OR FIRE STOPPING
MATERIALS AS REQUIRED TO MEET FIRE RATING OF
RESPECTIVE WALLS. SEE DETAILS ON SHEET XX.X.
5. SEE STRUCTURAL DRAWINGS FOR BRACING OF NON-LOAD
BEARING MASONRY WALLS.
6. FURNISH AND INSTALL FIRE-TREATED WOOD BLOCKING OR
METAL BACKING PLATE IN METAL STUD PARTITIONS FOR THE
PROPER ANCHORAGE OF ALL WALL ATTACHED ITEMS; I.E.
TOILET ACCESSORIES, CASEWORK, MILLWORK, WALL-
MOUNTED FIXTURES, DOOR STOPS, AUDIO VISUAL BRACKETS,
AND OTHER WALL ATTACHED ITEMS.
7. GYPSUM BOARD SURFACES SHALL BE ISOLATED WITH
CONTROL JOINTS WHERE SHOWN ON DRAWINGS AND AS
DESCRIBED IN THE SPECIFICATIONS.
8. MASONRY CONTROL JOINTS (CJ) AND CONTROL JOINTS ABOVE
(CJA) SHALL BE LOCATED AS SHOWN ON THE FLOOR PLAN AND
BUILDING ELEVATIONS, AND WHERE LARGE PLUMBING VENTS
OR RISERS OCCUR IN SINGLE WYTHE MASONRY WALLS, AND
WHERE MASONRY WALLS BEARING ON THE CONCRETE FLOOR
SLAB ABUT MASONRY WALLS BEARING ON CONCRETE
FOOTINGS OR AS INDICATED ON DRAWINGS.
9. EXTEND FURRING CHANNELS AND GYPSUM BOARD UP 4
INCHES ABOVE FINISHED CEILING ON CMU WALLS.
10. SCRIBE GYPSUM WALL BOARD OF WALLS AND PARTITIONS TO
IRREGULARITIES OF DECK ABOVE. SEAL TIGHTLY AROUND ALL
PENETRATIONS.
11. PROVIDE SEISMIC BRACING FOR SUSPENDED CEILINGS OR AS
SHOWN ON THE DRAWINGS.
XX. X. XX
CONSTRUCTION PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
PLAN KEYED NOTENO
NEW PARTITION
EXISTING PARTITION TO REMAIN
FIRE EXTINGUISHER CABINETFEC
DIMENSION / LEADERS
3' - 6"
ALIGN FACES
PARTITIONS CENTERED ON MULLION
CORNER GUARDSCG
SHEET NOTES#© DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 5:15:37 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -FLOOR
PLAN
A1.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FLOOR PLAN, LEVEL 2NSCALE:1/8" = 1'-0"
FLOOR PLAN, DECK
1 LARGE FORMAT PLOTTER
2 PLAN SHEET NOTE 2
3 PLAN SHEET NOTE 3
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
ROOF PLAN GENERAL NOTES
A. ROOF PLAN GENERAL NOTES APPLY TO ALL ROOF PLAN
SHEETS.
B. ROOF SLOPES ARE CREATED BY SLOPING THE ROOF
STRUCTURE UNLESS NOTED OTHERWISE. SEE STRUCTURAL
DRAWINGS FOR ELEVATIONS OF THE HIGH AND LOW POINTS TO
DETERMINE PROPER TAPER IN INSULATION.
C. TAPERED INSULATION SHALL PROVIDE A MINIMUM OF 1/4-INCH
PER FOOT OF SLOPE TO ROOF DRAINS, UNLESS NOTED
OTHERWISE.
D. AREAS MARKED WITH A HATCHED PATTERN
INDICATE TAPERED INSULATION.
E. ALL ROOF CURBS TO BE A MINIMUM OF 8 INCHES ABOVE
ROOFING LEVELS. PROVIDE TAPERED INSULATION ROOF
SADDLES AT ROOF CURBS TO PROVIDE DRAINAGE AROUND
CURB.
F. SEE STRUCTURAL DRAWINGS FOR FRAMING AROUND ROOF
PENETRATIONS.
G. COORDINATE THE SIZE AND LOCATION OF ROOF PENETRATIONS
FOR MECHANICAL AND ELECTRICAL EQUIPMENT. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS FOR PENETRATIONS
NOT SHOWN ON THIS DRAWING.
H. FLASH DRAINS, CURBS, VENTS AND STACKS PER
MANUFACTURER'S RECOMMENDATIONS IF DETAIL NOT SHOWN
ON DRAWINGS.
I. NO ROOF PENETRATIONS ALLOWED WITHIN 4'-0" EACH SIDE OF
FIREWALL. SEE CODE PLAN FOR FIRE WALL LOCATIONS.
PN Q R SMLK
1
2
3
4
HGFEDCBA
0.2
0.1
0.3
DECK ROOF
BELOW
J
9' - 3 1/2" 10' - 8 1/2" 10' - 3 1/2" 9' - 8 1/2"
9' - 7 7/8"1' - 4 1/8"11' - 6"1' - 6 3/8"12' - 10 9/16" 12' - 1 7/16" 1' - 10 3/16"
2
A1.3 1.6
2.2
2.8
3.4
22
T.O. WALL
36' - 0"
2
ROOF BEARING
32' - 8"
B.O. JOISTS
28' - 0"
SOLATUBE © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
R&D BLDG
OVERALL
1/13/2023 5:15:38 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ROOF PLAN
A1.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/16" = 1'-0"
ROOF
SCALE:3/8" = 1'-0"A1.3
2 TYP SOLATUBE SECTION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.
MR EWC
(ACC)
EWC URINAL URINAL
(ACC)
HD
(ACC)
PTD/R
(ACC)
LAV LAV TTD SD
WC
(ACC)
WC
(ACC)
SND SCD SNV
RH
(ACC)
RH-1 SH(ACC)
ELEVATION 1
SH(ACC)
ELEVATION 2
BCS
**T.O. TABLE IN OPEN
POSITION
MBH US SSS
ADA SAD 2010 - 604, 609
ANSI A117.1 2003 - 604.5.1
ADA SAD
2010 - 606.1
ADA SAD
2010 - 308
ADA SAD
2010 - 604.8.3
ADA SAD
2010 - 608.3.1
ADA SAD 2010 - 308.2.1
ADA SAD
2010 - 603.4
ADA SAD
2010 - 606.1
ADA SAD
2010 - 606.3
ADA SAD
2010 - 604.7
ADA SAD
2010 - 606.1
ADA SAD
2010 - 308
ADA SAD
2010 - 605.2
ADA SAD
2010 - 602.4
ADA SAD
2010 - 603.3
ADULT MOUNTING HEIGHTS
TO B.O.40" MAXTO SPOUT36" MAX27" MIN38" MIN43" MAX2' - 0"17" MAXT.O. CONTROLS44" MIN - 48" MAXT.O. CONTROLS48" MAX34" MAX27" MIN8" MIN
11" MIN 9" MIN34" MAX27" MIN9" MINTO DISPENSER15" MIN TO 48" MAXT.O. CONTROLS44" MIN - 48" MAXFLOOR MOUNTED WC
59" MIN AT
WALL HUNG WC
56" MIN AT
12" MAX42" MIN
C TO REAR WALL
41" MAX - 39" MIN
LGB-3
GB-2
GB-1
T.O. GRAB BAR33" MIN - 36" MAX7" TO 9"1' - 6"B.O. GRAB BAR41" MAX - 39" MIN18" MIN48" MAX60" MIN
1' - 6"
12" MIN 24" MIN
36" MIN
1' - 6"T.O. GRAB BAR33" MIN - 36" MAX2' - 4"T.O. DISPENSER48" MAXCONTROLS44" T.O.1' - 6" 1' - 6"
15" MAX
3' - 0"B.O. CONTROLS34" MINT.O. CONTROLS48" MAX5' - 9"48" MAX1' - 6" 1' - 6"19" MAX17" MIN3' - 0"T.O. CONTROLS44" MAX**34" MAX6' - 0"48" MAX40" MIN15" MINT.O. SPOUTREFLECTINGSURFACEADA SAD
2010 - 602.7
A. ACCESSIBLE URINAL SHALL PROVIDE CLEAR FLOOR SPACE PER
ADA SAD 2010 - 605.3
B. ACCESSIBLE WATER CLOSETS SHALL PROVIDE CLEAR SPACE
PER ADA SAD 2010 - 604.3.1
C. ACCESSIBLE LAVATORIES AND SINKS SHALL PROVIDE CLEAR
SPACE PER ADA SAD 2010 - 606.2
D. ACCESSIBLE TOILET ROOMS SHALL PROVIDE A TURNING SPACE
OF 60 INCHES IN DIAMETER PER ADA SAD 2010 - 304.3.1
E. ACCESSIBLE WATER FOUNTAINS SHALL PROVIDE CLEAR FLOOR
SPACE PER ADA SAD 2010 - 602.2
F. ACCESSIBLE TOILET PARTITIONS SHALL COMPLY WITH ADA SAD
2010 - 604.8.1
G. EXPOSED PIPES AND SURFACES UNDER LAVATORIES AND
SINKS SHALL BE INSULATED PER ADA SAD 2010 - 606.5
GENERAL NOTES FOR
ACCESSIBILITY
K
4
J
3.4
4
J
A2.1
2C
2B
A2.1
3B
3C
TOILET
208
TOILET
207
SA. 3. 20
SA. 3. 10
SA. 3. 10
SA. 3. 20
208
2074"SA. 3. 10
SA. 3. 10
3.43' - 1 1/2"5' - 3 1/2"11 1/4"7' - 10 1/2"11' - 6 3/8" 9 5/8"8"5' - 3 3/4"4
G
1B/ A2.1
1B
10' - 3 1/4"
SA. 2. 10
SA. 3. 20
1 3/8"
2' - 6"2' - 6"
3/4"
2' - 6"
3/4"
3' - 0"1' - 3"1' - 3"2' - 6"2' - 6"
T-01
QZ-01
PL-02
PL-03
ALL BASE CABS
AND TOE KICKS:
ALL UPPER CABS:
2A
A11.1
2B
A11.1
2' - 10"4"1' - 4" 2' - 6"2' - 4"1C
A11.1
1A
A11.1
1B
A11.1
1E
A11.1
T-04 T-03
T-03T-04 © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:15:39 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ENLARGED
FLOOR PLANS
A2.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELTOILET ACCESSORIES
ABBREVIATIONS
ABBREV DESCRIPTION
ACC ADA ACCESSIBLE
BCS BABY CHANGING STATION
EWC ELECTRIC WATER COOLER
GB-1 GRAB BAR (BACK WALL)
GB-2 GRAB BAR (SIDE WALL)
GB-3 GRAB BAR (VERTICAL)
GB-4 GRAB BAR (AMBULATORY STALL)
GB-5 GRAB BAR (SHOWER)
HD HAND DRYER
LAV LAVATORY
MBH MOP/BROOM HOLDER
MR MIRROR
MR/S MIRROR WITH SHELF
PTD PAPER TOWEL DISPENSER
PTD/R COMBINATION TOWEL DISPENSER/RECEPTACLE
RH ROBE HOOK
SCD SEAT COVER DISPENSER
SCR SHOWER CURTAIN ROD
SD SOAP DISPENSER
SND SANITARY NAPKIN DISPOSAL
SNV SANITARY NAPKIN VENDOR
SSS STAINLESS STEEL SHELF
TTD TOILET TISSUE DISPENSER
US UTILITY SHELF
WC WATER CLOSET
WR WASTE RECEPTACLE
SCALE:1/4" = 1'-0"A2.1
4A ENLARGED PLAN, L1 - RESTROOMS
SCALE:1/4" = 1'-0"A2.1
3A ENLARGED PLAN, L2 - TOILETS
SCALE:1/4" = 1'-0"A2.1
1A ENLARGED PLAN, L2 - MICROKITCHEN
SCALE:1/4" = 1'-0"A2.1
1B MICROKITCHEN
SCALE:1/4" = 1'-0"A2.1
2B TOILET 208 - A SCALE:1/4" = 1'-0"A2.1
2C TOILET 208 - B
SCALE:1/4" = 1'-0"A2.1
3B TOILET 207 - B
SCALE:1/4" = 1'-0"A2.1
3C TOILET 207 - A
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
P
P
P
301/4301/4
SD
SD
SDSDOS
OS
OS
OS
OS
OS
OS
OS
OS
OS
A. REFLECTED CEILING PLAN GENERAL NOTES APPLY TO ALL
REFLECTED CEILING PLAN SHEETS.
B. ALL CEILING GRIDS/PANELS SHALL BE CENTERED IN EACH
ROOM UNLESS NOTED OTHERWISE.
C. CEILING HEIGHTS ARE NOTED ON THE REFLECTED CEILING
PLANS ARE MEASURED FROM THE FINISH FLOOR OF THE
ROOM.
D. ALL ELECTRICAL FIXTURES, SPEAKERS, SMOKE AND THERMAL
DETECTORS, MECHANICAL GRILLES, SPRINKLER HEADS, AND
OTHER CEILING MOUNTED DEVICES, SHALL BE CENTERED
BETWEEN CEILING GRIDS UNLESS NOTED OTHERWISE.
SPRINKLER HEADS SHALL BE WITHIN A 3-INCH RADIUS
CENTERED BETWEEN CEILING GRIDS.
E. IN ACOUSTICAL CEILING PANELS WITH SCORE IN THE CENTER,
CENTER DEVICES REFERENCE IN NOTE D IN ONE HALF OF THE
TILE. DO NOT LOCATE ON THE SCORE. FOR ACP WITH
MULTIPLE SCORED PATTERNS, COORDINATE LOCATION WITH
THE ARCHITECT.
F. PROVIDE SUSPENSION SYSTEM AROUND ELECTRICAL
FIXTURES, MECHANICAL GRILLES, DIFFUSERS, AND OTHER
CEILING MOUNTED DEVICES. AT ACOUSTICAL PANEL CEILINGS.
G. ALL DIMENSIONS ON REFLECTED CEILING PLANS ARE ACTUAL
AND ARE TO THE FOLLOWING UNLESS NOTED OTHERWISE:
a. FACE OF FINISHED WALL
b. FACE OF FINISHED BULKHEADS
c. CENTERLINE OF COLUMNS
d. CENTERLINE OF TEES
H. IN AREAS WITH EXPOSED STRUCTURE CEILINGS, COORDINATE
EXACT LOCATIONS OF MECHANICAL GRILLES, DIFFUSERS,
DUCTWORK AND ELECTRICAL FIXTURES WITH EACH
REPRESENTATIVE SUBCONTRACTOR.
I. ALL WALLS EXTEND TO UNDERSIDE OF DECK EXCEPT THOSE
SHOWN SHADED IN WHICH GYPSUM BOARD OR MASONRY
EXTENDS MIN 4 INCHES ABOVE FINISHED CEILING. ALL METAL
STUDS EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECK.
REFLECTED CEILING PLAN
GENERAL NOTES
SHEET NOTES#
NMLK
1
2
3
4
HGFEDC
1E
A5.2
0.2
0.1
1C
A5.2
0.3
1A
A5.1
1A
A5.2
"REFLECTED CEILING PLAN, LEVEL 1 -DECK/CANOPY"
REF SHT. A3.1
GWB
7' -0"
APC-1
9' -0"
APC-1
10' -0"MATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
PRESENTATION
108
MODELING
ROOM
107
WOOD SHOP
104
TRUCK BAYS
126
MACHINE
SHOP
127
J
GWB
9' -0"
GWB
9' -0"
GWB
9' -0"
GWB
9' -0"
APC-2
9' -0"
GWB
9' -0"
MACHINE
SHOP
127
ROUTER ROOM
105
APC-1
9' -0"
APC-1
9' -0"
APC-1
8' -0"
APC-1
12' -0"
1.6
2.2
2.8
3.4
GWB
10' -0"
GWB
13' -8"
1D
A9.3
PN Q R SMLK
1
0.2
0.1
1E
A5.1
0.3
1C
A5.1
J
REFLECTED CEILING PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
PLAN KEYED NOTENO
ACP
GWB, GYPSUM BOARD CEILING
OTS OPEN TO STRUCTURE
XXX
X-XX
CEILING TYPE
CEILING HEIGHT
LED DOWNLIGHT
TRACK LIGHT
PENDANT LIGHT
REFER TO FINISH SCHEDULE FOR CEILING SPECIFICATIONS.
REFER TO ELECTRICAL FOR LIGHTING FIXTURE TYPE &
SPECIFICATIONS. © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 5:15:41 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -
REFLECTED
CEILING PLAN
A3.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL1 1" THICK 2'X4' FSORB PANELS, CENTERED
BETWEEN JOISTS, UNO.
2 RCP SHEET NOTE 2
3 RCP SHEET NOTE 3
NSCALE:1/8" = 1'-0"
REFLECTED CEILING PLAN, LEVEL 1NSCALE:1/8" = 1'-0"
REFLECTED CEILING PLAN, LEVEL 1 - DECK & CANOPY
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
301/4
30 1/4
30 1/4
P
P
P
751/4
P
P
301/4
301/4
SD
SD
SD SDSDSD SD
SLVSLVSLV
D
A. REFLECTED CEILING PLAN GENERAL NOTES APPLY TO ALL
REFLECTED CEILING PLAN SHEETS.
B. ALL CEILING GRIDS/PANELS SHALL BE CENTERED IN EACH
ROOM UNLESS NOTED OTHERWISE.
C. CEILING HEIGHTS ARE NOTED ON THE REFLECTED CEILING
PLANS ARE MEASURED FROM THE FINISH FLOOR OF THE
ROOM.
D. ALL ELECTRICAL FIXTURES, SPEAKERS, SMOKE AND THERMAL
DETECTORS, MECHANICAL GRILLES, SPRINKLER HEADS, AND
OTHER CEILING MOUNTED DEVICES, SHALL BE CENTERED
BETWEEN CEILING GRIDS UNLESS NOTED OTHERWISE.
SPRINKLER HEADS SHALL BE WITHIN A 3-INCH RADIUS
CENTERED BETWEEN CEILING GRIDS.
E. IN ACOUSTICAL CEILING PANELS WITH SCORE IN THE CENTER,
CENTER DEVICES REFERENCE IN NOTE D IN ONE HALF OF THE
TILE. DO NOT LOCATE ON THE SCORE. FOR ACP WITH
MULTIPLE SCORED PATTERNS, COORDINATE LOCATION WITH
THE ARCHITECT.
F. PROVIDE SUSPENSION SYSTEM AROUND ELECTRICAL
FIXTURES, MECHANICAL GRILLES, DIFFUSERS, AND OTHER
CEILING MOUNTED DEVICES. AT ACOUSTICAL PANEL CEILINGS.
G. ALL DIMENSIONS ON REFLECTED CEILING PLANS ARE ACTUAL
AND ARE TO THE FOLLOWING UNLESS NOTED OTHERWISE:
a. FACE OF FINISHED WALL
b. FACE OF FINISHED BULKHEADS
c. CENTERLINE OF COLUMNS
d. CENTERLINE OF TEES
H. IN AREAS WITH EXPOSED STRUCTURE CEILINGS, COORDINATE
EXACT LOCATIONS OF MECHANICAL GRILLES, DIFFUSERS,
DUCTWORK AND ELECTRICAL FIXTURES WITH EACH
REPRESENTATIVE SUBCONTRACTOR.
I. ALL WALLS EXTEND TO UNDERSIDE OF DECK EXCEPT THOSE
SHOWN SHADED IN WHICH GYPSUM BOARD OR MASONRY
EXTENDS MIN 4 INCHES ABOVE FINISHED CEILING. ALL METAL
STUDS EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECK.
REFLECTED CEILING PLAN
GENERAL NOTES
SHEET NOTES#
NMLK
1
2
3
4
HGFEDC
1E
A5.2
0.2
0.1
1E
A5.1
1C
A5.2
0.3
1A
A5.1
1A
A5.2
1C
A5.1
ELEC HEATER ELEC HEATERMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXISTMATCHLINE - EXISTMATCHLINE - NEW SCOPEMATCHLINE - NEW SCOPEMATCHLINE - EXIST
MOTHER
211
OFFICE
215
STUDIO
213
OFFICE
214
MED CONF
212
MICROKITCHEN
209
VR SPACE
210
TOILET
208
TOILET
207
OFFICE
206
OFFICE
205
STUDIO
200
OFFICE
202
OFFICE
203
PHONE
201
LIFT
L201
PRINT
204
PRESENTATION
108
TRUCK BAYS
126STAIR 1
S201
STAIR 2
S202
APC-1
9' -0"
J
APC-1
9' -0"
APC-1
9' -0"
APC-1
9' -0"
APC-2
25' -0"
GWB
9' -0"
GWB
9' -0"
APC-1
9' -0"
APC-1
9' -0"
APC-1
9' -0"
APC-1
9' -0"
SOLAR TUBE
SOLAR TUBE, TYP (6)
2
A1.3
1.6
2.2
2.8
3.4
1' - 4" 4' - 0" 1' - 4"
ALIGNALIGN8' - 0 1/4"2' - 4"2' - 0"2' - 4"2' - 4"2' - 0"2' - 4"2' - 0"2' - 0"4' - 5"4' - 0"6' - 0"4' - 0"6' - 0"4' - 0"6' - 0"4' - 5"4' - 0"6' - 0"4' - 0"6' - 0"5 5/8"
2' - 7 1/2" 4' - 0" 2' - 7 1/2" 4' - 0"7 5/8"1' - 8"2' - 0"3' - 6"OTS
OTS
1
PN Q R SMLK
1
0.2
0.1
1E
A5.1
0.3
1C
A5.1
ELEC HEATER ELEC HEATER MATCHLINE - NEW SCOPEMATCHLINE - EXIST
OFFICE
203 PRINT
204
J
APC-1
9' -0"
REFLECTED CEILING PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
PLAN KEYED NOTENO
ACP
GWB, GYPSUM BOARD CEILING
OTS OPEN TO STRUCTURE
XXX
X-XX
CEILING TYPE
CEILING HEIGHT
LED DOWNLIGHT
TRACK LIGHT
PENDANT LIGHT
REFER TO FINISH SCHEDULE FOR CEILING SPECIFICATIONS.
REFER TO ELECTRICAL FOR LIGHTING FIXTURE TYPE &
SPECIFICATIONS. © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 5:15:44 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -
REFLECTED
CEILING PLAN
A3.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL1 1" THICK 2'X4' FSORB PANELS, CENTERED
BETWEEN JOISTS, UNO.
2 RCP SHEET NOTE 2
3 RCP SHEET NOTE 3
NSCALE:1/8" = 1'-0"
REFLECTED CEILING PLAN, LEVEL 2NSCALE:1/8" = 1'-0"
REFLECTED CEILING PLAN, DECK
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
P NQRS M L K H
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
1E
A5.1
DECK
18' - 6"
LEVEL 02
16' - 0"
1A
A5.1
1C
A5.1
J
A146 A120 A119
1A
A9.1A9.1
1B 1C
A9.1
LEVEL 01
0' - 0"
10.20.1
DECK
18' - 6"
0.3
LEVEL 02
16' - 0"
LEVEL 01
0' - 0"
1 0.2 0.1
DECK
18' - 6"
0.3
LEVEL 02
16' - 0"
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
NMLKHGFEDC
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
1E
A5.2
1C
A5.2
LEVEL 02
16' - 0"
1A
A5.1
J
A142 A143 A144 A128
NEW CANOPY
1' - 10"
2"
4' - 6"
2"2"6' - 2"2"2' - 6"4' - 10" 2' - 7" 2' - 3" 4' - 10"4' - 10" 7' - 7"
3' - 6" 12' - 0" 4' - 6"10' - 0"© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:15:48 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
EXTERIOR
ELEVATIONS
A4.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/8" = 1'-0"A4.1
3A EXTERIOR ELEVATION - WEST - DECK
SCALE:1/8" = 1'-0"A4.1
5C EXTERIOR ELEVATION - DECK - SOUTH
SCALE:1/8" = 1'-0"A4.1
5E EXTERIOR ELEVATION - DECK - NORTH
SCALE:1/8" = 1'-0"A4.1
1A EXTERIOR ELEVATION - EAST
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
1234
ROOF BEARING
32' - 8"
B.O. JOISTS
28' - 0"
0.3
LEVEL 02
16' - 0"
A5.1
5A
A5.1
5B
1.62.22.83.4
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
1
ROOF BEARING
32' - 8"
0.2 0.1
DECK
18' - 6"
B.O. JOISTS
28' - 0"
0.3
LEVEL 02
16' - 0"
A5.1
5F
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
1
ROOF BEARING
32' - 8"
0.2 0.1
DECK
18' - 6"
B.O. JOISTS
28' - 0"
0.3
LEVEL 02
16' - 0"
A5.1
5D
A9.1
2B
A9.1
2A
LEVEL 01
0' - 0"
1 0.31
T.O. WALL
36' - 0"
1
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
0.3
11' - 0"5' - 0"1' - 6"18' - 6"TRUCK BAYS
126
DECK
301
BROOM FINISH
CONCRETE WITH
EXTERIOR SEALANT
LEVEL 01
0' - 0"
4 3.84
T.O. WALL
36' - 0"
4
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
STUDIO
200
SEE ST FOR FOOTING
AND COLUMN SIZING
INFORMATION, TYP.11' - 0"4' - 11"1' - 7"7' - 0"1' - 6"10' - 0"LEVEL 01
0' - 0"
1 0.31
T.O. WALL
36' - 0"
1
T.O. WDW
25' - 0"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
OFFICE
202 11' - 0"2' - 0"4' - 0"11' - 0"8' - 0"LEVEL 01
0' - 0"
1 0.31
T.O. WALL
36' - 0"
1
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
0.3
11' - 0"5' - 0"1' - 6"18' - 6"TRUCK BAYS
126 P-06, BLACK EXTERIOR
GRADE PAINT © DLR GroupREVISIONS
A B C D E F
1
2
3
4
1/13/2023 5:15:51 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
BUILDING
SECTIONS
A5.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/8" = 1'-0"A5.1
1A BUILDING SECTION
SCALE:1/8" = 1'-0"A5.1
1C DECK SECTION A
SCALE:1/8" = 1'-0"A5.1
1E DECK SECTION B
SCALE: 3/8" = 1'-0"A5.1
5D Section 5 - Callout 1
SCALE: 3/8" = 1'-0"A5.1
5A WALL SECTION - MAIN OFFICE ENTRANCE
SCALE: 3/8" = 1'-0"A5.1
5B WALL SECTION - ELEC ROOM
SCALE: 3/8" = 1'-0"A5.1
5F Section 11 - Callout 1
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
3 4
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
A5.2
5C
A5.2
5D
2.8 3.4
12' - 0"LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
K H
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
A5.2
5A
A5.2
5B
J
2
A1.3
3A
A9.2
LEVEL 01
0' - 0"
T.O. WALL
36' - 0"
3 4
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
A5.2
5E
A5.2
5F
2.8 3.4
LEVEL 01
0' - 0"
KK
T.O. WALL
36' - 0"
K
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"16' - 0"12' - 0"8' - 0"TRUCK BAYS
126
STUDIO
200
LEVEL 01
0' - 0"
HH
T.O. WALL
36' - 0"
H
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
1A
A5.1 16' - 0"12' - 0"8' - 0"PRESENTATION
108
STUDIO
200
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
2.8
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
T.O. FTG
-1' - 6"
LEVEL 02
16' - 0"3' - 4"4' - 8"3' - 0"5' - 0"1' - 6"2' - 6"3' - 0"5' - 0"8' - 0"1' - 6"PRESENTATION
108
2.8
A9.3
1E
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
2.8
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
T.O. FTG
-1' - 6"
LEVEL 02
16' - 0"3' - 4"4' - 8"3' - 0"5' - 0"1' - 6"2' - 6"3' - 0"5' - 0"8' - 0"1' - 6"2.8
16' - 0"VERIFY WITH EXISTING GANTRY CRANE WIDTH
2' - 6"
EXISTING GANTRY CRANE
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
44
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
4
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
T.O. FTG
-1' - 6"
LEVEL 02
16' - 0"3' - 4"4' - 8"3' - 0"5' - 0"1' - 6"2' - 6"3' - 0"5' - 0"8' - 0"1' - 6"LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
44
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
4
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
T.O. FTG
-1' - 6"
LEVEL 02
16' - 0"3' - 4"4' - 8"3' - 0"5' - 0"1' - 6"2' - 6"3' - 0"5' - 0"8' - 0"1' - 6"© DLR GroupREVISIONS
A B C D E F
1
2
3
4
1/13/2023 5:15:53 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
BUILDING
SECTIONS
A5.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/8" = 1'-0"A5.2
1C BUILDING SECTION
SCALE:1/8" = 1'-0"A5.2
1A BUILDING SECTION
SCALE:1/8" = 1'-0"A5.2
1E BUILDING SECTION
SCALE:3/8" = 1'-0"A5.2
5A Section 10 - Callout 1
SCALE:3/8" = 1'-0"A5.2
5B Section 10 - Callout 2
SCALE:3/8" = 1'-0"A5.2
5C Section 6 - Callout 1
SCALE:3/8" = 1'-0"A5.2
5E Section 3 - Callout 1
SCALE:3/8" = 1'-0"A5.2
5D Section 6 - Callout 2
SCALE:3/8" = 1'-0"A5.2
5F Section 3 - Callout 2
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
UP
DN
UP
DN
3
4
3D
A7.1
3B
A7.1
3F
A7.1
2.8
3.4
29' - 4 1/8"5' - 2 3/4"S102B
S102A
SA. 6. 20
3
4
3D
A7.1
3B
A7.1
3F
A7.1
2.8
3.4
1A
A9.3
3
5D
A7.1
5B
A7.1
5F
A7.1
J
SA. 6. 20
SA. 6. 20
SA. 6. 10
SA. 6. 20
SA. 6. 20
2.2
2.8
2 3/8" 4' - 11 1/4"5' - 8 7/8"8' - 5 3/8"5' - 2 3/8"118 3
5D
A7.1
5B
A7.1
5F
A7.1
J
SA. 6. 20
SA. 6. 20
2.2
2.8
3 5/8" 4' - 10 1/2"5 3/8"19' - 7 5/8"LEVEL 01
0' - 0"
C.3
1E
A5.2
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3D
A7.1
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
3 43.42.8 3.83 4
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3B
A7.1
3F
A7.1
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
C.3
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
1E
A5.2
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3D
A7.1
A9.3
1C
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
32.8 3
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
5B
A7.1
5F
A7.1
LEVEL 01
0' - 0"
JJ.5 J
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
5D
A7.1A9.3
1B
7' - 11"A9.3
1A
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
J J.5J
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3E
A7.3
5D
A7.1 © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:15:56 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
STAIR VIEWS
A7.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/4" = 1'-0"A7.1
2A SOUTH STAIR, L1
SCALE:1/4" = 1'-0"A7.1
1A SOUTH STAIR, L2
SCALE: 1/4" = 1'-0"A7.1
5A NORTH STAIR, L1
SCALE: 1/4" = 1'-0"A7.1
4A NORTH STAIR, L2
SCALE:1/4" = 1'-0"A7.1
3B SOUTH STAIR - INT1 - Transverse1
SCALE:1/4" = 1'-0"A7.1
3D SOUTH STAIR - INT1 - Longitudinal
SCALE:1/4" = 1'-0"A7.1
3F SOUTH STAIR - INT1 - Transverse2
SCALE: 1/4" = 1'-0"A7.1
5D NORTH STAIR - INT2 - Longitudinal
SCALE: 1/4" = 1'-0"A7.1
5B NORTH STAIR - INT2 - Transverse1
SCALE: 1/4" = 1'-0"A7.1
5F NORTH STAIR - INT2 - Transverse2
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
UP
DN
DN
DN
DN
K
1
0.2
0.1
0.3
3C
A7.2
3A
A7.2
3E
A7.2
K
1
0.2
0.1
0.3
3C
A7.2
3A
A7.2
3E
A7.2
3' - 11"
ADA LIFT
4' - 0 1/4"
K
1
0.2
0.1
0.3
3C
A7.2
3A
A7.2
3E
A7.2
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
K J.5K
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3C
A7.2
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
1 0.3 0.2 0.11
T.O. WALL
36' - 0"
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
ROOF BEARING
32' - 8"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3A
A7.2
3E
A7.2
LEVEL 01
0' - 0"
MECH MEZZ.
13' - 0"
KJ.5 K
B.O. SIDING
8' - 0"
T.O. WDW
25' - 0"
B.O. WDW
20' - 0"
DECK
18' - 6"
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
3C
A7.2 © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:15:58 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
STAIR VIEWS
A7.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE: 1/4" = 1'-0"A7.2
5A EXTERIOR STAIR, L1
SCALE: 1/4" = 1'-0"A7.2
5C EXTERIOR STAIR, L2
SCALE: 1/4" = 1'-0"A7.2
5D EXTERIOR STAIR, DECK
SCALE: 1/4" = 1'-0"A7.2
3A STAIR - EXT - Transverse1
SCALE: 1/4" = 1'-0"A7.2
3C STAIR - EXT - Longitudinal
SCALE: 1/4" = 1'-0"A7.2
3E STAIR - EXT - Transverse2
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
3
3E
A7.3
J
SA. 3. 30
SA. 3. 20 SA. 6. 20
SA. 6. 20
2.82' - 9 7/8"7 1/8"5' - 0"6' - 8 3/8" 3 5/8"
3
3E
A7.3
J
SA. 8. 20
SA. 6. 20
SA. 8. 20
2.87 1/8"4' - 10"LEVEL 01
0' - 0"
32.8 33
B.O. JOISTS
28' - 0"
LEVEL 02
16' - 0"
5F
A7.12.8 © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:15:59 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ELEVATOR VIEWS
A7.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/4" = 1'-0"A7.3
3D LIFT, L1
SCALE:1/4" = 1'-0"A7.3
2D LIFT, L2
SCALE:3/8" = 1'-0"A7.3
3E LIFT SECTION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
MATERIAL DESCRIPTION
S = STEEL (METAL STUDS)
W = WOOD STUDS
H = SHAFT WALLS
M = MASONRY
C = CONCRETE
RATING / HEIGHT
A = FULL HEIGHT / UNDERSIDE OF STRUCT (NOT RATED)
B = 6" ABOVE CEILING (NOT RATED)
C = UNDERSIDE OF CEILING (NOT RATED)
D = PARTIAL HEIGHT (NOT RATED)
X = VARIABLE HEIGHT (NOT RATED)
S = SMOKE PARTITON (NOT RATED)
0 = 0 HOUR RATED (CORRIDOR)
5 = 0.5 HOUR RATED
1 = 1 HOUR RATED
2 = 2 HOUR RATED
3 = 3 HOUR RATED
4 = 4 HOUR RATED
UNIT WIDTH / CONFIGURATION
F = FURRING STRIPS / CHANNELS
1 = 1 5/8" METAL
2 = 2 1/2" METAL / 1 1/2" WOOD
3 = 3 5/8" METAL
4 = 4" METAL / 3 1/2 WOOD / 3 5/8" CMU
6 = 6" METAL / 5 1/2" WOOD / 5 5/8" CMU / 6" CONC
8 = 8" METAL / 7 1/4" WOOD / 7 5/8" CMU / 8" CONC
10 = 10" CONC
12 = 11 5/8" CMU / 12" CONC
X = NON-STANDARD WIDTH, SEE DETAILS
D = DOUBLE STUD FRAMING
S = STAGGERED STUD FRAMING
GYPSUM WALLBOARD INDICATOR
(NOT INCLUDING SHAFT LINER)
0 = NO GWB
1 = ONE LAYER, TAG SIDE
2 = ONE LAYER, EACH SIDE
3 = TWO LAYERS TAG SIDE, ONE LAYER OTHER
4 = TWO LAYERS, EACH SIDE
5 = TWO LAYERS TAG SIDE, NO GWB OTHER
6 = THREE LAYERS, EACH SIDE
UNIQUE CONDITION (SEE SCHEDULE)
UNIQUE CONDITIONS ARE SEPARATELY
NUMBERED ON A PAARTITION TYPE - SPECIFIC BASIS.
A SINGLE VALUE CAN DESCRIBE AS MANY MATERIAL CONDITIONS
AS APPLY TO A SPECIFIC PARTITION; E.G.
1 = RESILIENT CHANNELS WITH SOUND ATTENUATION BLANKET
2 = TILE BACKER BOARD TO 4'-0" A.F.F., BOTH SIDES, WITH SOUND
ATTENUATION BLANKET.
EACH PARTITION TYPE HAS 10 POSSIBLE SUB-TYPES,
SUCH AS:
• SHEAR WALLS
• TILE BACKER BOARD
• PLYWOOD
• FURRING
• RESILIENT CHANNELS
• SOUND ATTENUATION BLANKET
• SECURITY WALLS
• ABUSE RESISTANCE
• BULLET RESISTANCE
• LEAD LINING
0 = NO UNIQUE CONDITION
1 = add specific conditions here
SA.3.10
MATERIAL
RATING / HEIGHT
UNIT WIDTH
GWB INDICATOR
UNIQUE CONDITION
WALL TYPE TAG
PARTITION TYPES
DESCRIPTIONS
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTERTHKROUGH
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTERTHKROUGH
CONCRETE MASONRY UNIT
CELLS GROUTED SOLID,
WHERE OCCURS, SEE STRUCT
THKROUGHGYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTERTHKROUGH
© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:03 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
PARTITION TYPES
A8.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELS_-_-1_ NON-RATED STUD PARTITION
MARK
ROUGH
THICKNESS
FIRE/SMOKE SOUND
T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
STC
RATING TESTED ASSEMBLIES
SA 2 10 <varies> NR NA
SA 3 10 4 1/4" NR NA
SA 6 10 6 5/8" NR NA
SA 8 10 8 5/8" NR NA
S_-_-2_ NON-RATED STUD PARTITION
MARK
ROUGH
THICKNESS
FIRE/SMOKE SOUND
T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
STC
RATING TESTED ASSEMBLIES
SA 3 20 4 7/8" NR NA
SA 6 20 7 1/4" NR NA
SA 8 20 9 1/4" NR NA
S_-_-3_ NON-RATED STUD PARTITION
MARK
ROUGH
THICKNESS
FIRE/SMOKE SOUND
T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
STC
RATING TESTED ASSEMBLIES
SA 3 30 5 1/2" NR NA
NON-RATED MASONRY PARTITION
MARK
ROUGH
THICKNESS
FIRE/SMOKE SOUND
T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
STC
RATING TESTED ASSEMBLIES
MA 6 00 5 5/8" NR NA
MA 8 00 7 5/8" NR NA
MA 12 00 11 5/8" NR NA
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
F N FG G
FLUSH PANEL NARROW LIGHT FULL LIGHT HALF LIGHT
SEE SCHEDULEMFRPERMFR
PER
SEE SCHEDULE MFR
PER
COIL HOUSING
FRAMED OPENING
CO
COILING
1
2"2"2"
SCHEDULE
SEE
SEE SCHEDULE2
2"4"2"
SCHEDULE
SEE
SEE SCHEDULEDG DUAL LITE GLASS
F FLUSH PANEL
FG FULL LITE GLASS
FL FULL LOUVERED
G HALF LITE GLASS
GL HALF LITE GLASS & LOUVERED
L LOUVERED (BOTTOM)
LL LOUVERED (TOP & BOTTOM)
N NARROW LITE GLASS
NL NARROW LITE GLASS & LOUVERED
TL LOUVERED (TOP)
V VISION LITE GLASS (10" SQUARE)
VL VISION LITE GLASS & LOUVERED
DOOR PANEL TYPE DESCRIPTIONS
DOOR AND FRAME SCHEDULE
GENERAL NOTES
A. ALL EXTERIOR HOLLOW METAL FRAMES SHALL BE FILLED WITH
INSULATION.
