HomeMy WebLinkAboutR-421228I—
LL
W
I^..L
O
r
n
z
rr
V
\a
N
/
O
O
O
AS-BUILTS WATER NOTES AND DETAILS
OF
BRENNON LANDING (VAUGHN TRUST PROPERTY)
A PORTION OF SECTION 05, TOWNSHIP 23 N., RANGE 05 E., W.M.
� CITY OF RENTON, KING COUNTY, WASHINGTON
WATER PLAN GENERAL NOTES Standard Plan No.3W
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CFTY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR
AND OR DEVELOPER SHALL, BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FORTHE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CLTY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ON -SITE.
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESSCLASS 52 PERAWWAC 151AND C
104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS
PER ANSI/AWWA C11O/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS.
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINLSHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS
AND 4B INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60 INCHES.
ANY DEVIATIONS MUST BE APPROVED BY THE CITY Of RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFLICTS OCCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURERS SPECIFICATION FOR SIZE OF PIPE USED. ALLTRENCH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST
METHOD (MDD) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MOD.
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS
AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAY BE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO
CONCRETE BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIOR TO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE
SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND REMOVE PLUGS,
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT / BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITY TESTING.
8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 P5I PRESSURE DROP DURING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE UNE SHALL BE DISINFECTED, FLUSHED,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR.
9, THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING
DAYS PRIOR TO MAKING CONNECTIONS TD THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION, THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORMS THE CONNECTION TOTHE EXISTING WATER SYSTEM, THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
PUBLIC WORKS STD. Pi" — 800.0
DEPARTMENT WATER PLAN GENERAL NOTES
MARCH 2010
EXISTING
WATER MAIN
TESTING CONNECTION
POLYPIG STATION PER STD PLAN 300.6
(1) VE RTICA L C ROSS (MJ x F L)
(II BLIND FLANGE ON TOP WITH Z" TAP AND 2" PLUG
(1) BLIND FLANGE ON BOTTOM
(1) PLUG (MJ) WITH 2"TAP AND TEMPORARY BLOW -OFF ASSEMBLY
WITH TEMPORARY THRUST BLOCKING
I
a
4 ■ ❑
j o` gi to NEW DI WATER MAIN
T
TEMPORARY BLOCKING
CONNECTION TO EXISTING MAIN (BY LICENSED WET TAP CONTRACTOR)
3 x iD
(1) TAPPING TEE (MJxFL) PER STD PLAN 300.6
MIN
III TAPPING GATE VALVE IFLxMJ)
(1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY
1
WITH CONCRETE THRUST BLOCKING PER STD PLAN 330.1
FINAL CONNECTION
UPON COMPLETION OF POLYP IGGING, HYDROSTATICTESTING,
AND D151NFECTION, REMOVE TEMPORARY THRUST BLOCKING
ANDTEMPORARY BLOW -OFF ASSEMBLIES
FINAL CONNECTION (SY CITY FORCES)
(2) DI SPOOLS
(1) DI SLEEVE (MJ)
4 di � � � •�F�❑ � I {_I ®J.' I�' NEW DI WATER MAIN
I PPP�ePP 99�e�;�f�(
a'
STD. PLAN 300.5
PUBLICW("KS CONNECTION TO WATER MAIN vPPaovED
DEPARTMENT TAPPING TEE AND VALVE
DATE
DATUM FBENCHMARK„ FOUND BRASS DOME IN MONUMENT IN MONUMENT IN CASE MARK I ,BRASS
C WITH XAT DISC
116TH ST.
HORIZONTAL DATUM: VERTICAL DATUM: CASE WITH 'T 0.65' BELOW GRADE OBSERVED (NAD 83/11) 0.6' BELOW GRADE OBSERVED (NAD 83/11) N0.
NAD '83/'91 NAVD '88 N: 186463.16, E: 1304865.21 N: 187664.64, E: 1304879.99
FINISHED GRADE 9" TO 12"
24" 70 30"
a
22 Yj°
MAIN —
LOOP DOWN TO CENTERLINE OF WATER MAIN
TO PROVIDE SLACK IN SERVICE LINE TO METER
MATERIALS
�I INUNIMPROVEDROW, zl
w� INSTALL METER BOX w. CITY I PRIVATE
p • AT PROPERTY LINE WITH p • �— —�
a 1" COPPER TAILPIECE Q. PI PING PIPING
I
. I
. I
�SIDEWALK I I
-- 1+12"�
^ li 21" TO 30"
I
s
1" BALL CORPORATION STOP WITH BALL VALVE, AWWA TAPERED THREAD (CC) INLET, QUICK JOINT OUTLET,
O A
CORPORATION 570P
FORD FB1000-4-Q-NL OR A.Y. MCDONALD 74701BQ
TUBING
1" TYPE "K" SOFT COPPER TUBING
1" SETTER, QUICK JOINT INLETAND OUTLET, PADLOCK WINGS ON INLET ANGLE BALL VALVE, SINGLE CHECK
OC
METER SETTER
VALVE ON OUTLET, FORD VBH74.15W-44.44-Q-N L, A.Y. MCDONALD 721.415WCQQ44, OR MUELLER
B-24701-6AN, INSTALL CENTERED AND SQUARED IN METER BOX, PROVIDE ADAPTERS FOR 5/8"x3/4" METERS
a
WATER METER
AMI WATER METER WITH RADIO AND BATTERY UNIT, TO BE PROVIDED BY THE CITY
OE
METER BOX
METER BOX, ARMORCASTA6001946PCX38, WITH METER BOX LID, ARMORCA5TA6001969RCI-H7, TO READ
"RENTON WATER"
(F
COUPLER AND PLUG
COUPLER (PACK JOINT x PACK JOINT), FORD C4#-4#-Q-NL, WITH 1" GALVANIZED PLUG IF SERVICE LINE TO
PROPERTY IS TO BE INSTALLED IN THE FUTURE
a
GRAVEL
1 VI" WASHED GRAVEL
STD. PLAN - 3ZO.1
PUBLIC WORKS I 1" WATER SERVICE
DEPARTMENT
RECORD DRAWINGS AS BUILT RK 5/4/22 BJT SURVEYED.
