HomeMy WebLinkAbout2023.03.24 .BEE.Air Barrier Test Report Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 1 of 10 SUNSET TERRACE BUILDING 1 WHOLE BUILDING AIR LEAKAGE TESTING REPORT Project Name: Sunset Terrace Building 1 Report Date: 03/28/2023 Air Barrier Testing E779 Project #: 1605-1003 Project Address: 2715 Sunset Lane NE Renton, WA 98056 Field Rep: Chris Shafer Test Date: 03/24/2023 Client: Colpitts Development Company, LLC Weather: Overcast, ~42 °F Present at Site: (BEE) – Chris S. (BEE) – Nate V. (BEE) – Robert S. BEE was retained by Colpitts Development Company, LLC for the purpose of providing whole building air leakage testing in accordance with ASTM E779 as required by the 2015 Washington State Energy Code. The Sunset Terrace project is a seven-story mixed use apartment building containing 108 units. This report contains the data for the whole building and completes the building air barrier test requirements. Testing was completed on 03/24/2023. BEE performed the building air barrier test procedure with positive and negative pressure. The whole building air leakage testing was completed using a total of nine mechanical blower door fans. Six fans were placed in the Lobby entryway on the Southern Elevation of level P1. Three fans were placed in the stair 2 entryway on level P2. Flow rates of each fan were recorded at different building pressures ranging between 25 (pa) to 80 (pa). Data was taken over 12 separate points. Result for Sunset Terrace Building 1: 0.349 CFM/SQFT at 75 Pa, Passed Combined Test, Final overall results of the building performance was an air leakage rate of 0.349 CFM/ SQFT of envelope at 75 Pa at the upper 95% confidence interval with the code maximum allowable defined as 0.40 CFM/ SQFT of envelope at 75 Pa. Final pressurization results of the building performance was an air leakage rate of 0.416 CFM/ SQFT of envelope at 75 Pa at the upper 95% confidence interval. Final depressurization results of the building performance was an air leakage rate of 0.282 CFM/ SQFT of envelope at 75 Pa at the upper 95% confidence interval. Below are the results with correlated diagrams. BEE Consulting LLC 170 West Dayton St., Suite 206 Edmonds, WA 98020 P: 425 672 3900 F: 425 712 8608 Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 2 of 10 Prepared by: X Chris Shafer, FAPCTesting Supervisor Reviewed and Approved by: X Denin Dazey Project Manager DISCLAIMER Please note that there is no guarantee expressed, written or implied by this report. The data complied herein is subject to change in case of new or additional data discovery. The information contained in this report is based on information available at the time that this report was prepared. Concerns do not represent a total listing of all locations with issues nor do they imply all similar locations to have issues. If additional information is discovered, it should be forwarded to our office for further review and comment. We reserve the right to amend and/or modify this report if new and/or significant data becomes available that impacts the situation and parameters of this investigation. Our services were performed using the degree of skill normally exercised by practicing investigation individuals in this area and similar locales. No other warranty is either expressed or implied. BEE Consulting LLC 170 West Dayton St., Suite 206 Edmonds, WA 98020 P: 425 672 3900 F: 425 712 8608 Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 3 of 10 Sunset Terrace Building 1 Air Barrier Test Report In accordance with ASTM E779 WSEC 2015 Air Leakage Protocol Performed by: BEE Consulting, LLC 170 W Dayton St, Ste. 206 Edmonds, WA 98020 425.672.3900 FanTestic version: 5.12.115 licensed to: BEE Consulting, LLC Building Address: 2715 Sunset Lane NE Renton, WA 98056 Performed for: Colpitts Development Company, LLC Performed by: Chris Shafer Test Date: 03/24/2023 Associated Test File: Sunset Terrace USACE 2023-03-24 1429 Project Number: 1605-1003 Testing Location: Sunset Terrace Building 1 Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 4 of 10 Summary Building and Test Information Test file name: Sunset Terrace USACE 2023-03-24 1429 Building Height (from ground to top) [ft]: 100 Envelope Area [ft2]: 109,675 Building Elevation (of ground, above sea level) [ft]: 310 Results Average air flowSTP at 75 Pa [CFM] 37475 Average equivalent leakage area at 75 Pa [sq in] 4027 Mean 95% Confidence Interval Lower Upper Average CFM / sq ft of envelope at 75 Pa 0.342 0.334 0.349 Building Information Building Measurements Building elevation above sea level [ft] 310 Building Envelope Area [ft] 109,675 Building Height [ft] 100 Isolation / Heating / Ventilation System All external HVAC and exhaust fan systems were properly set or isolated. All isolations were performed from the exterior with the exceptions for any unique interior conditioned spaces containing intentional penetrations through the building envelope. Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 5 of 10 Discussion of Results Combined Test Data (Average Values) Combined Test Data (Average Values) Average air flowSTP at +75 Pa [CFM] 37475 Average equivalent leakage area at 75 Pa [sq in] 4027 Mean 95% Confidence Interval Lower Upper Average CFM / sq ft of envelope at 75 Pa 0.342 0.334 0.349 Building Air Leakage Test Photo Documentation Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 6 of 10 Air Leakage Test Data Appendix– Depressurize (2) Data Set Test Dataset Date and Time: 2023-03-24-14:16:29 performed in (UTC-08:00) Pacific Time (US & Canada), displayed in Pacific Standard Time Finish Time: 14:18:54 Environmental Conditions Operator Location: Inside the building Greatest Initial Baseline Pressure -8.2 Pa Initial Bias Pressure: -2.40 Pa Final Bias Pressure: -5.59 Pa Initial Temperature: indoors: 73 outdoors: 42. Final Temperature: indoors: 73 outdoors: 42. Test Analysis Squared correlation coefficient r2 : 0.99803 Exponent, n: 0.561 Air leakage coefficient, C [CFM/Pan]: 2706.5 CFM referenced to STP at 75 Pa 30452 Equivalent leakage area at 75 Pa [sq in] 3272 Mean 95% confidence limits Lower Upper CFM/sq ft of envelope at 75 0.278 0.2732 0.2821 Induced Pressure [Pa] -25.2 -28.8 -35.3 -40.1 -44.5 -50.2 -54.2 -58.9 -64.3 -68.1 -74.3 -80.0 Total Flow [CFM] 15328.0 16862.9 19693.9 20991.4 22628.0 24293.3 25315.6 25535.4 27883.3 28766.1 30578.8 31790.1 Total Corrected flow [CFM] 14552 16009 18697 19929 21483 23064 24034 24243 26472 27310 29031 30181 Error [%] -1.4% -0.6% 1.9% 0.4% 1.4% 1.1% 0.6% -3.5% -0.1% -0.4% 0.6% 0.1% 12 induced pressures each taken for 10 of the required 10 seconds. 