B. ALL INTERIOR HOLLOW METAL FRAMES SET IN MASONRY AND
CONCRETE WALLS SHALL BE GROUTED SOLID.
C. ALL HOLLOW METAL FRAMES SET IN METAL STUD WALLS
SHALL BE FILLED WITH MINERAL WOOL BLANKET INSULATION.
D. ALL EXTERIOR FRAMES SHALL BE INSTALLED WITH 1/4" SHIM
AND SEALANT AROUND PERIMETER OF FRAME.
E. MASONRY LINTELS AND STEEL LINTELS ARE SHOWN ON
STRUCTURAL DRAWINGS.
F. GLASS TYPES FOR DOORS ARE INDICATED IN THE DOOR
GLAZING COLUMN OF THE DOOR AND FRAME SCHEDULE.
GLASS TYPES FOR FRAMES ARE INDICATED ON THE FRAME
ELEVATIONS.
G. FOR COILING DOORS, GRILLES AND SECTIONAL DOORS, WIDTH
AND HEIGHT DIMENSIONS SHOWN IN DOOR AND FRAME
SCHEDULE REPRESENT FINISHED OPENING SIZE.
CONTRACTOR TO COORDINATE EXACT SIZE OF DOOR WITH
MANUFACTURER.
H. FRAME MANUFACTURER SHALL COORDINATE LOCATIONS OF
ALL CONCEALED CONDUIT AND J-BOXES REQUIRED FOR
SECURITY SYSTEM HARDWARE PRIOR TO MANUFACTURING OF
HOLLOW METAL FRAMES AND COORDINATE WITH SECURITY
HARDWARE AND DEVICES.
I. PROVIDE HEAD RECEIVERS AT ALUMINUM STOREFRONTS AND
CURTAIN WALLS AS REQUIRED FOR STRUCTURAL DEFLECTION
ALLOWANCE.
J. SEE SPECIFICATIONS HARDWARE SECTION FOR HARDWARE
SETS NOTED IN DOOR AND FRAME SCHEDULE.
A
2"2"
4' - 0"2"2"6' - 0"1' - 4"CIG
F3' - 11"2"1' - 11"2"2"8' - 0"
2"3' - 9"2"3' - 9"2"
CIG CIG
2"2' - 2"2"L
2"7' - 8"2"2"3' - 8"2"E
2"7' - 8"2"
D2"3' - 8"2"2"5' - 8"2"
M2"1' - 4"2"4' - 8"2"2"4' - 6"2"3' - 4" 6' - 0"6' - 6"2' - 6"3' - 0" 4' - 0"3' - 0" 4' - 0"4' - 6" 2' - 6"© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:04 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
DOOR & WINDOW
FRAME TYPE AND
SCHEDULE
A8.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELDOOR AND FRAME SCHEDULE
NUMBER
PANEL FRAME
FIRE
RATING HARDWARE SET
DETAILS
COMMENTS
NO. OF
PANELS WIDTH HEIGHT THICKNESS MATERIAL GLASS TYPE MATERIAL TYPE HEAD JAMB LEFT JAMB RIGHT SILL
107A 1 11' - 0" 16' - 0" 0" STL CO STL -
118 1 3' - 0" 7' - 0" 1 3/4" WD F ALUM 1
119 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
120A 1 3' - 0" 7' - 0" 1 3/4" WD FG ALUM 1
120B 1 3' - 0" 7' - 0" 1 3/4" WD F HM 2
121A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 2
121B 1 14' - 0" 14' - 0" 0" STL CO STL N/A
121C 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
201 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
202 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
203 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
204A 2 3' - 0" 7' - 0" 1 3/4" HM HM
204B 1 3' - 0" 7' - 2" 1 3/4" HM N HM 1
205 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
206 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
207 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
208 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
211 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
212 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
214 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
215 1 3' - 0" 8' - 0" 1 3/4" <By
Category>
ALUM
BBB 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
CCC 1 16' - 0" 16' - 0" 0" STL CO STL -
S102A 1 3' - 0" 7' - 0" 1 3/4" WD N HM 1
S102B 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
YY 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
GLAZING TYPE DESCRIPTIONS
CG CLEAR FLOAT GLASS
CIG CLEAR INSULATING GLASS
CTG CLEAR TEMPERED FLOAT GLASS
CTIG CLEAR TEMPERED INSULATING GLASS
GL GLASS
IIP INSULATED INFILL PANEL GLASS
LG LAMINATED GLASS
PG PATTERN GLASS
PIG PATTERN INSULATING GLASS
SG SPANDREL GLASS
TFG TINTED FLOAT GLASS
TG TEMPERED GLASS
TIG TINTED INSULATING GLASS
TTG TINTED TEMPERED FLOAT GLASS
TTIG TINTED TEMPERED INSULATING GLASS
WG POLISHED WIRE GLASS
EXISTING DOOR AND FRAME SCHEDULE
NUMBER
PANEL FRAME
FIRE
RATING HARDWARE SET
DETAILS
COMMENTS
NO. OF
PANELS WIDTH HEIGHT THICKNESS MATERIAL GLASS TYPE MATERIAL TYPE HEAD JAMB LEFT JAMB RIGHT SILL
E101A 1 12' - 0" 12' - 0" 0" STL CO STL -
E101B 2 3' - 0" 7' - 0" 1 3/4" HM F HM 1
E103A 2 3' - 0" 7' - 0" 1 3/4" HM F HM 2
E103B 2 3' - 0" 7' - 0" 1 3/4" HM F HM 1
E104A 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E104B 1 14' - 0" 16' - 0" 0" STL CO STL -
E105A 1 12' - 0" 12' - 0" 0" STL CO STL -
E105B 1 12' - 0" 16' - 0" 0" STL CO STL -
E105C 1 3' - 0" 7' - 0" 1 3/4" HM G HM 1
E106A 1 10' - 0" 10' - 0" 0" STL CO STL -
E106B 1 3' - 0" 7' - 0" 1 3/4" HM G HM 1
E107C 1 14' - 0" 16' - 0" 0" STL CO STL -
E107D 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E108A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E108B 1 14' - 0" 16' - 0" 0" STL CO STL -
E108C 1 16' - 0" 16' - 0" 0" STL CO STL -
E108D 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E109A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E110A 1 3' - 0" 7' - 0" 1 3/4" Glass FG ALUM -
E110B 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E111A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E112A 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E113A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E114A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E115A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E116A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E119A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E120A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E120B 1 10' - 0" 10' - 0" 0" STL CO STL -
E121A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E121B 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E122A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E123A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E124A 1 3' - 0" 7' - 0" 1 3/4" HM F HM 1
E125A 2 3' - 0" 7' - 0" 1 3/4" HM F HM 1
E126A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
E126B 1 14' - 0" 16' - 0" 0" STL CO STL -
E126C 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E126D 1 14' - 0" 16' - 0" 0" STL CO STL -
E126E 1 14' - 0" 16' - 0" 0" STL CO STL -
E126F 1 14' - 0" 16' - 0" 0" STL CO STL -
E126G 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E126H 1 14' - 0" 16' - 0" 0" STL CO STL -
E126J 1 14' - 0" 16' - 0" 0" STL CO STL -
E128A 1 3' - 0" 7' - 0" 1 3/4" HM F HM 1
E128B 1 14' - 0" 16' - 0" 0" STL CO STL -
E128C 1 3' - 0" 7' - 2" 1 3/4" HM F HM 1
E128D 1 14' - 0" 16' - 0" 0" STL CO STL -
E129A 1 3' - 0" 7' - 0" 1 3/4" WD F HM 1
EXTERIOR WINDOW SCHEDULE
FRAME
FIRE RATING
DETAILS
COMMENTSNUMBER TYPE DEPTH MATERIAL HEAD JAMB LEFT JAMB RIGHT SILL
A119 F 6" ALUM
A120 F 6" ALUM
A146 A 4 1/2" ALUM
INTERIOR WINDOW SCHEDULE
FRAME
FIRE RATING
DETAILS
COMMENTSNUMBER TYPE MATERIAL HEAD JAMB LEFT JAMB RIGHT SILL
A112 L Metal - Aluminum,
Brushed
A113 L Metal - Aluminum,
Brushed
A114 E Metal - Aluminum,
Brushed
A115 L Metal - Aluminum,
Brushed
A116 L Metal - Aluminum,
Brushed
A118 L Metal - Aluminum,
Brushed
A123 D HM
A124 D HM
A128 M ALUM
A142 M ALUM
A143 M ALUM
A144 M ALUM
A145 D HM
DOOR TYPE ELEVATIONS DOOR FRAME TYPE ELEVATIONS DEMOUNTABLE FRAME TYPE ELEVATIONS
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
A. SEE SPECIFICATION FOR PAINTING OF ITEMS NOT NOTED IN THE
ROOM FINISH SCHEDULE OR FINISH PLANS.
B. EXPOSED CONCRETE FLOORS NOT SHOWN TO RECEIVE A
FINISH SHALL RECEIVE LIQUID FLOOR TREATMENT OR CURING
AND SEALING COMPOUND UNLESS NOTED OTHERWISE. SEE
SPEC SECTION 033000.
C. ALL GYPSUM WALLBOARD BULKHEADS SHALL BE PAINTED P-?
UNLESS NOTED OTHERWISE.
D. SEE REFLECTED CEILING PLANS FOR CEILING MATERIAL AND
HEIGHT.
E. CEILING HEIGHTS, AS NOTED ON THE REFLECTED CEILING
PLANS, ARE MEASURED FROM FINISH FLOOR OF THE ROOM.
F. CONTRACTOR SHALL FURNISH AND INSTALL WALL BASE
AROUND CASEWORK AND MILLWORK.
G. WHERE FLOOR FINISH CHANGES FROM ONE ROOM TO
ANOTHER, SET JOINT OF THE MATERIALS AT THE CENTER OF
THE COMMUNICATING DOOR.
H. SEE SHEET XX.X FOR TYPICAL TACKWALL DETAILS.
I. SEE SHEET XX.X FOR ACOUSTICAL WALL PANEL ELEVATIONS
AND DETAILS.
ROOM FINISH SCHEDULE
GENERAL NOTES
FLOOR NOTES:
1. DEPRESS CONCRETE SLAB 1-1/2 INCHES FOR
CERAMIC/QUARRY TILE AND SETTING BED.
2. DEPRESS CONCRETE SLAB 2-1/2 INCHES FOR WOOD ATHLETIC
FLOORING. VERIFY RECESS DEPTH WITH WOOD FLOOR
MANUFACTURER.
3. DEPRESS CONCRETE SLAB 3/8 INCH FOR EPOXY TERRAZZO
FLOORING. VERIFY DEPTH WITH MANUFACTURER.
4. DEPRESS CONCRETE SLAB 3/8 INCH FOR RECESS FLOOR MAT
AND FRAME. VERIFY RECESS DEPTH WITH MANUFACTURER.
5. SEE SHEET XX.X FOR FLOOR PATTERN.
6. SEE SHEET XX.X FOR CERAMIC TILE FLOOR PATTERN.
7. THIN-SET CERAMIC TILE FLOORS.
WALL NOTES:
1. SEE SHEET XX.X FOR CERAMIC TILE WALL ELEVATIONS.
2. CERAMIC TILE WAINSCOT TO X'-X" ABOVE FINISH FLOOR.
3. PAINT THE JANITOR'S CLOSET WALLS BUT NOT INSIDE THE
CHASE AREA.
4. PAINT GYMNASIUM WALLS HP-? TO X'-X" AFF WITH P-? ABOVE.
5. PAINT EXPOSED STEEL COLUMNS P-?.
6. REFER TO SHEET A12.XX FOR WALL ELEVATIONS INDICATING
WALL FINISH AND AWP PATTERNS.
7. PROVIDE PLYWOOD BACKBOARD WHERE INDICATED ON
SPECIAL SYSTEMS PLANS. PLYWOOD TO BE 4'X8', 3/4" THICK,
INTERIOR-GRADE, FIRE-RETARDANT-TREATED AND PAINTED P-
X. MOUNT 4" A.F.F.
CEILING NOTES:
1. SEE REFLECTED CEILING PLANS FOR CEILING ACCENT PAINT
COLORS AND LOCATIONS.
2. PAINT EXPOSED STEEL DECK P-?.
3. PAINT EXPOSED STRUCTURE P-?.
MISCELLANEOUS ITEMS:
1. PAINT HANDRAILS P-?.
2. PAINT MISCELLANEOUS STEEL AT STAIR (STRINGERS,
HANDRAILS, STEEL PANS, ETC.) P-?.
ROOM FINISH SCHEDULE
SPECIFIC NOTES
F
F
F
F
F
F
F
W
W
W
W
W
W
W
C
C
C
M
M © DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:05 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
ROOM FINISH
SCHEDULE
A8.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELFINISH SCHEDULE
TAG DESCRIPTION MANUFACTURER PRODUCT COLOR/FINISH SIZE COMMENTS
033300 CONCRETE FINISHING
PLC-01 POLISHED CONCRETE BOH CLEAR SEALER, PREMIUM QUALITY, LOW VOC
SCE-01 SEALED CONCRETE BOH CLEAR SEALER, PREMIUM QUALITY, LOW VOC
064000 INTERIOR ARCHITECTURE WOODWORK
CH-01 COAT HOOKS
HW-01 HARDWARE PULLS WIRE PULLS ARE NOT ACCEPTABLE
066400 CUSTOM CASEWORK
B-02 WOOD BASE PAINTED TO MATCH WALL ABOVE
F-01 WRAPPED PANEL
UPHOLSTERY
CAMIRA MAIN LINE FLAX BARBICAN
F-02 WRAPPED PANEL
UPHOLSTERY
CARNEGIE QUARTZ 10
PL-01 PLASTIC LAMINATE LAMINART FAWN CYPRESS WOOD GRAIN FINISH
PL-02 PLASTIC LAMINATE WILSONART OAK CHAR WOOD GRAIN FINISH
PL-03 PLASTIC LAMINATE ABET LAMINATI COLOR TBD; LUCIDA FINISH
PL-04 PLASTIC LAMINATE WILSONART TBD
WD-01 WOOD VENEER
066400 PLASTIC PANELING
FRP-01 FOOD SERVICE WALLS CRANE COMPOSITES GLASSBOARD CLASS A WHITE
088000 GLAZING
GF-01 GLAZING FILM 3M FASARA 7725SE-314 DUSTED CRYSTAL FILM STD ROLL: 60"WIDE X 50 YDS
GL-01 GLAZING CLEAR TEMPERED 3/8"
GL-02 GLAZING CLEAR TEMPERED 1/2"
GL-03 GLAZING PATTERN TEMPERED
GL-04 <varies><varies>
093000 TILING
G-01 GROUT - COFFEE LATICRETE PERMACOLOR COLOR TBD
G-02 GROUT - RESTROOM LATICRETE PERMACOLOR COLOR TBD
G-03 GROUT - RESTROOM FLOOR LATICRETE PERMACOLOR COLOR TBD
T-01 MK WALL TILE UNITED TILE POINT AND DASH NEUTRAL BURGUNDY 6" X 6"RANDOM STACKED INSTALL; USE G-01
T-02 RESTROOM FLOOR TILE MOSA TILE TERRA TONES MID GREY 206 12"X24"QUARTER TURN INSTALL; USE G-03
T-03 RESTROOM WALL TILE CREATIVE MATERIALS CORP RESIN COLORS TERRACOTTA; RUST 3"X12"RANDOM 50/50 BLEND; HORIZONTAL
STACKED INSTALL; USE G-02
T-04 RESTROOM WALL TILE CREATIVE MATERIALS CORP RESIN COLORS WHITE 3"X12"HORIZONTAL STACKED INSTALL; USE G-02
TS-01 TRANSITION SCHLUTER SLIMLINE TILE EDGE
TS-02 TRANSITION SCHLUTER SLIMLINE TILE COVE
095100 ACOUSTIC CEILING TILE
ACT-01 STANDARD CEILING TILE ARMSTRONG OPTIMA
096500 RESILIENT FLOORING
B-01 RESILIENT BASE ROPPE PINNACLE COLOR TBD 4" COVE BASE USED THROUGHOUT U.N.O.
RF-01 RESILIENT FLOORING TEKNOFLOR FOREST PLANK HPD DUSK COFFEE & VR LAB FLOOR
TS-03 RESILIENT FLOOR TRANSITION JOHNSONITE SLIMLINE COLOR TBD CARPET TO TILE
TS-04 RESILIENT FLOOR TRANSITION JOHNSONITE SLIMLINE COLOR TBD CARPET TO RESILIENT
096800 CARPET
CPT-01 CARPET - FIELD INTERFACE PLAIN STITCH GRAPHITE
CPT-02 CARPET - CONFERENCE INTERFACE STATIC LINES GRAPHITE
CPT-03 CARPET - ACCENT INTERFACE CIRCUIT BOARD RED
097200 WALL COVERING
WC-01 WALL COVERING DESIGNTEX DNA NON-VINYL; SUSIE CUSTOM COLORS CUSTOM SCALE STAIRWELL GRAPHIC
WC-02 WALL COVERING DESIGNTEX GRADIENT PACIFIC VERIFY INSTALL DIRECTION W/ ARCHITECT
098400 ACOUSTIC ROOM COMPONENTS
AP-01 ACOUSTIC PANEL -
CONFERENCE
FABRITRAK GEOTRAK WITH TERRACORE INFILL FAB-01 MOUNT @ 30" AFF U.N.O.
AP-02 ACOUSTIC PANEL - OFFICES FABRITRAK GEOTRAK WITH TERRACORE INFILL FAB-02 MOUNT @ 30" AFF U.N.O.
099000 PAINTING
P-01 WALL PAINT - FIELD BENJAMIN MOORE LOW VOC, PREMIUM PAINT CHANTILLY LACE; EGGSHELL FINISH USED THROUGHOUT U.N.O.
P-02 WALL PAINT - ACCENT BENJAMIN MOORE LOW VOC, PREMIUM PAINT; SUITABLE FOR INTERIOR AND EXTERIOR
APPLICATION
COLOR TBD; EGGSHELL FINISH (OR SATIN)KENWORTH RED ACCENT
P-03 CEILING AND STRUCTURE
PAINT
BENJAMIN MOORE LOW VOC, PREMIUM PAINT BLACK IRON; EGGSHELL ON WALLS; FLAT ON CEILING
P-04 WALL PAINT - ACCENT BENJAMIN MOORE LOW VOC, PREMIUM PAINT ETERNITY, EGGSHELL FINISH
P-05 WALL PAINT - ACCENT BENJAMIN MOORE LOW VOC, PREMIUM PAINT COLOR TBD, EGGSHELL FINISH MOTHER'S ROOM ACCENT PAINT
101100 INFORMATION SPECIALTIES
MB-01 MARKER BOARD CLARIDGE 4'X8' HORIZONTAL MOUNT @ 30" AFF U.N.O.
MB-02 MARKER BOARD CLARIDGE MAGNETIC MARKER BOARD 4'X8' HORIZONTAL MOUNT @ 30" AFF U.N.O.
102600 WALL PROTECTION
WP-01 WOOD PROTECTION SHEET INPRO 4 FT SHEET GOODS WITH ASSOCIATED TOP, BOTTOM, AND SEAM TRIM COLOR TBD, PEBBLETTE FINISH LOW VOC ADHESIVES. MECHANICALLY
ADHERE IF POSSIBLE
102613 CORNER GUARDS
CGD-01 CORNER GUARD INPRO 3/4" TAPE-ON CORNER GUARD ALTERNATES: KOROGUARD AND CS
ACROVYN
104400 FIRE PROTECTION SPECIALTIES
FEC-01 PAINTED FIRE EXTINGUISHER
CABINET
LARSEN PAINTED TO MATCH ADJACENT WALL FULLY RECESSED - 2409-R2, SEMI RECESSED 2409-R4
122000 WINDOW TREATMENT
WT-01 WINDOW TREATMENT MECHOSHADE SUN SHADE
WT-02 WINDOW TREATMENT MECHOSHADE BLACKOUT
123661 QUARTZ SURFACING
QZ-01 QUARTZ SOLID SURFACE CEASARSTONE LAYALITE 20 MM THICKNESS
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
0.1
GUTTER FASCIA BREAK
METAL, FINISHED TO
MATCH STRUCTURE.
GUTTER SLOPED TO
DOWNSPOUTS.
1 0.3
METAL DECK ROOF
B.O. WNDW OPENING
20' - 0"
0.1
B.O. WNDW OPENING
20' - 0"
0.1
DECK
18' - 6"
BROOM FINISH
CONCRETE WITH
EXTERIOR SEALANT
STAINLESS STEEL
BAULASTER @4'-0" O.C.
ANCHORED TO CONCRETE
DECK
STAINLESS STEEL PIPE RAIL
CONTINUOUS
3' - 6" GUARDRAIL HEIGHT @TREAD NOSEDECK
18' - 6"
1C
A9.1
4' - 2"
B.O. WNDW OPENING
20' - 0"
0.1
B.O. WNDW OPENING
20' - 0"
B.O. WDW
20' - 0"
0.1
DECK
18' - 6"© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:05 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
EXTERIOR
DETAILS
A9.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/2" = 1'-0"A9.1
2B DECK CANOPY DETAIL B
SCALE:1/2" = 1'-0"A9.1
2A DECK CANOPY DETAIL A
SCALE:1" = 1'-0"A9.1
1A DECK GUARDRAIL SECTION
SCALE:1" = 1'-0"A9.1
1B DECK GATE ELEVATION
SCALE:1" = 1'-0"A9.1
1C DECK GATE SECTION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
E - COMPRESSION STRUT ATTACHMENT
@ MAIN RUNNER
D - GRID BRACING DETAIL @
ACOUSTIC PANEL CEILING
C - FOUR-WAY CHANNEL BRACING DETAIL
@ SUSPENDED GYPSUM BOARD CEILING
1. SPLAY WIRES SHALL BE ATTACHED TO SUSPENDED
MEMBERS WITH MINIMUM OF THREE TURNS IN 1 1/2".
2. VERTICAL STRUT SHALL BE INSTALLED AT EACH SET OF
SPLAY WIRES - 200 POUND DESIGN FORCE
NOTES:
NO. 9 GA. HANGER WIRE AT 4'-0"
O.C.
SPLAY WIRES
CROSS TEE
NO. 12 GA. SPLAY WIRE BRACING
IN LINE WITH RUNNER, TYP. FOR 4
MAIN RUNNER
45° MAX.
TYP. FOR 4
NO. 9 GA. HANGER WIRE AT 4'-0" O.C.
SPLAY WIRES
METAL CLIP OR SADDLE WIRE TIE
MAIN RUNNER
NO. 12 GA. SPLAY WIRE IN LINE
WITH RUNNER
CROSS RUNNER
TYP.
2" MAX.
TYP.
2" MAX.
METAL STUD PARTITION
ANCHOR - SEE STRUCTURAL
1. WIRES SHALL BE ATTACHED TO SUSPENSION
MEMBERS WITH A MINIMUM OF FOUR TURNS IN 1
1/2".
2. MAXIMUM PARTITION HEIGHT - 10 FEET.
3. MAXIMUM PARTITION WEIGHT - 15 PSF.
NOTES:
TWO-WAY SPLAY WIRES AT 4'-0"
O.C. MAX. TWO PER WALL
SECTION OR AS PER
MANUFACTURER'S ENGINEER'S
DESIGN
SEE MECHANICAL FOR
EQUIPMENT HANGING DETAILS
SEE ELECTRICAL FOR LIGHT
FIXTURE HANGING DETAILS
45° MAX
DESIGNER TO VERIFY
REFERENCES TO
STRUCTURAL DRAWINGS
METAL STUD RUNNER
TEE GRID
COMPRESSION STRUT @ 4'-0" O.C.
MAX., SEE XX/AX.X FOR
CONNECTION TO STRUCTURE
45° OR LESS
45° OR LESS
45° OR LESS 45° OR LESS
MAIN BEAM
COMPRESSION STRUT
CROSS
TEE
NO. 1 2 GA SPLAY WIRE
45° MAX.
TYP. FOR 4
B - FOUR-WAY TEE BRACING DETAIL
@ SUSPENDED GYPSUM BOARD CEILING
A - PARTITION BRACING DETAIL
COMPRESSION STRUT
MAIN RUNNER
2 1/2" 16 GA METAL STUD W/ 1 3/8"
FLANGE, NOTCHED AT MAIN
RUNNER, WITHIN 2" OF CROSS
RUNNER
(2) 1/4" MACHINE BOLTS
TYP.
2" MAX.
COMPRESSION STRUT
E - COMPRESSION STRUT ATTACHMENT
@ STRUCTURE
2 1/2" 16 GA METAL STUD W/ 1 3/8"
FLANGE, NOTCHED AT CEILING
GRID
16 GA CONT RECEIVER CHANNEL
WITH 5" LEGS ATTACHED TO THE
METAL ROOF DECK OR FLOOR
ABOVE
2 - #10 SMS
L 1 1/2 " X 1 1/2 " X 2" 16 GA
CLIP
2-3/16" POWER DRIVEN STUDS @
CONC FILLED DECK OR 2-#10 SMS
@ UNFILLED DECK
SPRAY ON FIREPROOFING
12 GA SPLAYED BRACE WIRE WITH
MIN (4) TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE CONNECTED
TO MAIN RUNNERS (TYP).
12 GA VERT HANGER WIRE @ 4'-0"
EACH WAY (4'-0" O.C. @ MAIN
RUNNER) WITH MIN (3) TIGHT
TURNS IN 1-1/2" BOTH ENDS, TYP.
COMPRESSION STRUT AT 12'-0" X
12'-0" O.C. MAX. (8" MAX. FROM
END OF MAIN RUNNER) SHALL
NOT BE MORE THAN 1
(HORIZONTAL) IN 6 (VERTICAL)
OUT OF PLUMB
2" MAX FROM BRACE WIRES TO
CROSS RUNNERS AND
COMPRESSION STRUT.
MAIN RUNNER, @ 2'-0" O.C.
CROSS RUNNER @ 2'-0" O.C.
45° MAX.
45° MAX.45° MAX.
45° MAX.
5/8" GWB
ACOUSTICAL PANEL CEILING
SMS #12 AT
12" O.C., TYP
8" MAX.HANGER WIRES
3 5/8" METAL STUDS @ 16" O.C.
SHADOW MOLD, TYP W/ BERC-2
CLIP (OR EQUAL) PER ICC ESR-1308
FINISH CEILING
SEE RCP
FINISH CEILING
SEE RCP
3 5/8" METAL STUD BRACING @ 32" O.C.
NO. 12 GA PERIMETER HANGER
WIRES 8" MAX FROM WALL,
TYPICAL FOR MAIN AND CROSS
RUNNERSCEILING STRUTS @ MAIN RUNNER
@ 12"-0" O.C. 6'-0" MAX FROM
WALL, 2" MAX FROM CROSS
RUNNER. OMIT STRUTS WHERE
ROOM IS 144 SQ FT OR LESS
NO. 12 GA HANGER WIRES @ 48"
O.C. EACH WAY, SUSPENDED
FROM STRUCTURE ABOVE
CEILING GRID MAIN AND
CROSS RUNNERS
NOTES:
1. ALL HANGER WIRES TO HAVE A
MINIMUM OF 3 TURNS IN 1 1/2"
OF RUN.
2. ALL SPLAY WIRES TO HAVE A
MINIMUM OF 4 TURNS IN 1 1/2"
OF RUN.
3. CEILING GRID MEMBERS MAY
BE ATTACHED TO NOT MORE
THAN TWO ADJACENT WALLS.
4. CEILING GRID MEMBERS SHALL
BE AT LEAST 3/4" FREE OF
OTHER WALLS.6' MAX.6' MAX.12' O.C.NOTE: THIS DETAIL IS BASED ON IR 25-10 OF THE CALIFORNIA
BUILDING CODE, VERIFY LOCAL CODE REQUIREMENTS
NO. 9 GA PERIMETER HANGER
WIRES 6" MAX FROM WALL,
TYPICAL FOR MAIN AND CROSS
RUNNERSCEILING STRUTS @ MAIN RUNNER
@ 12'-0" O.C. 6'-0" MAX FROM WALL,
2" MAX FROM CROSS RUNNER.
OMIT STRUTS WHERE ROOM IS 144
SQ FT OR LESS
NO. 9 GA HANGER WIRES @ 48"
O.C. EACH WAY, SUSPENDED
FROM STRUCTURE ABOVE
CEILING GRID MAIN RUNNERS
NOTES:
1. ALL HANGER WIRES TO HAVE A
MINIMUM OF 3 TURNS IN 1 1/2"
OF RUN.
2. ALL SPLAY WIRES TO HAVE A
MINIMUM OF 4 TURNS IN 1 1/2"
OF RUN.
3. CEILING GRID MEMBERS MAY
BE ATTACHED TO NOT MORE
THAN TWO ADJACENT WALLS.
4. CEILING GRID MEMBERS SHALL
BE AT LEAST 3/4" FREE OF
OTHER WALLS.6' MAX.6' MAX.INSERT EXACT SPACING REQUIREDDESIGNER TO SEE IR 25-3.13 TABLE 1NOTE: THIS DETAIL IS BASED ON IR 25-10 OF THE CALIFORNIA
BUILDING CODE, VERIFY LOCAL CODE REQUIREMENTS
4' O.C. MAX
MAX2' O.C.CEILING GRID CROSS RUNNERS
FSORB PANEL
IMPALING CLIPADHESIVE © DLR GroupREVISIONS
A B C D E F
1
2
3
4
1/13/2023 5:16:06 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
CEILING DETAILS
A9.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:3" = 1'-0"A9.2
2A TYPICAL SEISMIC BRACING AT CEILING
SCALE:NTSA9.2
1A SEISMIC CLG PANEL RUNNER LAYOUT
SCALE:3" = 1'-0"A9.2
1B SEISMIC LOW GYP. TO HIGH GRID
SCALE:1" = 1'-0"A9.2
1C SEISMIC COMPRESSION STRUT PLAN @ SUSP APC
SCALE:1" = 1'-0"A9.2
1D SEISMIC COMPRESSION STRUT PLAN @ GWB CLG.
SCALE:1 1/2" = 1'-0"A9.2
3A ACOUSTIC CEILING PANEL CONNECTION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
B.O. JOISTS
28' - 0"3' - 10"SA. 6. 20
LED DOWNLIGHT.
SEE ELECTRICAL.
SAME WOOD AS
GUARDRAIL CAP
GWB CEILING 1"METAL FRAMING
TO B.O. JOISTS
LEVEL 02
16' - 0"3' - 6" 1"
WOOD
LEVEL 02
16' - 0"1' - 11"2.8
LEVEL 02
16' - 0"
2.8
6' - 0"5/8"
5/8" GWB
METAL
FRAMING TO
B.O. SLAB
LEVEL 02
16' - 0"
2.8
4' - 0"EXISTING
OVERHEAD DOOR
METAL FRAMING
TO B.O. SLAB
6 5/8"
5/8" GWB
© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:07 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
GENERAL
BUILDING
DETAILS
A9.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:3/4" = 1'-0"A9.3
1B NORTH STAIR SOFFIT DETAIL
SCALE:1" = 1'-0"A9.3
1A INTERIOR STAIR GUARDRAIL SECTION
CABLE RAILS CONTINUOUS
STAINLESS STEEL
BALUSTER @4'-0" O.C.
ANCHORED TO CONCRETE
SCALE:1" = 1'-0"A9.3
1C SOUTH STAIRS SOFFIT SECTION
SCALE:3/4" = 1'-0"A9.3
1E PRESENTATION SOFFIT SECTION
SCALE:3/4" = 1'-0"A9.3
1D MODELING ROOM SOFFIT SECTION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
A. CASEWORK AND MILLWORK GENERAL NOTES APPLY TO ALL
CASEWORK/MILLWORK SHEETS.
B. ELEVATIONS DENOTED AS MILLWORK ARE SPECIFIED UNDER
DIVISION 06. ALL OTHERS SHALL BE SPECIFIED UNDER
DIVISION 12, UNLESS NOTED OTHERWISE.
C. ALL BASE CABINETS TO BE 2'-0" DEEP UNITS, UNLESS NOTED
OTHERWISE.
D. ALL UPPER WALL CABINETS TO BE 1'-2" DEEP UNITS, UNLESS
NOTED OTHERWISE.
E. ALL TALL STORAGE CABINETS TO BE 2'-0" DEEP UNITS, UNLESS
NOTED OTHERWISE.
F. ALL SHELVING IN CASEWORK TO BE ADJUSTABLE SHELVING,
UNLESS NOTED OTHERWISE.
G. CATALOG NUMBERS SHOWN ON THE ELEVATIONS FOR
CASEWORK ARE XXXXX MANUFACTURER, UNLESS NOTED
OTHERWISE. (M) AFTER THE CATALOG NUMBER INDICATES
THE CABINET IS SHOWN MODIFIED FROM THE
MANUFACTURER'S STANDARD.
H. INDICATES CASEWORK TO BE BID AS AN ALTERNATE.
SEE ALTERNATES SECTION IN THE SPECIFICATIONS FOR
DESCRIPTIONS.
I. WHERE PLUMBING OR ELECTRICAL DEVICES ARE LOCATED IN
CASEWORK, CASEWORK CONTRACTOR SHALL PROVIDE
OPENINGS. COORDINATE LOCATION AND QUANTITY WITH THE
PLUMBING OR ELECTRICAL CONTRACTOR.
J. PROVIDE SEALANT AT ALL PERIMETER JOINTS WHERE
COUNTERTOPS, BACK AND SIDE SPLASHES, CASEWORK AND
MILLWORK ABUT WALLS.
K. FIELD VERIFY ALL DIMENSIONS OF CABINET LOCATIONS IN THE
BUILDING PRIOR TO FABRICATION.
L. PROVIDE LOCKS WHERE INDICATED AT DOORS AND DRAWERS.
M. PROVIDE FINISHED ENDS AT ALL EXPOSED ENDS OF
CASEWORK AND MILLWORK.
N. ALL EXPOSED SURFACES IN OPEN SHELVING SHALL BE PLASTIC
LAMINATE COVERED.
O. SEE DETAIL XX/AX.X FOR TYPICAL COUNTERTOP DETAIL.
CASEWORK AND MILLWORK
GENERAL NOTESREVIEW AND EDIT AS NECESSARY FOR PROJECT DESIGN NEEDS. PROVIDE CASEWORK MANUFACTURER BASIS OF DESIGN IN NOTE G.REFERENCE KEYNOTES
CMU- SEE PLAN FOR WALL TYPES
1/4" SHIM AS REQUIRED
GROUT FRAME SOLID
SEALANT BOTH SIDES, TYP
HOLLOW METAL FRAME, CENTER
ON WALL - SEE WINDOW SCHED.
GLAZING - SEE FRAME ELEVATIONS
APPLIED STOP
SOLID BOTTOM INVERTED BOND
BEAM BLOCK
BOND BEAM - SEE STRUCTURAL
FACE OF MASONRY BEYOND
CMU - SEE PLANS FOR WALL TYPES
COILING DOOR TRACK GUIDES
EXPANSION ANCHOR SPACED BY
MANUFACTURER'S REQUIREMENT
METAL STUD WALL - SEE PLANS
FOR WALL TYPES
SEE A10 GENERAL BULDING
DETAILS FOR HEAD/JAMB/ SILL
DETAILS @ METAL STUD FRAMING
ALUM STOREFRONT SYSTEM -
SEE SCHED.
SEALANT BOTH SIDES, TYP
WALL WHERE OCCURS
ALUM RECIEVER CHANNEL
WITH SOUND ATTENUATION
INSULATION @ HEAD
1/4" SHIM AS REQUIRED
4"J-MOLD, TYP
1/2" MAX1"GROUT FRAME SOLID
SEALANT BOTH SIDES, TYP
CMU - SEE PLANS FOR WALL
TYPES
1/4" SHIM AS REQUIRED
JAMB ANCHOR
HOLLOW METAL FRAME - SEE
DOOR AND FRAME SCHED.
DOOR - SEE DOOR AND FRAME SCHED.1/2"BULLNOSE EDGE
MASONRY LINTEL, WHERE
OCCURS - SEE STRUCTURAL
CMU - SEE PLAN FOR WALL TYPES
1/4" SHIM AS REQUIRED
GROUT FRAME SOLID
1/2"
SEALANT BOTH SIDES, TYP.
DOOR - SEE DOOR AND FRAME
SCHED.
FACE OF MASONRY BEYOND
HOLLOW METAL FRAME - SEE
DOOR AND FRAME SCHED.
REINFORCING - SEE STRUCTURAL
STEEL LINTEL WITH CMU SOAPS,
WHERE OCCURS - SEE
STRUCTURAL
MASONRY LINTEL, WHERE
OCCURS- SEE STRUCTURAL
CMU - SEE PLAN FOR WALL TYPES
FACE OF MASONRY BEYOND
OVERHEAD COILING DOOR
HOUSING
COILING DOOR TRACK GUIDES
REINFORCING - SEE STRUCTURAL
STEEL LINTEL WITH CMU SOAPS,
WHERE OCCURS - SEE
STRUCTURAL
GROUT FRAME SOLID
SEALANT BOTH SIDES, TYP
CMU- SEE PLANS FOR WALL TYPES
1/4" SHIM AS REQUIRED
JAMB ANCHOR
HOLLOW METAL FRAME CENTER
ON WALL- SEE WINDOW SCHED.
GLAZING - SEE FRAME
ELEVATIONS
APPLIED STOP
LINE OF MASONRY BELOW CONC SLAB - SEE STRUCTURAL
SEALANT BOTH SIDES, TYP
1/4" SHIM AS REQUIRED
ALUM STOREFRONT SYSTEM -
SEE SCHED.
GLAZING
EXIST WALL
1/4" SHIM AS REQUIRED
GROUT FRAME SOLID
SEALANT BOTH SIDES, TYP.
DOOR - SEE DOOR AND FRAME
SCHED.
FACE OF WALL BEYOND
HOLLOW METAL FRAME - SEE
DOOR AND FRAME SCHED.