REVISION PER COMMENTS DATED 6 30 23 RK 7/7/23 BJT DUM RK
WAINN. RK
cHE BJT
REVISION BY DATE APPR APPROV BJT
DATE
N/A
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
NOTES:
1, FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF SAFETY YELLOW DTM ACRYLIC GLOSS OR ENAMEL PAINT.
2. PUMPER NOZZLE TO FACE ROADWAY OR AS DIRECTED BY RRFA.
3. A MINIMUM 3' RADIUS UNOBSTRUCTED WORKING AREA SHALL BE PROVIDED AROUND THE OUTSIDE OF THE HYDRANT.
O A HYDRANT
B TEE
VALVE
CO
Q VALVE BOX
EO PIPE
OJOINT RESTRAINT
Q GRAVEL
HO CONCRETE BLOCK
0 BLOCKING
JO SHEAR BLOCK
PAVEMENTMARKER
COMPRESSION TYPE HYDRANT (SEE APPROVED MATERIALS LIST) WITH 6" MJ INLET WITH LUGS, 5 Y4" MVO,
1 %" PENTAGON OPERATING NUT, TWO (2) 2 X" NST HOSE NOZZLES, AND 4.87S" SST PUMPER NOZZLE
EQUIPPED WITH 5" STORZ ADAPTER AND 1/8" STAINLESS STEEL CABLE, WITH EXTENSION IF NECESSARY.
MAIN LINE TEE WITH 6" FLANGE 51DE OUTLET
6" GATE VALVE (FLxMJ)
VALVE BOX AND LID PER STO PLAN 330.7
CLASS 52 DI, LENGTH TO FIT
MECHANICALJOINT RESTRAINT OR (2) 3/4" CORTEN STEEL TIE RODS FOR DISTANCES OVER ONE PIPE LENGTH
1 X" WASHED DRAIN ROCK, MINIMUM V ABOVE BOOT FLANGE WITH 3-MIL POLYETHYLENE SHEETING
AROUND TOP AND SIDES OF GRAVEL
MINIMUM 16"x8"x4" CONCRETE BLOCKS UNDER FIRE HYDRANT AN D GATE VALVE
CONCRETE BLOCKING PER STD PLAN 330.1
4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT WITH EXPANSION JOINT AT BACK OF SIDEWALK,
FINISH TO MATCH SIDEWALK, ALL CONCRETE SHALL BE MINIMUM 3,000 PSI AND SHALL BE MECHANICALLY
MIXED -JOB SITE MIXING, HAND -MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT ALLOWED.
BLUE REFLECTIVE PAVEMENT MARKER PER STD PLAN 310.3
PUBLIC WORKS I FIRE HYDRANT ASSEMBLY
�:. DEPARTMENT
VOUIC- _ NAYD I
HORIZONTAL• NAD 1910 1991
DATU M
CALL BEFORE YOU DIG:
1-800-424-5555
AoRtIL
CITY OF
RENTON
Planning/Building/Public Works Dept.
STD. PLAN - 310.1
QATF.
CONSTRUCTION RECORD
DRAWING
THIS CONSTRUCTION RECORD DRAWING IS A COPY
OF THE APPROVED CONSTRUCTION DRAWINGS
PREPARED BY BARGHAUSEN CONSULTING
ENGINEERS, INC AND HAS BEEN EDITED TO
REFLECT ASBUILT CONDITIONS. THE INFORMATION
PROVIDED ON THESE RECORD DRAWINGS IS A
COMBINATION OF THE FIELD SURVEYED INFORMATION
AND DOCUMENTED FIELD REVISIONS.
A
�20' 00241, ��
s STERN
Slo L ECG
7/ 7/2023
V
E
V
rL
4
ul
7
•�
o
b.
C
W
c
�
N
M
a000N
m
Lo
v
c�
O
LO
4-7
N
N
/
W
U
�
r
Y
R-421228 �
W-421204
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
AS-BUILTS WATER NOTES AND DETAILS
VAUGHN PROPERTY
MAINVUE WA, LLC
121 3RD AVENUE
KIRKLAND, WA 98033
O
Lo
T
O
O
T
N
T
��
6LJ
rr
W
0- co
OM
T
� N
z
%�
`
DATE
7/7/2023
m
ZJ 0
FlELDB001C
PACE:
Q
J uj
DRAWING NO:
U
m
SIEET: 28 L}V