12 baseline pressures each taken for 10 of required 10 seconds. Greatest Initial Baseline Pressure: -8.2 Pa Static Pressure Averages: initial [Pa] ∆P01 -2.40 ∆P01- -2.40 ∆P01+ 0.00 final [Pa] ∆P02 -5.59 ∆P02- -5.59 ∆P02+ 0.00 Baseline, initial [Pa] -1.04 -2.95 -0.10 -2.31 -3.57 -1.73 -3.07 -3.59 -2.11 -3.69 -2.32 -2.37 Baseline, final [Pa] -6.76 -7.06 -6.22 -2.59 -6.35 -6.17 -4.63 -6.54 -3.20 -5.36 -6.85 -5.31 Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 7 of 10 Induced Pressure vs. Flow (Depressurize (2) Set) Building Gauge Pressure (Depressurize (2) Set) Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 8 of 10 Pressurize (1) Data Set Test Dataset Date and Time: 2023-03-24-13:18:40 performed in (UTC-08:00) Pacific Time (US & Canada), displayed in Pacific Standard Time Finish Time: 13:14:49 Environmental Conditions Operator Location: Inside the building Greatest Initial Baseline Pressure 7.1 Pa Initial Bias Pressure: -0.48 Pa Final Bias Pressure: -2.40 Pa Initial Temperature: indoors: 73 outdoors: 42. Final Temperature: indoors: 73 outdoors: 42. Test Analysis Squared correlation coefficient r2 : 0.99449 Exponent, n: 0.649 Air leakage coefficient, C [CFM/Pan]: 2699.9 CFM referenced to STP at 75 Pa 44500 Equivalent leakage area at 75 Pa [sq in] 4781 Mean 95% confidence limits Lower Upper CFM/sq ft of envelope at 75 0.406 0.3956 0.4159 Induced Pressure [Pa] 23.4 30.8 37.7 40.8 43.7 48.5 55.0 60.3 64.5 72.6 78.0 81.9 Total Flow [CFM] 21756.0 24741.5 27935.7 29639.1 31007.3 33431.9 34601.9 36987.1 38382.4 44608.4 46090.2 46677.0 Total Corrected flow [CFM] 22600 25701 29019 30789 32210 34729 35944 38422 39871 46339 47878 48488 Error [%] 3.2% -0.7% -1.3% -0.3% -0.1% 0.9% -3.5% -2.8% -3.3% 4.3% 2.9% 1.0% 12 induced pressures each taken for 10 of the required 10 seconds. 12 baseline pressures each taken for 10 of required 10 seconds. Greatest Initial Baseline Pressure: 7.1 Pa Static Pressure Averages: initial [Pa] ∆P01 -0.48 ∆P01- -0.91 ∆P01+ 0.40 final [Pa] ∆P02 -2.40 ∆P02- -2.40 ∆P02+ 0.00 Baseline, initial [Pa] -4.54 0.36 0.05 -0.29 0.68 0.50 -0.42 -0.76 -1.05 -0.06 -0.08 -0.10 Baseline, final [Pa] -1.04 -2.85 -0.10 -2.31 -3.57 -1.73 -3.07 -3.59 -2.18 -3.69 -2.32 -2.37 Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 9 of 10 Induced Pressure vs. Flow (Pressurize (1) Set) Building Gauge Pressure (Pressurize (1) Set) Sunset Terrace Building 1 / # 1605-1003 03/28/2023 Page 10 of 10 Test Equipment The following test equipment was used in the performance of the building air leakage test. Fan Model Fan Serial Fan Location Gauge Gauge Serial #1 Retrotec 3000SR PH001489 TL DM32 407027 #2 Retrotec 3000SR PH001492 Mid 2 DM32 400764 #3 Retrotec 3000SR PH001497 ML DM32 400794 #4 Retrotec 3000SR PH001507 Top 2 DM32 413490 #5 Retrotec 3000SR PH001510 BL DM32 413497 #6 Retrotec 3000SR PH002041 BR DM32 400830 #7 Retrotec 3000SR PH002042 TR DM32 400832 #8 Retrotec 3000SR PH002043 MR DM32 400771 #9 Retrotec 3000SR PH002735 Low 2 DM32 400796 Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:215216 095217 Calibration Date:2015-01-28 Results:As Found 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Mike Shtunyuk Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400764 Signature Environmental conditions: Temperature:20°C ±2°C Relative Humidity:50%±10% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:215216 095217 Calibration Date:2015-01-28 Results:As Found Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.98 -755.41 0.72 -749.98 -754.38 0.59 -600.02 -604.46 0.74 -600.02 -603.66 0.61 -300.03 -301.96 0.64 -300.03 -301.64 0.54 -150.01 -150.98 0.65 -150.01 -150.84 0.55 -75.00 -75.42 0.56 -75.00 -75.41 0.55 -49.99 -50.30 0.62 -49.99 -50.22 0.46 -25.01 -25.14 0.52 -25.01 -25.12 0.44 -15.00 -15.02 0.13 -15.00 -15.07 0.47 0.00 -0.04 N/A 0.00 -0.02 N/A 15.00 15.12 0.80 15.00 15.08 0.53 25.00 25.16 0.64 25.00 25.12 0.48 50.01 50.32 0.62 50.01 50.27 0.52 74.99 75.48 0.65 74.99 75.38 0.52 149.98 150.92 0.63 149.98 150.80 0.55 300.03 301.61 0.53 300.03 301.36 0.44 599.88 602.74 0.48 599.88 602.42 0.42 749.99 753.26 0.44 749.99 753.14 0.42 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 - 20 000 Pa)based on a 95%confidence interval,using coverage of K=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: NFPA 2001 EN13829 ATTMA:TS1 ASTM E779-10 CGSB GAP50-784 ±1 Pa ±2 Pa ±2 Pa ±5%or 0.25 Pa ±1 Pa ±1%or 1 Pa ±(10 to 50)Pa (up to ±60 Pa)(up to ±100 Pa)whichever is greater (up to ±50 Pa)whichever is greater ISO14520 EN15004 USACE TITLE 24 RESNET ±1 Pa ±1 Pa ±1%or 0.25 Pa ±1%or 0.2 Pa ±1%or 0.5 Pa (up to ±60 Pa)(up to ±100 Pa)±(25 to 250)Pa whichever is greater whichever is greater Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400771 102754 Calibration Date:2021-04-01 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Tina Lukyanets Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400771 Signature Issue Date:2021-04-01 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400771 102754 Calibration Date:2021-04-01 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.97 -751.02 0.14 -749.97 -750.69 0.10 -599.94 -600.96 0.17 -599.94 -600.72 0.13 -300.02 -300.30 0.09 -300.02 -300.24 0.07 -150.00 -150.05 0.03 -150.00 -149.97 0.02 -75.01 -74.99 0.03 -75.01 -74.99 0.03 -50.02 -49.96 0.12 -50.02 -49.96 0.12 -25.01 -24.98 0.12 -25.01 -24.95 0.24 -15.01 -14.91 0.67 -15.01 -14.95 0.40 0.01 -0.02 N/A 0.01 -0.02 N/A 15.01 15.14 0.87 15.01 15.09 0.53 24.99 25.16 0.68 24.99 25.08 0.36 49.99 50.14 0.30 49.99 50.15 0.32 75.01 75.23 0.29 75.01 75.18 0.23 150.02 150.30 0.19 150.02 150.24 0.15 299.99 300.45 0.15 299.99 300.32 0.11 600.00 600.42 0.07 600.00 600.25 0.04 749.93 750.44 0.07 749.93 750.30 0.05 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(10 to 50 Pa)2022-04-01 EN13829 ±2 Pa (up to ±60 Pa)2026-04-01 