INT FIN WALL FURRING, SEE PLANS
SAW-CUT OPENING
FLASHING TO MATCH EXIST
GROUT FRAME SOLID
SEALANT BOTH SIDES, TYP
1/4" SHIM AS REQUIRED
JAMB ANCHOR
HOLLOW METAL FRAME - SEE
DOOR AND FRAME SCHED.
DOOR - SEE DOOR AND FRAME SCHED.
GYPSUM BOARD ON METALS
STUDS - SEE PLANS FOR WALL
TYPES
HOLLOW METAL FRAME - SEE
DOOR AND FRAME SCHED.
SEALANT BOTH SIDES, TYP
FILL FRAME WITH MINERAL WOOL
INSULATION
HSS COLUMN - SEE STRUCTURAL
4"
METAL STUD WALL - SEE PLANS
FOR WALL TYPES
SEE A10 GENERAL BULDING
DETAILS FOR HEAD/JAMB/ SILL
DETAILS @ METAL STUD FRAMING
HOLLOW METAL FRAME - SEE
SCHED.
GLAZING
SEALANT BOTH SIDES, TYP
FILL FRAME WITH MINERAL WOOL
INSULATION
1/2"1/2"4"WALL WHERE OCCURS
APPLIED STOP © DLR Group1A 1B 1C 1D 1E 1F
2A 2B 2C 2D 2E 2F
3A 3B 3C 3D 3E 3F
4A 4B 4C 4D 4E 4F
5A 5B 5C 5D 5E 5F REVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:08 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
DOOR AND
WINDOW DETAILS
A9.4485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1 1/2" = 1'-0"A9.4
7 SILL @ WINDOW
SCALE:1 1/2" = 1'-0"A9.4
4 JAMB @ COILING DOOR
SCALE:1 1/2" = 1'-0"A9.4
5 HEAD / JAMB @ STOREFRONT
SCALE:1 1/2" = 1'-0"A9.4
9 JAMB @ DOOR
SCALE:1 1/2" = 1'-0"A9.4
6 HEAD @ DOOR
SCALE:1 1/2" = 1'-0"A9.4
2 HEAD @ COILING DOOR
SCALE:1 1/2" = 1'-0"A9.4
8 JAMB @ WINDOW
SCALE:1 1/2" = 1'-0"A9.4
10 SILL @ FLOOR
SCALE:1 1/2" = 1'-0"A9.4
1 HEAD @ DOOR
SCALE:1 1/2" = 1'-0"A9.4
3 JAMB @ DOOR
SCALE: 1 1/2" = 1'-0"A9.4
11 JAMB @ DOOR
SCALE: 1 1/2" = 1'-0"A9.4
12 HEAD / JAMB / SILL @ WINDOW / TRANSOM
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
5F
A7.1
ACCESS DOOR
A118A116A115
A124 A123
1B
A11.1
1A
A11.1
2' - 6" 2' - 6" 2' - 6" 1' - 3" 1' - 3"4"2' - 10"PL-01
QZ-01
ALL BASE CABS
AND TOE KICKS
COUNTERTOP
AND BACKSPLASH
EQ EQ
2' - 6"2' - 6" 2' - 6" 2' - 6"4"2' - 10"PL-01 ALL BASE CABINETS
AND TOE KICKS
PL-04 COUNTERTOP
AND BACKSPLASH
P-02 FROM BOTTOM OF STRUCTURE
TO BOTTOM OF JOIST
P-02 FROM BOTTOM OF JOIST TO
FINISHED FLOOR; REFER TO
FINISH PLANS FOR PAINT
COLOR
XX
B-01
© DLR GroupREVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:09 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
INTERIOR
ELEVATIONS
A10.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1/4" = 1'-0"A10.1
3A INTERIOR ELEVATION
SCALE:1/4" = 1'-0"A10.1
1A A110 LARGE CONF COUNTER ELEV
SCALE:1/4" = 1'-0"A10.1
1B TYPICAL AV WALL ELEVATION
SCALE:1/4" = 1'-0"A10.1
1C LUNCH ROOM KITCHEN ELEV
SCALE:1/4" = 1'-0"A10.1
1D 204 PRINT ROOM CASEWORK
SCALE:1/4" = 1'-0"A10.1
1E TYPICAL PAINT ELEVATION
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
NOTE: SEE CASEWORK ELEVATIONS FOR FINISHES,
WHITE MELAMINE INTERIORS TO CABINETS AND DRAWERS, UNO4"SEE ELEVATION2' - 1"
COUNTERTOP AS SPEC'D
3/4" X 2" HDWD. DRAWER STOP
DRAWER W/ FULL EXTENSION GLIDES, 1/2"
HARDWOOD DRAWER BACKS & FRONTS
1/4" PLYWOOD DRAWER BOTTOM
3/4" X 2" HDWD STOP FRAME
3/4" PLYWOOD DOOR W/ MATCHING
EDGE BAND ALL 4 EDGES
2X WOOD BLOCKING, TYP
3/4" ADJUSTABLE SHELF W/EDGE
BANDING FRONT AND BACK EDGES
HARDWARE, REFER TO ELEVATION, TYP
BACKSPLASH IF INDICATED,
SEE ELEVATION
3"
DRILLED PIN SUPPORT SYSTEM
3/4" X 2" HARDWOOD WEB FRAME, TYP
MATCHING SEALANT
1/4" PLYWOOD BACK PANEL
TOE-KICK
1X WOOD BLOCKING, TYP
HINGES- CONCEALED SELF-CLOSING, TYP6"PULL AS SCHEDULED
MELAMINE LINER ON ALL
INTERIOR SURFACES OF
CABINET
3/4" MDF DOOR
COUNTERTOP AS SCHEDULED
PROVIDE GALVANIZED BIN,
FIT TO OPENING
PULL OUT TRASH
DRAWER
EXTRA HEAVY DUTY FULL
EXTENSION GLIDES
2' - 1"SEE ELEVATIONEXTRA HEAVY DUTY FULL
EXTENSION GLIDES
BACKSPLASH IF SHOWN, SEE
ELEVATION
COUNTERTOP
BLACK MELAMINE ALL INTERIOR
FACES OF CABINET, PLAM AT
EXPOSED PORTIONS
APPLIANCE SHOWN DASHED
PROVIDE POWER FOR APPLIANCE
WHERE REQUIRED
PROVIDE WATER FOR APPLIANCE
WHERE REQUIRED
NOTE: SEE CASEWORK ELEVATIONS FOR FINISHES.SEE ELEVATION2' - 1"1 1/4"BACKSPLASH WHERE INDICATED,
SEE ELEVATION
MATCHING SEALANT
EQ.1/8"EQ.1/8"EQ.VERIFY HEIGHT IN ELEVATIONBASE AS SCHEDULED
1/2" PLYWOOD
THERMOFUSED MELAMINE
BACK TYPICAL ON 1X4
CLEATS
1.5" EASED EDGE
HDW-01;TYP
3/4" MDF DRAWERS W/
PLASTIC LAMINATE ON
ALL SIDES & FULL
EXTENSION DRAWER
GLIDES
MELAMINE LINER ON ALL
INTERIOR SURFACES
FINISH: BLACK
COUNTERTOP & BASE
AS SCHEDULED
2' - 1"
1"
NOTE: SEE CASEWORK ELEVATIONS FOR FINISHES
WHITE MELAMINE INTERIORS TO CABINETS AND
DRAWERS, UNO
3/4" ADJUSTABLE SHELVING W/EDGE
BANDING FRONT AND BACK EDGES,
SEE ELEV. FOR QUANTITIES.
DOOR HARDWARE, REFER TO INTERIOR
ELEVATIONS
HINGES- CONCEALED SELF-CLOSING, TYP
3/4" PLYWOOD DOORS W/ PLAM ON BOTH SIDES
SEE ELEVATION SEE ELEVATION
1' - 2"
1/4" PLYWOOD BACK PANEL
FINISHED BOTTOM
FIRE-RETARDANT-TREATED WOOD BLOCKING FOR
MOUNTING
2"UNDER CABINET LIGHT IF SPEC'D
3/4" ADJUSTABLE PLAM SHELVING
W/EDGE BANDING FRONT AND BACK
EDGES, SEE ELEV. FOR QUANTITIES.
UNDERCOUNTER WHERE LIGHT
OCCURS
HOLES FOR PINS
SEE ELEVATIONS2".END PANEL BEYOND VERIFY W/ EQUIPMENT1'-0" MINVERIFY WITH ELEVATIONBASE AS SCHEDULED
1/2" PLYWOOD THERMOFUSED
MELAMINE BACK TYPICAL ON 1X4
CLEATS
PLASTIC LAMINATE ON ALL
EXPOSED INTERIOR SURFACES
TO MATCH LAMINATE
SPECIFIED FOR EXTERIOR
1.5" EASED EDGE
COUNTERTOP & BASE
AS SCHEDULED
3/4" MDF DRAWERS W/ PLASTIC
LAMINATE ON ALL SIDES & FULL
EXTENSION DRAWER GLIDES
MELAMINE LINER ON ALL
INTERIOR SURFACES
FINISH: BLACK
MICROWAVE
HDW-01
1"
2' - 1"
ELEC
© DLR Group1A 1B 1C 1D 1E 1F
2A 2B 2C 2D 2E 2F
3A 3B 3C 3D 3E 3F
4A 4B 4C 4D 4E 4F
5A 5B 5C 5D 5E 5F REVISIONS
A B C D E F
1
2
3
4
5
1/13/2023 5:16:09 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
INTEROR DETAILS
A11.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELSCALE:1" = 1'-0"A11.1
1A BASE CABINET - DRAWER/DOOR
SCALE:1" = 1'-0"A11.1
1B BASE CABINET - PULL-OUT TRASH DRAWER
SCALE:1" = 1'-0"A11.1
1C BASE CABINET - SECTION AT APPLIANCE
SCALE:1" = 1'-0"A11.1
1D BASE CABINET - 3-DRAWERS
SCALE:1" = 1'-0"A11.1
2A UPPER CABINET - TYP
SCALE:1" = 1'-0"A11.1
2B UPPER CABINET - OPEN SHELVES
SCALE:1" = 1'-0"A11.1
1E BASE CABINET - MICROWAVE
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
UP
REF.UP
UP
UP
INTERIOR FINISH PLAN
GENERAL NOTES
A. INTERIOR FINISH PLAN GENERAL NOTES APPLY TO ALL INTERIOR
FINISH PLAN SHEETS.
B. NOT ALL FLOOR AND WALL FINISHES ARE NOTED ON THE
INTERIOR FINISH PLANS. SEE ELEVATIONS FOR FLOOR AND
WALL FINISHES NOT NOTED.
C. FLOOR PATTERN DIMENSIONS AND LOCATIONS ARE
APPROXIMATE. MINOR ADJUSTMENTS MAY BE MADE FOR
LAYOUT AND TO MINIMIZE WASTE AS LONG AS THE DESIGN
INTENT IS MAINTAINED.
D. FOR FLOOR TILE PRODUCTS, ADJUST LAYOUT AS NECESSARY
TO AVOID USING CUT WIDTHS THAT EQUAL LESS THEN ONE-
HALF OF A TILE AT ROOM PERIMETER.
E. ALL WALLS TO RECEIVE P-01 AND B-01 U.N.O.
F. WHERE FLOOR FINISH CHANGES FROM ONE ROOM TO
ANOTHER, SET JOINT OF THE MATERIALS AT THE CENTER OF
THE COMMUNICATING DOOR.
G. CARPET PATTERN TO ALIGN AT ALL SEAMS WITH ADJOINING
CARPET. PROVIDE SEAMING DIAGRAM TO ARCHITECT FOR
APPROVAL PRIOR TO ORDERING CARPET. ALL SEAMS SHALL BE
SECURED ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS.
H. VERIFY LEAD TIMES FOR ALL MATERIALS TO ENSURE TIMELY
DELIVERY.
I. CONTRACTOR TO SUBMIT THREE (3) SAMPLES OF ALL FINISH
MATERIALS AS SPECIFIED TO OWNER AND ARCHITECT FOR
APPROVAL PRIOR TO PLACEMENT OF ORDER.
J. CONTRACTOR SHALL CHECK AND VERIFY CONDITIONS AT JOB
SITE AND REQUEST CLARIFICATION FROM THE ARCHITECT OF
ANY POSSIBLE CONFLICTS BETWEEN DRAWINGS AND FIELD
CONDITIONS BEFORE COMMENCING ANY WORK.
K. SEE REFLECTED CEILING PLANS FOR CEILING MATERIAL AND
HEIGHT.
L. EXPOSED STRUCTURE CEILINGS AND EQUIPMENT SHALL BE
PAINTED P-02 U.N.O.
M. ALL FLOOR AND WALL FINISHES TO EXTEND BEHIND ANY BUILT-
IN CABINETRY OR MILLWORK U.N.O.
NMLK
1
2
3
4
HGFEDC
0.2
0.1
0.3
PRESENTATION
108
MODELING
ROOM
107
WOOD SHOP
104
ROUTER ROOM
105
TRUCK BAYS
126
MACHINE
SHOP
127
J
P-02P-04 AP-01
AP-01P-04
P-02P-02 P-021.6
2.2
2.8
3.4
LARGE CONF
110
MED CONF
119
CIRCULATION
117
CIRCULATION
111
SHARED
OFFICE
120
LIFT
L101
WOMEN
113
MEN
115
VEST.
114
VEST.
116
JANITOR
123
STORAGE
129
TOOL ROOM
125
LUNCH ROOM
122
ELEC
121
CPT-01
CPT-01
CPT-02
CPT-02
CPT-01 © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:10 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -FINISH
PLAN
A12.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FINISH PLAN, LEVEL 1
1 FINISH PLAN SHEET NOTE 1
2 FINISH PLAN SHEET NOTE 2
INTERIOR FINISH PLAN
SHEET NOTES
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.
INTERIOR FINISH PLAN
GENERAL NOTES
A. INTERIOR FINISH PLAN GENERAL NOTES APPLY TO ALL INTERIOR
FINISH PLAN SHEETS.
B. NOT ALL FLOOR AND WALL FINISHES ARE NOTED ON THE
INTERIOR FINISH PLANS. SEE ELEVATIONS FOR FLOOR AND
WALL FINISHES NOT NOTED.
C. FLOOR PATTERN DIMENSIONS AND LOCATIONS ARE
APPROXIMATE. MINOR ADJUSTMENTS MAY BE MADE FOR
LAYOUT AND TO MINIMIZE WASTE AS LONG AS THE DESIGN
INTENT IS MAINTAINED.
D. FOR FLOOR TILE PRODUCTS, ADJUST LAYOUT AS NECESSARY
TO AVOID USING CUT WIDTHS THAT EQUAL LESS THEN ONE-
HALF OF A TILE AT ROOM PERIMETER.
E. ALL WALLS TO RECEIVE P-01 AND B-01 U.N.O.
F. WHERE FLOOR FINISH CHANGES FROM ONE ROOM TO
ANOTHER, SET JOINT OF THE MATERIALS AT THE CENTER OF
THE COMMUNICATING DOOR.
G. CARPET PATTERN TO ALIGN AT ALL SEAMS WITH ADJOINING
CARPET. PROVIDE SEAMING DIAGRAM TO ARCHITECT FOR
APPROVAL PRIOR TO ORDERING CARPET. ALL SEAMS SHALL BE
SECURED ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS.
H. VERIFY LEAD TIMES FOR ALL MATERIALS TO ENSURE TIMELY
DELIVERY.
I. CONTRACTOR TO SUBMIT THREE (3) SAMPLES OF ALL FINISH
MATERIALS AS SPECIFIED TO OWNER AND ARCHITECT FOR
APPROVAL PRIOR TO PLACEMENT OF ORDER.
J. CONTRACTOR SHALL CHECK AND VERIFY CONDITIONS AT JOB
SITE AND REQUEST CLARIFICATION FROM THE ARCHITECT OF
ANY POSSIBLE CONFLICTS BETWEEN DRAWINGS AND FIELD
CONDITIONS BEFORE COMMENCING ANY WORK.
K. SEE REFLECTED CEILING PLANS FOR CEILING MATERIAL AND
HEIGHT.
L. EXPOSED STRUCTURE CEILINGS AND EQUIPMENT SHALL BE
PAINTED P-02 U.N.O.
M. ALL FLOOR AND WALL FINISHES TO EXTEND BEHIND ANY BUILT-
IN CABINETRY OR MILLWORK U.N.O.
PN Q R SMLK
1
0.2
0.1
0.3
J
NMLK
1
2
3
4
HGFEDC
0.2
0.1
0.3
MOTHER
211
OFFICE
215
STUDIO
213
OFFICE
214
MED CONF
212
MICROKITCHEN
209
VR SPACE
210
TOILET
208
TOILET
207
OFFICE
206
OFFICE
205
STUDIO
200
OFFICE
202
OFFICE
203
PHONE
201
LIFT
L201
PRINT
204
PRESENTATION
108
TRUCK BAYS
126STAIR 1
S201
STAIR 2
S202
MECH
MEZZANINE
M201
STAIR 4
S204
J
P-02
P-02
P-02P-04P-04P-04P-04P-04P-04P-04P-04P-04P-04
T-01
T-03
T-03 WC-01AP-01
WC-02P-05
1.6
2.2
2.8
3.4
CPT-01
CPT-01
CPT-01
RF-01
RFCPT RFCPTCPT-02
CPT-03
P-04
T-04
T-04
CPT-01
CPT-01
CPT-01
CPT-01
CPT-01CPT-01 P-04AP-02AP-02AP-02AP-02AP-02
AP-02FINISH PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
PLAN KEYED NOTE
RFCPT
NO
FLOOR FINISH TRANSITION
FLOOR MATERIAL DIRECTION
XX-01
XX-01
FINISH MATERIAL TAG
EXTENT OF WALL FINISH, SEE
INTERIOR ELEVATION FOR ADDITIONAL
INFORMATION © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 5:16:11 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -FINISH
PLAN
A12.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FINISH PLAN, DECK
NSCALE:1/8" = 1'-0"
FINISH PLAN, LEVEL 2
1 FINISH PLAN SHEET NOTE 1
2 FINISH PLAN SHEET NOTE 2
INTERIOR FINISH PLAN
SHEET NOTES
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.FURNITURE PLAN NOTES
A. FURNITURE FOR REFERENCE ONLY AND MAY NOT BE THE FINAL
TYPE AND LOCATION AS SHOWN.
B. SEE INTERIOR ELEVATIONS FOR EQUIPMENT LAYOUTS.
FURNITURE PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
FURNITURE TAGXX-XX
NMLK
1
2
3
4
HGFEDC
0.2
0.1
0.3
J
F-03
F-02
MB-01
MB-01 MB-01
F-05 F-05
F-01
F-21,
TYP
F-22
F-23
F-26
F-26
F-26
F-25
F-25
F-25
F-21,
TYP.
1.6
2.2
2.8
3.4
MB-01 © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:13 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 1 -FF&E
PLAN
A13.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FF&E PLAN, LEVEL 1
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
REF.
FURNITURE PLAN NOTES
A. FURNITURE FOR REFERENCE ONLY AND MAY NOT BE THE FINAL
TYPE AND LOCATION AS SHOWN.
B. SEE INTERIOR ELEVATIONS FOR EQUIPMENT LAYOUTS.
FURNITURE PLAN LEGEND
AREA NOT IN CONTRACT (NIC)
FURNITURE TAGXX-XX
NMLK
1
2
3
4
HGFEDC
0.2
0.1
0.3
MOTHER
211
OFFICE
215
STUDIO
213
OFFICE
214
MED CONF
212
MICROKITCHEN
209
VR SPACE
210
TOILET
208
TOILET
207
OFFICE
206
OFFICE
205
STUDIO
200
OFFICE
202
OFFICE
203
PHONE
201
LIFT
L201
PRINT
204
PRESENTATION
108
ACCESS
DOOR
4"
J
F-11
F-11
F-11
F-11
F-11
F-11
F-12
F-13
F-09
F-08
F-17 F-18,
TYP.
F-13
F-14
F-16
F-15
MB-02
MB-02
F-06
F-07
F-31
F-31
F-10
F-19
F-20
F-23
F-26
F-25
F-28
F-27
F-24 F-29 F-29 F-30F-30F-30F-30
F-21,
TYP.
1.6
2.2
2.8
3.4
MB-01 © DLR GroupREVISIONS
KEY PLAN
A B C D E F
1
2
3
4
5
OFFICE
1/13/2023 5:16:16 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_AR_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -FF&E
PLAN
A13.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FF&E PLAN, LEVEL 2
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
STRUCTURAL RENOVATION SCOPE
1. PROJECT STRUCTURAL SCOPE IS LIMITED TO THE FOLLOWING:
a. SEOR TO ITEMIZE ELEMENTS WITHIN THE STRUCTURAL SCOPE HERE.
EXISTING CONDITIONS
1. CONTRACTOR IS TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BIDDING. ALL WORK AND
MATERIALS NECESSARY TO INSTALL NEW WORK IN EXISTING BUILDING(S) SHALL BE INCLUDED.
2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AND SHALL CONTACT THE
ENGINEER IF ANY DISCREPANCIES ARE FOUND BEFORE PROCEEDING. NOTIFY ENGINEER
IMMEDIATELY IF EXISTING CONDITIONS DO NOT MATCH, OR SEEM IN CONFLICT WITH, INFORMATION
SHOWN ON DRAWINGS.
3. DIMENSIONS INDICATED ON PLAN AS FIELD VERIFY, OR “FV”, ARE DIMENSIONS THAT MAY BE
REQUIRED FOR FABRICATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF
DIMENSIONS IN THE FIELD NECESSARY FOR FABRICATION OF MEMBERS AND PRIOR TO SUBMISSION
OF SHOP DRAWINGS.
4. CONTRACTOR TO PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS AND EQUIPMENT
TO REMAIN FROM DAMAGE DUE TO DEMOLITION OR CONSTRUCTION OPERATIONS PERFORMED
UNDER THIS CONTRACT.
5. THE SEQUENCE OF CONSTRUCTION SHALL BE THE RESPONSIBILITY THE CONTRACTOR. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL TEMPORARY GUYS, BRACING, AND
OTHER SUPPORTS AS NEEDED TO SAFELY RESIST ALL GRAVITY AND LATERAL LOADS TO WHICH THE
EXISTING OR PROPOSED STRUCTURE MAY BE SUBJECTED, INCLUDING LOADS FROM ERECTION
EQUIPMENT AND ERECTION OPERATIONS, AND WIND OR SEISMIC FORCES COMPARABLE IN
INTENSITY FOR WHICH THE STRUCTURE IS DESIGNED. LOAD VERIFICATION OF EXISTING MEMBERS
TO RECEIVE TEMPORARY SHORING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR’S
ENGINEER.
6. ALL ERECTION AND CONSTRUCTION PROCEDURES SHALL MEET THE REQUIREMENTS OF ALL
APPLICABLE CODES AND ORDINANCES.
7. ALL FRAMING CONNECTIONS TO EXISTING STRUCTURE SHALL BE FIELD VERIFIED PRIOR TO SHOP
DRAWING PRODUCTION AND FABRICATION. FIELD VERIFIED DIMENSIONS SHALL BE INCLUDED ON
FIRST SHOP DRAWING SUBMITTAL AND NOTED AS SUCH.
8. EXISTING UTILITY LINES SHALL BE PROBED PRIOR TO CONSTRUCTION OF FOUNDATIONS. NOTIFY
ENGINEER IF THE TOP OF ANY UTILITY PIPE COMES WITHIN 3'-0" OF THE BOTTOM OF ANY
FOUNDATION. DETERMINE THE LOCATION OF ALL NEW AND EXISTING UNDERGROUND UTILITIES IN
AND ADJACENT TO THE AREA OF WORK PRIOR TO EXCAVATION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGES WHICH MAY RESULT FROM FAILURE TO EXACTLY LOCATE,
PROTECT, AND PRESERVE ALL EXISTING UNDERGROUND UTILITIES.
9. EXCAVATION UNDER OR NEAR IN-PLACE FOOTINGS WHICH DISTURBS THE COMPACTED SOIL
BENEATH THE FOOTINGS IS NOT PERMITTED.
10. CONTRACTOR SHALL LOCATE REBAR IN EXIST. CONSTRUCTION PRIOR TO DRILLING OF HOLES AND
SHALL TAKE CARE NOT TO DAMAGE EXIST. BARS. IF DAMAGE TO EXIST. REBAR OCCURS DURING
CONSTRUCTION, THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING THE DAMAGE. REPAIR
PROCEDURES NOT DETAILED IN THE CONTRACT DOCUMENTS W ILL REQUIRE PREPARATION BY A
QUALIFIED PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS
LOCATED AND MUST BE APPROVED BY THE ENGINEER.
EXISTING DOCUMENTATION
1. THE FOLLOWING DOCUMENTS WERE USED TO REPRESENT EXISTING STRUCTURE IN THE
CONSTRUCTION DOCUMENTS. NOT ALL ELEMENTS AND INFORMATION HAS BEEN PROVIDED. COPIES
OF THE EXISTING DRAWINGS MAY BE AVAILABLE AT THE CONTRACTOR’S REQUEST.
• ARCHITECTURAL DRAWINGS DATED JUNE 5, 2003 BY FREIHEIT & HO ARCHITECTS, INC. P.S.
• STRUCTURAL DRAWINGS DATED JUNE 5, 2003 BY SHUTLER CONSULTING ENGINEERS, INC.
DEMOLITION
1. DEMOLITION OF EXISTING STRUCTURE TO BE REMOVED SHALL BE PERFORMED BY THE
CONTRACTOR USING MEANS NECESSARY TO PREVENT DAMAGE TO THE EXISTING STRUCTURE TO
REMAIN. DAMAGE TO THE EXISTING STRUCTURE TO REMAIN SHALL BE REPAIRED AT THE
CONTRACTOR'S EXPENSE USING METHODS REVIEWED BY THE STRUCTURAL ENGINEER. IF EXISTING
CONDITIONS DIFFER FROM THOSE SHOWN IN THE CONTRACT DOCUMENTS CONTACT THE
ARCHITECT PRIOR TO PROCEEDING WITH WORK.
2. SHORING OF THE EXISTING STRUCTURE SHALL BE PROVIDED BY THE CONTRACTOR AND DESIGNED
BY A QUALIFIED PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS
LOCATED.
GENERAL
1. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE, NOT THE METHOD OF CONSTRUCTION. THE
CONTRACTOR SHALL PROVIDE ALL TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND
HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL ALL STRUCTURAL WORK AND CONNECTIONS
HAVE BEEN COMPLETED. THE RESEARCH, DESIGN, SAFETY, ADEQUACY, AND INSPECTION OF
ERECTION BRACING, SHORING, GUYING, TEMPORARY SUPPORTS, ETC, IS THE RESPONSIBILITY OF
THE CONTRACTOR.
2. THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS AND METHODS,
SEQUENCES OF CONSTRUCTION, OR CONSTRUCTION TECHNIQUES USED TO PERFORM THE WORK.
OBSERVATION VISITS TO THE SITE WILL NOT INVOLVE REVIEW OF THESE ITEMS.
3. THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PROGRAM. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL SAFETY PRECAUTIONS AND
REGULATIONS DURING THE WORK. THE ENGINEER WILL NOT ADVISE ON, NOR ISSUE DIRECTION, AS
TO SAFETY PRECAUTIONS AND PROGRAMS. OBSERVATION VISITS TO THE SITE WILL NOT INVOLVE
REVIEW OF THESE ITEMS.
4. CONTRACTOR IS TO ESTABLISH AND VERIFY OPENINGS AND INSERTS FOR ITEMS TO BE INSTALLED
BY OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND CONSTRUCTION.
5. CONSTRUCTION MATERIAL AND EQUIPMENT LOADS PLACED ON THE STRUCTURE DURING THE
CONSTRUCTION PROCESS SHALL NOT EXCEED THE DESIGN LIVE LOAD OF THE STRUCTURE NOTED
IN THESE DRAWINGS. THE ENGINEER SHALL NOT BE RESPONSIBLE TO INVESTIGATE, NOR APPROVE,
THE STRUCTURE FOR CONSTRUCTION MATERIAL OR EQUIPMENT LOADING. ERECTION OR
CONSTRUCTION LOADS ARE NOT TO BE APPLIED UNTIL PROPER STRUCTURAL FRAMING
CONNECTIONS ARE MADE, AND ALL TEMPORARY BRACING IS IN PLACE. THE CONTRACTOR SHALL
DESIGN AND PROVIDE TEMPORARY BRACING OF THE STRUCTURE WHERE NECESSARY FOR
CONSTRUCTION LOADS.
6. DETAILS THAT ARE NOTED AS "TYPICAL" OR "TYP" ON DETAIL TITLES ARE TO BE APPLIED TO THE
PROJECT CONSTRUCTION AS GENERAL CONSTRUCTION METHODS UNLESS NOTED OTHERWISE.
THESE DETAILS ARE NOT CUT AT ALL LOCATIONS WHERE THEY OCCUR, AND THEY MAY NOT BE CUT
AT ALL. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR
CONDITIONS ELSEWHERE ON THE PROJECT, SUBJECT TO APPROVAL OF THE ENGINEER.
7. DO NOT SCALE DRAWINGS. CONTRACTOR IS TO VERIFY ALL DIMENSIONS RELATIVE TO
ARCHITECTURAL OR OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION. ANY DISCREPANCIES
MUST BE REPORTED TO THE ENGINEER PRIOR TO CONSTRUCTION.
8. WHERE DISCREPANCIES OCCUR BETWEEN GENERAL NOTES, PLANS, DETAILS, AND SPECIFICATIONS,
THE MOST STRINGENT REQUIREMENTS SHALL GOVERN, UNLESS APPROVED OTHERWISE BY THE
ENGINEER IN WRITING PRIOR TO CONSTRUCTION.
9. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE DRAWINGS OF ALL OTHER
DISCIPLINES AND SPECIFICATIONS. THE CONTRACTOR SHALL ESTABLISH AND VERIFY THE
REQUIREMENTS OF OTHER TRADES AS TO SLEEVES, CHASES, HANGERS, INSERT ANCHORS, HOLES,
AND OTHER ITEMS TO BE PLACED OR SET IN THE STRUCTURAL WORK. DO NOT PENETRATE ANY
STRUCTURAL ELEMENTS (BEAMS, COLUMNS, WALLS, SLABS, STEEL DECKS, ETC) WITHOUT PRIOR
WRITTEN APPROVAL OF THE ENGINEER.
10. IF THE ENGINEER'S SEAL AND SIGNATURE IS NOT AFFIXED TO THESE DRAWINGS, THESE DRAWINGS
ARE INTENDED FOR PRELIMINARY PURPOSES ONLY AND SHALL NOT BE USED FOR CONSTRUCTION.
11. STRUCTURAL JOINT DIMENSIONS SHOWN ON PLANS AND DETAILS (EXPANSION, SEISMIC,
SEPARATION, ETC) INDICATE THE MINIMUM CLEAR DISTANCE REQUIRED. SEE ARCHITECTURAL
DRAWINGS FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
GEOTECHNICAL & FOUNDATIONS
1. FOUNDATION DESIGN IS BASED ON GEOTECHNICAL INVESTIGATION PERFORMED BY ________,
PROJECT NO. _________, DATED ________. BASED ON THE GEOTECHNICAL REPORT, THE FOLLOWING
HAS BEEN ASSUMED:
FROST DEPTH
ALLOWABLE NET SOIL BEARING PRESSURE PSF
EQUIVALENT ACTIVE (UNRESTRAINED) FLUID PRESSURE PCF
EQUIVALENT AT-REST (RESTRAINED) FLUID PRESSURE PCF
EQUIVALENT PASSIVE FLUID PRESSURE PCF
COEFFICIENT OF FRICTION
2. SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT AND PROJECT
SPECIFICATIONS.
3. CONTRACTOR SHALL PROVIDE TEMPORARY FROST PROTECTION FOR FOUNDATIONS NOT
CONSTRUCTED TO FROST DEPTH IF CONSTRUCTION IS TO TAKE PLACE IN WINTER MONTHS.
CONTACT GEOTECHNICAL ENGINEER FOR GUIDANCE.
4. IF DISCREPANCIES EXIST BETWEEN THE CONTRACT DOCUMENTS AND THE GEOTECHNICAL REPORT,
THE MOST STRINGENT REQUIREMENTS SHALL GOVERN, UNLESS DETERMINED OTHERWISE BY THE
ENGINEER IN WRITING.
5. ALL FOUNDATION EXCAVATIONS AND BEARING SURFACES SHALL BE OBSERVED AND APPROVED BY
THE GEOTECHNICAL ENGINEER / TESTING AGENCY PRIOR TO PLACING FOUNDATION CONCRETE.
6. NOTIFY ENGINEER OF ANY NECESSARY DEVIATIONS FROM THE FOOTING ELEVATIONS SHOWN ON
THE DRAWINGS PRIOR TO CONSTRUCTING THE FOOTINGS.
7. UNLESS NOTED OTHERWISE, COLUMN FOOTINGS SHALL BE CENTERED ON COLUMNS, AND WALL
FOOTING SHALL BE CENTERED ON WALLS.
8. BACKFILL FOUNDATION WALLS WITH FREE DRAINING FILL AND PROVIDE A SUBSURFACE DRAINAGE
SYSTEM BASED ON THE GEOTECHNICAL REPORT RECOMMENDATIONS.
9. NEW FOOTINGS LOCATED IMMEDIATELY ADJACENT TO EXISTING FOOTINGS SHALL BE FOUNDED AT
THE SAME ELEVATION AS THE EXISTING FOUNDATIONS, UNO. THE EXISTING FOOTINGS SHALL NOT
BE UNDERMINED BY NEW CONSTRUCTION, UNO.
CONCRETE CONSTRUCTION
1. THESE NOTES APPLY TO CONCRETE USED IN BUILDING CONSTRUCTION ONLY. SEE CIVIL/SITE WORK
DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 301 AND ACI 318.
3. REFER TO DRAWINGS OF OTHER DISCIPLINES AND VENDOR DRAWINGS FOR EMBEDDED ITEMS AND
RECESSES NOT SHOWN ON STRUCTURAL DRAWINGS.
4. SLEEVES OR OPENINGS, EXCEPT AS DETAILED ON THE STRUCTURAL DRAWINGS, SHALL NOT BE
PLACED IN WALLS, JOISTS, BEAMS, GIRDERS, OR IN SLABS ADJACENT TO A COLUMN (WITHIN A
DISTANCE EQUAL TO THE SLAB THICKNESS) UNLESS APPROVED BY THE ENGINEER. PLUMBING,
MECHANICAL, & ELECTRICAL CONTRACTORS SHALL SUBMIT SIZES AND LOCATIONS OF ALL
PENETRATIONS IN STRUCTURAL SLABS FOR THE ENGINEER'S APPROVAL BEFORE THE SLAB IS
PLACED. ALL PIPE PENETRATIONS THROUGH SLABS SHALL BE SLEEVED PER WITH ACI 318.
5. PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI 318. SUBMIT DRAWINGS SHOWING
PLACEMENT SEQUENCE FOR ENGINEERING REVIEW.
6. ALL CONCRETE SHALL BE MECHANICALLY CONSOLIDATED IN ACCORDANCE WITH ACI 309.
7. ALL EDGES OF PERMANENTLY EXPOSED CONCRETE SURFACES SHALL BE CHAMFERED 3/4", UNO.
SUBMITTALS
1. THE FOLLOWING ITEMS ARE REQUIRED STRUCTURAL SUBMITTALS AS DESCRIBED IN THE
SPECIFICATIONS.
a. 033000 CAST-IN-PLACE CONCRETE REINFORCING
b. 042000 UNIT MASONRY
c. 051200 STRUCTURAL STEEL FRAMING
d. 053100 STEEL DECKING
e. 316216 STEEL PILES
2. THE FOLLOWING ITEMS ARE DELEGATED DESIGN (DEFERRED SUBMITTALS PER THE BUILDING CODE)
AS DESCRIBED IN THE SPECIFICATIONS
a. 033000 CAST-IN-PLACE CONCRETE MIX DESIGNS
b. 055000 METAL FABRICATIONS
c. 055113 METAL PAN STAIRS
d. 055213 PIPE AND TUBE RAILINGS
3. DELEGATED DESIGN SUBMITTAL CALCULATIONS AND/OR SHOP DRAWINGS SHALL BE SIGNED AND
SEALED BY THE ENGINEER RESPONSIBLE FOR THEIR PREPARATION AND SHALL BE SUBMITTED TO
THE ENGINEER FOR REVIEW WITH THE SHOP DRAWING SUBMITTAL. ONCE REVIEWED, CONTRACTOR
SHALL FORWARD TO THE AHJ FOR APPROVAL. FABRICATION AND INSTALLATION OF THE DELEGATED
DESIGN SUBMITTAL ITEMS SHALL NOT OCCUR UNTIL APPROVAL OF THE AHJ IS RECEIVED.
MASONRY
1. MASONRY CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE "SPECIFICATIONS FOR
MASONRY STRUCTURES" (TMS 602), "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES"
(TMS 402), AND THE BUILDING CODE.
2. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90, NORMAL WEIGHT, WITH A MINIMUM NET
AREA COMPRESSIVE STRENGTH OF 2,000 PSI. CONCRETE MASONRY ASSEMBLIES SHALL HAVE A
MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2,000 PSI (f’m).
3. MORTAR FOR ABOVE GRADE MASONRY SHALL CONFORM TO ASTM C270, TYPE S AND BELOW GRADE
MASONRY SHALL BE TYPE M.` ALL MORTAR SHALL MEET THE "PROPORTION SPECIFICATION" OF ASTM
C270 AND BE MADE WITH PORTLAND CEMENT / LIME (NON-AIR - ENTRAINED). MASONRY CEMENT IS
NOT ACCEPTABLE.
4. UNO, ALL WALLS SHALL BE LAID IN RUNNING BOND. BOND CORNERS AND INTERSECTIONS OF LOAD
BEARING WALLS. ALL UNITS SHALL BE LAID WITH FULL MORTAR COVERAGE ON HEAD, BED (FACE
SHELL), WEBS, AND COLLAR JOINTS, UNLESS NOTED OTHERWISE. BED JOINT THICKNESS SHALL NOT
EXCEED 5/8”.
5. GROUT SHALL CONFORM TO ASTM C476 WITH A MIN. 28-DAY COMPRESSIVE STRENGTH OF 3,000 PSI
BUT NOT LESS THAN THE SPECIFIED NET AREA COMPRESSIVE STRENGTH OF THE MASONRY UNITS.
6. FILL ALL BOND BEAMS, LINTELS, AND REINFORCED CELLS SOLID WITH GROUT. ALL MASONRY BELOW
GRADE SHALL BE GROUTED SOLID BELOW HIGHEST ADJACENT GRADE.
7. MASONRY REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. REINFORCING STEEL TO BE
WELDED SHALL BE ASTM A706, GRADE 60.
8. HORIZONTAL JOINT REINFORCING SHALL COMPLY WITH ASTM A 951 AND BE 9 GAUGE STANDARD
LADDER TYPE, GALVANIZED, AT 16-INCHES ON CENTER. SPACE JOINT REINFORCING AT 8-INCHES ON
CENTER AT NON-CAVITY MULTIWYTHE WALLS. COLLAR JOINT BETWEEN WYTHES OF NON-CAVITY
MULTIWYTHE WALLS ARE TO BE MORTARED/GROUTED SOLID.
9. SPACE JOINT REINFORCING AT 8-INCHES ON CENTER AT NON-CAVITY MULTIWYTHE WALLS. COLLAR
JOINT BETWEEN WYTHES OF NON-CAVITY MULTIWYTHE WALLS ARE TO BE MORTARED/GROUTED
SOLID.
10. PROVIDE BOND BEAMS AT TOP OF ALL WALLS, ALL ROOF AND FLOOR LINES, AND WHERE INDICATED.
MINIMUM BOND BEAM REINFORCING SHALL BE (2) #5 IN 6" AND 8" WIDE BOND BEAMS AND (2) #6 IN 12"
WIDE BOND BEAMS. DISCONTINUE BOND BEAM REINFORCING AT CONTROL JOINTS EXCEPT AT
FLOOR LEVELS, ROOF LEVELS, AND TOPS OF WALLS. PROVIDE CORNER BARS AT CORNERS AND
WALL INTERSECTIONS.
11. ALL CMU WALL OPENINGS REQUIRE LINTELS.
12. SPLICE LENGTHS FOR MASONRY REINFORCEMENT SHALL BE IN 72 TIMES THE REINFORCING BAR
DIAMETER, UNO.
13. REINFORCING SHALL BE HELD IN PLACE PRIOR TO GROUTING WITH AT LEAST TWO WIRE
POSITIONERS PER GROUT POUR AND AT REINFORCING SPLICES. POSITIONERS SHALL PROVIDE
REBAR SPACING OF 2 3/8-INCH CENTER TO CENTER REBAR SPACING FOR 8” BLOCK, AND 6 3/8”
CENTER TO CENTER SPACING FOR 12” BLOCK., UNO.
14. VERTICAL REINFORCING SHALL BE AS FOLLOWS UNO ON PLANS OR DETAILS:
6" CMU: (1) #5 @ 4’-0" OC
8" CMU: (1) #5 @ 4'-0" OC
12" CMU: (1) #6 @ 4'-0" OC
15. UNO, PROVIDE ADDITIONAL REINFORCED CELL FOR THE FULL HEIGHT OF THE WALL AT EACH SIDE OF
ALL OPENINGS, CONTROL JOINTS, EXPANSION JOINTS, WALL ENDS, WALL CORNERS, AND WALL
INTERSECTIONS.
16. ALL VERTICAL REINFORCING REQUIRED BY THESE NOTES OR SHOWN ON THE PLANS SHALL EXTEND
FROM THE FOUNDATION TO THE TOP OF WALL. PROVIDE DOWELS FROM FOUNDATION OR
SUPPORTING STRUCTURE TO MATCH VERTICAL BAR SIZE AND SPACING.
17. MASONRY CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL AND ELECTRICAL
CONTRACTORS AND BUILD IN OPENINGS FOR ELECTRICAL PANELS, CONDUITS, PIPES, FIRE
EXTINGUISHER CABINETS, DUCTS, ETC. AS NOT TO INTERFERE WITH REINFORCED AND/OR GROUTED
CELLS. PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH WALLS SHALL BE SLEEVED.
MINIMUM SPACING OF SLEEVES SHALL BE THREE SLEEVE DIAMETERS.
18. MORTAR FINAL PROJECTION INTO THE GROUT SPACE SHALL NOT EXCEED 1/2 INCH.
19. SPACE CONTROL JOINTS IN MASONRY WALLS SUCH THAT NO STRAIGHT RUN OF WALL EXCEEDS
EITHER 2 TIMES WALL HEIGHT OR 40’-0", UNO. THE CONTRACTOR SHALL NOT PLACE CONTROL
JOINTS ABOVE / BELOW OPENINGS, WITHIN SCHEDULED JAMB EXTENTS, OR WITHIN 16” OF
BEAM/JOIST BEARING PLATES. CONTROL JOINTS SHALL NOT JOG HORIZONTALLY.
STRUCTURAL STEEL
1. FABRICATOR QUALIFICATIONS: FABRICATOR SHALL BE AISC CERTIFIED OR AN “APPROVED
FABRICATOR” IN ACCORDANCE WITH THE BUILDING CODE AND APPROVED BY THE AHJ. IN LIEU OF
THE PREVIOUS, FABRICATOR SHALL INCLUDE IN THEIR BID THE SERVICES OF A SPECIAL INSPECTOR
TO PROVIDE INSPECTION/TESTING SERVICES FOR WORK COMPLETED ON THE FABRICATOR’S
PREMISES TO MEET BUILDING CODE REQUIREMENTS. AT THE COMPLETION OF WORK, FABRICATOR
SHALL SUBMIT A “CERTIFICATE OF COMPLIANCE” TO THE ARCHITECT AND AHJ STATING THAT THE
WORK WAS PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION DOCUMENTS.
2. STRUCTURAL STEEL SHAPES AND CONNECTING COMPONENTS SHALL CONFORM TO THE FOLLOWING
MATERIAL SPECIFICATIONS UNO:
FOLLOWING MATERIAL SPECIFICATIONS:
WIDE FLANGE SHAPES ASTM A992, Fy = 50 KSI
HOLLOW STRUCTURAL SECTIONS (HSS)
RECTANGULAR & SQUARE ASTM A500, GRADE C, Fy = 50 KSI
ROUND ASTM A500, GRADE C, Fy = 46 KSI
STEEL PIPE ASTM A53, GRADE B, Fy = 35 KSI
OTHER STEEL SHAPES AND PLATES ASTM A36, Fy = 36 KSI
HIGH STRENGTH STRUCTURAL BOLTS ASTM F3125, GRADE A325N
COLUMN ANCHOR RODS ASTM F1554, GRADE 55 WELDABLE (S1)
MACHINE BOLTS ASTM A307
THREADED RODS ASTM A36
WELDING ELECTRODES E70XX
DEFORMED BAR ANCHORS (DBA) ASTM A496, Fy = 70 KSI
WELDED HEADED STUDS (WHS) ASTM A108, Fu = 65 KSI
WELDED THREADED STUDS (WTS) ASTM A108, Fu = 65 KSI
3. CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE BUILDING SYSTEM AT ALL TIMES DURING
THE ERECTION PROCESS. ELEMENTS HAVE BEEN DESIGNED FOR THE FINAL COMPLETED CONDITION
AND HAVE NOT BEEN INVESTIGATED FOR TEMPORARY LOADING DURING CONSTRUCTION.
INVESTIGATION OF THE STRUCTURAL ELEMENTS FOR ADEQUACY DURING THE STEEL ERECTION AND
CONSTRUCTION PROCESS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR TO
PROVIDE TEMPORARY SUPPORTS AS REQUIRED TO MAINTAIN STABILITY.
4. COLUMNS AND BEAMS WITH BASE, CAP OR END PLATES SHALL HAVE SQUARE CUT OR MILLED ENDS.
5. NON-METALLIC, NON-SHRINK, CHLORIDE FREE GROUT UNDER ALL COLUMN BASE PLATES AND BEAM
BEARING PLATES SHALL CONSIST OF A PRE-MIXED PRODUCT COMPLYING WITH ALL REQUIREMENTS
OF ASTM C1107. THE 28-DAY COMPRESSIVE STRENGTH OF THE GROUT SHALL BE TWICE THE
FOUNDATION REQUIRED CONCRETE COMPRESSIVE STRENGTH, 5,000 PSI MINIMUM.
6. UNO, ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER, INCLUDING ALL BRICK
SHELF ANGLES AND EXTERIOR LINTELS, SHALL BE HOT DIP GALVANIZED AFTER FABRICATION IN
ACCORDANCE WITH ASTM A123. ALL DAMAGED GALVANIZING SHALL BE REPAIRED IN ACCORDANCE
WITH ASTM A780. STAINLESS AND WEATHERING STEELS, WHERE SPECIFIED, ARE EXEMPT FROM THIS
REQUIREMENT.
7. COAT STEEL BELOW GRADE WITH COLD-APPLIED ASPHALT EMULSION PER ASTM D1187.
8. ALL ARCHITECTURALLY EXPOSED STRUCTURAL STEEL (AESS) SHALL COMPLY WITH AISC CODE OF
STANDARD PRACTICE, SECTION 10. REFER TO DRAWINGS FOR LOCATIONS OF AESS.
9. WHERE CONNECTIONS ARE NOTED TO BE SLIP CRITICAL (EXAMPLE: A325-SC), BOLTS SHALL BE
TIGHTENED TO THE MINIMUM PRETENSION FOR FULLY TIGHTENED BOLTS BY ONE OF THE AISC
APPROVED METHODS. SLIP-CRITICAL BOLTS SHALL HAVE CLASS "A" FAYING SURFACES.
10. ALL BOLTS (HIGH STRENGTH, ANCHOR BOLTS, EXPANSION BOLTS, ADHESIVE ANCHORS, ETC.) SHALL
BE INSTALLED WITH STEEL NUTS AND WASHERS. NUTS AND WASHERS FOR HIGH STRENGTH BOLTS
SHALL CONFORM TO ASTM A563 AND TO ASTM F436, RESPECTIVELY.
11. WELDING PROCEDURES, ELECTRODES, AND WELDER QUALIFICATIONS SHALL CONFORM TO THE
AMERICAN WELDING SOCIETY CODE D1.1, AISC STANDARDS, AND LOCAL CODE REQUIREMENTS.
12. ALL WELDS SHOWN ON THE DRAWINGS SHALL BE SHOP W ELDS, UNO. WHERE SHOWN, FIELD
WELDING SHALL BE USED. CONTRACTOR MAY SUBSTITUTE FIELD WELDS FOR SHOP WELDS AT
THEIR DISCRETION. SHOP DRAWINGS SHALL CLEARLY NOTE ALL WELDING USING AWS A2.4 SYMBOLS.
13. WHERE CONTINUOUS ANGLES OR BENT PLATES ARE INDICATED, PROVIDE A CONTINUOUS BUTT
WELD OR FULL PENETRATION WELD AT THE SPLICE POINTS, UNO. THE STEEL FABRICATOR MAY
SUBMIT AN ALTERNATE BOLTED CONNECTION DETAIL FOR APPROVAL.
14. COORDINATE WITH ALL OTHER TRADES WHICH STEEL INTERACTS. THIS INCLUDES BUT IS NOT
LIMITED TO COORDINATING WITH MASONRY, PRECAST CONCRETE, CAST-IN-PLACE CONCRETE, JOIST,
AND METAL DECK SUPPLIERS.
DESIGN CRITERIA
1. ALL CONSTRUCTION, MATERIALS, AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF
THESE DRAWINGS, SPECIFICATIONS, AND THE CODES, RULES AND REGULATIONS OF THE 2018
INTERNATIONAL BUILDING CODE (IBC), AS ADOPTED AND AMENDED BY THE CITY OF RENTON
HEREAFTER REFERRED TO AS THE BUILDING CODE.
2. MATERIAL SPECIFIC DESIGN STANDARDS LISTED IN THESE GENERAL NOTES ARE THE VERSION
REFERENCED BY THE BUILDING CODE. IF NOT REFERENCED BY THE BUILDING CODE, USE THE
LATEST EDITION APPROVED BY THE AUTHORITY HAVING JURISDICTION ON THE DATE OF THE PERMIT
ISSUANCE.
3. RISK CATEGORY II
4. DESIGN DEAD LOADS
ROOF - TOTAL 25 PSF (INCLUDES STRUCTURE SELF WEIGHT)
FLOOR 71 PSF (INCLUDES STRUCTURE SELF WEIGHT)
5. DESIGN LIVE LOADS
FIRST FLOOR 100 PSF
STAIRS & EXIT WAYS 100 PSF
OFFICES 65 PSF (INCLUDES 15 PSF PARTITIONS)
UPPER LEVEL CORRIDORS 80 PSF
ROOF LIVE LOAD 20 PSF
6. SNOW LOADS
GROUND SNOW LOAD, Pg 20 PSF
MINIMUM SNOW LOAD, Pmin 20 PSF
FLAT-ROOF SNOW LOAD, Pf 14.0 PSF (TYP HEATED)
16.8 PSF (UNHEATED CANOPY)
SNOW EXPOSURE FACTOR, Ce 1.0
THERMAL FACTOR, Ct 1.0 (TYP HEATED)
1.2 (UNHEATED CANOPY)
SNOW LOAD IMPORTANCE FACTOR, ls 1.00
RAIN-ON-SNOW SURCHARGE 5 PSF
DRIFT LOADS SEE LOADING DIAGRAMS
7. WIND LOADS
BASIC WIND SPEED (3 SECOND GUST), V 98 MPH
NOMINAL WIND SPEED, Vasd 76 MPH
EXPOSURE CATEGORY B
TOPOGRAPHIC FACTOR, Kzt 1.0
AIR DENSITY FACTOR, Ke 1.0
INTERNAL PRESSURE COEFFICIENT, GCpi +/- 0.18
COMPONENTS AND CLADDING: SEE LOADING DIAGRAMS
8. SEISMIC LOADS
SITE LATITUDE 47.4914
SITE LONGITUDE -122.1959
SITE CLASS _
IMPORTANCE FACTOR, Ie 1.00
MAPPED SPECTRAL RESPONSE ACCELERATIONSSS = 1.436
S1 = 0.490
DESIGN SPECTRAL RESPONSE ACCELERATIONS SDS = 1.149
SD1 = _
SEISMIC DESIGN CATEGORY
SEISMIC FORCE RESISTING SYSTEM:
RESPONSE MODIFICATION FACTOR, R
OVERSTRENGTH FACTOR, Ωo
DEFLECTION AMPLIFICATION FACTOR, Cd
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SEISMIC RESPONSE COEFFICIENT, Cs
DESIGN BASE SHEAR, V
STEEL DECK
1. ALL STEEL DECK SHALL BE MANUFACTURED, DETAILED, FABRICATED AND ERECTED IN ACCORDANCE
WITH THE LATEST EDITION OF THE "DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS, AND
ROOF DECKS" BY THE STEEL DECK INSTITUTE (SDI).
2. STEEL DECK & ACCESSORIES SHALL BE FABRICATED FROM STEEL PER ASTM A1008 OR A653.
3. DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
A. 2” COMPOSITE DECK:
a. MINIMUM YIELD STRENGTH Fy = 50 KSI
b. DEPTH/GAGE: 2” / 20
c. MOMENT OF INERTIA (Ip): 0.407 IN
4 / FT
d. SECTION MODULUS (Sp): 0.337 IN
3 / FT
B. WIDE RIB ROOF DECK (TYPE B):
a. MINIMUM YIELD STRENGTH Fy = 50 KSI
b. DEPTH/GAGE: 1 1/2" / 20
c. MOMENT OF INERTIA (Ip): 0.197 IN
4 / FT MIN
d. SECTION MODULUS (Sp): 0.224 IN
3 / FT MIN
4. COMPOSITE DECK SHALL BE ATTACHED TO SUPPORTING STRUCTURAL MEMBERS BY 5/8” EFFECTIVE
DIAMETER PUDDLE WELDS PLACED AT EACH DECK RIB OR 24 INCHES ON CENTER MAX. THIS WELD
CAN BE OMITTED IN RIBS THAT HAVE SHEAR STUD CONNECTORS. SIDE LAPS BETWEEN ADJACENT
UNITS ARE TO BE ATTACHED WITH #12 TEK SCREWS AT 36 INCHES MAXIMUM (MINIMUM 2 SCREWS
PER SPAN).
5. MINIMUM DECK BEARING SHALL BE 2" AT EXTERIOR SUPPORTS & 3" FOR INTERIOR SUPPORTS, UNO.
6. ALL DECK SHALL BE CONTINUOUS OVER 3 SPANS. WHERE LESS THAN 3 SPANS ARE AVAILABLE, THE
DECK SUPPLIER SHALL INCREASE THE DECK GAGE AS REQUIRED SO THAT DECK IS CAPABLE OF
SUPPORTING PUBLISHED DEAD AND LIVE LOAD CAPACITIES NOTED FOR 3 SPAN CONDITIONS.
7. COMPOSITE DECK DESIGN IS INTENDED TO BE UNSHORED, UNO.
8. CONCRETE REQUIRED FOR COMPOSITE ACTION SHALL MEET 28-DAY COMPRESSIVE STRENGTH
PRIOR TO SUPPORTING TOPPING SLABS, MASONRY WALLS, AND/OR OTHER HEAVY LOADS.
9. NO DIRECT ATTACHMENT TO UNDERSIDE OF METAL ROOF DECK IS ALLOWED UNLESS INDICATED ON
THE STRUCTURAL DRAWINGS. ALL SUSPENDED LOADS, INCLUDING BUT NOT LIMITED TO, CEILINGS,
LIGHT FIXTURES, DUCTWORK, PIPING, AND OTHER UTILITIES TO BE SUPPORTED FROM THE PRIMARY
STRUCTURAL MEMBERS OR SECONDARY SUPPORTS BETWEEN STRUCTURAL FRAMING.
COORDINATE HANGER AND/OR WIRE SUPPORTS WITH ASSOCIATED SPECIFICATIONS AND TRADES.
10. CONDUITS LOCATED IN THE COMPOSITE SLAB SHALL BE LIMITED TO THE LARGER OF 3/4-INCH OR
ONE-FOURTH OF THE TOPPING THICKNESS (MEASURED TOP OF DECK TO TOP OF CONCRETE) AND
SPACED A MINIMUM OF THREE DIAMETERS ON CENTER. CONDUITS RUNNING PERPENDICULAR TO
THE DECK FLUTES SHALL BE LAID DIRECTLY ON THE DECK WITH CONDUITS PARALLEL TO THE DECK
FLUTES LOCATED IN THE DECK VALLEY BELOW THE CONDUITS RUNNING PERPENDICULAR TO THE
DECK FLUTES. ALUMINUM CONDUIT IS PROHIBITED.
POST-INSTALLED ANCHORS
1. UNO, THE FOLLOWING APPLIES TO ALL POST-INSTALLED ANCHORAGE INTO HARDENED CONCRETE
OR MASONRY WHICH INCLUDES TYPES SUCH AS EXPANSION, WEDGE, SLEEVE, ADHESIVE / EPOXY,
SHOT-PIN, SCREW AND UNDERCUT.
2. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED.
3. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD PRIOR TO USING POST-
INSTALLED ANCHORS FOR MISSING, DAMAGED OR MISPLACED CAST-IN-PLACE ANCHORS.
4. CARE SHALL BE GIVEN TO AVOID CONFLICTS WITH EXISTING REBAR WHEN DRILLING HOLES. HOLES
SHALL BE DRILLED AND CLEANED PER THE MANUFACTURER’S INSTRUCTIONS.
5. MAINTAIN A MINIMUM OF 2 INCHES FROM EXISTING REINFORCEMENT, CONDUIT, POST-TENSIONING
(WHERE OCCURS), ETC. USE NON-DESTRUCTIVE TESTING TO LOCATE PRIOR TO DRILLING, CORING
OR SHOOTING PINS INTO THE EXISTING CONCRETE OR MASONRY. FOR INSTALLATION DEEPER THAN
3 INCHES USE GROUND PENETRATING RADAR OR X-RAY METHODS.
6. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS,
MANUFACTURER’S RECOMMENDATIONS AND ALL APPLICABLE ICC-ES REPORTS, INCLUDING, BUT
NOT LIMITED TO, ALL ANCHOR SPACINGS, EMBEDMENTS AND EDGE DISTANCES.
7. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE
ENGINEER PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT
THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE
SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY HAVING AN ICC ESR SHOWING
COMPLIANCE WITH THE BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION
CATEGORY, AND AVAILABILITY OF COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE
ANCHOR EVALUATION WILL ALSO CONSIDER CREEP, IN-SERVICE AND INSTALLATION
TEMPERATURES.
8. EMBEDMENT REFERS TO THE FINAL INSTALLED EFFECTIVE DEPTH “Hef”. ALL ANCHORS SHALL HAVE
EMBEDMENT NOTED OR EMBEDMENT AS RECOMMENDED BY MANUFACTURER WHERE NO
EMBEDMENT IS SHOWN. REQUIRED ANCHOR HOLE DEPTH FOR INSTALLATION MAY BE DEEPER.
9. IF THE FULL ANCHOR EMBEDMENT DEPTH, SPACING OR EDGE DISTANCE CANNOT BE ACHIEVED,
NOTIFY THE ENGINEER.
10. ALL PERSONNEL INSTALLING POST-INSTALLED ANCHORS SHALL BE TRAINED BY THE
MANUFACTURER ON PROPER INSTALLATION TECHNIQUE. TRAINING DOCUMENTATION FROM THE
MANUFACTURER SHALL BE AVAILABLE UPON REQUEST.
11. INSTALLATION OF ADHESIVE ANCHORS IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION
SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI
AND IN ACCORDANCE WITH ACI 318. PROOF OF CURRENT CERTIFICATION SHALL BE SUBMITTED TO
THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
12. EXPANSION BOLTS IN MASONRY SHALL BE ONE OF THE FOLLOWING:
a. HILTI KWIK BOLT 3 MASONRY ANCHORS (ICC ESR-1385)
b. DEWALT – POWER STUD+SD1 (ICC ESR-2966)
c. SIMPSON STRONG-TIE WEDGE-ALL (ICC ESR-1396)
d. SIMPSON STRONG-TIE STRONG BOLT-2 WEDGE ANCHOR (IAMPO UES ER-240)
13. SCREW ANCHORS IN MASONRY SHALL BE ONE OF THE FOLLOWING:
a. HILTI KH-EZ SCREW ANCHOR (ICC ESR-3056)
b. DEWALT – SCREW BOLT+, SCREW ANCHOR (ICC ESR-4042)
c. SIMPSON STRONG-TIE TITEN HD SCREW ANCHORS (ICC ESR-1056)
14. ADHESIVE ANCHORS IN MASONRY SHALL BE ONE OF THE FOLLOWING:
a. HILTI HY-270 FAST CURE ADHESIVE ANCHORS (ICC ESR-4144 FOR URM, ICC ESR-4143)
b. DEWALT AC100+GOLD FAST CURE ADHESIVE ANCHOR (ICC ESR-3200)
c. SIMPSON STRONG-TIE SET-XP ADHESIVE ANCHORING SYSTEM (IAPMO UES ER-265)
15. EXPANSION BOLTS IN CONCRETE SHALL BE ONE OF THE FOLLOWING:
a. HILTI KWIK BOLT TZ2 CONCRETE ANCHORS (ICC ESR-4266)
b. DEWALT POWER-STUD+SD1 (ICC ESR-2818), POWER STUD +SD2 (ICC ESR-2502)
c. SIMPSON STRONG-TIE STRONG-BOLT 2 WEDGE ANCHORS (ICC ESR-3037)
16. SCREW ANCHORS IN CONCRETE SHALL BE ONE OF THE FOLLOWING:
a. HILTI HUS-EZ SCREW ANCHOR (ICC ESR-3027)
b. DEWALT SCREW BOLT+, SCREW ANCHOR (ICC ESR-3889)
c. SIMPSON STRONG-TIE TITEN HD SCREW ANCHORS (ICC ESR-2713)
17. ADHESIVE ANCHORS IN CONCRETE SHALL BE ONE OF THE FOLLOWING:
a. HILTI HY-200 SAFE SET SYSTEM ADHESIVE ANCHORS (ESR-3187) (FAST CURE APPLICATIONS)
b. HILTI RE-500 V3 ADHESIVE ANCHORS (ESR-3814)
c. HILTI RE-100 ADHESIVE ANCHORS (ICC ESR-3829) (STANDARD CURE APPLICATIONS)
d. DEWALT AC200+ ADHESIVE ANCHORS (ICC ESR-4027) (FAST CURE APPLICATIONS)
e. DEWALT PURE 110+ ADHESIVE ANCHORS (ICC ESR-3298) (STANDARD CURE APPLICATIONS)
f. SIMPSON STRONG-TIE SET-3G ADHESIVE ANCHORING SYSTEM (ESR-4057)
g. SIMPSON STRONG-TIE AT-XP ADHESIVE ANCHORING SYSTEM (IAPMO UES ER-263)
h. SIMPSON STRONG-TIE SET-XP ADHESIVE ANCHORING SYSTEM (ESR-2508) (STANDARD CURE
APPLICATIONS)
18. ANCHORS ARE NOT TO BE INSTALLED UNTIL CONCRETE OR GROUT HAS REACHED IT’S DESIGN
STRENGTH. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE WITH A MIN. AGE OF 21 DAYS.
19. MASONRY CELLS SHALL BE FULLY GROUTED AND CURED FOR INSTALLATION OF POST-INSTALLED
ANCHORS.
20. USE INSTALLATION PROCEDURES FOR CRACKED CONCRETE CONDITIONS. DO NOT CORE DRILL FOR
ANCHOR HOLES WITHOUT ENGINEER APPROVAL.
21. PROVIDE GALVANIZED CARBON STEEL ANCHORS AT DRY INTERIOR LOCATIONS AND STAINLESS-
STEEL TYPE 304 OR 316 AT EXTERIOR / DAMP INTERIOR LOCATIONS. ANCHORS SHALL BE CLEAN AND
FREE OF DEBONDING SUBSTANCES.
22. PATCH ABANDONED HOLES AND SPALLS USING NON-SHRINK GROUT AND REPAIR FINISHES AS
REQUIRED. ANCHORS PENETRATING THROUGH WATERPROOFING OR VAPOR MEMBRANES SHALL BE
SEALED OR FLASHED.
23. ADHESIVE / EPOXY ANCHORS ON THIS PROJECT ARE NOT DESIGNED TO SUPPORT OR INTENDED TO
RESIST SUSTAINED TENSION LOADS.
LATERAL LOAD RESISTANCE SYSTEM
1. LATERAL LOAD SYSTEM CONSISTS OF FLOOR AND ROOF DIAPHRAGMS TRANSFERRING LATERAL
LOADS TO MASONRY SHEAR WALLS, CONCRETE SHEAR WALLS, STRUCTURAL STEEL BRACED
FRAMES, AND MOMENT RESISTING FRAMES.
2. STEEL FRAME IS A "NON-SELF-SUPPORTING" STEEL FRAME REQUIRING INTERACTION OF THE STEEL
FRAMING, FLOOR/ROOF DIAPHRAGMS AND SHEAR WALLS/BRACED FRAMES. CONTRACTOR SHALL
PROVIDE TEMPORARY BRACING AS NECESSARY TO PROVIDE SUPPORT OF FRAMING UNTIL ALL
ATTACHMENTS ARE COMPLETE, INCLUDING STRUCTURAL STEEL, STRUCTURAL STEEL TO
DIAPHRAGM/SHEAR WALLS, AND DIAPHRAGM TO SHEAR WALLS/BRACED FRAMES.
CONCRETE TOPPING SLABS
1. TOPPING THICKNESS SHOWN ON PLAN IS NOMINAL. ACTUAL THICKNESS WILL VARY DUE TO
SUPPORTING MEMBER CAMBER AND DEFLECTIONS. PROVIDE THICKNESS AS REQUIRED TO ACHIEVE
A LEVEL FLOOR WITH A FINAL THICKNESS NO LESS THAN 1/2 INCH LESS THAN SPECIFIED.
2. UNO IN PLAN OR DETAIL, PROVIDE (1) #4 IN TOPPING SLAB EACH SIDE OF OPENINGS EXCEEDING 12
INCHES IN SIZE. EXTEND REINFORCING 1’-6” PAST CORNER OF OPENING.
3. ALL COMPOSITE TOPPING SLABS SHALL BE REINFORCED W/ 6x6 – W2.9 x W2.9 WWR, UNO. WELDED
WIRE REINFORCING IN THE TOPPING SHALL BE FLAT SHEETS CENTERED ON THE TOPPING
THICKNESS AND CHAIRED TO MAINTAIN LOCATION. LAP ONE FULL MESH AT SPLICES AND WIRE
TOGETHER.
4. DO NOT PROVIDE CONTROL JOINTS IN TOPPING SLABS.
5. CONDUITS IN THE TOPPING SLAB SHALL BE LIMITED TO THE LARGER OF ¾-INCH OR ONE-FOURTH
THE TOPPING THICKNESS AND SPACED A MINIMUM OF THREE DIAMETERS ON CENTER.
CAST-IN-PLACE CONCRETE MIX DESIGNS
1. THE CONCRETE MIX TABLE SHOWN BELOW SHALL APPLY TO ALL CONCRETE MIX DESIGNS USED FOR
STRUCTURAL ITEMS IN THIS PROJECT. MIX DESIGN SUBMITTALS SHALL BE IDENTIFIED FOR
INTENDED STRUCTURAL USE AND SUBMITTED TO THE OWNER’S REPRESENTATIVE AND ENGINEER
FOR REVIEW PRIOR TO PLACING ANY CONCRETE. WHEN CONCRETE MIX DESIGNS ARE A
DELEGATED DESIGN ITEM, THE SUBMITTED MIX DESIGN SHALL BEAR THE SEAL AND SIGNATURE OF
THE ENGINEER RESPONSIBLE FOR THEIR DESIGN.
2. REFER TO PROJECT SPECIFICATION FOR ADDITIONAL INFORMATION.
3. SUBSTITUTION OF FLY ASH FOR PORTLAND CEMENT FOR SLABS ON GRADE AND STRUCTURAL
SLABS SHALL NOT BE PERMITTED.
4. FLY ASH MAY BE USED TO REPLACE 15% TO 25% OF PORTLAND CEMENT. FLY ASH SHALL CONFORM
TO ASTM C618, TYPE F. PERCENTAGE LISTED IS BY WEIGHT OF TOTAL CEMENTITIOUS MATERIAL
INCLUDING ASTM C150, C595, C845, AND C1157 CEMENT. DO NOT USE FLY ASH IF CONTENT WITHIN
THE PERCENTAGES SHOWN CANNOT BE ACHIEVED.
CONCRETE REINFORCEMENT
1. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60.
2. REINFORCING STEEL TO BE WELDED SHALL BE ASTM A706, GRADE 60. NO WELDING OF
REINFORCEMENT SHALL BE PERMITTED UNLESS SPECIFICALLY CALLED FOR OR REVIEWED AND
APPROVED BY THE ENGINEER.
3. DEFORMED BAR ANCHORS (DBA) SHALL BE PROVIDED IN ACCORDANCE WITH NELSON STUD
WELDING, INC ICC ESR 2907. ANCHORS SHALL BE SHOP WELDED TO STEEL USING A STUD WELDING
GUN.
4. CONCRETE COVER REQUIREMENTS FOR CAST-IN-PLACE, NON-PRESTRESSED REINFORCEMENT
UNLESS OTHERWISE NOTED ON DETAILS SHALL BE AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
FORMED CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 BARS AND LARGER 2"
#5 BARS AND SMALLER: 1 1/2"
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:
SLABS, WALLS, AND JOISTS:
#14 AND #18 BARS: 1 1/2"
#11 BARS AND SMALLER 3/4"
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT: 1 1/2"
TIES, STIRRUPS, SPIRALS: 1 1/2"
5. REINFORCING BAR SPLICES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 318 AND
THE REINFORCING SPLICE LENGTH SCHEDULE. PROVIDE CLASS 'B' LAP SPLICE, UNO.
6. ALL HORIZONTAL WALL AND BEAM REINFORCING SHALL BEND AROUND ALL CORNERS, LAP WITH
INTERSECTING REINFORCEMENT, AND LAP SHALL CONFORM TO LAP SPLICE AND ANCHORAGE
SCHEDULE PROVIDED, UNO.
7. ALL REINFORCEMENT SHALL BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES IN
CONFORMANCE WITH CRSI MANUAL OF STANDARD PRACTICE AND ACI 315 DURING CONCRETE
PLACEMENT. NO WET SETTING OF REINFORCEMENT OR ACCESSORIES.
8. PROVIDE CORROSION RESISTANT ACCESSORIES SUCH AS PLASTIC COATED (NOT PLASTIC TIPPED)
OR STAINLESS-STEEL CHAIRS IN ALL EXPOSED CONCRETE CONSTRUCTION. PRECAST CONCRETE
CHAIRS OR SAND PLATE CHAIRS SHALL BE USED FOR THE SUPPORT OF REINFORCING ON GRADE.
CONCRETE BLOCK OR CLAY MASONRY BRICK ARE NOT PERMITTED.
9. NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT UNLESS
SPECIFICALLY DETAILED AS SUCH OR APPROVED BY THE ENGINEER IN WRITING.
10. WELDED WIRE REINFORCING (WWR) SHALL COMPLY WITH ASTM A1064. USE ONLY FLAT SHEETS.
LAP ALL WWR AT LEAST ONE FULL WIRE SPACING PLUS 2 INCHES. ALL WWR SHALL BE CHAIRED TO
ITS PROPER HEIGHT AND MAINTAINED AT THE PROPER LEVEL THROUGHOUT THE CONCRETE
PLACING OPERATION. LIFTING OF WWR WITH A HOOK DURING CONCRETE PLACEMENT SHALL NOT
BE PERMITTED.
11. MECHANICAL COUPLERS SHALL BE TYPE 2 COUPLERS CAPABLE OF SUSTAINING 125% Fy.
COMPOSITE BEAM SHEAR CONNECTOR STUDS
1. SHEAR STUDS SHALL BE 3/4-INCH DIAMETER X LENGTH SHOWN ON PLANS, WITH A FINAL LENGTH
NOT LESS THAN DEPTH OF DECK PLUS 1.5" CONFORMING TO AWS D1.1. PROVIDE SHEAR STUDS AT
2’-0” OC MAXIMUM FOR ALL BEAMS SUPPORTING SLAB WITHOUT A DESIGNATED STUD QUANTITY.
ACCEPTABLE TYPES SHALL BE "TRU-WELD" (ICC ESR 2577) OR "NELSON" (ICC ESR 2856).
DRILLED CONCRETE PIERS AND SHAFTS
1. DRILLED PIERS SHALL EXTEND INTO SUITABLE MATERIAL CAPABLE OF MEETING GEOTECHNICAL
REQUIREMENTS AND AS NOTED ON THE DRAWINGS. HEAVY DUTY DRILL BITS MAY BE NEEDED TO
INSTALL PIERS TO FINAL BEARING ELEVATION AND SHOULD BE ANTICIPATED IN THE CONTRACT
PRICE. SEE GEOTECHNICAL REPORT FOR BORINGS.
2. HOLES SHOULD BE FILLED WITH CONCRETE WITHIN 12 HOURS OF BEING DRILLED. HOLES WILL NEED
TO BE CLEANED, REBAR CAGE INSTALLED, AND INSPECTED PRIOR TO PLACING CONCRETE.
3. REFER TO ACI 336.1 “SPECIFICATION FOR THE CONSTRUCTION OF DRILLED PIERS” FOR TOLERANCE
REQUIREMENTS.
4. DRILLED PIERS SHALL BEAR ON MACHINE CLEANED, INSPECTED SOIL STRATA. BOTTOM OF DRILLED
PIER ELEVATIONS NOTED ON THE DRAWINGS ARE APPROXIMATE AND ARE INCLUDED FOR BIDDING
PURPOSES ONLY. FINAL BEARING ELEVATIONS SHALL BE ADJUSTED SUCH THAT EACH DRILLED PIER
BEARS LEVEL AT BOTTOM OF SOCKET.
5. THE GEOTECHNICAL ENGINEER/TESTING LABORATORY SHALL VERIFY SHAFT DIAMETER, DEPTH,
BEARING STRATA, AND PROPER CLEANING OF INSTALLATION.
6. REBAR CAGE POSITION IN CENTER OF SHAFT SHALL BE HELD IN PLACE BY MEANS OF "WAGON
WHEEL" REBAR POSITIONERS OR EQUIVALENT.
7. CONTRACTOR TO DETERMINE THE NEED FOR REMOVABLE STEEL CASINGS TO MAINTAIN DRILLED
PIER SHAPE IN UNSTABLE SOIL STRATA AND INCLUDE COST IN THE CONTRACT PRICE.© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:32 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
GENERAL
STRUCTURAL
NOTES
S0.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELCONCRETE MIX DESIGNS
PLACEMENT LOCATION 28 DAY f'c
(psi)
MAX W/C
RATIO
ENTRAINED
AIR
MAX
AGGREGATE
SIZE
WEIGHT
FOOTINGS 3,500 0.55 6% ± 1.5% 1 1/2" NWC
DRILLED PIERS 3,000 0.55 6% ± 1.5% 1 1/2" NWC
FOUNDATION WALLS & RETAINING WALLS 4,500 0.45 6% ± 1.5% 1" NWC
TOPPING SLABS 4,000 0.55 — 3/4" NWC
SLAB ON METAL DECK 4,000 0.55 — 3/4" NWC
INTERIOR SLAB ON GRADE 4,000 0.45 — 3/4" NWC
EXTERIOR CONCRETE 5,000 0.40 6% ± 1.5% 3/4" NWC
POST-TENSIONED SLABS 5,000 0.45 — 3/4" NWC
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
STATEMENT OF SPECIAL INSPECTIONS
1. IN ACCORDANCE WITH IBC, SECTION 1704, THE OWNER'S REPRESENTATIVE SHALL EMPLOY ONE
OR MORE QUALIFIED SPECIAL INSPECTORS AND/OR TESTING AGENCIES TO PERFORM
STRUCTURAL TESTS AND SPECIAL INSPECTIONS ON THE TYPES OF WORK LISTED IN THE
STATEMENT OF SPECIAL INSPECTIONS.
2. THE DESIGNATED ENGINEER OF RECORD FOR SPECIAL INSPECTIONS SHALL BE RESPONSIBLE FOR
DEFINING THE ACTIVITIES OF THE INSPECTORS, FOR CERTIFYING THE QUALIFICATIONS OF THE
INSPECTORS WITH THE AHJ, AND TO ATTEND THE PRE-CONSTRUCTION MEETING TO DEFINE THEIR
SCOPE OF SERVICES AND THE TESTING OR TEST PROCEDURES THAT ARE REQUIRED AS OUTLINED
IN THE BUILDING CODE.
3. THE INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO VERIFY CONFORMANCE WITH THE
APPROVED CONTRACT DOCUMENTS.
4. THE INSPECTOR SHALL FURNISH DAILY INSPECTION REPORTS ON THE WORK TO THE OWNER'S
REPRESENTATIVE, AHJ AND ENGINEER. ALL DISCREPANCIES SHALL BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION, AND, IF UNCORRECTED, TO THE
ENGINEER AND THE AHJ.