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-04-01 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-04-01 CGSB ±1 Pa (up to ±50 Pa)2022-04-01 GAP50-784 ±1%or 1 Pa whichever is greater 2022-04-01 ISO14520 ±1 Pa (up to ±60 Pa)2026-04-01 EN15004 ±1 Pa (up to ±100 Pa)2026-04-01 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-04-01 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-04-01 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-04-01 ISO9972 ±1 Pa (up to ±100 Pa)2026-04-01 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-04-01 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400794 021732 Calibration Date:2021-08-18 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Tina Lukyanets Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400794 Signature Issue Date:2021-08-18 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400794 021732 Calibration Date:2021-08-18 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.83 -756.04 0.83 -749.83 -755.98 0.82 -599.86 -605.41 0.93 -599.86 -605.46 0.93 -299.99 -302.32 0.78 -299.99 -302.36 0.79 -149.99 -151.13 0.76 -149.99 -151.14 0.77 -74.98 -75.58 0.80 -74.98 -75.55 0.76 -49.99 -50.37 0.76 -49.99 -50.40 0.82 -24.98 -25.18 0.80 -24.98 -25.19 0.84 -14.99 -15.10 0.73 -14.99 -15.13 0.93 0.01 0.04 N/A 0.01 0.03 N/A 14.99 15.04 0.33 14.99 15.04 0.33 25.00 25.16 0.64 25.00 25.12 0.48 50.00 50.31 0.62 50.00 50.32 0.64 75.01 75.49 0.64 75.01 75.52 0.68 150.03 150.89 0.57 150.03 150.97 0.63 299.96 301.57 0.54 299.96 301.66 0.57 599.82 602.43 0.44 599.82 602.74 0.49 749.75 752.61 0.38 749.75 752.94 0.43 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(10 to 50 Pa)2022-08-18 EN13829 ±2 Pa (up to ±60 Pa)2026-08-18 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-08-18 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-08-18 CGSB ±1 Pa (up to ±50 Pa)2022-08-18 GAP50-784 ±1%or 1 Pa whichever is greater 2022-08-18 ISO14520 ±1 Pa (up to ±60 Pa)2026-08-18 EN15004 ±1 Pa (up to ±100 Pa)2026-08-18 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-08-18 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-08-18 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-08-18 ISO9972 ±1 Pa (up to ±100 Pa)2026-08-18 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-08-18 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:215213 084058 Calibration Date:2016-09-08 Results:As Found 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Mike Shtunyuk Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400796 Signature Environmental conditions: Temperature:20°C ±2°C Relative Humidity:50%±10% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:215213 084058 Calibration Date:2016-09-08 Results:As Found Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.97 -753.88 0.52 -749.97 -754.82 0.65 -600.01 -603.22 0.53 -600.01 -603.94 0.65 -300.03 -301.55 0.51 -300.03 -301.75 0.57 -150.05 -150.70 0.43 -150.05 -150.87 0.55 -74.99 -75.28 0.39 -74.99 -75.33 0.45 -49.99 -50.17 0.36 -49.99 -50.21 0.44 -25.00 -25.10 0.40 -25.00 -25.07 0.28 -15.00 -15.02 0.13 -15.00 -15.00 0.00 0.00 -0.02 N/A 0.00 -0.03 N/A 14.99 15.10 0.73 14.99 15.12 0.87 25.01 25.12 0.44 25.01 25.22 0.84 49.99 50.28 0.58 49.99 50.37 0.76 75.00 75.41 0.55 75.00 75.47 0.63 150.00 150.68 0.45 150.00 150.87 0.58 300.02 301.30 0.43 300.02 301.50 0.49 599.98 602.55 0.43 599.98 602.70 0.45 749.99 752.96 0.40 749.99 753.11 0.42 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 - 20 000 Pa)based on a 95%confidence interval,using coverage of K=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: NFPA 2001 EN13829 ATTMA:TS1 ASTM E779-10 CGSB GAP50-784 ±1 Pa ±2 Pa ±2 Pa ±5%or 0.25 Pa ±1 Pa ±1%or 1 Pa ±(10 to 50)Pa (up to ±60 Pa)(up to ±100 Pa)whichever is greater (up to ±50 Pa)whichever is greater ISO14520 EN15004 USACE TITLE 24 RESNET ±1 Pa ±1 Pa ±1%or 0.25 Pa ±1%or 0.2 Pa ±1%or 0.5 Pa (up to ±60 Pa)(up to ±100 Pa)±(25 to 250)Pa whichever is greater whichever is greater Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400830 080958 Calibration Date:2021-08-19 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Tina Lukyanets Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400830 Signature Issue Date:2021-08-19 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400830 080958 Calibration Date:2021-08-19 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.98 -752.22 0.30 -749.98 -751.91 0.26 -600.00 -602.34 0.39 -600.00 -601.98 0.33 -299.99 -301.02 0.34 -299.99 -300.88 0.30 -150.02 -150.49 0.31 -150.02 -150.47 0.30 -75.00 -75.19 0.25 -75.00 -75.20 0.27 -49.98 -50.10 0.24 -49.98 -50.16 0.36 -25.00 -25.06 0.24 -25.00 -25.05 0.20 -15.00 -15.01 0.07 -15.00 -15.01 0.07 0.00 0.02 N/A 0.00 0.01 N/A 15.00 15.06 0.40 15.00 15.08 0.53 25.00 25.10 0.40 25.00 25.11 0.44 49.99 50.22 0.46 49.99 50.21 0.44 75.01 75.33 0.43 75.01 75.29 0.37 149.99 150.59 0.40 149.99 150.55 0.37 300.02 301.01 0.33 300.02 301.03 0.34 599.97 602.00 0.34 599.97 601.74 0.30 749.92 752.31 0.32 749.92 752.16 0.30 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(10 to 50 Pa)2022-08-19 EN13829 ±2 Pa (up to ±60 Pa)2026-08-19 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-08-19 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-08-19 CGSB ±1 Pa (up to ±50 Pa)2022-08-19 GAP50-784 ±1%or 1 Pa whichever is greater 2022-08-19 ISO14520 ±1 Pa (up to ±60 Pa)2026-08-19 EN15004 ±1 Pa (up to ±100 Pa)2026-08-19 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-08-19 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-08-19 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-08-19 ISO9972 ±1 Pa (up to ±100 Pa)2026-08-19 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-08-19 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400832 032537 Calibration Date:2021-08-18 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Tina Lukyanets Manufacturer:Retrotec Model Number:DM32 10A Serial Number:400832 Signature Issue Date:2021-08-18 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:400832 032537 Calibration Date:2021-08-18 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.88 -754.80 0.66 -749.88 -755.78 0.79 -599.93 -603.88 0.66 -599.93 -604.61 0.78 -299.92 -301.66 0.58 -299.92 -302.01 0.70 -150.00 -150.74 0.49 -150.00 -150.98 0.65 -74.98 -75.38 0.53 -74.98 -75.49 0.68 -50.00 -50.22 0.44 -50.00 -50.30 0.60 -25.00 -25.08 0.32 -25.00 -25.13 0.52 -15.01 -15.01 0.00 -15.01 -14.99 0.13 0.01 -0.02 N/A 0.01 -0.04 N/A 15.01 15.13 0.80 15.01 15.16 1.00 25.00 25.19 0.76 25.00 25.20 0.80 50.00 50.25 0.50 50.00 50.37 0.74 74.98 75.39 0.55 74.98 75.52 0.72 149.96 150.76 0.53 149.96 151.00 0.69 299.99 301.41 0.47 299.99 301.80 0.60 599.91 601.74 0.31 599.91 602.92 0.50 749.97 752.19 0.30 749.97 753.57 0.48 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(10 to 50 Pa)2022-08-18 EN13829 ±2 Pa (up to ±60 Pa)2026-08-18 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-08-18 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-08-18 CGSB ±1 Pa (up to ±50 Pa)2022-08-18 GAP50-784 ±1%or 1 Pa whichever is greater 2022-08-18 ISO14520 ±1 Pa (up to ±60 Pa)2026-08-18 EN15004 ±1 Pa (up to ±100 Pa)2026-08-18 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-08-18 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-08-18 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-08-18 ISO9972 ±1 Pa (up to ±100 Pa)2026-08-18 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-08-18 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:407027 025229 Calibration Date:2022-09-20 Results:As Left Page 1 of 3 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Tina Lukyanets Manufacturer:Retrotec Model Number:DM32 10A Serial Number:407027 Signature Issue Date:2022-09-20 Environmental conditions: Temperature:73.3°F (73.2-73.4)°F Relative Humidity:37%(37-37)% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:407027 025229 Calibration Date:2022-09-20 Results:As Left Page 2 of 3 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.98 -755.43 0.73 -749.98 -755.70 0.76 -599.98 -604.41 0.74 -599.98 -604.72 0.79 -300.00 -301.75 0.58 -300.00 -301.90 0.63 -149.98 -150.70 0.48 -149.98 -150.90 0.61 -75.00 -75.33 0.44 -75.00 -75.40 0.53 -50.01 -50.15 0.28 -50.01 -50.25 0.48 -25.01 -25.05 0.16 -25.01 -25.08 0.28 -15.01 -15.05 0.27 -15.01 -15.05 0.27 0.00 0.00 N/A 0.00 -0.03 N/A 15.00 15.14 0.93 15.00 15.07 0.47 24.99 25.19 0.80 24.99 25.17 0.72 50.02 50.28 0.52 50.02 50.30 0.56 75.00 75.37 0.49 75.00 75.48 0.64 150.00 150.75 0.50 150.00 150.90 0.60 300.00 301.16 0.39 300.00 301.40 0.47 599.97 601.41 0.24 599.97 601.90 0.32 750.02 751.35 0.18 750.02 751.95 0.26 Traceability is to the International System of Units (SI),consensus standards,or ratio type measurements through national standards realized and maintained by NIST or an NMI. Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is 0.073%of reading +0.14 Pa (Range 0 -2 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:407027 025229 Calibration Date:2022-09-20 Results:As Left Page 3 of 3 Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(10 to 50 Pa)2023-09-20 EN13829 ±2 Pa (up to ±60 Pa)2027-09-20 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2023-09-20 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2027-09-20 CGSB ±1 Pa (up to ±50 Pa)2023-09-20 GAP50-784 ±1%or 1 Pa whichever is greater 2023-09-20 ISO14520 ±1 Pa (up to ±60 Pa)2027-09-20 EN15004 ±1 Pa (up to ±100 Pa)2027-09-20 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2024-09-20 TITLE 24 ±1%or 0.2 Pa whichever is greater 2023-09-20 RESNET380 ±1%or 0.25 Pa whichever is greater 2023-09-20 ISO9972 ±1 Pa (up to ±100 Pa)2027-09-20 FD E51-767 ±2.5%or 3 Pa whichever is greater 2024-09-20 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:413490 122410 Calibration Date:2021-07-19 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Mike Shtunyuk Manufacturer:Retrotec Model Number:DM32 10A Serial Number:413490 Signature Issue Date:2021-07-09 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:413490 122410 Calibration Date:2021-07-19 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -749.99 -752.04 0.27 -749.99 -751.78 0.24 -600.00 -601.69 0.28 -600.00 -601.94 0.32 -299.99 -300.59 0.20 -299.99 -300.73 0.25 -150.04 -150.25 0.14 -150.04 -150.34 0.20 -74.98 -75.11 0.17 -74.98 -75.10 0.16 -49.99 -50.05 0.12 -49.99 -50.07 0.16 -25.00 -24.98 0.08 -25.00 -24.99 0.04 -14.99 -15.02 0.20 -14.99 -14.91 0.53 -0.01 -0.02 N/A -0.01 0.04 N/A 15.00 15.05 0.33 15.00 15.14 0.93 25.02 25.10 0.32 25.02 25.19 0.68 50.00 50.15 0.30 50.00 50.27 0.54 75.03 75.17 0.19 75.03 75.34 0.41 149.98 150.30 0.21 149.98 150.52 0.36 299.95 300.49 0.18 299.95 300.87 0.31 599.99 600.64 0.11 599.99 601.26 0.21 749.97 750.49 0.07 749.97 751.45 0.20 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(0 to 50 Pa)2022-07-19 EN13829 ±2 Pa (up to ±60 Pa)2026-07-19 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-07-19 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-07-19 CGSB ±1 Pa (up to ±60 Pa)2022-07-19 GAP50-784 ±1%or 1 Pa whichever is greater 2022-07-19 ISO14520 ±1 Pa (up to ±60 Pa)2026-07-19 EN15004 ±1 Pa (up to ±100 Pa)2026-07-19 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-07-19 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-07-19 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-07-19 ISO9972 ±1 Pa (up to ±100 Pa)2026-07-19 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-07-19 End of report Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:413497 125424 Calibration Date:2021-07-19 Results:As Left Page 1 of 2 1060 E Pole Rd. Everson,WA,USA 98247 T:+1 (360)738-9835 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025.E:calibration@retrotec.com W:www.retrotec.com Instrument: Description:Pressure and Flow Gauge Calibrated by:Mike Shtunyuk Manufacturer:Retrotec Model Number:DM32 10A Serial Number:413497 Signature Issue Date:2021-07-09 Environmental conditions: Temperature:68°F ±10°F Relative Humidity:50%±30% Mains Voltage:120V ±10V Mains Frequency:60Hz ±1Hz Comments: Results recorded as received.No adjustment performed. This calibration applies only to the unit listed on this certificate. Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full,without written approval from Retrotec. Certificate of Gauge Calibration Issued by:Retrotec Certificate Number:413497 125424 Calibration Date:2021-07-19 Results:As Left Page 2 of 2 Calibration Results Channel A Channel B Applied Value (Pa)Reading (Pa)Error (%)Applied Value (Pa)Reading (Pa)Error (%) -750.00 -751.96 0.26 -750.00 -752.10 0.28 -599.99 -601.80 0.30 -599.99 -601.82 0.31 -300.02 -300.67 0.22 -300.02 -300.73 0.24 -150.02 -150.19 0.11 -150.02 -150.28 0.17 -75.05 -75.01 0.05 -75.05 -75.10 0.07 -50.00 -50.02 0.04 -50.00 -50.04 0.08 -24.97 -24.98 0.04 -24.97 -24.98 0.04 -15.00 -14.95 0.33 -15.00 -14.93 0.47 -0.01 -0.03 N/A -0.01 -0.01 N/A 14.99 15.08 0.60 14.99 15.11 0.80 25.02 25.13 0.44 25.02 25.14 0.48 49.96 50.18 0.44 49.96 50.20 0.48 75.01 75.22 0.28 75.01 75.28 0.36 150.04 150.35 0.21 150.04 150.45 0.27 300.01 300.48 0.16 300.01 300.67 0.22 600.01 600.36 0.06 600.01 600.90 0.15 749.99 750.18 0.03 749.99 750.90 0.12 Instrument display resolution is 0.1 Pa. Uncertainties Calibration and measurement capability (Expanded Uncertainty)is .01 Pa +0.3%of reading (Range 0 -20 000 Pa)based on a 95%confidence interval,using coverage of k=2. Initial The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from)the following standards or guidelines: Name Accuracy Requirements Expiration Date NFPA 2001 ±1 Pa ±(0 to 50 Pa)2022-07-19 EN13829 ±2 Pa (up to ±60 Pa)2026-07-19 ATTMA:TS1 ±2 Pa (up to ±100 Pa)2022-07-19 ASTM E779-10 ±5%or 0.25 Pa whichever is greater 2026-07-19 CGSB ±1 Pa (up to ±60 Pa)2022-07-19 GAP50-784 ±1%or 1 Pa whichever is greater 2022-07-19 ISO14520 ±1 Pa (up to ±60 Pa)2026-07-19 EN15004 ±1 Pa (up to ±100 Pa)2026-07-19 USACE ±1%or 0.25 Pa ±(25 to 250)Pa 2023-07-19 TITLE 24 ±1%or 0.2 Pa whichever is greater 2022-07-19 RESNET380 ±1%or 0.25 Pa whichever is greater 2022-07-19 ISO9972 ±1 Pa (up to ±100 Pa)2026-07-19 FD E51-767 ±2.5%or 3 Pa whichever is greater 2023-07-19 End of report Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201807050947-PH001489 Calibration Date:2018-07-05 Results:As Left Page 1 of 3 Calibration Date:2018-07-05 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Mike Cline Model Number:Model 3000SR Shell Serial Number:PH001489 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2023-07-05 CGSB 2002 2023-07-05 ATTMA-TS1 2019-07-05 ASTM-E779 2023-07-05 RESNET 2023-07-05 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201807050947-PH001489 Calibration Date:2018-07-05 Results:As Left Page 2 of 3 Calibration Date:2018-07-05 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 49.3 24.2 102.600 50.6 14.2 3344.69 3476.36 3.9% Open 50.0 23.9 102.600 52.9 96.3 10024.01 10069.50 0.5% Open 51.7 23.4 102.600 51.6 157.2 12723.43 13218.17 3.9% A 51.3 23.6 102.600 50.9 20.7 2147.95 2155.90 0.4% A 51.3 23.5 102.600 52.1 183.6 6360.68 6378.77 0.3% A 51.7 23.4 102.600 51.4 296.0 8048.99 8087.34 0.5% B 51.3 23.7 102.600 51.3 33.0 1649.14 1667.63 1.1% B 51.3 23.6 102.600 52.0 251.0 4522.39 4518.11 0.1% B 51.3 23.6 102.600 51.0 405.4 5707.86 5717.03 0.2% C8 51.0 23.8 102.600 50.5 90.2 1311.90 1320.78 0.7% C8 51.1 23.8 102.600 51.1 326.9 2523.43 2529.45 0.2% C8 51.1 23.8 102.600 50.9 506.0 3135.47 3153.35 0.6% C6 50.8 24.0 102.600 51.2 34.1 631.79 622.82 1.4% C6 51.0 23.9 102.600 51.0 310.4 1859.87 1852.69 0.4% C6 50.7 24.0 102.600 52.6 508.9 2374.47 2364.32 0.4% C4 50.3 24.2 102.600 50.5 75.0 603.50 605.99 0.4% C4 50.2 24.2 102.600 50.0 309.4 1246.76 1252.29 0.4% C4 50.2 24.2 102.600 50.9 483.6 1562.20 1574.40 0.8% C2 49.7 24.5 102.600 50.5 66.8 285.79 295.76 3.5% C2 49.6 24.5 102.600 51.0 290.7 661.90 660.87 0.2% C2 49.9 24.4 102.600 50.6 459.6 832.56 848.97 2.0% C1 49.1 24.8 102.600 50.9 60.2 158.65 160.61 1.2% C1 49.2 24.8 102.600 51.7 271.7 371.47 369.30 0.6% C1 49.3 24.7 102.600 50.9 431.6 472.52 476.80 0.9% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201807050947-PH001489 Calibration Date:2018-07-05 Results:As Left Page 3 of 3 Calibration Date:2018-07-05 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.555 798.88 8.6 A 0.497 477.70 12 B 0.491 299.80 10 C8 0.505 136.14 10 C6 0.493 109.26 10 C4 0.512 66.31 10 C2 0.547 29.72 10 C1 0.552 16.72 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108241009-PH001492 Calibration Date:2021-08-26 Results:As Left Page 1 of 3 Calibration Date:2021-08-26 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Shelby Zettle Model Number:Model 3000SR Shell Serial Number:PH001492 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07 and ASTM E1258-88 standards: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2026-08-26 CGSB 2002 2026-08-26 ATTMA-TS1 2022-08-26 ASTM-E779 2026-08-26 RESNET 2026-08-26 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108241009-PH001492 Calibration Date:2021-08-26 Results:As Left Page 2 of 3 Calibration Date:2021-08-26 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 52.1 20.9 101.900 50.7 21.6 4568.37 4454.68 -2.5% Open 52.9 20.6 101.900 48.8 97.0 9701.20 9937.81 2.4% Open 53.7 20.3 101.900 48.6 159.1 12375.15 12944.92 4.6% A 53.4 20.5 101.900 51.0 22.7 2239.70 2268.64 1.3% A 53.7 20.4 101.900 50.5 163.9 5999.16 6026.48 0.5% A 53.8 20.5 101.900 50.8 275.0 7794.78 7778.62 -0.2% B 53.2 20.7 101.900 50.9 33.1 1650.00 1649.09 -0.1% B 53.6 20.6 101.900 50.5 223.6 4260.28 4255.41 -0.1% B 53.7 20.6 101.900 51.1 377.6 5494.98 5517.14 0.4% C8 53.1 20.9 101.900 50.1 94.4 1334.68 1347.25 0.9% C8 53.3 20.8 101.900 50.5 302.0 2407.32 2419.22 0.5% C8 53.3 20.8 101.900 49.5 478.7 3036.45 3049.92 0.4% C6 53.4 20.9 101.900 50.6 34.4 620.13 621.09 0.2% C6 53.5 20.9 101.900 50.8 272.3 1743.10 1746.41 0.2% C6 53.6 20.9 101.900 49.9 475.8 2307.74 2305.95 -0.1% C4 52.8 21.3 101.900 50.7 77.2 618.85 626.09 1.2% C4 53.1 21.1 101.900 49.7 280.6 1199.61 1202.92 0.3% C4 53.2 21.2 101.900 48.8 451.0 1521.88 1528.63 0.4% C2 52.4 21.5 101.900 50.2 69.7 286.36 294.35 2.8% C2 52.7 21.4 101.900 49.5 278.0 635.10 631.47 -0.6% C2 52.9 21.4 101.900 49.8 447.6 813.47 820.46 0.9% C1 52.1 21.8 101.900 50.2 61.4 164.24 166.10 1.1% C1 52.3 21.7 101.900 50.8 257.7 355.51 354.00 -0.4% C1 52.5 21.6 101.900 49.5 425.6 455.09 460.90 1.3% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108241009-PH001492 Calibration Date:2021-08-26 Results:As Left Page 3 of 3 Calibration Date:2021-08-26 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.534 859.83 8.6 A 0.494 483.38 12 B 0.496 290.48 10 C8 0.504 136.37 10 C6 0.500 105.99 10 C4 0.506 69.40 10 C2 0.552 28.35 10 C1 0.528 19.00 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202109171048-PH001497 