5. THE DESIGNATED ENGINEER OF RECORD FOR SPECIAL INSPECTIONS SHALL COMPLETE, SIGN AND
SEAL A FINAL REPORT CERTIFYING THAT TO THE BEST OF THEIR KNOWLEDGE, THE WORK IS IN
CONFORMANCE WITH THE APPROVED CONTRACT DOCUMENTS.
6. SPECIAL INSPECTION IS TO BE PROVIDED IN ADDITION TO THE INSPECTIONS CONDUCTED BY THE
AHJ AND SHALL NOT BE CONSTRUED TO RELIEVE THE OWNER OR AUTHORIZED AGENT FROM
REQUESTING THE INSPECTIONS REQUIRED BY IBC SECTION 110.
7. CONTRACTOR RESPONSIBILITY: EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A
MAIN WIND- OR SEISMIC FORCE-RESISTING COMPONENT LISTED IN THE STATEMENT OF SPECIAL
INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE AHJ AND THE
OWNER'S REPRESENTATIVE ACKNOWLEDGING AWARENESS OF REQUIRED SPECIAL INSPECTIONS
PRIOR TO COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT.
8. CONCRETE: PER IBC SECTION 1705.3 AND TABLE 1705.3 WITH EXCEPTIONS. THE FOLLOWING ITEMS
REQUIRE SPECIAL INSPECTION: ALL CONCRETE, EXCEPT; SLAB-ON-GRADE, SIDE WALKS, AND
PAVEMENT.
9. STRUCTURAL MASONRY: MASONRY CONSTRUCTION SHALL BE INSPECTED AND VERIFIED IN
ACCORDANCE WITH TMS 402/602-16:
a. ENGINEERED MASONRY IN RISK CATEGORY I, II, OR III STRUCTURES: THE MINIMUM SPECIAL
INSPECTION PROGRAM FOR MASONRY SHALL COMPLY WITH LEVEL 2 QUALITY ASSURANCE,
TABLE 4.
10. STEEL CONSTRUCTION: SPECIAL INSPECTIONS FOR STRUCTURAL STEEL SHALL BE IN
ACCORDANCE WITH THE QUALITY ASSURANCE INSPECTION REQUIREMENTS OF AISC 360-16.
PROVIDE INSPECTION PER IBC SECTION 1704.2.5 FOR STRUCTURAL LOADING-BEARING MEMBERS
AND ASSEMBLIES FABRICATED ON THE PREMISES OF A FABRICATOR’S SHOP. THESE INSPECTIONS
SHALL BE AT CONTRACTOR'S EXPENSE IF THE FABRICATOR IS NOT AN APPROVED FABRICATOR
PER SECTION 1704.2.5.1.
11. WELDING: WELDING INSPECTION SHALL BE IN COMPLIANCE WITH AWS D1.1. THE BASIS FOR
WELDING INSPECTOR QUALIFICATIONS SHALL BE AWS D1.1. PROVIDE SPECIAL INSPECTION IN
ACCORDANCE WITH AISC 360-16 TABLE N5.4-1 THROUGH TABLE N5.4-3.
12. STEEL DETAILING: AN INSPECTION OF THE STEEL FRAME SHALL BE PERFORMED TO VERIFY
COMPLIANCE WITH THE DETAILS SHOWN ON THE APPROVED CONSTRUCTION DOCUMENTS, SUCH
AS BRACING, STIFFENING, MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT
EACH CONNECTION.
13. HIGH STRENGTH BOLTING: INSTALLATION OF HIGH STRENGTH BOLTS SHALL BE PERIODICALLY
INSPECTED IN ACCORDANCE WITH AISC SPECIFICATIONS. HIGH STRENGTH BOLTING. PROVIDE
SPECIAL INSPECTION IN ACCORDANCE WITH AISC 360-16 TABLE N5.6-1 THROUGH TABLE N5.6-3.
14. COLD-FORMED STEEL DECK: SPECIAL INSPECTION AND QUALIFICATION OF MATERIAL
VERIFICATION, WELDING AND MECHANICAL FASTENERS FOR COLD FORMED STEEL FLOOR AND
ROOF DECK SHALL BE IN ACCORDANCE WITH THE STEEL DECK INSTITUTE (SDI) QA/QC STANDARD.
15. GRADING, EXCAVATION AND FILLING: PER SECTION 1705.6 AND TABLE 1705.6.
16. PILING, DRILLED PIERS, AND CAISSONS: PER SECTION 1705.7 & 1705.8 AND TABLES 1705.7 & 1705.8.
17. SPRAY-APPLIED FIREPROOFING: PER SECTION 1705.14.
18. MASTIC AND INTUMESCENT FIRE RESISTING COATINGS: PER SECTION 1705.15.
19. FIRE-RESISTANT PENETRATIONS AND JOINTS: PER SECTION 1705.17.
20. SMOKE CONTROL: PER SECTION 1705.18.
21. EXPANSION BOLT, SCREW ANCHOR AND ADHESIVE ANCHORS: INSTALLATION TO VERIFY
INSTALLATION IN ACCORDANCE WITH ICC-ES REPORTS NOTED PREVIOUSLY OR APPROVED EQUAL.
22. HEADED CONCRETE SHEAR CONNECTORS: INSPECTED AND TESTED PER AMERICAN WELDING
SOCIETY CODE AWS D1.1.© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:36 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
GENERAL
STRUCTURAL
NOTES & SPECIAL
INSPECTIONS
S0.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL b. Specific requirements for special inspection shall be included in the research report for the anchor issued by an
approved source in accordance with 17.8.2 in ACI 318, or other qualification procedures. Where specific
requirements are not provided, special inspection requirements shall be specified by the registered design
professional and shall be approved by the building official prior to the commencement of the work.
a. Where applicable, see also Section 1705.12, Special inspections for seismic resistance.
12. Inspect formwork for shape, location and
dimensions of the concrete member being
formed.
— X
ACI 318:
26.11.1.2(b)—
11. Verify in-situ concrete strength, prior to stressing
of tendons in post-tensioned concrete and prior to
removal of shores and forms from beams and
structural slabs.
— X ACI 318: 26.11.2 —
10. Inspect erection of precast concrete members.— X ACI 318: 26.9 —
b. Grouting of bonded prestressing tendons.X — —
a. Application of prestressing forces; and X —ACI 318:
26.10
—
9. Inspect prestressed concrete for:
8. Verify maintenance of specified curing
temperature and techniques.— X
ACI 318:
26.5.3-26.5.5 1908.9
7. Inspect concrete and shotcrete placement for
proper application techniques.X — ACI 318: 26.5
1908.6, 1908.7,
1908.8
6. Prior to concrete placement, fabricate specimens
for strength tests, perform slump and air content
tests, and determine the temperature of the
concrete.
X —
ASTM C172
ASTM C31
ACI 318: 26.5,
26.12
1908.10
5. Verify use of required design mix.— X
ACI 318: Ch. 19,
26.4.3, 26.4.4
1904.1, 1904.2,
1908.2, 1908.3
b. Mechanical anchors and adhesive anchors
not defined in 4.a.— X ACI 318: 17.8.2 —
a. Adhesive anchors installed in horizontally or
upwardly inclined orientations to resist
sustained tension loads.
X —
ACI 318:
17.8.2.4 —
4. Inspect anchors post-installed in hardened
concrete members. (b)
3. Inspect anchors cast in concrete.— X ACI 318: 17.8.2 —
c. Inspect all other welds.X —
b. Inspect single-pass fillet welds, maximum
5/16"; and — X
a. Verify weldability of reinforcing bars other
than ASTM A706;— X
AWS D1.4
ACI 318: 26.6.4 —
2. Reinforcing bar welding:
1. Inspect reinforcement, including prestressing
tendons, and verify placement.— X
ACI 318: Ch. 20,
25.2, 25.3,
26.6.1-26.6.3
1908.4
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD (a)
IBC
REFERENCE
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
IBC — TABLE 1705.3
5. Prior to placement of compacted fill, inspect
subgrade and verify that site has been prepared
properly.
— X
4. Verify use of proper materials, densities and lift
thicknesses during placement and compaction of
compacted fill.
X —
3. Perform classification and testing of compacted
fill materials.— X
2. Verify excavations are extended to proper depth
and have reached proper material.— X
1. Verify materials below shallow foundations are
adequate to achieve the design bearing capacity.— X
TYPE CONTINUOUS PERIODIC
REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS
IBC — TABLE 1705.6
7. For specialty elements, perform additional
inspections as determined by the registered
design professional in responsible charge.
— —
6. For concrete elements and concrete-filled
elements, perform additional inspections in
accordance with Section 1705.3.
— —
5. For steel elements, perform additional inspections
in accordance with Section 1705.2.— —
4. Verify placement locations and plumbness,
confirm type and size of hammer, record number
of blows per foot of penetration, determine
required penetrations to achieve design capacity,
record tip and butt elevations and document any
damage to foundation element.
X —
3. Inspect driving operations and maintain complete
and accurate records for each element.X —
2. Determine capacities of test elements and
conduct additional load tests, as required.X —
1. Verify element materials, sizes and lengths
comply with the requirements.X —
TYPE CONTINUOUS PERIODIC
REQUIRED SPECIAL INSPECTIONS AND TESTS OF DRIVEN DEEP FOUNDATION ELEMENTS
IBC — TABLE 1705.7
3. For concrete elements, perform tests and
additional special inspections in accordance with
Section 1705.3.
— —
2. Verify placement locations and plumbness,
confirm element diameters, bell diameters (if
applicable), lengths, embedment into bedrock (if
applicable) and adequate end-bearing strata
capacity. Record concrete or grout volumes.
X —
1. Inspect drilling operations and maintain complete
and accurate records for each element.X —
TYPE CONTINUOUS PERIODIC
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
IBC — TABLE 1705.8
a. R = Required, NR = Not Required
During construction, verification of proportions of
materials as delivered to the project site for premixed or
preblended mortar, prestressing grout, and grout other
than self-consolidating grout.
NR NR R Art. 1.4B
During construction, verification of f'm and f'AAC for
every 5,000 square feet (465 square meters).NR NR R Art. 1.4B
During construction, verification of Slump flow and
Visual Stability Index (VSI) when self-consolidating
grout is delivered to the project site.
NR R R Art. 1.5 & 1.6.3
Prior to construction, verification of f'm and f'AAC,
except where specifically exempted by the Code.NR R R Art. 1.4B
Prior to construction, verification of compliance of
submittals.R R R Art. 1.5
LEVEL
1
LEVEL
2
LEVEL
3 TMS 602
MINIMUM VERIFICATION
REQUIRED FOR QUALITY
ASSURANCE (a)REFERENCE FOR CRITERIA
MINIMUM VERIFICATION REQUIREMENTS
TMS 402 / 602 — TABLE 3
c. Required after the first 5,000 square feet (465 square meters) of AAC masonry.
b. Required for the first 5,000 square feet (465 square meters) of AAC masonry.
NR = Not Required, P = Periodic C = Continuous
a. Frequency refer to the frequency of inspection, which may be continuous during the task listed or periodically
during the listed task, as defined in the table.
4. Observe preparation of grout specimens,
mortar specimens, and / or prisms
NR P C
Art. 1.4B.2.a.3,
1.4B.2.b.3,
1.4B.2.c.3,
1.4B.3 &
1.4B.4
i. Placement of AAC masonry units and
construction of thin-bed mortar joints NR C (b) /
P (c)C Art. 3.3B.9 &
3.3F.1.b
h. Placement of grout and prestressing grout for
bonded tendons is in compliance NR C C Art. 3.5 & 3.6C
g. Application and measurement of prestressing
force NR C C Art. 3.6B
f. Preparation, construction, and protection of
masonry during cold weather (temperature
below 40°F) or hot weather (temperature
above 90°F)
NR P P
Art. 1.8C &
1.8D
e. Welding of reinforcement NR C C Sec. 6.1.6.1.2
d. Type, size, and location of anchors, including
other details of anchorage of masonry to
structural members, frames, or other
construction
NR P C
Sec. 1.2.1(e),
6.2.1 & 6.3.1
c. Size and location of structural members NR P P Art. 3.3F
b. Placement of masonry units and mortar joint
construction NR P P Art. 3.3B
a. Materials and procedures with the approved
submittals NR P P Art. 1.5
3. Verify compliance of the following during
construction:
d. Proportions of site-prepared grout and
prestressing grout for bonded tendons NR P P
Art. 2.6B &
2.4G.1.b
c. Placement of reinforcement, connectors, and
anchor bolts NR P C Art. 3.2E & 3.4
b. Placement of prestressing tendons and
anchorages NR P P
Sec. 10.8 &
10.9 Art. 2.4 & 3.6
a. Grout Space NR P C
Art. 3.2D &
3.2F
2. Prior to grouting, verify that the following are in
compliance
f. Sample panel construction NR P C Art. 1.6D
e. Properties of thin-bed mortar for AAC
masonry NR C (b) /
P (c)C Art. 2.1C.1
d. Prestressing technique NR P P Art. 3.6B
c. Grade, type, and size of reinforcement,
connectors, anchor bolts, and prestressing
tendons and anchorages
NR P P Art. 3.4 & 3.6A
b. Grade and size of prestressing tendons and
anchorages NR P P
Art. 2.4B &
2.4H
a. Proportions of site-prepared mortar NR P P
Art. 2.1, 2.6A,
& 2.6C
1. As masonry construction begins, verify that the
following are in compliance:
LEVEL
1
LEVEL
2
LEVEL
3 TMS 402 TMS 602
INSPECTION TASK
FREQUENCY (a) REFERENCE FOR CRITERIA
MINIMUM SPECIAL INSPECTION
TMS 402 / 602 — TABLE 4
P - Perform these tasks for each welded joint or member.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
[a] The fabricator or erector, as applicable, shall maintain a system by which a welder who has welded a joint or
member can be identified. Stamps, if used, shall be the low-stress type.
Check welding equipment O —
• Tacking (tack weld quality and location)
• Cleanliness (condition of steel surfaces)
• Dimensions (alignment, gaps at root)
Fit-up of fillet welds
O O
Configuration and finish of access holes O O
• Tacking (tack weld quality and location)
• Cleanliness (condition of steel surfaces)
• Dimensions (alignment, root opening, root face, bevel)
• Joint preparations
Fit-up of CJP groove welds of HSS T-, Y- and K-joints without backing (including joint
geometry)
P O
• Backing type and fit (if applicable)
• Tacking (tack weld quality and location)
• Cleanliness (condition of steel surfaces)
• Dimensions (alignment, root opening, root face, bevel)
• Joint preparations
Fit-up of groove welds (including joint geometry)
O O
Welder identification system [a]O O
Material identification (type / grade)O O
Manufacturer certifications for welding consumables available P P
Welding procedure specifications (WPS) available P P
Welder qualification records and continuity records P O
INSPECTION TASKS PRIOR TO WELDING QC QA
INSPECTION TASKS PRIOR TO WELDING
AISC 360 — TABLE N5.4-1
P - Perform these tasks for each welded joint or member.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
Placement and installation of steel headed stud anchors P P
• Each pass meets quality requirements
• Each pass within profile limitations
• Interpass and final cleaning
Welding techniques
O O
• Proper position (F, V, H, OH)
• Interpass temperature maintained (min. / max.)
• Preheat applied
• Shielding gas type / flow rate
• Selected welding materials
• Travel Speed
• Settings on welding equipment
WPS Followed
O O
• Precipitation and temperature
• Wind speed within limits
Environmental conditions
O O
No welding over cracked tack welds O O
• Exposure Control
• Packaging
Control and handling of welding consumables
O O
INSPECTION TASKS DURING WELDING QC QA
INSPECTION TASKS DURING WELDING
AISC 360 — TABLE N5.4-2
P - Perform these tasks for each welded joint or member.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
[b] After rolled heavy shapes (see Section A3.1c) and built-up heavy shapes (see Section A3.1d) are welded, visually
inspect the weld access hole for cracks.
[a] When welding of doubler plates, continuity plates or stiffeners has been performed in the k-area, visually inspect
the web k-area for cracks within 3 inches (75 mm) of the weld.
No prohibited welds have been added without the approval of the EOR O O
Document acceptance or rejection of welded joint or member P P
Repair activities P P
Backing removed and weld tabs removed (if required)P P
Weld access holes in rolled heavy shapes and build-up heavy shapes [b]P P
k-area [a]P P
Arc strikes P P
• Porosity
• Undercut
• Weld size
• Weld profiles
• Crater cross section
• Weld / base-metal fusion
• Crack prohibition
Welds meet visual acceptance criteria
P P
Size, length and location of welds P P
Welds cleaned O O
INSPECTION TASKS AFTER WELDING QC QA
INSPECTION TASKS AFTER WELDING
AISC 360 — TABLE N5.4-3
P - Perform these tasks for each bolted connection.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
Proper storage provided for bolts, nuts, washers, and other fastener components O O
Pre-installation verification testing by installation personnel observed and documented for
fastener assemblies and methods used P O
Connecting elements, including the appropriate faying surface condition and hole
preparation, if specified, meet applicable requirements O O
Proper bolting procedure selected for joint detail O O
Proper fasteners selected for the joint detail (grade, type, bolt length if threads are to be
excluded from shear plane)O O
Fasteners marked in accordance with ASTM requirements O O
Manufacturer's certifications available for fastener materials O P
INSPECTION TASKS PRIOR TO BOLTING QC QA
INSPECTION TASKS PRIOR TO BOLTING
AISC 360 — TABLE N5.6-1
P - Perform these tasks for each bolted connection.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
Fasteners are pretensioned in accordance with the RCSC Specification, progressing
systematically from the most rigid point toward the free edges O O
Fastener component not turned by the wrench prevented from rotating O O
Joint brought to the snug-tight condition prior to the pretensioning operation O O
Fastener assemblies placed in all holes and washers and nuts are positioned as required O O
INSPECTION TASKS DURING BOLTING QC QA
INSPECTION TASKS DURING BOLTING
AISC 360 — TABLE N5.6-2
P - Perform these tasks for each bolted connection.
O - Observe these items on a random basis. Operations need not be delayed pending these inspections.
Document acceptance or rejection of bolted connections P P
INSPECTION TASKS AFTER BOLTING QC QA
INSPECTION TASKS AFTER BOLTING
AISC 360 — TABLE N5.6-3
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
B.Document acceptance or rejection of deck and deck accessories P P
A.Verify complaiance of materials (deck and all deck accessories) with construction
documents, including profiles, material properties, and base metal thickness P P
TASK QC QA
INSPECTION OR EXECUTION TASKS PRIOR TO DECK PLACEMENT
ANSI / SDI QA/QC— TABLE 1.1
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
C.Document acceptance or rejection of installation of deck and deck accessories P P
B.Verify deck materials are represented by the mill certifications that comply with the
construction documents N/A P
A.Verify complaiance of deck and all deck accessories installation with construction
documents P P
TASK QC QA
INSPECTION OR EXECUTION TASKS AFTER DECK PLACEMENT
ANSI / SDI QA/QC— TABLE 1.2
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
D.Check welding equipment O O
C.Meterial identification (type / grade)O O
B.Manufacturer certifications for welding consumables available O O
A.Welding procedure specifications (WPS) available O O
TASK QC QA
INSPECTION OR EXECUTION TASKS PRIOR TO WELDING
ANSI / SDI QA/QC— TABLE 1.3
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
D. WPS followed O O
C. Environmental conditions (wind speed, moisture, temperature) O O
B. Control and handling of welding consumables O O
A.Use of qualified welders.O O
TASK QC QA
INSPECTION OR EXECUTION TASKS DURING WELDING
ANSI / SDI QA/QC— TABLE 1.4
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
D.Document acceptance or rejection of welds P P
C.Verify repair activities P P
B.Welds meet visual acceptance criteria P P
A.Verify size and location of welds, including support, sidelap, and perimeter welds P P
TASK QC QA
INSPECTION OR EXECUTION TASKS AFTER WELDING
ANSI / SDI QA/QC— TABLE 1.5
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
C.Proper storage for mechanical fasteners O O
B.Proper tools available for fastener installation O O
A.Manufacturer installation instructions available for mechanical fasteners O O
TASK QC QA
INSPECTION OR EXECUTION TASKS PRIOR TO MECHANICAL FASTENING
ANSI / SDI QA/QC— TABLE 1.6
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
B.Fasteners are installed in accordance with manufacturer's instructions O O
A.Fasteners are positioned as required O O
TASK QC QA
INSPECTION OR EXECUTION TASKS DURING MECHANICAL FASTENING
ANSI / SDI QA/QC— TABLE 1.7
P - Perform these tasks prior to final acceptance for each item or element.
O - Observe these items on an intermittent basis. Operations need not be delayed pending these inspections.
E.Document acceptance or rejection on mechanical fasteners P P
D.Verify repair activities P P
C.Check spacing, type, and installation of perimeter fasteners P P
B.Check spacing, type, and installation of sidelap fasteners P P
A.Check spacing, type, and installation of support fasteners P P
TASK QC QA
INSPECTION OR EXECUTION TASKS AFTER MECHANICAL FASTENING
ANSI / SDI QA/QC— TABLE 1.8
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
GENERAL STRUCTURAL NOTES
A. STRUCTURAL GENERAL NOTES APPLY TO ALL SHEETS.
B. STRUCTURAL ELEVATION 0' - 0" = ARCHITECTURAL ELEVATION
0' - 0". REFERENCE CIVIL DRAWINGS FOR SITE SURVEY
ELEVATIONS.
C. ELEVATIONS ARE REFERENCED FROM DATUM ELEVATION AND
ARE SHOWN THUS #' - #", -#' - #".
D. SEE ARCHITECTURAL DRAWINGS FOR LAYOUT AND
DIMENSIONS NOT SHOWN.
E. SEE CIVIL, LANDSCAPE, AND ARCHITECTURAL DRAWINGS FOR
SIDEWALKS, PAVING AND SITE DETAILS NOT SHOWN ON
STRUCTURAL DRAWINGS.
F. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND
EXTENTS OF SPECIAL FINISHES OR TREATMENTS TO EXPOSED
CONCRETE.
G. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND
EXTENTS OF FLOOR AND ROOF SLOPES, ELEVATION CHANGES,
THICKENED SLABS, RECESSES, RAISES AND DEPRESSIONS.
H. SEE ARCHITECTURAL DRAWINGS FOR FIREPROOFING
REQUIREMENTS.
I. LINTELS ARE REQUIRED AT ALL MASONRY WALL OPENINGS,
WHETHER INDICATED ON STRUCTURAL PLANS OR NOT.
LINTELS NOT INDICATED ON STRUCTURAL PLANS ARE TO BE
SIZED BASED ON WIDTH OF OPENING PER LINTEL TABLE. SEE
ARCHITECTURAL DRAWINGS FOR BOTTOM OF LINTEL
ELEVATIONS.
J. SEE ARCHITECTURAL DRAWINGS FOR MISCELLANEOUS STEEL
NOT SHOWN ON STRUCTURAL DRAWINGS, INCLUDING BUT NOT
LIMITED TO STEEL AT ROOF DRAINS, INSERTS, EMBEDDED
ITEMS AND STEEL ASSOCIATED WITH ARCHITECTURAL DETAILS.
K. SEE MEP AND ARCHITECTURAL DRAWINGS FOR LOCATIONS
AND SIZES OF EQUIPMENT PADS AND SUPPORTS.
L. SEE ARCHITECTURAL AND MEP DRAWINGS FOR SLAB AND
ROOF PENETRATIONS, WHETHER INDICATED ON STRUCTURAL
DRAWINGS OR NOT.
M. SEE MEP AND OTHER SPECIALTY DRAWINGS FOR THE
FOLLOWING, WHETHER INDICATED ON STRUCTURAL
DRAWINGS OR NOT:
a. SUMPS
b. PIPE RUNS, SLEEVES, HANGERS, AND TRENCHES.
c. CONDUIT RUNS, BOXES, AND OUTLETS.
d. EMBEDS, ANCHORAGE AND BRACING FOR EQUIPMENT,
DUCTS, PIPING, ETC.
N. EQUIPMENT SIZES, LOCATIONS AND WEIGHTS INDICATED ON
STRUCTURAL DRAWINGS ARE SCHEMATIC AND SUBJECT TO
CHANGE. COORDINATE FINAL SELECTION AND PLACEMENT
WITH CERTIFIED EQUIPMENT MANUFACTURER DRAWINGS.
NOTIFY ENGINEER IF FINAL SELECTION DIFFERS FROM THOSE
INDICATED.
CONCRETE
PRECAST CONCRETE
STEEL
CONCRETE MASONRY
UNIT
BRICK VENEER
PLYWOOD
(LARGE SCALE)
GEOFOAM
GROUT
ISOLATION JOINT /
EXPANSION JOINT
EARTH
GRAVEL
SAND
STONE
RIGID INSULATION
STRUCTURAL HATCHES
(E) STRUCTURAL
ELEMENT
DEEP FOUNDATION SYMBOLS
(-2' - 0")
DP36
CONCRETE COLUMN
DRILLED PIER TYPE MARK
(W/ TOP OF PIER CAP
ELEVATION INDICATOR)
PC60
C12B COLUMN TYPE MARK
PIER CAP TYPE MARK
GRADE BEAM
STRUCTURAL WALLCW12
GB3.0
GRADE BEAM TYPE MARK
(W/ TOC INDICATOR)
WALL TYPE MARK
(-0' - 8")
DRILLED PIER
PIER CAP
(TWE -1' - 0")MISCELLANOUS ELEVATION
(W/ INDICATOR PREFIX)
FOUNDATION SYMBOLS
WF3.0 WALL FOOTING
FOOTING STEP
FOOTING TYPE MARK
(W/ TOF INDICATOR)S(-3' -0")(-4' -0")STRUCTURAL WALLCW12
WALL TYPE MARK
(-4' - 0")ISOLATED COLUMN FOOTING
HSS4X4X1/4
(-3' - 0")
COLUMN SIZE
P18
F5.0
PEDESTAL TYPE MARK
FOOTING TYPE MARK
(W/ TOF INDICATOR)
PEDESTAL
COLUMN
BPX BASE PLATE TYPE MARK
(TPE -1' - 0")MISCELLANEOUS ELEVATION
(W/ INDICATOR PREFIX)
SLAB & DECK SYMBOLS
STRUCTURAL FLOOR TYPE INDICATOR & SPAN
DIRECTION
(W/ TOP OF SLAB ELEVATION INDICATOR)
STRUCTURAL ROOF TYPE INDICATOR & SPAN DIRECTION
(LETTER BELOW INDICATES DECK ATTACHMENT TYPE,
IF APPLICABLE)
ROOF OR FLOOR PENETRATION
STRUCTURAL WALL BELOW
8"TOP OF SLAB ELEVATION CHANGE (W/ STEP DIMENSION)
TOP OF SLAB SLOPED (SLOPED UP OR SLOPED DOWN)
SF#
(13' - 6")
SR#
A
SG#SLAB ON GRADE TYPE INDICATOR
(W/ TOP OF SLAB ELEVATION INDICATOR)
(0' -0")
SUPPLEMENTAL SLAB REINFORCEMENT
(REINFORCEMENT SIZE & EXTENTS PER PLAN)
BEAM SYMBOLS
SIZE
W16X40 [30] c=1"
CAMBER
10K
FACTORED LRFD AXIAL FORCE
AT COLLECTOR (IF OCCURS)
NUMBER OF HEADED STUDS
[#] NUMBER OF HS EQUALLY SPACED
[#-#-#] INDICATES NUMBER OF HS BETWEEN BEAMS
SEE "FRAMING
SYMBOLS" FOR
SPECIAL END
CONDITIONS
BRACED FRAME,
SEE ELEVATIONS
5KFT
FACTORED LRFD END
MOMENT (IF OCCURS)
( 14'-0" )
TOS ELEVATION INDICATOR
FACTORED LRFD VERTICAL
SHEAR END REACTION
(IF OCCURS)10K
FRAMING SYMBOLS
STEEL BEAM CONT OVER TOP OF HSS COLUMN
STEEL BEAM TO STEEL BEAM MOMENT CONN
WF BEAM TO CONCRETE WALL COLLECTOR CONN
STEEL ANGLE KICKER (DIAGONAL) BRACE
'x' INDICATES CONN POINT TO STRUCTURE
STEEL BEAM TO HSS COLUMN COLLECTOR CONN
STEEL BEAM TO WF COLUMN SHEAR CONN
STEEL BEAM TO STEEL BEAM SHEAR CONN
STEEL BEAM TO WF COLUMN MOMENT CONN
S STAIR STRINGER CONN TO STRUCTURE
(SCHEMATIC ONLY; DELEGATED DESIGN)
STEEL BEAM TO STEEL BEAM COLLECTOR CONN
ML#MASONRY WALL LINTEL
(MLX INDICATES MASONRY LINTEL
PLX INDICATES PRECAST LINTEL
(W/ BOTTOM OF LINTEL ELEVATION INDICATOR)
JOIST BEARING SEAT HEIGHT
(ONE OR BOTH ENDS)
STEEL BEAM TO HSS COLUMN SHEAR CONN
5" BS
5" BS
WF BEAM TO CONCRETE WALL EMBED CONN
(W/ EMBED PLATE TYPE MARK IF OCCURS)
WF BEAM TO PRECAST WALL EMBED CONN
(W/ EMBED PLATE TYPE MARK IF OCCURS)
STEEL BEAM TO STEEL BEAM SHEAR SPLICE CONN
MASONRY EDGE STIFFENER
(TAG INDICATES # OF BARS -BAR SIZE -# OF CELLS)
WF BEAM TO MASONRY WALL COLLECTOR CONN
STEEL BEAM TO HSS COLUMN MOMENT CONN
OR CANTILEVERED BEAM CONN
EXTENTS OF NON-TYPICAL VERTICAL MASONRY
WALL REINFORCEMENT
WF BEAM ROTATED 90° DEGREES
(PLACED NEXT TO BEAM SIZE TAG)
#5 AT 16" OC
CONCRETE SLAB REINFORCEMENT BAR TYPE, # OF
BARS & EXTENTS
SOLID LINE INDICATES TOP BARS
DASHED LINE INDICATES BOTTOM BARS
BARS SHOWN W/ 180°, 135°, OR 90° HOOKS (IF OCCURS)
(12) #6 x 14'-0"
CONCRETE WALL CONTROL JOINTCJ
(BOL 8' -0")
WF BEAM OR JOIST BEARING PL AT MASONRY WALL
(W/ BEARING PLATE TYPE MARK IF OCCURS)
EP#
EP#
BPL#
STEEL BEAM CONT OVER TOP OF WF COLUMN
STEEL BEAM TO WF COLUMN COLLECTOR CONN
ES 4-#6-2
MASONRY WALL TYPE MARK MW#
CONCRETE WALL TYPE MARKCW#
W16X40
CJ MASONRY WALL CONTROL JOINT
COLUMN
HELICAL PILE
PILE CAP
COLUMN
CONCRETE OR TIMBER PILE
PILE CAP © DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:38 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
GENERAL
STRUCTURAL
NOTES, SYMBOLS
AND
ABBREVIATIONS
S0.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODEL# REINFORCING BAR SIZE, SHEET METAL SCREW SIZE
@ AT (SPACING)
Ø DIAMETER
AB ANCHOR BOLT
ABC AGGREGATE BASE COURSE
ADDL ADDITIONAL
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANCH ANCHOR
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
B/ BOTTOM OF
BDE BOTTOM OF DECK ELEVATION
BLDG BUILDING
BLKG BLOCKING
BM(S) BEAM(S)
BOF BOTTOM OF FOOTING
BOL BOTTOM OF LINTEL
BOS BOTTOM OF STEEL
BOT BOTTOM
BRBF BUCKLING RESTRAINED BRACE FRAME
BRDG BRIDGING
BRG BEARING
BTWN BETWEEN
C CHANNEL
CANT CANTILEVER
CFMF COLD-FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPOSITE
CONC CONCRETE
CONN(S) CONNECTION(S)
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACT(OR)
CSTJ CONSTRUCTION JOINT
CTR CENTER
CY CUBIC YARD
(D) DEMOLISH
db BAR DIAMETER
DBA DEFORMED BAR ANCHOR
DCW DEMAND CRITICAL WELD
DEG DEGREE
DEPR DEPRESS(ION)(ED)
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DT PRESTRESSED PRECAST DOUBLE TEE
DTL DETAIL
DWA DEFORMED WIRE ANCHOR
DWG(S) DRAWING(S)
DWL(S) DOWEL(S)
(E) EXISTING
EA EACH
EBF ECCENTRICALLY BRACED FRAME
EBOF EXISTING BOTTOM OF FOOTING
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EN EDGE NALING
EOD EDGE OF DECK
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ETOF EXISTING TOP OF FOOTING
EW EACH WAY
EWP ENGINEERED WOOD PRODUCT
EXP EXPANSION
EXT EXTERIOR
F'c 28 DAY CONCRETE STRENGTH
f'c MINIMUM CONCRETE COMPRESSIVE STRENGTH AT 28 DAYS
f'm SPECIFIED COMPRESSIVE STRENGTH OF MASONRY
FA FACE
FAB FABRICATE(D)
FD FLOOR DRAIN
FDN FOUNDATION
FRT FIRE RESISTANCE TREATED
FS FAR SIDE
FT FEET
FTG FOOTING
FV FIELD VERIFY
FY YIELD STRENGTH
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GEN GENERAL
GLB GLUE LAMINATED BEAM
GR GRADE
H HEIGHT
HC HOLLOW CORE
HDR HEADER
HGR HANGER
HORIZ HORIZONTAL
HS HEADED STUD
HSA HEAD STUD ANCHOR
HSS HOLLOW STRUCTURAL SHAPE
ID INSIDE DIAMETER
IF INSIDE FACE
IMF INTERMEDIATE MOMENT FRAME
IN INCH
INC INCLUDE(ING)
INT INTERIOR
JBE JOIST BEARING ELEVATION
JST JOIST
JT JOINT
k KIPS
KSF KIPS PER SQUARE FOOT
L ANGLE
LB(S) POUND(S)
Ld REINFORCING BAR DEVELOPMENT LENGTH
Ldh HOOKED REINFORCING BAR DEVELOPMENT LENGTH
LF LINEAR FOOT
LFRS LINEAR FOOT RESISTING SYSTEM
LIN LINEAR
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LENGTH HORIZONTAL
LLV LONG LENGTH VERTICAL
LONG LONGITUDINAL
Ls REINFORCING BAR LAP SPLICE LENGTH
LSH LONG SLOTTED HOLE
LV LAMINATED VENEER LUMBER
LW LONG WAY
LWC LIGHT WEIGHT CONCRETE
ABBREVIATIONS
MAS MASONRY
MAX MAXIMUM
MC MOMENT CONNECTION
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
MWFRS MAIN WIND FORCE RESISTING SYSTEM
(N) NEW
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OCBF ORDINARY CONCENTRICALLY BRACED FRAME
OCCS ORDINARY CANTILEVER COLUMN SYSTEM
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OH OPPOSITE HAND
OMF ORDINARY MOMENT FRAME
OPG(S) OPENING(S)
OPP OPPOSITE
OWJ OPEN WEB JOIST
PAF POWDER ACTUACTED FASTENER
PC PRECAST CONCRETE, PILE CAP
PCBE PRECAST CONCRETE BEARING ELEVATION
PCF POUNDS PER CUBIC FOOT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PROJ PROJECT(OR) (ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POST-TENSION(ED)(ING)
PTW PRESERVATIVE TREATED WOOD
RAD RADIUS
RC REINFORCED CONCRETE
REF REFERENCE
REINF REINFORCEMENT
REQ(D) REQUIRE(D)
REV REVISION(S)
RTU ROOF TOP UNIT
SC SHEAR CONNECTOR(S)
SCBF SPECIAL CONCENTRICALLY BRACED FRAME
SCCS SPECIAL CANTILEVER COLUMN SYSTEM
SCHED SCHEDULE
SDL SUPERIMPOSED DEAD LOAD
SDS SELF-DRILLING SCREWS
SECT SECTION
SF SQUARE FEET
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SIM SIMILAR
SL SNOW LOAD
SLBB SHORT LEG BACK TO BACK
SMF SPECIAL MOMENT FRAME
SOG SLAB ON GRADE/GROUND
SPA SPACE (ING)
SPEC SPECIFICATION(S)
SQ SQUARE
SSH SHORT SLOTTED HOLE
SST STAINLESS STEEL
STAG'D STAGGERED
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMETRICAL
t PLATE THICKNESS
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T.O. TOP OF
T/ TOP OF
TC TENSION CONTROL
TCW TOP OF CONCRETE WALL
TEMP TEMPORARY
THRD THREADED
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TPE TOP OF PIER ELEVATION
TRANS TRANSVERSE
TSE TOP OF SLAB ELEVATION
TWE TOP OF WALL ELEVATION
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VFY VERIFY
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WFRS WIND FORCE RESISTING SYSTEM
WGT WIEGHT
WHA WATER HAMMER ARRESTOR
WP WORK POINT
WPS WELDING PROCEDURE SPECIFICATION
WT STEEL TEE SECTION
WWR WELDED WIRE REINFORCEMENT
X-STR EXTRA STRONG
XX-STR DOUBLE EXTRA STRONG
YD YARD
ZRC ZINC RICH COATING
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
PN Q RMLK
1
2
3
4
JHGFEDC
3.4
2.2
2.8
1.6
0.3
0.2
0.1
J.5C.3
3.8
6' - 6" 13' - 6"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0" 8' - 6" 11' - 6" 20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"9' - 0"9' - 0"2' - 0"15' - 0"10' - 0"5' - 0"15' - 0"5' - 0"10' - 0"10' - 0"5' - 0"4' - 4"2' - 0"9' - 8"GB2.0
GB2.0 GB2.0GB2.0GB2.0GB2.0
GB2.0
GB2.0GB2.0
GB2.0GB2.0
GB2.0 PC2PC1PC1PC1PC1PC1PC1HSS12X12X5/8HSS12X12X5/8HSS12X12X5/8HSS12X12X5/8HSS12X12X5/8HSS12X12X5/8HSS16x16x1/2PC2HSS16x16x1/2HSS6X6X3/8HSS6X6X3/8HSS3x3x1/41A
S3.1
TYP
1B
S3.1
1C
S3.1
TYP
2F
S3.1
TYP
1D
S3.1
STOOP
1A
S4.1
TYP
S4.1
1C
TYP
S4.1
1E
TYP
TYP
S4.1
1DHSS8X8X3/8© DLR GroupREVISIONS
KEY PLAN -NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 7:48:39 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
FOUNDATION
PLAN
S1.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FOUNDATION PLAN
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
PN Q RMLK
1
2
3
4
JHGFEDC
3.4
2.2
2.8
1.6
0.3
0.2
0.1
6' - 6" 13' - 6"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0" 8' - 6" 11' - 6" 20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"
J.5
6' - 0"9' - 6"8' - 0" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 0" 7' - 0" 6' - 0"
W27X84 [34]W18X35 [17]W18X35 [17]W18X35 [17]W18X35 [17]W18X35 [17]W18X35 [6,3,6]
W16X31 [3,3,3,1]W18X35 [16,3]W10X19 [10]W10X19 [10]W10X19 [10]W14X22 [10]W14X22 [10]W14X22 [10]W14X22 [10]W18X35 [16]W18X35 [16]W14X22 [10]W27X84 [32]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]W18X35 [16]6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8" 6' - 8"
1' - 6"
4' - 0" 4' - 6" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 4' - 6" 4' - 6"W18X50W18X50W18X40
TOS 18' - 0"
W18X40
TOS 18' - 4 1/2"
W18X40
TOS 18' - 4 1/2"
W18X40
TOS 18' - 0"W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X19W10X22TOS 18' - 0"W24X62 [32]
TOS 18' - 0"
W24X62 [32]
TOS 18' - 0"W10X22 [10]TOS 18' - 0"W12x35 [5,5]TOS 18' - 0"W12X26 [6,7]TOS 18' - 0"W10X22 [10]TOS 18' - 0"W10X22 [10]TOS 18' - 0"W10X22 [10]TOS 18' - 0"W12X26
TOS 15' - 7"
W12X26 [3]
TOS 18' - 0"
W12X26 [3]
TOS 18' - 0"W12X26 [5]TOS 18' - 0"W12X26 [4]
TOS 18' - 0"W10X22W10X19W12x35TOS 15' - 7"9' - 0"9' - 0"2' - 0"15' - 0"10' - 0"5' - 0"15' - 0"5' - 0"10' - 0"10' - 0"5' - 0"W18X35 [17]6" EOD
C.3
3.8W18X35 [16]W10X22 [4]W10X22 [3]4" EOD
6" EOD 6" EODW18X35 W18X35W18X3510"3' - 11"HSS6x4x3/16
2' - 6" 8' - 6"4' - 9"EXISTING STEEL FRAMING
TO REMAIN4' - 6"STAIR, RAILING,
AND LANDING BY
STAIR DESIGNER
STAIR, RAILING,
AND LANDING BY
STAIR DESIGNER
4" EOD4" EOD4" EOD
4" EOD
4" EOD
SF1
SF1 SR1
SR1OPENEXISTING STEEL FRAMING
TO REMAIN
W10X19
TOS 18' - 2 1/2"
W10X19
TOS 18' - 2 1/2"
W10X19
TOS 18' - 2 1/4"
W10X19
TOS 18' - 2 1/2"ML2ML2 ML2 ML2STAIR, RAILING, AND LANDING BY STAIR DESIGNER1A
S4.1
TYP
S4.1
1E
S4.1
1D
TYP
TYP
2A
S4.1
TYP
2B
S4.1
TYP
3A
S4.1
2F
S4.1
TYP
S5.1
2A
TYP
2' - 0"2C
S5.1
TYP
2D
S5.1
TYP
TYP
1E
S5.1
1F
S5.1
TYP
A
S5.1
4A
TYP
2' - 0"
1C
S5.2
1C
S5.2
TYP
TYP
B
A
1E
S5.2
TYP
EOD
4"
EOD
8"EOD4"12
S5.2
2B
S5.2
TYP
2A
S5.2
TYP
2B
S5.2
TYP
2C
S5.2
2C
S5.2
3A
S5.2
TYP
3C
S5.2
TYP
3B
S5.2
TYP
3D
S5.2 W10X19(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BRG)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BRG)(AT DECK BRG)(AT DECK BRG)(AT DECK BRG)(AT DECK BRG)© DLR GroupREVISIONS
KEY PLAN -NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
OFFICE
DECK/CANOPY
1/13/2023 7:48:41 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 2 -
FRAMING PLAN
S1.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
FRAMING PLAN
FLOOR FRAMING PLAN NOTES:
1. SF1 IS 3" NW CONCRETE REINFORCED WITH 6x6 - W2.9xW2.9 WWR
ON 2" x 20 GA COMPOSITE METAL DECK (5" OVERALL).
2. SR1 IS 1 1/2" 20 GA TYPE B METAL DECK.
3. TOP OF SLAB ELEVATION AT SECOND LEVEL = 16' - 0" TYP, UNO.
4. TOP OF STEEL ELEVATION AT SECOND LEVEL = 15' - 7" TYP, UNO.
5. DO NOT CUT CONTROL JOINTS IN ELEVATED SLABS.
6. FOR ELEVATIONS, WALL SECTIONS, AND DIMENSIONS NOT SHOWN,
SEE ARCHITECTURAL DRAWINGS.
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
PN Q RMLK
1
2
3
4
JHGFEDC
3.4
2.2
2.8
1.6
0.3
0.2
0.1
J.5
6' - 6"13' - 6"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"8' - 6"11' - 6"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"20' - 0"
5' - 9"5' - 9"5' - 0"5' - 0"5' - 0"5' - 0"5' - 0"5' - 0"5' - 0"5' - 0"W12x35W18X50
TOS 28' - 6"
W18X50
TOS 28' - 10 1/2"W10X22W12x35W10X22W10X22W10X22W10X22W10X22W10X22W12X26
TOS 28' - 10 1/2"W12x35W12X26
TOS 28' - 6"W10X22C.3
3.8
6" EOD 6" EOD6" EOD
6" EOD9' - 0"9' - 0"2' - 0"15' - 0"10' - 0"5' - 0"15' - 0"5' - 0"10' - 0"10' - 0"5' - 0"SR1
S5.1
2A
TYP
1F
S5.1
A
TYP
2C
S5.1
TYP
2D
S5.1
TYP
S5.1
4A
TYP(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)(AT DECK BEARING)© DLR GroupREVISIONS
KEY PLAN -NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
DECK/CANOPY
1/13/2023 7:48:41 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
LEVEL 3 -ROOF
FRAMING PLAN
S1.3485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNSCALE:1/8" = 1'-0"
ROOF FRAMING PLAN
ROOF FRAMING PLAN NOTES:
1. SR1 IS 1 1/2" 20 GA TYPE B METAL DECK.
2. FOR ELEVATIONS, WALL SECTIONS, AND DIMENSIONS NOT SHOWN,
SEE ARCHITECTURAL DRAWINGS.
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
CL CL
CLCL
STEEL COLUMN AND BASE
PLATE - SEE PLAN AND
SCHEDULE (PROVIDE 1 5/16"Ø
HOLES IN BASE PLATE)
4 - 3/4"Ø THREADED RODS UNO.
LOCATE RODS 2" FROM EDGE OF
BASE PLATE, UNO.
ADHESIVE ANCHOR WITH 8" MIN
EMBEDMENT. LOCATE TO MISS
EXISTING SLAB REINFORCEMENT.
PLATE WASHER 5/16 x 2 1/2 x 2 1/2
WITH 13/16"Ø HOLES
SHIM PACKS AS REQUIRED
(AT STEEL HSS COLUMN)
FIN FL EL
SEE PLANSUNOPROJ. 5 1/2"NON-SHRINK GROUT
2"COAT STEEL BELOW GRADE
WITH COLD-APPLIED ASPHALT
EMULSION PER ASTM D1187
1/4
3/16 1 1/24 SIDES
EXISTING CONCRETE SLAB
FOR PIPES IN THIS AREA, LOWER
ENTIRE FOOTING TO ALLOW PIPE
TO EXTEND THRU WALL
PROVIDE SLEEVE 2" (NOMINAL)
LARGER THAN PIPE OUTSIDE
DIAMETER
PIPE OR CONDUIT
PERPENDICULAR TO
FOOTING
AREA OKAY FOR PIPE SLEEVE
FOR PIPES IN THIS AREA, LOWER
BOTTOM OF FOOTING TO ALLOW
PIPE TO EXTEND THRU FOOTING
PIPE OR CONDUIT
PERPENDICULAR TO FOOTING
PROVIDE SLEEVE 2" (NOMINAL)
LARGER THAN PIPE OUTSIDE
DIAMETER
NOTES:
1. FOR PIPES 3'-0" OR LESS BELOW FOOTING, PROVIDE SLEEVE AS SHOWN.
2. FOR PIPES AND CONDUITS MORE THAN 3'-0" BELOW FOOTING, PIPE SLEEVE MAY BE ELIMINATED.
3. COORDINATE WITH MECHANICAL, ELECTRICAL, AND ALL OTHER EFFECTED TRADES.
WALL WIDTH
FOOTING DEPTH1' - 8"6"6"FOOTING WIDTH1' - 0"1' - 0"MAX 3' - 0"(PERPENDICULAR TO FOOTING)
GROUND LINE
TRENCH EXCAVATION
BOTTOM OF EXCAVATION SHALL
NOT EXTEND BELOW THIS LINE
NOTE:
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING, SHEATHING, OR OTHERWISE
MAINTAINING THE SIDES OF THE EXCAVATION FROM CAVE-IN AND OTHER HAZARDS UNTIL
ALL BACKFILL IS COMPLETED. BACKFILL AS PER SPECIFICATIONS.
(PARALLEL TO FOOTING)SPECIFICATIONSBEDDING PERWIDTH
FOOTING
AT RETAINING WALLS
1' - 6"
MIN EXCEPT 5' - 0"
1 1/2
1
2
1
WIDTH
WALL
VERTICAL MASONRY WALL
REINFORCING, SEE PLANS
AND STRUCTURAL NOTES
CMU
DOWELS TO MATCH
VERTICAL WALL REINFORCING,
ADHESIVE ANCHOR WITH 8"
MIN EMBEDMENT
FIN FL EL
SEE PLANSREQ(D) SPLICEEXISTING CONCRETE SLAB
(AT FOOTINGS)
EXCAVATION
PIPE TO CLEAR
SLEEVE BY 2" (TYP)
IF PIPES ARE LOCATED
IN THIS HEIGHT,
THEN LOWER FOOTING
NO EXCAVATION FOR PIPE TRENCH PARALLEL
TO FOOTING BELOW THIS LINE, STEP FOOTING
AS REQUIRED BY THESE CONDITIONS
1 1/2
1 1' - 0"MIN
1' - 6"DRAIN TILE)4" MIN(0" MIN ATCMU OR CONCRETE WALL
REBAR SIZE
#3 #10 16
REINFORCING LAP SPLICE (PER ACI 318-14 AND 2018 IBC)
CONCRETE MEMBER
SOFT
METRIC
FOOTING GRADE
BEAM
(TOP)
GRADE
BEAM
(BOTT)
WALL
HORIZ
WALL
VERT
SLAB
17 16 12 16 16
#4 #13 19 23 18 19 19 20
#5 #16
24
#6 #19 29
28
34
22 28 28 30
26 37 37 40
NOTES:
(1) FOR COMPRESSION LAPS ONLY, Fy ≤ 60,000 PSI, F'c ≥ 3,000 PSI.
(2) GENERALLY NOT PERMITTED.
#7
#8
#9
#10
#11
#14
#18
#22 41 49 38 60 60 64
#25 47 56 43 74 74 80
#29 53
#32 60
69
85
54 90 90 96
66 108 108 116
#36 66 103 79 127 127 136
#43 (2)
#57 (2)
(2)
(2)
16 16 --
20 16 15
25 19 19
29 23 23
48 37 27
61 47 30
75 58 34
91 70 39
109 84 43
BEAM
(TOP)
BEAM
(BOTT)
COLUMN
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
STEEL COLUMN AND BASE
PLATE, SEE PLAN AND
SCHEDULE (PROVIDE 1 5/16"Ø
HOLES IN BASE PLATE)
4 - 3/4"Ø x 1'-3" HEADED ANCHOR
RODS UNO. LOCATE 2" FROM
FACE OF FLANGE UNO.
PLATE WASHER 5/16 x 2 1/2 x 2 1/2
WITH 13/16" HOLES
SHIM PACKS AS REQUIRED
TOF EL
SEE PLANS
NON-SHRINK GROUT
COAT STEEL BELOW GRADE
WITH COLD-APPLIED ASPHALT
EMULSION PER ASTM D1187
3/16 1 1/2
4 SIDES
5/16
TYP
UNO
FOR SIZE AND REINFORCING
SEE PLANS AND SCHEDULE
3" CLR4" CLRDEPTH2" CLRTOP REINFORCING
WHERE INDICATED,
SEE PLANS &
SCHEDULE'D'UNO5 1/2"PROJPIPE PILE BY
PILE DESIGNER
(AT EXTERIOR STEEL COLUMN)2"UNO5 1/2"PROJ 8"NOTE:
3/4" CHAMFER
ALL EXPOSED
CORNERS.
TOF / TO PIER EL
SEE PLANS
SHIM PACKS
AS REQUIRED
NON-SHRINK GROUT
USE PLATE WASHER
5/16 x 2 1/2 x 2 1/2
WITH 13/16"Ø HOLES
4 - 3/4"Ø x 1'-3" HEADED
ANCHOR RODS UNO,
LOCATE RODS 2" FROM
EDGES OF BASEPLATE UNO
BEVELED TOP 1"
BEVELED SEALANT 1/2"
STEEL COLUMN &
BASEPLATE - SEE PLAN
(PROVIDE 1 5/16"Ø HOLES
IN BASE PLATE)
4 - #3 TIES AT 3" OC TOP
REMAINDER AT 12" OC
4 - #4 A706 REBAR
WELDED TO EDGE
OF BASEPLATE
24"Ø CONCRETE COLUMN COVER
BASE PLATE BEYOND
3/16 1 1/2
4 SIDES
1/4
THIS CONDITION AT GRADE.
DETAIL IS SIMILAR AT SIDES
OF STRUCTURAL STOOP.
#4 @ 12" OC EXTEND 1'-0"
INTO STOOP SLAB
SEE SITE PLANS FOR
SIDEWALK LOCATIONS
VOID FORM x WIDTH
OF SIDEWALK
4" VOID FORMS x WIDTH
OF STOOP
2'-0"
2'-0"
3/8" COMPRESSIBLE
FILLER AND SEALANT
5" CONC SLAB
WITH #4 @ 12" OC EW
SUPPORT SLAB ON
FOOTING AND PROVIDE
3/8" COMPRESSIBLE
FILLER AND SEALANT
AT WALLS ADJACENT
TO DOOR OPENING
#4 x 4'-0" @ 12" OC.
EPOXY ANCHOR INTO
EXISTING SLAB WITH 5"
MIN EMBEDMENT
CONTROL
JOINT
#3 TIES
@ 24" OC
2 - #6 TOP
AND BOTTOM
#4 @ 12" OC THUS UNO
1' - 4"
EXISTING FOOTING
SLOPE
SEE SITE
1" CLR7' - 8" MAXMIN
4"
3' - 0"
.
MIN
1' - 0"EQEQEXISTING
CONCRETE
SLAB
T.O. EXIST FTG
FIELD VERIFY
#4 @ 12" OC, EPOXY
ANCHOR INTO EXISTING
FOOTING WITH 6" MIN
EMBEDMENT
2'-0"© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:44 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
CONCRETE
DETAILS
S3.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNO SCALES3.1
1B COLUMN BASE DETAIL
NO SCALES3.1
2A TYP INSTALLATION OF PIPES
NO SCALES3.1
2C TYP INSTALLATION OF PIPES
NO SCALES3.1
1A MASONRY WALL BASE DETAIL
NO SCALES3.1
2B TYP INSTALLATION OF PIPES
NO SCALES3.1
1E CONCRETE REINFORCING LAP SPLICE TABLE
NO SCALES3.1
1C TYP COLUMN BASE PLATE DETAIL
NO SCALES3.1
2F TYP COLUMN COVER DETAIL
NO SCALES3.1
1D STOOP DETAIL AT EXISTING
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
EDGE STIFFENER. SEE
PLANS FOR LOCATION
AND REINFORCING. SEE
TYPICAL VERTICAL WALL
REINFORCING DETAIL
FOR PLACEMENT.
16 OUNCE SMOOTH
COPPER BOND BARRIER
AT MASONRY LINTELS.
PROVIDE FULL MORTAR
BED UNDER BEARING.
CONDITION WITH
NO CONTROL JOINT
CONDITION WITH
CONTROL JOINT
CONTROL JOINT. SEE DETAIL,
ARCHITECTURAL ELEVATIONS
AND PLANS FOR LOCATIONS.
6'-0" LENGTH OF JOINT
REINFORCING (MINIMUM)
EDGE STIFFENER WITH
CELLS GROUTED, SEE
SECTION "A".
MASONRY LINTEL REINFORCING
MASONRY LINTEL OR STEEL
LINTEL, PROVIDE BOND BEAM
ABOVE STEEL LINTEL
TYPICAL MASONRY OPENING
BOND BEAM REINFORCING
GROUT JAMB CELL SOLID
TO FOOTING (TYPICAL
EACH SIDE OF OPENING)
CONTROL JOINT. START
AT TOP OF FOOTING UNO
3/4"3/4"3/4"8"4"
2' - 0"
A
A SLIP JOINT
VERTICAL MASONRY REINFORCING,
SEE PLANS AND STRUCTURAL NOTES
MESH WALL TIE (1/2"x16 GA),
4"x8" @ 16" OC
RAKED CONTROL JOINT
WITH SEALANT
FILL WITH GROUT
AS SPECIFIED
(AT MASONRY WALLS)
NOTES:
1. SEE PLANS AND STRUCTURAL NOTES FOR
BAR SIZE.
2. LOCATE REINFORCING AT ALL CORNERS,
EACH SIDE OF OPENINGS, CONTROL
JOINTS AND AT SPACING SHOWN ON PLANS.
3. PROVIDE WIRE REBAR POSITIONERS TO
HOLD BARS IN PLACE.
MAX FACE SHELL
THICKNESS
= 1 3/8" AT 8" WIDE UNITS
= 1 3/4" AT 12" WIDE UNITS
HORIZONTAL REINFORCING (WHERE
REQUIRED), LOCATE PER DETAIL 'B' BELOW.
WHERE SINGLE HORIZONTAL BAR IS
REQUIRED, LOCATE NEXT TO VERTICAL
(REINFORCING DETAIL)
HORIZONTAL REINFORCING (WHERE REQUIRED),
LOCATE INSIDE AND NEXT TO VERTICAL.
WHERE SINGLE HORIZONTAL BAR IS
REQUIRED, LOCATE AT CENTER OF CORE.CLR3/4"CLR3/4".A BAR AT CENTER
B BAR AT EDGE.6 3/8" FOR 12" CMU
2 3/8" FOR 8" CMU OPTION A
OPTION B BUILDING PAPER ONE SIDE AND
GROUT FULL
CONTROL JOINT KEY AS SPECIFIED
MASONRY CONTROL JOINT
(SASH) BLOCK
(AT MASONRY WALLS)
PROVIDE REINFORCING EACH SIDE
OF CONTROL JOINT TO MATCH
WALL REINFORCING UNO
NOTES:
1. PROVIDE SHORING UNDER
BEAM FOR A MINIMUM OF 7 DAYS
AFTER GROUTING.
2. MONOLITHICALLY GROUT
BOND BEAM AND ALL CELLS
SOLID. GROUTING SHALL HAVE
NO VERTICAL OR HORIZONTAL
COLD JOINTS FULL HEIGHT AND
LENGTH OF LINTEL INCLUDING
END BEARINGS.
3. MECHANICALLY VIBRATE
GROUT.
4. SEE TYPICAL MASONRY BEAM /
LINTEL BEARING DETAIL FOR
BEARING.
5. HORIZONTAL REINFORCEMENT
SHALL NOT BE SPLICED.
BOND BEAM REINFORCING -
SEE PLANS AND SCHEDULE3 1/2"MAX1"CLRDEPTH - SEE PLANBOTTOM EL
SEE PLANS
CMU OPEN END UNITS
UNO
2' - 0"UNO2' - 0"MASONRY BEAM
OR LINTEL
GROUT SOLID FOUNDATION
TO LINTEL BEARING
EXTEND LINTEL REINFORCING PER
TYPICAL MASONRY OPENING DETAIL
WHERE WALL CORNER OR T-
INTERSECTION PREVENTS EXTENSION,
EXTEND TO FAR FACE OF
INTERSECTING WALL AND TERMINATE
REINFORCING WITH STANDARD HOOK
GROUT CELLS SOLID AT
OPENINGS 6'-0" AND LARGER
GROUT CELLS SOLID AT
OPENING LESS THAN 6'-0"
OPENING LOAD BEARING WALL OR
NON-LOAD BEARING WALL
BOND
BEAM
STEEL JOIST
OR BEAM
NOTES:
1. LOAD-BEARING WALLS: LOCATE BETWEEN JOISTS OR BEAMS AS SHOWN. IF OPENINGS MUST
BE UNDER BEAM, TOP OF OPENING SHALL BE A MINIMUM OF 1/2 OF THE OPENING WIDTH
+ 8 INCHES OR 2'-0" BELOW THE JOIST BEARING, OR CONTACT THE ENGINEER.
2. NON-BEARING WALLS: PROVIDE 8" BOND BEAM FOR OPENINGS 4'-8" AND LESS AND 16" BOND
BEAM FOR OPENINGS GREATER THAN 4'-8" AND LESS THAN 6'-0". CONTACT ENGINEER FOR
LARGER OPENINGS.
3. WHERE VENEER OCCURS, PROVIDE SUPPORT PER TYPICAL LINTEL DETAILS.
4. GENERAL CONTRACTOR SHALL COORDINATE LOCATION OF OPENINGS WITH MECHANICAL,
ELECTRICAL AND OTHER CONTRACTORS BEFORE CONSTRUCTING WALLS.
(AT MECHANICAL OPENING)
EQ OPENING EQ
8" MIN 8" MIN
2 BENT BARS TO
MATCH BOND
BEAM REINF
2
1
BOND BEAM LAP
2' - 0"REQ(D) SPLICE
SPLICE
REQ(D)
BENT BAR TO
MATCH BOND
BEAM REINF
A STEP DETAIL B CORNER DETAIL
FINGER TIGHTEN NUTS AND UPSET
THREADS - TYPICAL UNO
BEARING PLATE 1/2"x7"x0'-7"
UNO ON PLANS CENTER ON
WALL UNO STEEL BEAM
1" NON-SHRINK
GROUT MIN
FILL ALL CELLS WITH
GROUT IN SHADED AREA
2 - 3/4"Ø x 1'-3" HEADED ANCHOR
BOLTS AND WASHERS.
PROVIDE 3" LONG SLOTTED
HOLES IN BEAM FLANGE.
(PERPENDICULAR WALL)
1' - 4"
MIN
1' - 4"
MIN
2' - 0" UNOPL 3/8x5x0'-5" WITH
2 - #6 x 7'-0" A706 REINFORCING BARS.
LAP WITH BOND BEAM REINFORCING.
STEEL BEAM -
SEE TYPICAL
BEARING DETAIL
CONTINUOUS BOND
BEAM REINFORCING
CMU WALL
3/16 4
(21.1k ALLOWABLE CAPACITY)
PL 3/8x4x0'-6"
3/16
STEEL BEAM
SEE TYP BEARING STEEL ON
MASONRY DETAIL
CONTINUOUS
BOND BEAM TYP
SEE TYP BEAM SPLICE
DETAIL
2' - 0" MAX
CMU WALL
2B/ S5.1
2E/ S4.1
MARK
ML2 1'-4"
2 - #4 IN 6"
2 - #4 IN 8"
2 - #5 IN 12"
MASONRY LINTEL SCHEDULE
BOND BEAM
REINFORCING
SHEAR
REINFORCING
REMARKSDEPTH
NOTES:
1. USE LINTEL ML2 FOR ALL OPENINGS ≤4'-0" AND ML3 FOR ALL OPENINGS
≤6'-8" WIDE UNLESS NOTED OTHERWISE.
2. WHERE LINTEL IS NOTED AS SIMILAR, PROVIDE BOND BEAM AND
REINFORCING PER SCHEDULE AT TOP AND BOTTOM OF LINTEL.
3. BOND BEAM REINFORCING SHALL BE CONTINUOUS WITHOUT SPLICES.
-
ML3 2'-0"
ML4 2'-8"
ML5 3'-4"
2 - #4 IN 8"
2 - #5 IN 12"
2 - #4 IN 8"
2 - #5 IN 12"
2 - #4 IN 8"
2 - #5 IN 12"
-
-
-© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:46 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
MASONRY
DETAILS
S4.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNO SCALES4.1
1A TYP MASONRY WALL OPENING DETAIL
NO SCALES4.1
1C TYP INTERSECTION
NO SCALES4.1
1D TYP MASONRY WALL REINFORCING PLACEMENT
NO SCALES4.1
1E TYP CONTROL JOINT (CJ)
NO SCALES4.1
2A TYP MASONRY LINTEL DETAIL
NO SCALES4.1
2B TYP MASONRY BEAM / LINTEL BEARING DETAIL
NO SCALES4.1
2D TYP MASONRY WALL OPENING DETAIL
NO SCALES4.1
2C TYP BOND BEAM DETAIL
NO SCALES4.1
2E TYP BEARING STEEL ON MASONRY
NO SCALES4.1
3A DRAG STRUT CONNECTION
NO SCALES4.1
2F TYP ALIGNED BEAM ON CMU
NO SCALES4.1
1F TYP MASONRY LINTEL SCHEDULE
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
CL
CL
CL
CLCL
CLCL
CL
STEEL ANGLE (WHERE REQUIRED)SPACING W/4 WELDS (36/4)SPACING W/5 WELDS (36/5)SPACING W/7 WELDS (36/7)CL OF STEEL JOIST, BEAM
OR DECK BEARING WALL
SIDELAP
ATTACHMENT
DIAPHRAGM
PERIMETER
METAL DECK SPAN
EDGE OF DECKDECK SIDE LAPSA
ATTACHMENT
TYPE
ATTACHMENT
AT SUPPORTS
ATTACHMENT
AT SIDE LAPS SHEAR (ASD)
36/4: 4-5/8Ø PER 36"
WIDE SHEET
360 PLF AT 20 GA DECK
470 PLF AT 18 GA DECK
DECK ATTACHMENT SCHEDULE
1'-0" 1'-0" 1'-0"1'-0"1'-0"6" 6"6" 6" 6" 6" 6" 6"
(DIAPHRAGM ATTACHMENT)
CMU/PRECAST WALL
2 - NO. 12 SCREWS
@ 1/3 POINTS
3"3"3"3"3"3"6"6"6"3"6"6"3"5/8
ATTACHMENT AT
SUPPORTS
5/8
TO MATCH
SIDELAP ATTACH.
SPACING OR 1'-6"
OC MAX
REMARKS
USE UNO ON
PLANS
3/8" STIFFENER PLATE
EACH SIDE CLIP CORNERS
STEEL BEAM
1/2" CAP PLATE
4 - 3/4"Ø A325-N BOLTS
STEEL COLUMN
(AT HSS COLUMN)
1 1/2"
1 1/2"
TOS EL
SEE PLANS
END OF BEAM WHERE
OCCURS
VIEW ON PLAN
3/163 SIDES
3/4"Ø A325-N BOLTS
13/16"Ø STANDARD HOLES
PLATE EACH SIDE,
SEE SCHEDULE
BM
SIZE
NO OF
BOLTS
L=PLATE
LENGTH
PLATE
THICKNESS
SHEAR
CAPACITY
Φ RN
W8, W10 2 5 1/2"1/4" 24K
3
4
5
6
7
8
9
W12, W14
W16, W18
W21
W24
W27
W30, W33
W36
8 1/2"
11 1/2"
14 1/2"
17 1/2"
20 1/2"
23 1/2"
26 1/2"
1/4"
1/4"
1/4"
1/4"
1/4"
5/16"
5/16"
52K
89K
130K
154K
179K
241K
273K
CONNECTION SCHEDULE (LRFD)
TOS EL
SEE PLANS
(STEEL PLATE SPLICE)
NOTE:
1. CAPACITIES ARE LRFD.
1 1/2"
1 1/2"
1/2"
1 1/2"
1 1/2"L1 3/4"1 1/4"@ 3" OCNO BOLTS1 1/4"2' - 0" UNO STEEL BEAM
CL COLUMN OR FACE
OF MASONRY
PL 5/16x4x0'-8" TENSION TIE
WHERE INDICATED ON PLANS
1/4 3
2 - L4x3 1/2, THICKNESS
PER SCHEDULE
STEEL BEAM
1 3/4" TYP (INCREASE
TO CLEAR WEB COPE
WHERE REQUIRED)
(CLIP ANGLE CONNECTION)L1/2"1 3/4"1 1/4"@ 3" OCNO BOLTS1 1/4"2 - L4x3 1/2, THICKNESS
PER SCHEDULE
STEEL BEAM
1 3/4" TYP (INCREASE
TO CLEAR WEB COPE
WHERE REQUIRED)L1/2"1 3/4"1 1/4"@ 3" OCNO BOLTS1 1/4"1 3/4"
1 1/4"
BM
SIZE
NO OF
BOLTS
L=ANGLE
LENGTH
ANGLE
THICKNESS
ΦRn SHEAR
CAPACITY
W8, W10 2 5 1/2" 1/4" 19K
3
4
5
6
7
8
9
W12, W14
W16, W18
W21
W24
W27
W30, W33
W36
8 1/2"
11 1/2"
14 1/2"
17 1/2"
20 1/2"
23 1/2"
26 1/2"
1/4"
1/4"
1/4"
1/4"
5/16"
5/16"
5/16"
35K
59K
125K
141K
193K
227K
278K
CONNECTION SCHEDULE (LRFD)
NOTES:
1. BOLTS ARE 3/4"Ø A325-N, HOLES ARE 13/16"Ø.
2. USE SIMILAR CONNECTION AT WIDE FLANGE COLUMN FLANGE OR WEB.
3. LRFD CAPACITIES PER TABLES 10-1 AND 10-2, AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION.
4. STEEL BEAMS ARE ASTM A992, ANGLES ARE ASTM A36.
3"
3/16
A WELDED CONN B BOLTED CONN
EACH BM
SIZE
NO OF
BOLTS
PLATE
SIZE
WELD
SIZE
ΦRn SHEAR
CAPACITY
W8, W10 2
3
4
5
6
7
8
9
1/4"
1/4"
5/16"
5/16"
5/16"
W12, W14
W16, W18
W21
W24
W27
W30, W33
W36
1/4"
1/4"
1/4"
1/4"
1/4"
3/16"
3/16"
1/4"
CONNECTION SCHEDULE (LRFD)
PLATE SIZE -
SEE SCHEDULE
STEEL BEAM
95K
111K
79K
59K
35K
19K
NOTES:
1. BOLTS ARE 3/4"Ø A325-N, HOLES ARE 13/16"Ø STANDARD HOLES.
2. LRFD CAPACITIES PER TABLE 10-9a, AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION.
STEEL COLUMN
127K
142K
L1 3/4"1 1/4"@ 3" OCNO BOLTS1 1/4"1/2"
2" 2"
PLATE SIZE -
SEE SCHEDULE
STEEL BEAM
STEEL COLUMN
5/16"
5/16"
5/16"
(SINGLE PLATE CONNECTION)
VIEW ON PLAN
A PLAN B BOLTED CONN
SEE
SCHED
SEE
SCHED
PL 5/16x3 1/2"x 0'-4"
TENSION TIE WHERE
INDICATED ON PLANS
1/4
(AT SNOW DRIFTING)
.
L
..Pf/Lr
P(drift)
A
TYPE
MARK
LOADING (PSF)
JOIST LOADING DIAGRAM SCHEDULE
Lr P(drift) LENGTH
20 46 11'-1"
Pmin
20
NOTES:
1. ROOF DEAD LOAD SHOWN ON S0.1.
2. DRIFTING LOADS SHALL BE COMBINED WITH OTHER LOADS NOTED IN
ACCORDANCE WITH BUILDING CODE PRESCRIBED COMBINATIONS..DL
Pf
16.8
2"2"2"1 31/32"2"1/2"
2" 3" 2"
TOS EL
SEE PLANS
1/2" PLATE, T&B
STEEL COLUMN
1/4" CAP PL
STEEL BEAM
PROVIDE SHIMS
AS REQUIRED
TYP BEAM TO COLUMN
CONNECTION, SEE
4 - 3/4"Ø BOLTS, T&B
5/16
3 SIDES OF
COLUMN
5/16 3 SIDES
STEEL BEAM
5/8" PLATE, T&B
STEEL COLUMN
NOTES:
1. BOLT DIAMETER: SEE DETAIL
2. BOLT TYPE: A325-N
3. BOLT HOLES: BOLT DIAMETER + 1/16"
4. BEAM GAGE: 3 1/2"
5. INSPECTION:
a. WELDS - 100% VISUAL
b. BOLTS - 100% FIELD INSPECTION OF
LOAD INDICATED WASHERS
6. PROVIDE LOAD INDICATED WASHER AND HARDENED WASHER
PER BOLT FULLY TIGHTEN BOLTS TO REQ'D PRETENSION FORCE.
7. MIRROR AT LOCATIONS WITH MOMENT FRAME CONNECTIONS ON EACH
SIDE OF COLUMN. USE BEVEL GROOVE WELD TO CONNECT PLATES.
2"2"2"
2"2"2"2"2"2"
TYP
5/16
A ONE SIDE B TWO SIDES © DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:50 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
STEEL DETAILS
S5.1485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNO SCALES5.1
2A TYP METAL DECK ATTACHMENT
NO SCALES5.1
1E TYP BEAM TO COLUMN DETAIL
NO SCALES5.1
2B TYP BEAM SPLICE DETAIL
NO SCALES5.1
2C TYP STEEL BEAM CONNECTION DETAIL
NO SCALES5.1
2D TYP STEEL BEAM CONNECTION DETAIL
NO SCALES5.1
1F JOIST LOADING DIAGRAM
NO SCALES5.1
4A MOMENT CONNECTION DETAIL
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
CL
CL CL
CLCL
CL
CL
1"
TOP OF CONC
SEE PLANS
1/2"Ø DBA, SEE SCHEDULE
CONCRETE TOPPING
(DIRECTION VARIES)
BENT PLATE, SEE SCHEDULE
STEEL BEAM
A 3 @ 1'-0"OR ARCH
SEE PLANS
1/4
"L"
"L" PLATE THICKNESS DBA
0"-6"
13"-18"
19"-24"
1/4" 1/2"Øx2'-0" AT 18" OC
5/16" 1/2"Øx3'-6" AT 12" OC
5/16" 1/2"Øx4'-0" AT 12" OC
7"-12" 1/4" 1/2"Øx2'-6" AT 18" OC
A
3/16
3/16
1/4
1/4
2 - #5 x CONTINUOUS CHORD/OPENING REINFORCING.
EXTEND 10'-0" PAST EDGE OF OPENINGS & CORNER UNO. 1 1/2"NOTE:
"L" = 6" TYP UNO ON PLANS.
A. BEAMS:
1. THE NUMBER SHOWN THUS (NO) FOLLOWING THE BEAM SIZE INDICATES THE NUMBER OF 3/4"
HEADED STUDS TO BE PLACED ON THE BEAM. THE MAXIMUM STUD SPACING SHALL BE 2'-0".
DECK VALLEYS WITHOUT STUDS SHALL BE WELDED.
2. STUD PLACEMENT SHALL BE AS FOLLOWS:
A. NUMBER OF STUDS IS LESS THAN THE NUMBER OF DECK VALLEYS.
UNIFORMLY SPACE STUDS SYMMETRICALLY WITH THE BEAM CENTERLINE.
B. NUMBER OF STUDS IS GREATER THAN THE NUMBER OF DECK VALLEYS.
PLACE ONE STUD IN EACH VALLEY STARTING AT THE ENDS OF THE BEAM.
WHEN TWO STUDS ARE REQUIRED, PLACE STUDS 1 1/2" EACH SIDE OF THE BEAM WEB.
NOTE:
SPACE 'A' TO COORDINATE WITH DECK LAYOUT.
B. GIRDERS:
1. THE SERIES OF NUMBERS SHOWN THUS [NO-NO-NO] FOLLOWING THE GIRDER SIZE WHEN ADDED
TOGETHER, REPRESENT THE TOTAL NUMBER OF STUDS TO BE PLACED ON THE GIRDER. FOR
EXAMPLE, [10-3-10] REPRESENTS THE TOTAL OF 23 STUDS TO BE LOCATED ON THE GIRDER. THE
FIRST AND LAST NUMBERS REPRESENTS THE NUMBER OF STUDS TO BE PLACED BETWEEN THE END
OF THE GIRDER AND THE FIRST (OR LAST) INTERSECTING BEAM. THE MIDDLE NUMBER REPRESENTS
THE NUMBER OR STUDS TO BE LOCATED BETWEEN THE TWO INTERSECTING BEAMS.
2. PLACE STUDS UNIFORMLY ALONG THE BEAMS OR PORTION OF BEAM INDICATED. CENTER THE
STUDS OVER THE WEB AND PROVIDE A MAXIMUM SPACING OF 3'-0" AND A MINIMUM SPACING OF 4 1/2".
IF THE REQUIRED NUMBER OF STUDS EXCEEDS WHAT CAN BE PLACED AT 4 1/2", PLACE A SECOND
ROW OF STUDS SPACED AT 4 1/2" CENTERS STARTING AT THE END OF THE BEAM UNTIL THE
REQUIRED NUMBER OF STUDS IS REACHED. WHEN TWO ROWS OF STUDS ARE REQUIRED, PLACE
STUDS 1 1/2" EACH SIDE OF THE BEAM CENTER LINE.
A EQUALLY SPACED A
MAX
2'-0"
UNIFORMLY PLACE
10 STUDS
UNIFORMLY PLACE
3 STUDS
UNIFORMLY PLACE
10 STUDS
STUDS STUDS
EXAMPLE LAYOUT
EXAMPLE: [10-3-10]
EXAMPLE LAYOUT SEE PLAN1" UNOSEE PLAN1" UNO1 1/2"
B AT COMP GIRDERAAT COMP BEAM
3/4"Ø SHEAR
STUDS
#4 x 4'-0"
@ 1'-6" OC
ALTERNATE
SIDES
NOTES:
1. SHEAR STUD LENGTH IS TOTAL THICKNESS (METAL DECK PLUS TOPPING) MINUS 1".
2. PROVIDE DECK GIRDER FILLER PLATE IF REQUIRED.
SW TYP
WWR - SEE PLANS3/4"Ø x 5"
SHEAR STUDS
WWR - SEE PLANS
1 1/2"(AT CONSTRUCTION JOINT)1"1 1/2"FIN FLOOR EL
SEE PLANS
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
(DIRECTION VARIES)
#4 x 5'-0" @ 4'-0" OC
CONSTRUCTION JOINT
NOTE:
LOCATE CONSTRUCTION JOINTS IN
MIDDLE OF SPANS. DO NOT LOCATE
DIRECTLY OVER BEAM.