Calibration Date:2021-09-20 Results:As Left Page 1 of 3 Calibration Date:2021-09-20 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Shelby Zettle Model Number:Model 3000SR Shell Serial Number:PH001497 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07 and ASTM E1258-88 standards: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2026-09-20 CGSB 2002 2026-09-20 ATTMA-TS1 2022-09-20 ASTM-E779 2026-09-20 RESNET 2026-09-20 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202109171048-PH001497 Calibration Date:2021-09-20 Results:As Left Page 2 of 3 Calibration Date:2021-09-20 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 58.9 18.4 102.300 50.3 14.8 3646.71 3622.82 -0.7% Open 59.4 18.2 102.300 50.0 115.7 10243.32 10125.72 -1.1% Open 59.8 18.1 102.300 47.8 184.3 12924.54 12770.58 -1.2% A 58.7 18.5 102.300 50.1 21.7 2215.86 2261.20 2.0% A 58.9 18.4 102.300 50.0 188.0 6507.22 6616.88 1.7% A 59.1 18.4 102.300 48.8 299.4 8204.95 8340.98 1.7% B 58.6 18.5 102.300 50.7 34.7 1669.50 1702.41 2.0% B 58.8 18.5 102.300 50.2 261.2 4567.63 4644.57 1.7% B 58.8 18.5 102.300 49.8 419.6 5794.08 5879.02 1.5% C8 58.4 18.6 102.300 49.6 89.5 1308.39 1329.64 1.6% C8 58.4 18.6 102.300 50.2 331.5 2543.50 2577.42 1.3% C8 58.2 18.7 102.300 49.1 522.0 3186.72 3240.57 1.7% C6 58.1 18.8 102.200 50.7 33.5 623.10 622.95 0.0% C6 58.2 18.8 102.200 49.9 310.0 1873.11 1894.19 1.1% C6 58.0 18.8 102.200 49.8 523.6 2433.33 2461.18 1.1% C4 57.5 19.0 102.200 50.8 77.0 611.50 622.38 1.8% C4 57.7 18.9 102.200 49.9 312.3 1265.25 1277.30 1.0% C4 57.6 19.0 102.200 49.4 495.1 1595.52 1616.92 1.3% C2 56.8 19.2 102.200 49.6 65.5 289.78 296.02 2.2% C2 57.1 19.1 102.200 50.3 293.0 669.28 669.47 0.0% C2 56.9 19.2 102.200 48.6 469.9 848.06 865.13 2.0% C1 56.3 19.4 102.200 49.6 64.1 168.52 164.41 -2.4% C1 56.7 19.3 102.200 50.1 271.2 373.67 364.76 -2.4% C1 56.4 19.4 102.200 49.4 431.5 478.45 470.94 -1.6% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202109171048-PH001497 Calibration Date:2021-09-20 Results:As Left Page 3 of 3 Calibration Date:2021-09-20 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.499 930.34 8.6 A 0.498 481.40 12 B 0.497 287.98 10 C8 0.506 135.35 10 C6 0.500 106.44 10 C4 0.513 66.25 10 C2 0.545 30.03 10 C1 0.553 16.35 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108240721-PH001507 Calibration Date:2021-08-26 Results:As Left Page 1 of 3 Calibration Date:2021-08-26 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Shelby Zettle Model Number:Model 3000SR Shell Serial Number:PH001507 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07 and ASTM E1258-88 standards: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2026-08-26 CGSB 2002 2026-08-26 ATTMA-TS1 2022-08-26 ASTM-E779 2026-08-26 RESNET 2026-08-26 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108240721-PH001507 Calibration Date:2021-08-26 Results:As Left Page 2 of 3 Calibration Date:2021-08-26 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 54.3 18.3 101.900 50.6 20.9 4411.82 4338.66 -1.7% Open 55.5 17.9 101.900 50.7 90.8 9509.88 9387.99 -1.3% Open 57.4 17.3 101.900 50.5 142.9 12072.78 11930.44 -1.2% A 56.2 17.8 101.900 50.0 26.0 2385.31 2405.86 0.9% A 56.4 17.7 101.900 50.5 173.3 6095.46 6131.56 0.6% A 56.8 17.5 101.900 48.5 298.7 7890.68 8022.44 1.6% B 56.2 17.8 101.900 50.3 35.2 1676.81 1700.31 1.4% B 56.2 17.8 101.900 50.7 235.4 4305.15 4327.39 0.5% B 56.4 17.7 101.900 48.9 403.4 5599.80 5640.32 0.7% C8 56.0 17.9 101.900 50.0 92.0 1331.54 1341.48 0.7% C8 56.0 17.9 101.900 49.7 301.0 2423.52 2442.67 0.8% C8 55.9 17.9 101.900 50.8 479.1 3065.80 3088.96 0.8% C6 55.5 18.1 101.900 50.7 35.9 641.03 644.19 0.5% C6 55.6 18.1 101.900 51.6 270.6 1744.82 1757.61 0.7% C6 55.5 18.1 101.900 49.9 477.8 2314.02 2331.13 0.7% C4 55.0 18.3 101.900 50.5 78.4 616.61 617.46 0.1% C4 55.3 18.2 101.900 49.8 282.3 1199.85 1199.12 -0.1% C4 55.2 18.3 101.900 50.0 455.4 1529.43 1535.87 0.4% C2 54.9 18.4 101.900 50.6 68.4 289.52 298.43 3.1% C2 54.8 18.4 101.900 50.1 266.0 634.04 635.27 0.2% C2 54.7 18.5 101.900 50.5 433.8 812.91 833.12 2.5% C1 54.2 18.7 101.900 50.5 61.9 163.95 166.54 1.6% C1 54.3 18.7 101.900 51.4 247.8 355.54 350.68 -1.4% C1 54.2 18.7 101.900 49.2 406.3 456.53 456.86 0.1% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202108240721-PH001507 Calibration Date:2021-08-26 Results:As Left Page 3 of 3 Calibration Date:2021-08-26 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.525 868.77 8.6 A 0.494 474.87 12 B 0.492 290.94 10 C8 0.506 134.39 10 C6 0.497 107.41 10 C4 0.519 63.64 10 C2 0.556 28.22 10 C1 0.537 18.06 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202209211004-PH001510 Calibration Date:2022-09-22 Results:As Left Page 1 of 3 Calibration Date:2022-09-22 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the InternationalSystem of Units (SI),consensus standards,or ratiotype measurements through national standards realized and maintainedby NIST oran NMI. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Robert Shelton Model Number:Model 3000SR Shell Serial Number:PH001510 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Issued Date:2022-09-22 Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07 and ASTM E1258-88 standards: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 415445 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of k=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This calibration applies only tothe unit listed on this certificate. This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2027-09-22 CGSB 2002 2027-09-22 ATTMA-TS1 2023-09-22 ASTM-E779 2027-09-22 RESNET 2027-09-22 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202209211004-PH001510 Calibration Date:2022-09-22 Results:As Left Page 2 of 3 Calibration Date:2022-09-22 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 52.1 19.0 101.500 49.5 16.3 3423.66 3577.21 4.5% Open 52.2 19.0 101.500 51.8 101.7 8978.67 9090.04 1.2% Open 52.1 19.0 101.500 51.4 170.5 11947.50 11821.31 -1.1% A 51.7 19.3 101.500 50.8 22.3 2215.17 2261.43 2.1% A 52.0 19.2 101.500 51.8 161.2 5917.51 6011.67 1.6% A 51.9 19.2 101.500 51.1 288.3 7816.46 8010.72 2.5% B 51.4 19.4 101.500 50.8 32.8 1610.29 1666.93 3.5% B 51.8 19.3 101.500 51.4 229.2 4238.79 4369.00 3.1% B 51.6 19.4 101.400 51.1 401.6 5614.58 5770.18 2.8% C8 51.3 19.6 101.400 50.5 90.3 1314.58 1317.01 0.2% C8 51.5 19.5 101.400 50.4 292.8 2380.80 2384.93 0.2% C8 51.5 19.5 101.400 50.8 478.9 3043.92 3057.78 0.5% C6 50.9 19.8 101.400 50.9 35.3 637.35 628.85 -1.3% C6 51.1 19.7 101.400 51.9 266.0 1731.46 1740.11 0.5% C6 51.0 19.8 101.400 51.0 480.5 2324.03 2344.39 0.9% C4 50.3 20.1 101.400 50.6 77.1 614.53 620.01 0.9% C4 50.5 20.1 101.400 50.0 277.2 1190.47 1194.45 0.3% C4 50.5 20.1 101.400 51.1 455.9 1530.93 1541.01 0.7% C2 49.2 20.9 101.400 50.3 66.9 290.02 299.68 3.3% C2 49.2 20.9 101.400 49.8 262.9 627.83 624.31 -0.6% C2 49.4 20.9 101.400 49.4 440.6 814.67 823.54 1.1% C1 49.2 21.1 101.400 51.3 60.3 165.65 163.30 -1.4% C1 49.4 21.0 101.400 50.5 242.1 355.31 343.30 -3.4% C1 49.7 20.9 101.400 49.8 408.8 464.53 454.27 -2.2% Calibration and measurement capability (Expanded Uncertainty):Laminar Flow Elements (0.01 to 3300CFM)=1.4%of reading +0.11 CFM.Flow Nozzles (10 to 8200CFM)=1.5%of reading +78 CFM.The uncertainty statement is based on a 95%confidence interval,using a coverage of k=2. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202209211004-PH001510 Calibration Date:2022-09-22 Results:As Left Page 3 of 3 Calibration Date:2022-09-22 Published Flow Equation Parameters (Units in m³/h): Range Configuration n k MF (Pa) Open 0.509 865.78 8.6 A 0.494 488.32 12 B 0.496 294.94 10 C8 0.505 135.47 10 C6 0.504 104.32 10 C4 0.512 66.97 10 C2 0.536 31.45 10 C1 0.535 18.23 10 Flow =P^n x k Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. End of report Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071309-PH002041 Calibration Date:2019-02-07 Results:As Left Page 1 of 3 Calibration Date:2019-02-07 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Mike Cline Model Number:Model 3000SR Shell Serial Number:PH002041 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2024-02-07 CGSB 2002 2024-02-07 ATTMA-TS1 2020-02-07 ASTM-E779 2024-02-07 RESNET 2024-02-07 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071309-PH002041 Calibration Date:2019-02-07 Results:As Left Page 2 of 3 Calibration Date:2019-02-07 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 26.2 21.3 101.200 50.8 14.6 3565.80 3682.75 3.3% Open 26.7 20.9 101.200 51.6 93.1 10094.64 10225.49 1.3% Open 28.7 19.4 101.200 51.1 138.1 12589.77 12706.97 0.9% A 28.5 19.7 101.200 50.9 21.1 2233.50 2211.09 1.0% A 28.4 19.8 101.200 52.2 180.4 6390.78 6409.08 0.3% A 28.6 19.6 101.200 51.3 274.6 7909.95 7893.48 0.2% B 28.9 19.5 101.200 51.4 33.2 1713.78 1704.64 0.5% B 28.8 19.6 101.200 51.1 248.1 4585.19 4575.71 0.2% B 29.1 19.4 101.200 52.3 378.9 5662.33 5633.12 0.5% C8 28.9 19.5 101.200 50.0 90.5 1321.56 1317.37 0.3% C8 28.8 19.6 101.200 51.4 332.9 2547.41 2557.40 0.4% C8 28.6 19.7 101.200 50.6 503.9 3133.23 3158.57 0.8% C6 28.0 20.2 101.200 51.0 35.5 637.72 633.87 0.6% C6 28.0 20.2 101.200 51.5 315.3 1882.22 1887.93 0.3% C6 28.0 20.2 101.200 51.0 509.3 2392.12 2399.24 0.3% C4 27.7 20.3 101.200 50.7 79.7 623.71 624.61 0.1% C4 27.8 20.3 101.200 49.8 323.9 1278.30 1285.43 0.6% C4 27.8 20.4 101.200 50.0 489.9 1578.77 1590.33 0.7% C2 27.6 20.5 101.200 50.7 66.7 292.91 295.43 0.9% C2 27.6 20.5 101.200 51.3 298.4 669.67 667.61 0.3% C2 27.6 20.5 101.200 50.3 457.5 835.66 842.29 0.8% C1 27.4 20.7 101.200 51.2 66.4 162.53 166.71 2.6% C1 27.3 20.8 101.200 51.9 282.5 371.13 370.82 0.1% C1 27.3 20.8 101.200 51.5 434.6 464.75 470.39 1.2% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071309-PH002041 Calibration Date:2019-02-07 Results:As Left Page 3 of 3 Calibration Date:2019-02-07 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.551 842.48 8.6 A 0.496 487.10 12 B 0.491 305.51 10 C8 0.509 132.95 10 C6 0.500 106.52 10 C4 0.514 65.69 10 C2 0.544 30.08 10 C1 0.552 16.45 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202102161221-PH002042 Calibration Date:2021-02-16 Results:As Left Page 1 of 3 Calibration Date:2021-02-16 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Shelby Zettle Model Number:Model 3000SR Shell Serial Number:PH002042 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07 and ASTM E1258-88 standards: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2026-02-16 CGSB 2002 2026-02-16 ATTMA-TS1 2022-02-16 ASTM-E779 2026-02-16 RESNET 2026-02-16 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202102161221-PH002042 Calibration Date:2021-02-16 Results:As Left Page 2 of 3 Calibration Date:2021-02-16 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 31.6 16.5 101.700 51.0 21.8 4529.10 4474.47 1.2% Open 32.4 16.1 101.700 51.2 101.5 10096.35 10271.53 1.7% Open 33.7 15.4 101.700 50.7 158.2 12693.80 13062.67 2.9% A 33.4 15.6 101.700 51.1 20.8 2198.27 2243.00 2.0% A 33.3 15.6 101.700 50.8 184.3 6459.71 6613.83 2.4% A 33.5 15.5 101.700 49.1 284.0 8008.37 8195.84 2.3% B 33.1 15.7 101.700 50.9 34.0 1718.95 1743.21 1.4% B 33.3 15.8 101.700 51.4 250.8 4599.35 4679.28 1.7% B 32.5 16.3 101.700 48.3 397.9 5772.22 5871.51 1.7% C8 32.0 16.5 101.700 50.8 93.1 1327.81 1353.65 1.9% C8 32.1 16.8 101.700 50.0 336.1 2539.69 2580.87 1.6% C8 31.9 17.0 101.700 49.1 512.4 3144.40 3185.16 1.3% C6 30.9 17.6 101.700 50.7 34.5 619.19 626.03 1.1% C6 31.1 17.5 101.700 51.4 304.3 1841.24 1865.50 1.3% C6 31.0 17.7 101.700 51.5 496.8 2359.70 2379.97 0.9% C4 30.1 18.4 101.700 50.6 82.0 621.03 631.19 1.6% C4 30.2 18.4 101.700 50.0 318.1 1247.99 1259.35 0.9% C4 30.5 18.2 101.700 49.2 489.9 1555.73 1567.52 0.8% C2 30.1 18.5 101.700 50.7 67.2 284.70 295.24 3.7% C2 30.2 18.5 101.700 49.7 298.9 657.70 660.86 0.5% C2 30.4 18.5 101.700 50.4 459.9 818.88 832.24 1.6% C1 29.9 19.0 101.700 50.5 65.8 161.19 162.66 0.9% C1 30.0 18.9 101.700 49.8 280.3 358.50 362.13 1.0% C1 30.2 19.0 101.700 50.5 430.9 448.43 458.32 2.2% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:202102161221-PH002042 Calibration Date:2021-02-16 Results:As Left Page 3 of 3 Calibration Date:2021-02-16 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.540 830.76 8.6 A 0.495 488.64 12 B 0.495 298.20 10 C8 0.504 135.53 10 C6 0.502 104.87 10 C4 0.510 66.24 10 C2 0.541 30.04 10 C1 0.553 15.97 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071055-PH002043 Calibration Date:2019-02-07 Results:As Left Page 