2'-6"
2'-6"
3/16 3
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
#4 @ 4'-0" OC
METAL DECK
BOND BEAM
CUT MASONRY COURSE
IF REQUIRED
BENT PL 1/4x6x3xCONT
WITH 1/2"Ø x 2'-0" DBA
@ 2'-0" OC
PL 1/4x4x0'-6" WITH
2 - 1/2"Ø x 4" HEADED
STUDS @ 2'-0" OC
VERTICAL MASONRY WALL REINFORCING.
SEE PLANS AND STRUCTURAL NOTES.
METAL STUD FRAMING
FIN FL EL
SEE PLANS
BOD
SEE PLANS
5/8 2'-0" OC MAX
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
BOND BEAM
CUT MASONRY COURSE
IF REQUIRED
PL 1/4x4x0'-6" WITH
2 - 1/2"Ø x 4" HEADED
STUDS @ 2'-0"
VERTICAL MASONRY WALL
REINFORCING. SEE PLANS
AND STRUCTURAL NOTES.
TSE
SEE PLANS
TSE
SEE PLANS
STEEL BEAM, SEE PLAN
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK,
SEE PLANS
ARCHITECTURAL GUARDRAIL,
ATTACHEMENT TO SLAB PER
GUARDRAIL SUPPLIER
TYP SLAB EDGE REF:
SEE PLAN
"L"
3/16 2 @ 1'-0"
3/16
STAIR PER ARCH
DESIGN PER STEEL SUPPLIER
STRINGER BEARING ON WF BEAM
DESIGN PER STEEL SUPPLIER
TYP SLAB EDGE, RE:
1/4" CLOSURE PLATE
ANGLED BENT PLATE AS REQUIRED
FOR STAIR GEOMETRY
CONCRETE TOPPING WITH WWR
ON COMPOSITE DECK SEE PLAN
(DIRECTION VARIES)
1/2"Ø DBA, RE:
SEE
"L"
PLAN
PLATE SIZE -
SEE SCHEDULE
STEEL BEAM
EXISTING
CONCRETE WALLL1 3/4"1 1/4"@ 3" OCNO BOLTS1 1/4"1"2"2"
SEE
SCHED
NOTES:
1. BOLTS: 3/4"Ø A325N BOLTS.
2. HOLE: 13/16"Ø STANDARD HOLES IN BEAM.
13/16"Ø x 2" HORIZONTAL SLOTS IN PLATE.
3. CONTINUOUS PLATE WASHERS, 5/16" THICK,
WITH STANDARD HOLES SHALL BE PROVIDED
AT PLATE.
EACH BM
SIZE
NO OF
BOLTS
PLATE
SIZE
WELD
SIZE
ΦRn SHEAR
CAPACITY
W8, W10 2 1/4" 3/16"
CONNECTION SCHEDULE (LRFD)
19K
VIEW ON PLAN
PLATE SIZE -
SEE SCHEDULE
W12, W14
W16, W18
W21
W24
3 1/4" 3/16"
4 5/16" 1/4"
5 5/16" 1/4"
6 5/16" 1/4"
(AT EXISTING CONCRETE WALL)
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
(DIRECTION VARIES)
L4x4x3/8xCONTINUOUS
5/8
SPACE AS REQ(D)
FOR DIAPHRAGM
OR 1'-0" OC MAX
TSE
SEE PLANS
EXISTING CONCRETE WALL
2 - #5 x CONTINUOUS
CHORD/OPENING REINFORCING.
EXTEND 10'-0" PAST EDGE OF
OPENINGS & CORNER UNO.
3/4"Ø EXPANSION BOLTS
WITH 5" MINIMUM EMBEDMENT
@ 2'-0" OC
(AT EXISTING CONCRETE WALL)
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
(DIRECTION VARIES)
L4x4x3/8xCONTINUOUS
5/8
SPACE AS REQ(D)
FOR DIAPHRAGM
OR 1'-0" OC MAX
TSE
SEE PLANS
EXISTING MASONRY WALL
2 - #5 x CONTINUOUS
CHORD/OPENING REINFORCING.
EXTEND 10'-0" PAST EDGE OF
OPENINGS & CORNER UNO.
1/2"Ø ADHESIVE ANCHORS AT
2'-0" OC WITH 2" MIN EMBEDMENT
AND GROUT SCREEN WITH HILTI
HIT-HY 270
(AT EXISTING MASONRY WALL)
CONCRETE TOPPING WITH
WWR ON COMPOSITE DECK
L6x4x3/8xCONTINUOUS LLV,
EACH SIDE
5/8
SPACE AS REQ(D)
FOR DIAPHRAGM
OR 1'-0" OC MAX
TSE
SEE PLANS
EXISTING MASONRY WALL,
CUT 1/2" BELOW DECK
2 - #5 x CONTINUOUS
CHORD/OPENING REINFORCING
1/2"Ø ADHESIVE ANCHORS AT
2'-0" OC WITH 2" MIN EMBEDMENT
AND GROUT SCREEN WITH HILTI
HIT-HY 270, EACH SIDE
(AT EXISTING MASONRY WALL)
2 - #5 x CONTINUOUS
CHORD/OPENING
REINFORCING © DLR GroupREVISIONS-NOT FOR CONSTRUCTION -A B C D E F
1
2
3
4
5
1/13/2023 7:48:52 AMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_ST_2022.rvt73-22135
01/13/2023PACCAR-KENWORTH R&DDESIGN
DEVELOPMENT
STEEL DETAILS
S5.2485 HOUSER WAY NRENTON, WA 98057R&D BUILDING OFFICE REMODELNO SCALES5.2
1E TYP SLAB EDGE DETAIL
NO SCALES5.2
1A TYP STUD PLACEMENT DETAIL
NO SCALES5.2
1C TYP COMPOSITE BEAM AND GIRDER DETAIL
NO SCALES5.2
1D TYP SLAB DETAIL
NO SCALES5.2
2A DECK BEARING DETAIL
NO SCALES5.2
2B DECK BEARING DETAIL
NO SCALES5.2
12 FLOOR SLAB EDGE DETAIL
NO SCALES5.2
2C TYP STAIR CONNECTION TO FLOOR SLAB DETAIL
NO SCALES5.2
3A TYP STEEL BEAM CONNECTION DETAIL
NO SCALES5.2
3B TYP DECK BEARING DETAIL
NO SCALES5.2
3C DECK BEARING DETAIL
NO SCALES5.2
3D DECK BEARING DETAIL
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
* NOTE *ALL NOTES ON THIS SHEET ARE APPLICABLE TO ALL OTHER SHEETS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE APPLICABLE IN THIS SET OF DRAWINGS.SSSSSSSSSSSSSSSPOLE WITH POLE MOUNTED AREA LIGHTING FIXTUREWALL MOUNTED AREA LIGHTING FIXTUREPOLE MOUNTED AREA LIGHTING FIXTUREBOLLARD LIGHT FIXTURESITE LIGHTING - POLEIN GRADE LIGHT FIXTUREPHOTOELECTRIC CELLLOW VOLTAGE RELAYLIGHTING CONTACTORLIGHTING CONTROL PANELTHEATRICAL LIGHTING LCD STATIONMOUNT 50-INCHES AFF, UNOTHEATRICAL LIGHTING ENTRY STATIONMOUNT 42-INCHES AFF, UNOREMOTE EMERGENCY BATTERY PACKTHEATRICAL OUTLET BOXMOUNT 18-INCHES AFF, UNOTHEATRICAL NETWORK OUTLETMOUNT 18-INCHES AFF, UNOTHEATRICAL CONTROL CONSOLE OUTLETMOUNT 18-INCHES AFF, UNOCEILING MOUNTED LIGHTING CONTROL DEVICESMAXIMUM MOUNTING HEIGHT OF 10-FEET AFFSWITCH, DOUBLE POLESWITCH, SINGLE POLESWITCH, 3-WAYSWITCH, MOMENTARY CONTACTSWITCH, LOW VOLTAGE SWITCH, EMERGENCYSWITCH, WALL-BOX OCCUPANCY SENSORSWITCH, WALL-BOX OCCUPANCY SENSOR, 2-POLESWITCH, DIMMERSWITCH, 4-WAYLIGHTING TRACK, TRACK MOUNTED LIGHT FIXTURESLIGHTING FIXTURELIGHTING FIXTURE ON EMERGENCY SYSTEMLIGHTING FIXTURE ON EMERGENCY SYSTEMLIGHTING FIXTURE WALL MOUNTED LIGHTING FIXTUREHIGH BAY LIGHTING FIXTURECEILING FIXTURE, SURFACE, RECESSED OR PENDANTWALL WASHERWALL MOUNTED LIGHTING FIXTURESWITCH WITH PILOT LIGHTEXIT SIGN, CEILING MOUNTED,DIRECTIONAL ARROW(S) AS INDICATEDEXIT SIGN, WALL MOUNTED, DIRECTIONAL ARROW(S)AS INDICATED. MOUNT 94-INCHES AFF, UNOSELF CONTAINED EMERGENCY LIGHTING UNIT MOUNT 94-INCHES AFF, UNOSWITCH, LOW VOLTAGE, ASSOCIATED WITH RELAY PANEL SWITCH, EXPLOSION-PROOFSWITCH, ECO-SYSTEMCENTRAL INVERTERSWITCHES: MOUNT 42-INCHES AFF UNOTHEATRICAL LIGHTING DEVICES:SWITCH, TIMEROCCUPANCY SENSOR VACANCY SENSOROCCUPANCY SENSORWALL MOUNTED LIGHTING CONTROL DEVICES:MOUNT 94-INCHES AFF, UNOVACANCY SENSORRPxCVxPCRLCLCDEBATTOTNTC23D4EMCOS2POSLVRTESEPOSVSOSVSLIGHTINGSXSWITCH SYMBOLSUPERSCRIPT , SWITCH SHALL CONTROL FIXTURE DENOTED WITH SAME LOWER CASE LETTERxSUBSCRIPT, SWITCH TYPE - SEE BELOWXXXXXX-XXXX-XCKT DESIGNATION (PNL - CKT NO.)FIXTURE TYPERELAY PANEL - RELAY NO. OR LOCAL SWITCH DESIGNATIONLIGHTING FIXTURE TAGLINE THRU SWITCH INDICATES A KEY OPERATED SWITCHLIGHTING FIXTURESAREA LIGHTINGLIGHTING CONTROL DEVICESSWITCHES AND WALL-BOX CONTROLSSS**SSWITCH, PUSH BUTTON, SINGLESWITCH, PUSH BUTTON, DOUBLEDUPLEX RECEPTACLEDUPLEX RECEPTACLE, EMERGENCYSIMPLEX RECEPTACLESWITCH, PUSH BUTTON, TRIPLECIRCUIT HOME RUNCONDUIT STUB-UPCONDUIT SLEEVECONDUIT TURNING UPCONDUIT TURNING DOWNCONDUIT SEALTRANSFORMEREXPOSED CONDUIT, POWERCONDUIT CONCEALED IN CEILING OR WALLS, POWERCONDUIT CONCEALED IN FLOOR OR UNDERGROUND, POWERSPECIAL RECEPTACLE, DEEP WELL BOXFLUSH FLOOR OUTLET BOX UNODUPLEX RECEPTACLE, SWITCHEDRANGE RECEPTACLE, MOUNT 8-INCHES AFFWITH FLEX CONNECTIONSWITCHBOARDGENERATOREQUIPMENT CABINET, AS NOTEDAUTOMATIC TRANSFER SWITCHCURRENT TRANSFORMER ENCLOSURETHERMOSTATMUSHROOM SWITCHELECTRICAL MANHOLEMOTOR CONNECTION, HORSEPOWER AS INDICATEDMANUAL CONTROLLER WITH THERMAL OVERLOADFUSE AND SWITCH ASSEMBLYELECTRICAL HAND HOLEFLUSH JUNCTION BOX, CEILING MOUNTEDJUNCTION BOX ABOVE SUSPENDED CEILINGSURFACE JUNCTION BOX, WALL MOUNTEDFLUSH JUNCTION BOX, WALL MOUNTEDSURFACE JUNCTION BOX, CEILING MOUNTEDFOURPLEX RECEPTACLE, EMERGENCYDUPLEX RECEPTACLE, LOWER SWITCHFLUSH FLOOR BOX WITH DUPLEX RECEPTACLE UNODUPLEX RECEPTACLE, FLUSH IN CEILINGEQUIPMENT CONNECTIONMANUAL CONTROLLER W/O THERMAL OVERLOADSYSTEM GROUND ELECTRODECABLE TRAY, LADDER TYPE OR RUNWAYMULTI-OUTLET ASSEMBLIESMOUNT 18-INCHES AFF, UNOWHERE DENOTED 'AC', MOUNT ABOVE COUNTERFIRE RATED SLEEVECIRCUIT BREAKER ENCLOSUREWEATHER RESISTANT GFI DUPLEX RECEPTACLE,ROOF MOUNT 18-INCHES ABOVE ADJACENTSTRUCTURE WITH A WEATHERPROOF, IN-USE COVERDUPLEX RECEPTACLE TO SERVE TELEVISION,MOUNT AT SAME HEIGHT AND WITHIN 8-INCHESOF ADJACENT TV OUTLETRECEPTACLES: MOUNT 18-INCHES AFF, UNO DIAGONAL LINE THROUGH SYMBOL OR DENOTED 'AC' INDICATES MOUNT DEVICE ABOVE COUNTER.WHERE INDICATED AS 'MOUNT ABOVE COUNTER' MOUNT BOTTOM OF BOX 2-INCHES ABOVE TOP OF BACKSPLASH OR 6-INCHES ABOVE COUNTERTOP IF NO BACKSPLASH EXISTS.LABELS SHALL BE MACHINE PRINTED, UNOJUNCTION BOX FOR FUTURE PROJECTOR POWERMOUNT 24-INCHES ABOVE SUSPENDED CEILINGMOUNT TIGHT TO CEILING AT EXPOSED STRUCTURELABEL BOX COVER 'PROJECTOR POWER'MULTI-DEVICE FLOOR BOX WITH DUPLEXRECEPTACLE AND TELECOMMUNICATIONS OUTLETSSTD DUPLEX RECEPTACLE TO SERVE ELECTRIC WATER COOLER, MOUNT AT HEIGHT PEREQUIPMENT MANUFACTURER'S INSTALLATIONGUIDELINES. WIRE TO GFCI BKR IN PANELBOARD.CONDUIT CONCEALED IN CEILING OR WALLS,OTHER (* = SEE ABBREVIATIONS)CONDUIT CONCEALED IN FLOOR OR UNDERGROUND,OTHER (* = SEE ABBREVIATIONS)EXPOSED CONDUIT,OTHER (* = SEE ABBREVIATIONS)BRANCH CIRCUIT PANELBOARD MOUNT 72-INCHES TO TOPDISTRIBUTION PANELBOARD MOUNT72-INCHES TO TOPPUSHBUTTON STATION: MOUNT 42-INCHES AFF UNOWEATHER RESISTANT GFI DUPLEX RECEPTACLE,MOUNT 18-INCHES AFF WITH A WEATHERPROOF,IN-USE COVERJJPBHHMHXXXXXXXXXMCTMATSGENTTFTMBJJJFRSPOWERMETER*PULL BOXRTVPWPDIVIDED SURFACE RACEWAYMOUNT 18-INCHES AFF, UNOWHERE DENOTED 'AC', MOUNT ABOVE COUNTERDUPLEX RECEPTACLE, GFI TYPEFOURPLEX RECEPTACLEFOURPLEX RECEPTACLE, GFI TYPEDUPLEX RECEPTACLE, MOUNT ABOVE COUNTERDUPLEX RECEPTACLE, GFI TYPE, MOUNT ABOVE COUNTERFOURPLEX RECEPTACLE, MOUNT ABOVE COUNTERFOURPLEX RECEPTACLE, GFI TYPE, MOUNT ABOVE COUNTERDUPLEX RECEPTACLE, HORIZONTALLY MOUNTEDDUPLEX RECEPTACLE, HORIZ. MTD, GFI TYPEDUPLEX RECEPTACLE, HORIZ. MTD, ABOVE COUNTERDUPLEX RECEPTACLE, HORIZ. MTD, GFI TYPE, MOUNT ABOVE COUNTERHAND DRYER, INSTALL HAND DRYER SPECIFIED IN DIV. 11HUSB ONLY RECEPTACLEURECEPTACLE WITH USB PORTSUEWCMOTOR STARTER OR DRIVEDISCONNECT SWITCHCOMBINATION STARTER / DISCONNECT SWITCHCABLE TRAYFOURPLEX RECEPTACLE, FLUSH IN CEILINGSAFETYTSFAAFACPSMOKE DETECTOR - IONIZATION TYPE (D = DUCT)FIRE ALARM SPEAKER WITH VISUAL WARNING SIGNALMINI FIRE ALARM HORN WITH VISUAL WARNING SIGNALSMOKE DETECTOR - PHOTOELECTRIC TYPE (D = DUCT)REMOTE INDICATOR LAMPWATER FLOW ALARM SWITCHTAMPER SWITCHBEAM TRANSMITTERBEAM RECEIVEROS&Y VALVESMOKE DETECTOR - PHOTOELECTRIC TYPEHEAT DETECTOR, FIXED TEMPERATURE ONLY, 135 FSMOKE DETECTOR - IONIZATION TYPEFIRE ALARM HORN WITH VISUAL WARNING SIGNALFIRE ALARM BELL WITH VISUAL WARNING SIGNALMANUAL FIRE ALARM PULL STATIONFIRE ALARM VISUAL WARNING SIGNALFIRE ALARM CONTROL PANELFIRE ALARM ANNUNCIATOR PANELMOUNT CENTER OF DISPLAY 54-INCHES AFFMOUNT CENTER OF DISPLAY 54-INCHES AFFMOUNT 42-INCHES AFFFIRE ALARM A/V DEVICES: MOUNT 94-INCHES AFF, OR 6-INCHES BELOW CEILING, WHICHEVER IS LOWER UNOHEAT DETECTOR RATE-OF-RISE ANDFIXED TEMPERATURE, 135 FHEAT DETECTOR, RATE-OF-RISE ANDFIXED TEMPERATURE, 200 FHEAT DETECTOR, FIXED TEMPERATURE ONLY, 200 FFIRE ALARM MAGNETIC DOORHOLDER MOUNT 74-INCHES AFFFIRE FIGHTERS TELEPHONEMOUNT 54-INCHES AFFTFFRDLFFFFFFFFPIPDIDFIRE ALARM HORNFIRE ALARM BELLFIRE ALARM SPEAKER, FLUSH IN CEILINGFSPRINKLER SYSTEMS ELECTRIC BELL ALARMSFIRE ALARM SPEAKER WITH VISUAL WARNING SIGNAL, CEILINGFFIRE ALARM VISUAL WARNING SIGNAL, CEILINGFECS SPEAKER, FLUSH IN CEILINGEECS SPEAKER WITH VISUAL WARNING SIGNAL, CEILINGEECS VISUAL WARNING SIGNAL, CEILINGELOCLOCAL OPERATOR'S CONSOLEMOUNT CENTER OF DISPLAY 54-INCHES AFFNACNOTIFICATION APPLIANCE CIRCUIT CABINETMOUNT CENTER OF DISPLAY 54-INCHES AFFFSOSYDAS ANTENNAGBSECURITYINTRUSION DETECTOR, WALLMOTION DETECTOR - LONG RANGEMOTION DETECTOR - BROAD RANGEMOTION DETECTOR - 360 DEGREESINTRUSION DETECTOR, CEILINGVIDEO CAMERA - WALLGLASS BREAK DETECTORVIDEO CAMERA - CEILINGPOWER SUPPLY, 120V INPUTDOOR POSITION SWITCHCARD READERMOUNT 36-INCHES AFFSECURITY KEYPADMOUNT 48-INCHES AFFACCESS CONTROL SYSTEM CONTROL PANELDOOR TAGMDMDMDXXXXXXIDIDCRKPPSACPELXXX360LRBRDOOR WITH ELECTRIFIED DOOR HARDWARE. REFER TO DOOR HARDWARE SPECIFICATIONS.INTRUSION DETECTIONVIDEO SURVEILLANCEACCESS CONTROLTELEVISION OUTLET, FLUSH IN CEILINGFLUSH FLOOR BOX WITH MICROPHONE OUTLETSPEAKER/HORN, WALLDIRECTORS HEADSETCLASS PROGRAM BELLCLOCK - DOUBLE FACETELECOMMUNICATIONS OUTLET MOUNTED IN FLOOR BOXCOMMUNICATIONSCLOCK - WALL MOUNT1,0,00,0,1TELECOMMUNICATIONS OUTLETS: MOUNT 18-INCHES AFF,UNO, AND WITHIN 8-INCHES OF ADJACENT RECEPTACLEWHERE DENOTED 'AC', MOUNT ABOVE COUNTERWHERE DENOTED 'C', MOUNT FLUSH IN CEILINGVIDEO ONLY TELECOM OUTLET (TELEVISION OUTLET)MOUNT 94-INCHES AFF, UNO. EQUIVALENT TOANALOG VOICE ONLY TELECOM OUTLET (TELEPHONE OUTLET)MOUNT 18-INCHES AFF, UNO. EQUIVALENT TOWHERE DENOTED 'W' MOUNT 50-INCHES AFFTELECOMMUNICATIONS OUTLETPROVIDE JACKS UNDER A COMMON FACEPLATE:X = QTY OF VOICE JACKSY = QTY OF DATA JACKSZ = QTY OF VIDEO JACKSINTERCOM CALLBACK STATIONMOUNT 42-INCHES AFFSPEAKER, WALLBELLS, BUZZERS, CHIMES AND WALL SPEAKERS:MOUNT 94-INCHES AFF, UNOINTERCOM HANDSETMOUNT 50-INCHES AFFVOLUME CONTROL, WALLMOUNT 42-INCHES AFFMICROPHONE OUTLET, WALLMOUNT 18-INCHES AFFFLOOR MOUNTED TELECOMMUNICATIONS RACKPUBLIC ADDRESS (A/V) SYSTEM SPEAKER, FLUSH IN CEILINGWIRELESS ACCESS POINTCLOCK - CEILING MOUNT, DOUBLE FACECLOCKS: MOUNT 94-INCHES AFF, UNOSPEAKER, FLUSH IN CEILING, ENCLOSED IN BACKBOX WHERE EXPOSEDTWO-WAY INTERCOM/CALL STATION COMBINATIONUNIT MOUNT 42-INCHES AFFINTERCOM MASTER STATION OUTLETMOUNT 18-INCHES AFF2MAV OUTLET. TVAVTVMMVICHSICICSSX,Y,ZDHCDSCMDSBUZZERCHIMECLOCK - MASTERCLOCK - OUTLETPAAPWIRELESS ACCESS POINT, WALL MOUNTEDAPENCLOSED SWITCH; MOUNT 60-INCHES AFF TO TOPXX/X = AMP RATING / NO. OF POLESXXAF = FUSE SIZE; AF=AMP FUSE; NF=NO FUSEX = STARTER NEMA SIZECOMBINATION CONTROLLER \ DISCONNECT; MOUNT 60-INCHES AFF TO TOPXX/X = AMP RATING / NO. OF POLESXXAF = FUSE SIZE; AF=AMP FUSE; NF=NO FUSEXX = ENCLOSURE NEMA RATING; BLANK=NEMA 1; WP=NEMA 3RONE-LINE DIAGRAMMXXX/XLSIGXXX/3METER SOCKET/METERENCLOSED CONTROLLER (ACROSS-THE-LINE UNO)MOUNT 60-INCHES AFF TO TOPX = STARTER NEMA SIZEXXX/XXXAFXXXX/XXXAFXXSPDSURGE PROTECTION DEVICETXXTRANSFORMERT = TRANSFORMER IDXX = SIZE BREAKERXXX/X = AMP RATING / POLESLSIG = ADJUSTABLE SETTINGS (WHERE NOTED)L = LONG TIMES = SHORT TIMEI = INSTANTANEOUSG = GROUND FAULT PROTECTION OF EQUIPMENTGFPE = GROUND FAULT PROTECTION OF EQUIPMENTERMS = ENERGY REDUCTION MAINTENANCE SWITCHFUSIBLE SWITCHXXX/X = SWITCH AMP RATING / POLESXXX = FUSE SIZEXXXGROUNDING ELECTRODE SYSTEM© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:39:54 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusELECTRICALSYMBOLS,ABBREVIATIONS &NOTESE0.1Enter address hereclient nameGENERAL DEMOLITION NOTES1 ITEMS INDICATED ON DEMOLITION PLANS ARE BASED ON AS-BUILT DRAWINGS AND FIELDOBSERVATIONS AND ARE INTENDED TO GIVE THE BIDDER A GENERAL REPRESENTATIONOF EXISTING CONDITIONS.2 REMOVE ALL ITEMS SHOWN FULL-TONE OR NOTED ELSEWHERE IN THE DOCUMENTS TOBE REMOVED OR DEMOLISHED. DEMOLISH ADDITIONAL ITEMS NOT SHOWN ONDRAWINGS, BUT WHICH MUST BE REMOVED TO COMPLETE THE PROJECT.3 ITEMS SHOWN HALF-TONE ARE EXISTING TO REMAIN.4 RELOCATE ITEMS DENOTED 'ER'. SEE LIGHTING, POWER AND/OR SPECIAL SYSTEMSHEETS FOR NEW LOCATIONS. 'ER' IS DEFINED AS EXISTING (TO BE) RELOCATED.5 EXISTING CONDUIT MAY REMAIN IF ALL THE FOLLOWING ARE TRUE:A. IT CAN BE REUSED TO FEED DEVICES INSTALLED UNDER THIS CONTRACT.B. IT DOES NOT INTERFERE WITH OTHER TRADES.C. IT WAS ORIGINALLY INSTALLED MEETING SPECIFICATIONS RELATED TO THIS PROJECT.D. IT WILL NOT BE EXPOSED IN A FINISHED AREA (UNLESS NOTED OTHERWISE).6 PROVIDE ELECTRICAL DEMOLITION ASSOCIATED WITH MECHANICAL EQUIPMENT TO BEREMOVED. IN ADDITION TO DEVICES SHOWN, REFER TO MECHANICAL ANDARCHITECTURAL DEMOLITION SHEETS TO DETERMINE EQUIPMENT TO BE REMOVED.7 MAINTAIN FUNCTIONALITY OF ALL EXISTING LOW VOLTAGE SYSTEMS INCLUDING, BUTNOT LIMITED TO, TELECOM CABLING NETWORKS, INTERCOM, CLOCKS, FIRE ALARM,SAFETY AND SECURITY DURING ALL PHASES OF CONSTRUCTION. PROVIDE TEMPORARYINTERCONNECTIONS AS REQUIRED TO ACCOMMODATE CONSTRUCTION SCHEDULE.GENERAL LIGHTING NOTES1 SEE LIGHT FIXTURE SCHEDULE AND SYMBOLS LEGEND FOR MOUNTING HEIGHTS, UNLESSNOTED OTHERWISE.2 PROVIDE #10AWG MINIMUM CONDUCTORS FOR ALL EXTERIOR LIGHTING CIRCUITS.3 SEE ARCHITECTURAL BUILDING ELEVATIONS FOR LOCATION OF BUILDING MOUNTEDEXTERIOR LIGHT FIXTURES.4 PROVIDE BEAD OF SILICONE SEALANT AROUND RECESSED BACK BOX PERIMETER AT ALLBUILDING MOUNTED EXTERIOR LIGHT FIXTURE LOCATIONS.5 CIRCUIT FIXTURES DENOTED WITH 'NL' AS UNSWITCHED NIGHT LIGHTS.6 FIXTURES DENOTED WITH LOWER CASE LETTERS SHALL BE CONTROLLED BY SWITCHESDENOTED WITH THE SAME LOWER CASE LETTER IN EACH ROOM.(R) RELOCATEDØ PHASEA AMPEREAC ABOVE COUNTERAF AMP FRAME (CIRCUIT BREAKER)AIC AMPERE INTERRUPTING CAPACITYAL ALUMINUMAMP AMPEREAP WIRELESS ACCESS POINTAT AMP TRIP (CIRCUIT BREAKER OR FUSE)ATS AUTOMATIC TRANSFER SWITCHAV AUDIO-VIDEO, AUDIO-VISUALAWG AMERICAN WIRE GAUGEBAS BUILDING AUTOMATION SYSTEMBJ BONDING JUMPERBKR BREAKERBMS BUILDING MANAGEMENT SYSTEMC CONDUITCATV CABLE TELEVISIONCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLEDCKT CIRCUITCTL CONTROLCU COPPERDB DECIBELDC DIRECT CURRENTDISC DISCONNECTDP DISTRIBUTION PANELBOARDDW DISHWASHERECS EMERGENCY COMMUNICATION SYSTEMEGB ELECTRICAL GROUNDING BUSBAREMD ESTIMATED MAXIMUM DEMANDEMGB ELECTRICAL MAIN GROUNDING BUSBAREP EXPLOSION PROOFERMS ENERGY REDUCTION MAINTENANCE SWITCHEWC ELECTRIC WATER COOLERFA FIRE ALARMFAA FIRE ALARM ANNUNCIATORFACP FIRE ALARM CONTROL PANELFC FOOT CANDLEFLA FULL LOAD AMPSFS FLOW SWITCHFSD FIRE SMOKE DAMPERG EQUIPMENT GROUNDING CONDUCTORGEN GENERATORGFI, GFCI GROUND FAULT CIRCUIT INTERRUPTERGFPE GROUND FAULT PROTECTION OF EQUIPMENTGND EQUIPMENT GROUNDING CONDUCTORHH HANDHOLEHOA HAND-OFF-AUTOMATICHP HORSE POWERIC INTERCOMIG ISOLATED GROUNDJB JUNCTION BOXKAIC THOUSAND AMPERE INTERRUPTING CIRCUITKV KILOVOLTKVA KILOVOLT AMPERESKW KILOWATTLT LIGHTLTG LIGHTINGMCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMH MANHOLEMLO MAIN LUGS ONLYMOCP MAXIMUM OVERCURRENT PROTECTIONMRTS MOTOR RATED TOGGLE SWITCHMSB MAIN SWITCHBOARDMTD MOUNTEDMTG MOUNTINGMTS MAIN TRANSFER SWITCHN NEUTRALN.C. NORMALLY CLOSEDN.O. NORMALLY OPENNF NON-FUSEDNL NIGHT LIGHTOFCI OWNER FURNISHED CONTRACTOR INSTALLEDOS&Y OUTSIDE SCREW AND YOKEP POLE(S)PA PUBLIC ADDRESSPB PULL BOXPH PHASEPIV POST INDICATOR VALVEPNL PANELPWR POWERRCP REFLECTED CEILING PLANRECPT RECEPTACLEREF REFERENCERESP RESPONSIVESCCR SHORT CIRCUIT CURRENT RATINGSD SMOKE DAMPERSEC SECONDARYSPD SURGE PROTECTION DEVICESWBD SWITCHBOARDTBB TELECOMMUNICATIONS BONDING BACKBONETC TIME CLOCKTGB TELECOMMUNICATIONS GRONDING BUSBARTMGB TELECOMMUNICATIONS MAIN GRONDING BUSBARTO TELECOMMUNICATIONS OUTLETTR TELECOMMUNICATIONS ROOMTS TAMPER SWITCHTV TELEVISIONUG UNDERGROUNDUPS UNINTERRUPTABLE POWER SUPPLYV VOLTVA VOLT-AMPEREVFD VARIABLE FREQUENCY DRIVEW WIREWA TELECOMMUNICATIONS WORK AREAWG WIRE GUARDWP WEATHER-PROOF (NEMA 3R)XFMR TRANSFORMERGENERAL NOTES1 MODIFICATIONS TO EXISTING POWER DISTRIBUTION EQUIPMENT: MATCH EXISTINGMANUFACTURER, SWITCH TYPE, FUSE TYPE, BREAKER TYPE AND KAIC RATING FOR ALLINSTALLED DEVICES.2 EXISTING PANEL DIRECTORIES AT PANELS AFFECTED BY WORK: PROVIDE UPDATEDTYPED PANEL DIRECTORY. CONSULT OWNER FOR INPUT ON LABELING OF ALL EXISTINGCIRCUITS.3 DEVICES AND LIGHT FIXTURES DENOTED 'ER' ARE EXISTING TO BE RELOCATED. NOTIFYA/E IF DEVICES OR FIXTURES ARE DAMAGED.GENERAL SYSTEMS NOTESDIVISION 261 TELECOMMUNICATIONS OUTLETS: PROVIDE TWO-GANG BOX (2.25-INCH DEEPMINIMUM) WITH SINGLE-GANG STRAP MOUNT PLASTER RING AND 1-INCHCONDUIT STUBBED INTO ACCESSIBLE SPACE ABOVE FINISHED CEILING(EXCEPTION: VOICE-ONLY OR VIDEO-ONLY OUTLETS PER NOTE BELOW).2 TELECOMMUNICATIONS OUTLET INDICATED AS ROUGH IN ONLY (NOSUBSCRIPTS): INSTALL PER NOTE ABOVE, WITH BLANK 302SS SINGLE-GANGWALLPLATE.3 VOICE-ONLY OR VIDEO-ONLY TELECOMMUNICATIONS OUTLET: PROVIDESINGLE-GANG BOX WITH 1-INCH CONDUIT STUBBED INTO ACCESSIBLE SPACEABOVE FINISHED CEILING.4 MISCELLANEOUS LOW VOLTAGE OUTLETS (CALL STATIONS, HANDSETS, VOLUMECONTROL, MICROPHONE OUTLETS, SURFACE-MOUNT WALL SPEAKERS AND FIREALARM DEVICES): PROVIDE SINGLE-GANG BOX WITH 3/4-INCH CONDUIT STUBBEDINTO ACCESSIBLE SPACE ABOVE FINISHED CEILING.5 INSULATED BUSHINGS: PROVIDE BUSHINGS ON ALL CONDUIT STUB UPS,INCLUDING BUT NOT LIMITED TO, OUTLETS FOR TELECOMMUNICATIONS, FIREALARM, SECURITY, ACCESS CONTROL, MASS NOTIFICATION, PUBLIC ADDRESS,ALL OTHER LOW VOLTAGE INTERCOMMUNICATIONS AND UNUSED STUB-UPS ORSTUB-UPS INDICATED FOR FUTURE USE.6 FLOOR BOXES CONTAINING TELECOMMUNICATIONS OUTLETS: FOR EACHLOW-VOLTAGE COMPARTMENT, ROUTE 1-INCH CONDUIT WITH PULL STRINGUNDERFLOOR, UP NEAREST WALL, AND STUB INTO ACCESSIBLE SPACE ABOVEFINISHED CEILING. LABEL CONDUIT END 'FLOOR BOX'7 SLEEVES FOR LOW VOLTAGE CABLES: PROVIDE 2-INCH SLEEVES UNLESS NOTEDOTHERWISE. COORDINATE WITH PATH OF DUCTWORK AND GWB CEILING TOENSURE ACCESSIBILITY, EXTEND SLEEVES AS REQUIRED. INSTALL ALL SLEEVES4-INCHES ABOVE HIGHER CEILING OF TWO ADJACENT SPACES. REFER TO ROOMFINISH SCHEDULES AND REFLECTED CEILING PLANS FOR CEILING HEIGHTS.STUB SLEEVES INTO JOIST SPACE OF FINISHED ROOMS WITH EXPOSEDSTRUCTURE. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF ALL SLEEVES,INCLUDING UNUSED SLEEVES. PROVIDE GROUT OR ESCUTCHEONS TO SECURESLEEVES TO WALL. PROVIDE FIRE-RATED SLEEVES AT ALL FIRE-RATED WALLS.8 PROVIDE ADDITIONAL CONDUIT, BOXES, CONDUCTORS AND OVERCURRENTPROTECTION FOR 120-VOLT BRANCH CIRCUITS NOT SPECIFICALLY COVEREDUNDER DIVISION 26 WORK, BUT REQUIRED TO COMPLETE DIVISION 08 AND 28WORK. DEVICES SHALL INCLUDE, BUT NOT BE LIMITED TO, POWER SUPPLIESFOR DOOR HARDWARE, ACCESS CONTROL, FIRE ALARM AND VIDEOSURVEILLANCE.9 CARD READERS: PROVIDE RECESSED SINGLE-GANG BOX WITH GASKETEDBLANK COVERPLATE AND EMPTY 1-INCH CONDUIT STUBBED INTO NEARESTACCESSIBLE SPACE ABOVE FINISHED CEILING OR JOIST SPACE OF ADJACENTEXPOSED STRUCTURE. LABEL CONDUIT END 'CARD READER'.10 PROVIDE WATERFALL DROPOUTS AT ALL CABLE TRAY LOCATIONS ABOVERUNWAYS, WALL/FLOOR MOUNTED RACKS, AND EQUIPMENT ENCLOSURES.11 AUDIO VISUAL (AV) SYSTEMS: PROVIDE RECESSED BOXES, CONDUIT AND PULLSTRINGS FOR ALL SYSTEM COMPONENTS.GENERAL POWER NOTES1 VERIFY ANY NEUTRAL WIRES REQUIRED ON 1Ø OR 3Ø MECHANICAL UNITSFURNISHED UNDER DIVISION 23. IF REQUIRED, PROVIDE NEUTRAL.2 PROVIDE DEDICATED 120-VOLT CIRCUITS TO ALL HVAC BAS CONTROL DEVICESAND PANELS. COORDINATE QUANTITY WITH DIVISION 23. UTILIZE NEARESTSPARE 120-VOLT, 20/1 BREAKER. LABEL TYPED PANEL DIRECTORY ACCORDINGTO LOAD BEING SERVED.3 IN ADDITION TO DEVICES SHOWN, SEE SCHEDULE SHEETS FOR CONNECTIONSTO ALL MECHANICAL EQUIPMENT.4 LOCATE SWITCHES FOR CONTROL OF FANS IN TWO-GANG BOX WITH LIGHTSWITCH WHERE APPLICABLE.5 PROVIDE #10AWG CONDUCTORS FOR ALL WARM AIR DRYER CIRCUITS. PROVIDELOCKOUT DEVICE AT ALL BREAKERS SERVING WARM AIR DRYERS.ELECTRICAL SYMBOLSGENERAL DEVICE BOX NOTES1 SEE SYMBOLS LEGEND THIS SHEET FOR MOUNTING HEIGHTS UNLESS NOTED OTHERWISEON DRAWINGS.2 ALL MOUNTING HEIGHTS ARE TO CENTERLINE OF BOXES UNLESS NOTES OTHERWISE.3 PROVIDE BOX EXTENDER FOR FLUSH INSTALLATION OF DEVICES LOCATED INARCHITECTURAL CASEWORK THAT IS FLUSH WITH ADJACENT WALL (SUCH ASRECEPTACLES FOR GARBAGE DISPOSERS).4 FLOOR BOXES: OBTAIN OWNER APPROVAL OF ALL BOX LOCATIONS PRIOR TO ROUGH IN.PROVIDE DEVICE PLATES AT DEVICES AND BLANK PLATES AT ALL UNUSEDCOMPARTMENTS.5 COORDINATE LOCATION OF DEVICE BOXES FOR SWITCHES, RECEPTACLES, ANDSYSTEMS DEVICES WITH MARKERBOARDS. ADJUST BOX LOCATIONS TO AVOIDMARKERBOARDS.6 COORDINATE LOCATION OF DEVICE BOXES FOR SWITCHES, RECEPTACLES, ANDSYSTEMS DEVICES WITH TACKBOARDS. ADJUST BOX LOCATIONS TO AVOIDTACKBOARDS. PROVIDE BOX EXTENDER FOR A FLUSH INSTALLATION WHERE DEVICESMUST BE MOUNTED AT TACKBOARD/TACKWALL.7 CEILING MOUNTED RECEPTACLES: AT SUSPENDED CEILINGS, ROUTE POWER TORECEPTACLE VIA FLEXIBLE METALLIC CONDUIT WITH 6-FOOT SERVICE LOOP. FEED FMCFROM A J-BOX RIGIDLY SUPPORTED A MAXIMUM OF 24-INCHES ABOVE SUSPENDEDCEILING OR AT BOTTOM OF STRUCTURE ABOVE, WHICHEVER IS LOWER. LOCATE J-BOXDIRECTLY ABOVE RECEPTACLE AND SUPPORT VIA STRUCTURE, OR VIA THREAD ROD ANDUNISTRUT HUNG FROM STRUCTURE ABOVE IN HIGH STRUCTURE APPLICATIONS.8 DEVICES RECESSED IN MULLIONS: BACK BOXES TO BE RECESSED FOR FLUSHINSTALLATION OF DEVICE AND WALLPLATE. EXTEND CONCEALED CONDUIT IN MULLIONUP TO WALL ABOVE AND STUB OUT ABOVE ACCESSIBLE CEILING. IN AREAS WITH NOCEILING, EXTEND CONDUIT TOWARDS CABLING SOURCE TO ABOVE NEARESTACCESSIBLE CEILING.NOTESGENERAL SYSTEMS NOTESDIVISION 271 ALL SPEAKERS AND HORN-TYPE SPEAKERS ARE PART OF THE INTERCOMSYSTEM, UNLESS NOTED OTHERWISE.2 PROVIDE SURFACE MOUNT ENCLOSURE AND BAFFLE FOR ALL SPEAKERS INFINISHED SPACES WITH NO CEILINGS (EXPOSED STRUCTURE).3 PROVIDE WIREGUARDS ON ALL CLOCKS IN GYMNASIUMS.4 UTILIZE SLEEVES AND FIRE RATED SLEEVES AT RATED WALLS PROVIDED UNDERDIVISION 26 FOR INSTALLATION OF ALL LOW VOLTAGE CABLING. FOLLOWINDUSTRY STANDARDS TO MAINTAIN 40% FILL REQUIREMENTS IN ALL SLEEVES(SUPERSEDES NEC - DO NOT FILL SLEEVES TO CAPACITY). PROVIDE ADDITIONALSLEEVES MEETING DIVISION 26 REQUIREMENTS AS REQUIRED.5 SYSTEM PANEL LOCATIONS: AUXILIARY SYSTEM PANELS, POWER SUPPLIES OROTHER EQUIPMENT ENCLOSURES SHALL NOT BE LOCATED IN TELECOM ROOMSUNLESS NOTED OTHERWISE. IF DRAWINGS DO NOT DEPICT LOCATIONS FORAUXILIARY COMPONENTS, CONSULT OWNER OR A/E FOR APPROVED LOCATIONSPRIOR TO EQUIPMENT INSTALL.GENERAL SYSTEMS NOTESDIVISION 281 PROVIDE MINIMUM CANDELA RATINGS FOR ROOMS WITH WALL MOUNTED VISUALNOTIFICATION APPLIANCES AS FOLLOWS:• <20'x20' = 15cd• <28'x28' = 30cd• <40'x40' = 60cd• >40'x40' = 110cd2 PROVIDE MINIMUM CANDELA RATINGS FOR ROOMS WITH CEILING MOUNTEDVISUAL NOTIFICATION APPLIANCES ON MAXIMUM 10' HIGH CEILING AS FOLLOWS:• <20'x20' = 15cd• <30'x30' = 30cd• <40'x40' = 60cd• >40'x40' = 110cd3 INCREASE DEVICE RATINGS/SETTINGS WHEN LOCATED OFF-CENTER IN ROOMSTO MAINTAIN NFPA COVERAGE.4 VISUAL DEVICES IN CORRIDORS SHALL BE 15cd. VISUAL DEVICES LOCATED INOTHER AREAS SHALL BE 110cd UNLESS NOTED OTHERWISE.5 IN ADDITION TO DEVICES SHOWN, SEE SCHEDULE SHEETS FOR FIRE ALARMSYSTEM DEVICES CONNECTIONS TO MECHANICAL EQUIPMENT.6 PROVIDE FIRE ALARM MONITORING OF ALL FLOW AND TAMPER SWITCHES.CONFIRM QUANTITIES AND LOCATION WITH DIVISION 21.7 UTILIZE SLEEVES AND FIRE RATED SLEEVES AT RATED WALLS PROVIDED UNDERDIVISION 26 FOR INSTALLATION OF ALL LOW VOLTAGE CABLING. FOLLOWINDUSTRY STANDARDS TO MAINTAIN 40% FILL REQUIREMENTS IN ALL SLEEVES(SUPERSEDES NEC - DO NOT FILL SLEEVES TO CAPACITY). PROVIDE ADDITIONALSLEEVES MEETING DIVISION 26 REQUIREMENTS AS REQUIRED.8 SYSTEM PANEL LOCATIONS: AUXILIARY SYSTEM PANELS, POWER SUPPLIES OROTHER EQUIPMENT ENCLOSURES SHALL NOT BE LOCATED IN TELECOM ROOMSUNLESS NOTED OTHERWISE. IF DRAWINGS DO NOT DEPICT LOCATIONS FORAUXILIARY COMPONENTS, CONSULT OWNER OR A/E PRIOR TO EQUIPMENTINSTALLATION.9 DUCT SMOKE DETECTION: DETERMINE QUANTITY AND PLACEMENT OFDETECTORS REQUIRED FOR COVERAGE OF DUCTWORK BASED ON NFPAREQUIREMENTS. PROVIDE MECHANICAL EQUIPMENT FAN SHUTDOWN RELAY ATALL DUCT DETECTORS. SEE HVAC PLANS FOR EQUIPMENT LOCATIONS.COORDINATE SHUTDOWN CONTROL WITH DIVISION 23.10 SMOKE DAMPERS AND FIRE-SMOKE DAMPERS: PROVIDE FIRE ALARMCONNECTION AND 120-VOLT POWER TO EACH FIRE/SMOKE DAMPER SHOWN ONHVAC PLANS. PROVIDE DEDICATED CIRCUIT TO DAMPERS, ROUTED THROUGHNORMALLY CLOSED FIRE ALARM RELAY, MOUNTED ON WALL IN NEARESTELECTRICAL ROOM. COORDINATE WITH DAMPER MANUFACTURER FOR SPECIFICDAMPER LOAD REQUIREMENTS. RELAY SHALL BE CONTROLLED BY FACP, SUCHTHAT, ON GENERAL ALARM DAMPERS CLOSE. FIRE ALARM CONNECTION TODAMPER SHALL BE A SUPERVISORY CIRCUIT MONITORING STATUS OF INTEGRALSMOKE DETECTOR, AND SHALL PROVIDE REMOTE FIRE/SMOKE DAMPER RESET.FACP SHALL INITIATE A SUPERVISORY SIGNAL WHEN INTEGRAL DETECTORGOES INTO ALARM. FIRE/SMOKE DAMPERS MAY BE GROUPED TOGETHER ONSUPERVISORY CIRCUITS TO SIMPLIFY WIRING. COORDINATE REQUIREMENTSWITH FIRE/SMOKE DAMPER MANUFACTURER. UTILIZE SPARE 20/1 BREAKERS.LABEL TYPED PANEL DIRECTORY 'FIRE/SMOKE DAMPERS - (INDICATE AREASERVED)'.11 PROVIDE WIREGUARDS ON ALL FIRE ALARM STROBES AND HORN/STROBES INGYMNASIUMS.DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
JJJJJNMLK1234JHGFEDC© DLR GroupREVISIONSKEY PLANABDC-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:17 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 01 -ELECTRICALDEMOLITIONPLANED1.1Enter address hereclient nameGENERAL NOTESABSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 01 - ELECTRICAL DEMOLITION PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
TTTNMLK1234JHGFEDC© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:18 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 02 -ELECTRICALDEMOLITIONPLANED1.2Enter address hereclient nameGENERAL NOTESABSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 02 - ELECTRICAL DEMOLITION PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
SDSDSDSDOSOSOSOSOSOSOSOSOSOSNMLK1234JHGFEDCDL2 DL2 DL2 DL2 DL2 DL2PL3PL3PL3DL2DL2DL2 DL2 DL2 DL2PL2PL2PL2PL2RL2RL2RL2RL2RL2RL2RL2RL2RL2RL2RL2RL2RL2PL3 PL3 PL3 PL3DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2DL2 DL2 DL2 DL2 DL2 DL2 DL2 DL2 DL2 DL2PL1TK2TK2TH2 TH2TH2TH2TYP.TYP.MODELING ROOM107CIRCULATION111LARGE CONF110WOMEN113VEST.114MEN115VEST.116LUNCH ROOM122STORAGE129JANITOR123CIRCULATION117MED CONF119CLOS-1118-1LIFTL101SHARED OFFICE120© DLR GroupREVISIONSKEY PLANABDC-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:39:56 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 01 -LIGHTING PLANE1.1Enter address hereclient nameGENERAL NOTESA SAMPLE NOTE 1B SAMPLE NOTE 2SHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 01 - LIGHTING PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
OSOSOSOSOSOSOSOSSDSDSDSDSDSDSDSLVSLVOSOSSLVNMLK1234JHGFEDCSTUDIO213OFFICE214MED CONF212VR SPACE210MICROKITCHEN209MOTHER211STUDIO200OFFICE202OFFICE203PRINT204STAIR 1S201PHONE201LIFTL201OFFICE205OFFICE206TOILET208TOILET207PRESENTATION-2108-2SpaceA173DL2RL1RL1RL1RL1RL1RL1RL1RL1RL1RL1RL1RL1RL1RL1PL1 PL1 PL1 PL1PL1PL1PL1PL1PL1 PL1 PL1PL1PL1PL1PL1PL2PL2PL2PL2PL2PL2PL2PL2PL2PL2PL3PL3PL3TYPTK1TH1PL1UC1 UC1PL2PL1PL1PL1PL1PL1PL1WL1WL1WL1DL2DL2DL2DL2PL1PL1PL1PL1PL2 PL2 PL2 PL2PL2PL2PL2PL2PL2PL2PL1 PL1 PL1 PL1 PL1 PL1 PL1 PL1PL1 PL1 PL1 PL1PL1PL1PL1PL1PL1PL1PL1PL4PL5PL5PL5PL5PL5 PL5PL5PL5 PL5 PL5 PL5 PL5 PL5PL5PL5PL5PL5PL5PL5 PL5 PL5 PL5 PL5© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:04 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 02 -LIGHTING PLANE1.2Enter address hereclient nameGENERAL NOTESA SAMPLE NOTE 1B SAMPLE NOTE 2SHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 02 - LIGHTING PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
AVJJAVNMLK1234JHGFEDC© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:06 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 01 -POWER PLANE2.1Enter address hereclient nameGENERAL NOTESABCSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 01 - POWER PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
JJJJJAVNMLK1234JHGFEDCTG-BA2ATG-AC2LCPCMDP© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:09 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 02 -POWER PLANE2.2Enter address hereclient nameGENERAL NOTESABCSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 02 -POWER PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
AVPPP301/4301/4JJAVNMLK1234JHGFEDC© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:10 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 01 -SPECIALSYSTEMS PLANE3.1Enter address hereclient nameGENERAL NOTESABSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 01 - SPECIAL SYSTEMS PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
JJJJJAV301/4301/4301/4PPP751/4PP301/4301/4NMLK1234JHGFEDC© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:12 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusLEVEL 02 -SPECIALSYSTEMS PLANE3.2Enter address hereclient nameGENERAL NOTESABSHEET NOTEST R U EN SCALE:1/8" = 1'-0"LEVEL 02 -SPECIAL SYSTEMS PLANDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
SUBSTATION XFMR12.47KV-2400/1390V600450????XFMR TG-MDP2400V-480Y/277V1500 KVASWITCHBOARD,MDP480Y277 VOLT2000 AMP BUS42K SCCRROOM XXXXMAIN2000/3GFPEERMSxxE6.xSPDM225/3150-PTG-A150 KVA150-SPANELASPDPANELASECONDSECTIONPANELA2110/3225/3225/3400/3TG-B75 KVAPANELB75-P75-S225/3225-4WPANELCLCP225-4WPANELC2400-4WPANELC3600/3SPACE225/3SPACE225/3SPACE225/3PANELC4225-4WPANELC3SECONDSECTIONPANELA3SECONDARYx SETS xxx KCMIL IN x-INCH C.PRIMARYPROVIDE EMPTY C. AS DIRECTED BY THE UTILITYSUBSTATION 1MH7MSC BLDG.PPD WAREHOUSEPB7AFEEDER SCHEDULE - COPPERMARK (AMPS)MARK SUFFIXCONDUIT SIZE# SETS Ø & N GND-3W-4W -2W2015 1 12 12 3/4" 3/4" 3/4"1 12 12 3/4" 3/4" 3/4"25 1 10 10 3/4" 3/4" 3/4"30 1 10 3/4" 3/4" 3/4"35 1 8 3/4" 3/4" 3/4"40 1 8 3/4" 3/4"45 1 6 1" 3/4" 3/4"50 1 6 1" 3/4" 3/4"101010103/4"60 170 180 190 1100 1110 1125 1150 1175 1200 1225 1250 14 10 1-1/4" 1" 3/4"4 8101-1/4" 1"8883211-1/4" 1"1-1/4"1-1/4" 1"1-1/4"1-1/2" 1-1/4"1-1/2"61 1-1/2" 1-1/4"1-1/2"666611/01-1/2" 1-1/4"1-1/2"1-1/2" 1-1/4"2"2/0 1-1/2" 1-1/4"2"3/0 2" 1-1/2"2"300 1350 1400 1450 2500 244/0 2" 1-1/2"2-1/2"4433250350 2"2-1/2"3"500 2-1/2"3"3-1/2"600 3" 2-1/2"3-1/2"224/0 2" 1-1/2"2-1/2"250 2"2-1/2"2-1/2"600700800100012001600200025003000400011/01/02/03/04/0250350400500223505002"2-1/2"3"2-1/2"3"3-1/2"2 600 3"3-1/2"3 400 2-1/2"3"3"3 600 3"3-1/2"4 600 3"3-1/2"5 600 3"3-1/2"4"6 600 3"3-1/2"4"8 500 3-1/2"10 600 3"3-1/2"4"ABBREVIATIONS:Ø PHASEN NEUTRALGND EQUIPMENT GROUNDING CONDUCTOR-4W FOUR WIRE + GROUND (3Ø,N,GND)-3W THREE WIRE + GROUND (3Ø,GND or 2Ø,N,GND)-2W TWO WIRE + GROUNDNOTES:1. CONDUCTOR AMPACITIES ARE BASED ON NEC TABLE 310.15(B)(16).2. CONDUIT SIZES ARE BASED ON A MAXIMUM FILL RATIO OF 40%.3. SCHEDULE SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS WHERE APPLICABLE.4. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR.5. SCHEDULE IS VALID FOR TYPE THHN, THWN-2, AND XHHW-2 CONDUCTORS. SEE SPECIFICATIONS FOR CONDUCTOR TYPES REQUIRED.6. SCHEDULE IS VALID FOR TYPE EMT, IMC, FMC, LFMC, HDPE, AND RNC-40 RACEWAYS. SEE SPECIFICATIONS FOR RACEWAY APPLICATIONS.7. OPTIONAL CONFIGURATIONS (1 OR 2 SETS) ARE GIVEN FOR SOME SIZES. 8. NOT ALL SIZES USED.3/4"2" 1-1/2"2-1/2"2-1/2"3-1/2"3-1/2"2-1/2"3"400 2 33/0 2" 1-1/2"2"3-PHASE TRANSFORMER PRIMARY AND SECONDARY SCHEDULE - ALUMINUMXFMRKVAGND C153045754112.541502225130K-S45K-S75K-S112K-S12"2"3001/0150K-S2-1/2"3-1/2"2-1/2"ABBREVIATIONS:NOTES:1. CONDUCTOR AMPACITIES ARE BASED ON NEC TABLE 310.15(B)(16).2. CONDUIT SIZES ARE BASED ON A MAXIMUM FILL RATIO OF 40%.3. SCHEDULE SHALL BE USED FOR TRANSFORMERS WITH THE FOLLOWING CONFIGURATION:480 V DELTA PRIMARY AND 208Y/120 V SECONDARY4. ALL FEEDERS TO TRANSFORMERS SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR.5. SCHEDULE IS VALID FOR TYPE THHN, THWN-2, AND XHHW-2 CONDUCTORS. SEE SPECIFICATIONS FOR CONDUCTOR TYPES REQUIRED.6. SCHEDULE IS VALID FOR TYPE EMT, IMC, FMC, LFMC, HDPE, AND RNC-40 RACEWAYS. SEE SPECIFICATIONS FOR RACEWAY APPLICATIONS.7. NOT ALL SIZES USED.15K-S3/0 41 300 1/01 3/0750225K-S300K-S2 3/03502 4/07503 250600# SETSMARK ØØ & NPRIMARYBJ C# SETSMARKSECONDARY15K-PAMPSAMPS150150225175350250500350700500100030K-P45K-P75K-P112K-P150K-P225K-P300K-P1 3/01 4/01 3501 7502 3502"3"4"4"4"3"Ø PHASEBJ BONDING JUMPERC CONDUIT SIZEN NEUTRALGND EQUIPMENT GROUNDING CONDUCTOR-P PRIMARY - THREE WIRE + GROUND (3Ø,GND)-S SECONDARY - FOUR WIRE + BONDING JUMPER (3Ø, N, BJ)ALUMINUM NOT PERMITTED - USE COPPERALUMINUM NOT PERMITTED - USE COPPERALUMINUM NOT PERMITTED - USE COPPERALUMINUM NOT PERMITTED - USE COPPERALUMINUM NOT PERMITTED - USE COPPER3-PHASE TRANSFORMER PRIMARY AND SECONDARY SCHEDULE - COPPERXFMRKVAGND C153010458756112.561504225330K-S45K-S75K-S112K-S3/4"1"1 6111-1/2"1-1/2"3002150K-S2"3"2-1/2"ABBREVIATIONS:NOTES:1. CONDUCTOR AMPACITIES ARE BASED ON NEC TABLE 310.15(B)(16).2. CONDUIT SIZES ARE BASED ON A MAXIMUM FILL RATIO OF 40%.3. SCHEDULE SHALL BE USED FOR TRANSFORMERS WITH THE FOLLOWING CONFIGURATION:480 V DELTA PRIMARY AND 208Y/120 V SECONDARY4. ALL FEEDERS TO TRANSFORMERS SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR.5. SCHEDULE IS VALID FOR TYPE THHN, THWN-2, AND XHHW-2 CONDUCTORS. SEE SPECIFICATIONS FOR CONDUCTOR TYPES REQUIRED.6. SCHEDULE IS VALID FOR TYPE EMT, IMC, FMC, LFMC, HDPE, AND RNC-40 RACEWAYS. SEE SPECIFICATIONS FOR RACEWAY APPLICATIONS.7. NOT ALL SIZES USED.10 15K-S3/4" 6 811/0 61 4/0 21 1/0500225K-S300K-S2 1/02502 2/05003 3/0400# SETSMARK ØØ & NPRIMARYBJ C# SETSMARKSECONDARY10115K-P1"AMPSAMPS25505010070150150225175350250500350700500100030K-P45K-P75K-P112K-P150K-P225K-P300K-P1 61 41 1/01 2/01 2501 5002 2501-1/2"2"2-1/2"3-1/2"3-1/2"3"2-1/2"Ø PHASEBJ BONDING JUMPERC CONDUIT SIZEN NEUTRALGND EQUIPMENT GROUNDING CONDUCTOR-P PRIMARY - THREE WIRE + GROUND (3Ø,GND)-S SECONDARY - FOUR WIRE + BONDING JUMPER (3Ø, N, BJ)FEEDER SCHEDULE - ALUMINUMMARK (AMPS)MARK SUFFIXCONDUIT SIZE# SETS Ø & N GND-3W-4W -2W125 1150 1175 1200 1225 1250 144442/03/02" 1-1/2"2"2"4/0250300 1350 1400 2450 2500 22300113505007502501/01/030035060070080010001200160020002500300040002/03/03/04/0250350400600500 cu225007503 4003 6004 5005 6006 6007 750811 750ABBREVIATIONS:Ø PHASEN NEUTRALGND EQUIPMENT GROUNDING CONDUCTOR-4W FOUR WIRE + GROUND (3Ø,N,GND)-3W THREE WIRE + GROUND (3Ø,GND or 2Ø,N,GND)-2W TWO WIRE + GROUNDNOTES:1. CONDUCTOR AMPACITIES ARE BASED ON NEC TABLE 310.15(B)(16).2. CONDUIT SIZES ARE BASED ON A MAXIMUM FILL RATIO OF 40%.3. SCHEDULE SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS WHERE APPLICABLE.4. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR.5. SCHEDULE IS VALID FOR TYPE THHN, THWN-2, AND XHHW-2 CONDUCTORS. SEE SPECIFICATIONS FOR CONDUCTOR TYPES REQUIRED.6. SCHEDULE IS VALID FOR TYPE EMT, IMC, FMC, LFMC, HDPE, AND RNC-40 RACEWAYS. SEE SPECIFICATIONS FOR RACEWAY APPLICATIONS.7. OPTIONAL CONFIGURATIONS ( 1 OR 2 SETS) FOR SOME SIZES LISTED.8. USE A COPPER GROUNDING CONDUCTOR FOR THE 4000 AMP FEEDER AS LISTED ABOVE. 9. NOT ALL SIZES USED.2" 1-1/2"2-1/2" 2" 1-1/2"2-1/2" 2"2-1/2"223" 2"2-1/2"3" 2"2-1/2"3-1/2" 2-1/2"3"4" 3"3-1/2"2-1/2" 2"2-1/2"3" 2"2-1/2"3" 2"2-1/2"3-1/2" 2-1/2"3"4" 3"3-1/2"2-1/2"3"3"3"3-1/2"3-1/2"3-1/2" 2-1/2"3"4" 3"3-1/2"4" 3"3-1/2"4" 3-1/2"4"600750 4" 3-1/2"4"4" 3-1/2"4"350 2 14/0 2-1/2" 1-1/2"2"110 1 41/0 1-1/2" 1-1/4"2"201525303540455060708090100ALUMINUM IS NOT PERMITTED FOR SIZES 100AMP AND UNDER -USE COPPER100-4W© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:13 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusELECTRICALONE-LINEDIAGRAMSE5.1Enter address hereclient nameDocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
© DLR GroupREVISIONS-NOT FOR CONSTRUCTION -ABCDEF123451/12/2023 5:40:14 PMAutodesk Docs://73-22135-00 Paccar-Kenworth R & D Building Remodel/73-22135-00_Paccar-Kenworth R & D Building_MEP_2022.rvtProject NumberIssue DateDLR MEP 2022 STARTER PROJECTProject StatusELECTRICALSCHEDULESE7.1Enter address hereclient nameIECC COMMISSIONING NOTES:PROJECT SHALL BE COMMISSIONED IN ACCORDANCE WITH SECTION C408 OF IECC 2021.IN ADDITION TO OTHER PROJECT REQUIREMENTS. THE FOLLOWING DOCUMENTATIONSHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF RECEIPTOF THE CERTIFICATE OF OCCUPANCY. • OPERATING AND MAINTENANCE MANUAL WITH COMPONENTS INDICATED IN C408.2.5.2. • AS BUILT DRAWINGS FOR ELECTRICAL POWER SYSTEMS. • DOCUMENTATION CERTIFYING LIGHTING SYSTEM FUNCTIONAL TESTING INCLUDING: 1. OCCUPANT SENSOR CONTROLS 2. TIME-SWITCH CONTROLS 3. DAYLIGHT RESPONSIVE CONTROLSNOTES:1. VERIFY ALL ON / OFF, OCCUPIED / UNOCCUPIED TIMES WITH OWNER PRIOR TO PROGRAMMING.GENERAL NOTES:A. ALL LIGHTING CONTROLS TO COMPLY WITH 2021 IECC.B. PROVIDE RELAY PANEL SYSTEM WITH ONE MASTER PANEL AND MULTIPLE SUB-PANELS. COORDINATE EXACT LOCATION WITH ELECTRICAL ENGINEER PRIOR TO ROUGH-IN.C. PROVIDE NUMBER OF ZONES AS INDICATED ON PLANS.D. PROVIDE 1 - 10 V DIMING ON ALL 277V DIMMING ZONES AND FORWARD PHASE DIMMING ON ALL 120 V DIMMING ZONES.E. LIGHTING CONTROLS INDICATED ARE FOR REFERENCE ONLY AND MUST BE COORDINATED WITH CONTROLS SHOP DRAWINGS FOR EXACT QUANTITIES OF SENSORS, DEVICES, AND ALL NECESSARY CONNECTIVITY EQUIPMENT.F. PROVIDE UL 924 RELAYS FOR EMERGENCY EGRESS LIGHTING TO ALLOW FULL CONTROLS UNDER NORMAL CONDITIONS. EMERGENCY EGRESS LUMINAIRES SHALL TURN FULL "ON" UPON LOSS OF NORMAL POWER.G. COMPLETE COMMISSIONING OF CONTROL SYSTEM AND PROVIDE REPORT TO ENGINEER FOR REVIEW.LIGHTING CONTROL MATRIXSPACE TYPEROOM / ZONECATEGORY FIXTURE GRADE (S, VR, MIN, MAX) NIGHT LIGHT SWITCH TYPE ALWAYS ON(SECURITY) STANDARD SWITCHING (ON - OFF ONLY) CONTROLLED BY COMMAND CENTER VACANCY SENSOR (MANUAL ON, AUTO OFF) OCCUPANCY SENSOR (AUTO ON, AUTO OFF) SENSOR TIMEOUTPERIOD(MIN) RELAY PANEL DISTRIBUTEDRELAY PROGRAMMED SCHEDULE CONTROL SCHEDULED ON AT ( NOTE 1 ) SCHEDULED OFF AT ( NOTE 1 ) DIMMINGCONTROL DUSK TO DAWN LIGHT LEVEL MAINTAINED AT(IN FOOTCANDLES @ 2'-6" AFF) RECEPTACLE CONTROLCOMMENTSIECC COMMISSIONING NOTES:PROJECT SHALL BE COMMISSIONED IN ACCORDANCE WITH SECTION C408 OF IECC 2021. INADDITION TO OTHER PROJECT REQUIREMENTS. THE FOLLOWING DOCUMENTATION SHALL BEPROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THECERTIFICATE OF OCCUPANCY. • OPERATING AND MAINTENANCE MANUAL WITH COMPONENTS INDICATED IN C408.2.5.2. • AS BUILT DRAWINGS FOR ELECTRICAL POWER SYSTEMS. • DOCUMENTATION CERTIFYING LIGHTING SYSTEM FUNCTIONAL TESTING INCLUDING: 1. OCCUPANT SENSOR CONTROLS 2. TIME-SWITCH CONTROLS 3. DAYLIGHT RESPONSIVE CONTROLSNOTES:1. VERIFY ALL ON / OFF, OCCUPIED / UNOCCUPIED TIMES WITH OWNER PRIOR TO PROGRAMMING.GENERAL NOTES:A. ALL LIGHTING CONTROLS TO COMPLY WITH 2021 IECC.B. PROVIDE RELAY PANEL SYSTEM WITH ONE MASTER PANEL AND MULTIPLE SUB-PANELS. COORDINATE EXACT LOCATION WITH ELECTRICAL ENGINEER PRIOR TO ROUGH-IN.C. PROVIDE NUMBER OF ZONES AS INDICATED ON PLANS.D. PROVIDE 1 - 10 V DIMING ON ALL 277V DIMMING ZONES AND FORWARD PHASE DIMMING ON ALL 120 V DIMMING ZONES.E. LIGHTING CONTROLS INDICATED ARE FOR REFERENCE ONLY AND MUST BE COORDINATED WITH CONTROLS SHOP DRAWINGS FOR EXACT QUANTITIES OF SENSORS, DEVICES, AND ALL NECESSARY CONNECTIVITY EQUIPMENT.F. PROVIDE UL 924 RELAYS FOR EMERGENCY EGRESS LIGHTING TO ALLOW FULL CONTROLS UNDER NORMAL CONDITIONS. EMERGENCY EGRESS LUMINAIRES SHALL TURN FULL "ON" UPON LOSS OF NORMAL POWER.G. COMPLETE COMMISSIONING OF CONTROL SYSTEM AND PROVIDE REPORT TO ENGINEER FOR REVIEW.LIGHTING CONTROL MATRIXROOM / AREA FIXTURE GRADE (S, VR, MIN, MAX) NIGHT LIGHT SWITCH TYPE ALWAYS ON(SECURITY) STANDARD SWITCHING (ON - OFF ONLY) CONTROLLED BY COMMAND CENTER VACANCY SENSOR (MANUAL ON, AUTO OFF) OCCUPANCY SENSOR (AUTO ON, AUTO OFF) SENSOR TIMEOUTPERIOD(MIN) RELAY PANEL DISTRIBUTEDRELAY PROGRAMMED SCHEDULE CONTROL SCHEDULED ON AT ( NOTE 1 ) SCHEDULED OFF AT ( NOTE 1 ) DIMMINGCONTROL DUSK TO DAWN LIGHT LEVEL MAINTAINED AT(IN FOOTCANDLES @ 2'-6" AFF) RECEPTACLE CONTROLCOMMENTSNO NAMENOTES:1.2.3.4.5.LIGHTING FIXTURE SCHEDULETYPECONSTRUCTIONLIGHT SOURCEELECTRICALPRODUCTNOTEDESCRIPTIONLENS/LOUVER MOUNTING LAMPLUMENSDOWNLUMENS UP CCT CRI BALLAST/DRIVER VOLT WATTSWATTS PERFOOTEMERGENCYCOMPONENTMFR MODEL CATALOG NUMBEREQUIVALENTMFRDL21.5" X 6" LINEAR MICROLIGHT DOWNLIGHT. GRAY INTERIOR FINISH WITHWHITE FLANGE. REMOTE DRIVERGRAY RECESSED LED 500 lm 0 lm 3500 K 80 1% 0-10V DIMMING 277 V 5 WAXIS LIGHTING PIXEL MIKROLITE 1.5PIMMLR-1X4-500-D55-GR-80-30-W-UNV-DP-1LUMENWERXPL16" PENDANT DOWNLIGHT SEMI-SPECULARPENDANT - 9'AFFLED 1000 lm 0 lm 3500 K 80LED DRIVER, 0-10VDIMMABLE, 10%120 V 10 WCOOPER LIGHTING PORTFOLIO LERSPC6BLERSPC6B10D010SL-EC6B10208035-6LBSS3HLITHONIAPL2PENDANT DIRECT-INDIREACT DRUM FIXTURE WITH ACOUSTIC FELT WRAP.BLACK CANOPY. GRAY FELT WITH RED EDGE BAND. CONFIRM FINAL FELTSELECTIONS WITH ARCHITECT.OPALPENDANT - 9'AFFLED 2000 lm 2000 lm 3500 K 80 1% 0-10V DIMMING 277 V 29 WCOOPER LIGHTING Shaper Sense DRUM DUOShSe-DRUM-DUO-1-L35-80-UNV-CB-STD-BL175-BL179PL3 SAME AS TYPE PL2 EXCEPT WITHOUT DRUM. 1/2" THICK RING PENDANT OPAL PENDANT LED 2000 lm 2000 lm 3500 K 80 1% 0-10V DIMMING 277 V 28 WCOOPER LIGHTING ShSe CIRCLEShSe-CIRCLE-1-L35-80-UNV-CW-STDPL420' LINEAR PENDANT WITH (5) MIKRO OPTIC DOWNLIGHTS SPACED EVENLYALONG LENGTH OF FIXTURE. SILVER FINISH.GRAY MICROLOUVERPENDANT-12'AFFLED 2500 lm 0 lm 3500 K 80 1% 0-10V DIMMING 277 V 25 WAXIS LIGHTING BEAM 2 WITH MIKRO OPTIC LUMENWERXPL5 2.5" OUTDOOR PENDANT DOWNLIGHT SEMI-SPECULARPENDANT - 9'AFFLED 1100 lm 0 lm 3500 K 90LED DRIVER, 0-10VDIMMABLE, 10%277 V 10 WCOOPER LIGHTING LUMIERE LANTERRA 10021002-A1-RCS-RW-LED3590-W-CS-L1-UNV-RSM-LSL2LITHONIARL1 2X4 LED TROFFER. CENTER LENS WITH RAISED SIDE LENSES OPAL GRID LED 3600 lm 0 lm 3500 K 80 1% 0-10V DIMMING 277 V 27 WCOOPER LIGHTING CORELITE DX3D3X-WO-36L-8-35-LD5-UNV-24-T1-STDLITHONIARL2 2X2 LED TROFFER. CENTER LENS WITH RAISED SIDE LENSES OPAL GRID LED 3500 lm 0 lm 3500 K 80 1% 0-10V DIMMING 277 V 27 WCOOPER LIGHTING CORELITE DX3D3X-WO-35L-8-35-LD5-UNV-22-T1-STDLITHONIATH1 3.25" DIAMTER BY 6" LONG TRACK HEAD, 5-50 DEGREE ZOOM ZOOM TRACK LED 1500 lm 0 lm 3500 K 90TRAILING EDGEDIMMING120 V 20 WLIGHTINGSERVICES INCLX2030-T19-08-98-30-S4-TE-120-BLZ-C0615-9035ZM-PT2-TE-120-STH2 4" DIAMTER BY 8" LONG TRACK HEAD 40 DEGREE SPOT. WHITE FINISH. ZOOM TRACK LED 1500 lm 0 lm 3500 K 98 1% 0-10V DIMMING 120 V 17 WLIGHTINGSERVICES INCLX2030-T19-08-98-30-S4-TE-120-BLX2044-T1920-9835MTK1SILVER PENDANT TRACKNAPENDANT -11'-0" AFF UNO.- 0 lm 0 lm 0 K 0 0 V 0 WLIGTHINGSERVICES INC.GEMINI TRACKTK2 WHITE SURFACE TRACK, 0-10V CONTROL NA SURFACE - 0 lm0 lm 0 K 0 0 V 0 WLIGTHINGSERVICES INC.CONTROL TRACKUC1 1" DEEP 3.5" WIDE UNDER CABINET LIGHTING. WHITE FINISH SEMI-SPECULARUNDER-CABINETLED 300 lm 0 lm 3000 K 90 1% 0-10V DIMMING 120 V <varies>COOPER LIGHTING HALO HU11 HU11-XX-D9-S-P LITHONIAWL1 LINEAR WALL FIXTURE WITH ROUND OPAL LENS. WHITE FINISH OPAL WALL LED 2950 lm 0 lm 3500 K 80 1% 0-10V DIMMING 277 V 28 WSPI LIGHTING LYON WALLSIW12108-L28W-UNV-3500K-SJB-4'-BVISANOTES:1.2.3.4.5.MECHANICAL EQUIPMENT SCHEDULEIDLOCATIONSERVESAIRFLOW(CFM)SMOKE DETECTION ELEC HEATING ELEMENTECMLOADVOLTAGE(V)PHASE DISCONNECT STARTER PANEL CIRCUIT NOCONDUIT &WIRE SIZENOTESNO. NAMELOCATION REQUIRED QTY KW SCR STAGES HPFLA(A)MCA(A)MOCP(A)TOTALLOAD(VA)DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
DLR Group inc.
a Washington corporation
51 University Street, Suite 600
Seattle, WA 98101
January 12, 2023
Re: Project Name: Paccar- Kenworth R&D DD Mechanical Summary
DLR Group Project No.: 73-22135
Paccar-Kenworth R&D DD Mechanical Summary
There exists seven rooftop gas/electric Rooftop Units (RTU’s) currently serving the building.
Of the existing rooftop units, four (4) will not be affected by the new building layout. The unaffected
units will be RTU-1, RTU-2, RTU-4 and RTU-7. These units, their associated ductwork and air terminals
serve areas that will not be altered. The other units, and the areas they serve will be addressed as
follows:
RTU-3
RTU-3 is a 7.5 ton unit that serves the existing full-height Modeling room. One half the Modeling room
will be split to two floors. The ductwork for RTU-3 will be modified so the now-single-story East half of
the room will remain conditioned by RTU-3. The new, upstairs areas will be served by new equipment.
RTU-5
Existing RTU-5 is a 3-ton gas/electric unit that serves a conference room and the rear projection room.
This unit may be reused for the future conf room. However, the duct drop from the unit at the roof into
the lower floor will need to be modified to traverse the new floor layout.
RTU-6
Existing unit RTU-6 is an 8.5 ton gas/electric rooftop unit that serves a work area, office, break room and
restrooms. This unit may be modified to serve the new level 01 layout. The existing roof opening is
located over the new stair and accordant accommodation will need to be made. The new 2nd floor office
space will be served by new equipment.
Demolition
The vacuum forming room and all the mechanical systems serving it (exhaust fan, hood ventilation and
roof hood) will be demolished for the new construction. The roof penetrations will be patched.
DocuSign Envelope ID: 159A417A-1EDB-4F08-A72F-D715A2DCA7DA
Paccar- Kenworth R&D – DD Mech summary
Page 2
Code Compliance – NEW HVAC
The conditioned cooling floor area is increased in this project. For the areas where the rooftop unit
remains and ductwork is modified to match the floor plan (RTU’s 3, 5, and 6), the equipment will not be
required to comply with current code.
The new 2nd floor offices will be conditioned with a de-coupled system, compliant with the 2018 WA
energy code. A Dedicated Outdoor Air System will be located on the roof to bring ventilation air to the
2nd floor offices. It will be equipped with an enthalpy energy recovery plate for heat recovery of exhaust
air.
Room conditioning may be achieved with a 6-ton VRF system with heat recovery. Wall mounted and
ducted terminals will address the heating and cooling needs of each space with an estimated 4-8 zones.
An economizer exception will be used for code compliance.
Sincerely,
DLR Group
Kathi Shoemake
Mechanical Engineer