1 of 3 Calibration Date:2019-02-07 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Mike Cline Model Number:Model 3000SR Shell Serial Number:PH002043 Main Voltage:110 V -240 V Main Frequency:50 Hz /60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2024-02-07 CGSB 2002 2024-02-07 ATTMA-TS1 2020-02-07 ASTM-E779 2024-02-07 RESNET 2024-02-07 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071055-PH002043 Calibration Date:2019-02-07 Results:As Left Page 2 of 3 Calibration Date:2019-02-07 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 25.4 21.5 101.300 51.0 14.2 3495.32 3521.24 0.7% Open 26.1 21.0 101.300 54.3 90.4 9834.67 9840.58 0.1% Open 28.5 19.3 101.300 51.5 136.7 12447.85 12372.93 0.6% A 27.9 19.8 101.300 51.7 22.8 2296.15 2276.91 0.8% A 27.9 19.8 101.300 53.5 182.3 6405.44 6380.79 0.4% A 27.9 19.8 101.300 52.7 276.1 7867.03 7838.63 0.4% B 27.4 20.2 101.300 51.4 33.8 1697.96 1697.93 0.0% B 27.5 20.2 101.300 51.8 249.0 4575.25 4563.99 0.2% B 27.2 20.4 101.300 49.4 388.4 5700.16 5687.36 0.2% C8 26.9 20.6 101.300 50.6 87.9 1313.86 1362.06 3.7% C8 26.9 20.7 101.300 50.9 329.4 2560.63 2636.18 3.0% C8 26.7 20.8 101.300 50.2 501.0 3156.34 3250.95 3.0% C6 26.5 20.9 101.300 52.1 33.5 654.29 626.31 4.3% C6 26.5 21.0 101.300 51.9 312.3 1895.03 1898.62 0.2% C6 26.5 21.0 101.300 50.6 503.4 2407.99 2407.00 0.0% C4 26.5 20.9 101.300 51.2 78.4 626.41 632.14 0.9% C4 26.7 20.9 101.300 51.3 315.9 1279.70 1284.67 0.4% C4 26.7 20.9 101.300 50.6 483.7 1587.76 1595.68 0.5% C2 26.5 21.0 101.300 50.7 59.8 285.01 284.96 0.0% C2 26.5 21.0 101.300 50.6 296.2 679.13 679.96 0.1% C2 26.5 21.0 101.300 51.2 455.0 848.74 858.54 1.2% C1 26.4 21.1 101.200 51.0 64.4 165.11 164.40 0.4% C1 26.2 21.3 101.200 52.5 276.1 375.84 369.06 1.8% C1 26.3 21.3 101.200 51.5 424.0 469.35 468.31 0.2% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201902071055-PH002043 Calibration Date:2019-02-07 Results:As Left Page 3 of 3 Calibration Date:2019-02-07 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.554 809.62 8.6 A 0.496 483.27 12 B 0.495 297.24 10 C8 0.500 145.30 10 C6 0.497 109.28 10 C4 0.509 68.68 10 C2 0.543 30.87 10 C1 0.555 16.27 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD. Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201811061056-PH002735 Calibration Date:2018-11-06 Results:As Left Page 1 of 3 Calibration Date:2018-11-06 Calibration laboratory Retrotec 1060 East Pole Road Everson,WA,US 98274 +1 (360)738-9835 calibration@retrotec.com http://www.retrotec.com This calibration laboratory has been assessedby the ANSI-ASQ National Accreditation Board andmeets the requirements ofinternational standard ISO/IEC 17025.All pressure and flow devices used in this calibration are traceable to the National Institute ofStandards and Technology. Device being calibrated: Description:Test Fan Manufacturer:Retrotec Calibrated by:Mike Cline Model Number:Model 1000 Shell Serial Number:PH002735 Main Voltage:120 V Main Frequency:60 Hz Signature Reference Flow: Nozzle 2010 Chamber,in accordance with ANSI/AMCA 210-07: Device Under Test Gauge:DM-32 Gauge Serial number 408019 Reference Gauge:DM-32 Gauge Serial number 407350 Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards.The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95%confidence level.In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account.The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure:Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced exceptin full,without writtenapproval fromRetrotec. Name Calibration Expiration Date Name Calibration Expiration Date ISO 9972 2023-11-06 CGSB 2002 2023-11-06 ATTMA-TS1 2019-11-06 ASTM-E779 2023-11-06 RESNET 2023-11-06 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201811061056-PH002735 Calibration Date:2018-11-06 Results:As Left Page 2 of 3 Calibration Date:2018-11-06 Calibration Results: Flow rates are corrected to STP conditions of 20°C,101.325 kPa,50%RH and Air Density:1.19886 Range Humidity % (RH)Temp (C) Barometric Pressure (kPa) Chamber Pressure (Pa) Fan Pressure (Pa) Reference Flow (m³/h) Fan Flow (m³/h)Error (%) Open 53.7 19.2 100.600 50.2 14.0 3469.94 3449.89 0.6% Open 54.7 18.9 100.600 53.1 101.9 10147.76 10159.00 0.1% Open 58.4 17.7 100.600 50.1 163.8 12942.96 13154.92 1.6% A 57.3 18.0 100.600 50.7 22.3 2211.43 2220.85 0.4% A 57.1 18.1 100.600 51.0 182.2 6179.54 6219.04 0.6% A 57.6 17.9 100.600 49.2 294.8 7831.50 7875.38 0.6% B 56.8 18.2 100.600 50.9 35.7 1634.36 1651.58 1.1% B 57.0 18.2 100.600 51.5 244.8 4266.59 4290.60 0.6% B 57.3 18.1 100.600 50.8 394.0 5415.24 5432.28 0.3% C8 56.6 18.3 100.600 50.6 100.3 1301.86 1326.67 1.9% C8 56.8 18.3 100.600 51.4 340.2 2409.69 2435.64 1.1% C8 57.0 18.2 100.600 50.5 520.7 2994.89 3010.07 0.5% C6 56.6 18.4 100.600 50.5 41.5 611.04 615.55 0.7% C6 56.5 18.4 100.600 52.3 311.0 1661.00 1673.43 0.8% C6 56.6 18.3 100.600 51.8 510.4 2126.95 2139.94 0.6% C4 56.0 18.5 100.600 50.3 98.4 612.03 626.23 2.3% C4 56.1 18.5 100.600 50.4 329.3 1125.44 1148.08 2.0% C4 56.0 18.6 100.600 49.5 504.0 1393.08 1421.37 2.0% C2 55.4 18.8 100.600 51.1 93.9 276.63 283.14 2.4% C2 55.6 18.7 100.600 51.1 308.0 524.63 526.01 0.3% C2 55.6 18.7 100.600 51.6 463.6 648.47 650.95 0.4% C1 54.9 19.0 100.600 50.6 123.0 154.06 157.23 2.1% C1 54.8 19.0 100.600 49.8 319.7 255.20 263.33 3.2% C1 54.8 19.0 100.600 51.0 465.7 310.17 322.71 4.0% Calibration and measurement capability (Expanded Uncertainty)is 1.58%of reading,based on a 95%confidence interval,using a coverage of K=2 Certificate of Calibration Tested in accordance to ISO 9972,CGSB 2002,ATTMA-TS1,ASTM-E779,RESNET:Pass Issued by:Retrotec Certificate Number:201811061056-PH002735 Calibration Date:2018-11-06 Results:As Left Page 3 of 3 Calibration Date:2018-11-06 Published Flow Equation Parameters (Units in m³/h): Range Configuration n K MF (Pa) Open 0.534 866.99 8.6 A 0.491 480.34 12 B 0.497 278.68 10 C8 0.506 126.81 10 C6 0.503 95.91 10 C4 0.512 58.41 10 C2 0.520 26.52 10 C1 0.528 12.07 10 Flow =P^n x K Where P =Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C1 0 0.4 0 Date Format: This report adheres to ISO 8601:Data elements and interchange formats -Representation of dates and times. All dates on this report are in the format:YYYY-MM-DD.