Stairwell Pressurization
TEST, ADJUST & BALANCE
Revision Date:Revision Number:-
05/25/23Project Completion Date:
Renton, WA 98056
CERTIFIED REPORT
CT-1646-23
Report Title
Project: Sunset Terrace
Stairwell Pressurization
Renton, WA 98056
NEI Job#: CT-1646-23
Engineer: Abossein Engineering LLC
Contractor: Oak Hill Builds
TAB Firm: Neudorfer Engineers Inc
5516 1st Avenue South
Seattle, WA 98108
Test Engineer:
Architect:-
5516 1st Ave S
Seattle, WA 98108 Vancouver, WA 98661
Phone (206) 621-1810 Phone (503) 235-8924
Fax (206) 343-9820 Fax (503) 235-8925
CERTIFIED REPORTCERTIFIED TEST:
Tony Amort
2501 SE Columbia Way, Ste. #230
If Integra Testing fails to comply with the specifications for any reason other than
equipment malfunction or inadequacy which prevents proper balancing of the
systems,Integra Testing’s Quality Control Team will investigate and,if warranted,
will provide supervisory personnel to assist in the rebalancing of the air or hydronic
system(s).The rebalancing of any of the air or hydronic systems will be provided at
no additional cost to the building owner.Reported items documented outside of
design tolerances with reason are not included in this warranty.If a complaint
issue is due to a mechanical equipment failure,control or maintenance related
issue,the return trip may be subject to a service charge which is not covered under
this warranty.Third party adjustments made to the system prior to invocation of
warranty also voids this warranty.
This Guaranty is valid for one year from the date of submission of a test and balance report and may only be invoked in
writing by the building owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as
stated herein. Response to complaints will be provided within 10 business days of initial complaint.
Pursuant to the agreement between Integra Testing Services,LLC and/or its
subsidiaries (“Integra Testing”)and Client,all systems shall be tested,adjusted,
and balanced in accordance with the project plans and specifications and to the
optimum performance capabilities of the equipment.Testing and balancing shall
be done in accordance with the standards published by the Associated Air Balance
Council (AABC)and/or the National Environmental Balancing Bureau (NEBB).
Submitted and Certified by:
NEBB TAB Firm: Neudorfer Engineers Inc
Certification No: 3856
Expiration Date: December 31, 2023
Certification Date: May 25, 2023
(Date completed)
Signed and Sealed by:
NEBB Supervisor: William C. Neudorfer
Noted deficiencies are not Neudorfer Engineers responsibility to repair.Prior to
issuance of this report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from the date of substantial completion.Within
that time,any discrepancies,ambiguities,or omissions found in this report will be
retested, adjusted, or balanced as needed. A written notification will be required.
Significant /Noteworthy Remarks are noted on the General Remarks and General
Field Notes pages. Other remarks are noted on individual test sheets.
CERTIFICATION
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the
NEBB Procedural Standards for Testing,Adjusting,and Balancing of
Environmental Systems.Any variances from design quantities which exceed
NEBB tolerances are noted in the Test-Adjust-Balance Report Project Summary.
Warranty
Project:Sunset Terrace
Stairwell Pressurization
Renton, WA 98056
Warranty of Services:
Warranty Procedures:
Voided Warranty and Additional Charges:
Document Archiving
An electronic file of all test documents will be kept on file until the end of the Warranty period.During that
time an electronic copy of the test data will be provided a no charge.Any additional hard /bound copies
requested will be subject to a fee.
For all warranty items,Neudorfer Engineers requires written request.The written request should be specific
on the areas of concern,such rooms,or equipment,and the type of issue the occupants are experiencing.
Once written notification is received,Neudorfer Engineers will schedule a Technician.It is recommended
that an Owner or A/E Representative be on site at that time.
If a complaint issue is due to a mechanical equipment failure,control or maintenance related,the return trip
maybe subject to a service charge,not covered under warranty.Neudorfer Engineers reserves the right to
resolve any TAB issue.If a third party or competing Test &Balance Commissioning firm test or adjust any
equipment,all project warranty is voided.(This is typical standard for the Mechanical industry,as
Manufacture,Mechanical and Control Contractor voids all warranty when a competing firm tests or
manipulates their systems.)Any return trips to the job site are subject to a service charge and a purchase
order will be required before returning to the job site.
Neudorfer Engineers,Inc.warrants that the air balancing,evaluated during this performance evaluation are
operating at the specified levels as documented within this report.At and only this time,and makes no other
warranties,stated or implied,concerning the continued performance,operation or safety in the use of this
equipment past this time.Neudorfer Engineers warrants the air balancing for 1 year from the date of
substantial completion.Neudorfer Engineers reserves the right to correct errors or omissions in the
collections of data.
Terms and Abbreviations
Project:Sunset Terrace
Stairwell Pressurization
Renton, WA 98056
AC or ACU Air Conditioner or Air Conditioning Unit Dia.Diameter
Act.Actual Disch.Discharge
ACCU Air Cooled Condensing Unit DNL Data Not Listed
Address Equipment designation number given mechanical cooling.
Arr Arrangement EDC Electric Duct Coil
AVG Average Economizer Controls and components that allow an
Amps Amperage air handler to logically utilize outdoor air
AP Access Point for cooling as opposed to the use of
APP.Application EDH Electric Duct Heater
BHP Brake Horsepower EF Exhaust Fan
BTU British Thermal Units EG Exhaust Grille
BTUH British Thermal Units per Hour EMCS Energy Management Control System
CAV Constant Air Volume ERU Energy Recovery Unit
CBV Calbirated Balancing Valve E.S.P.External Static Pressure
(Circuit Setter)Evap.Evaporator
CC Cooling Coil EWT Entering Water Temperature
CD Ceiling Diffuser FCU Fan Coil Unit
CFLA Correct Full Load Amperage FD Fire Damper
CFM Cubic Feet per Minute FH Fume Hood
CH Chiller FLA Full Load Amperage: Maximum
CHWS Chilled Water Supply amperage a motor can draw.
CHWR Chilled Water Return Flow Hood Instrument that captures air and
Coeff.Coefficient converts the reading to CFM.
CP Circulating Pump FPB Fan Powered Box
CR Ceiling Register FPM Feet per Minute
CRAC Computer Room Air Conditioner FR Field Report
CRU Computer Room Unit FT Foot, Feet
CT Cooling Tower FTU Fan Terminal Unit
CU Condenser Unit GPM Gallons per Minute
CUH Cabinet Unit Heater HC Heating Coil
CWS Condenser Water Supply HD Pressure Difference across the entering
CWR Condenser Water Return and leaving side of a pump.
DAT Discharge Air Temperature Heater O.L.Thermal overload protection for motors
DB Dry Bulb located at the motor starter (starter heaters)
DD Direct Drive HEPA High Efficiency Particulate Arrestance
DDC Direct Digital Controls: EMS Control HOA Hand / Off / Auto Switch
System for the HVAC HP Horsepower
Delta (Δ) Difference, net decrease or increase HRC Heat Recovery Coil
Des.Design HUH Hydronic Unit Heater
Terms and Abbreviations
Project:Sunset Terrace
Stairwell Pressurization
Renton, WA 98056
HVAC Heating Ventilation and Air Conditioning SAT Supply Air Temperature
HWS Heating Water Supply S.F.Service Factor
HWR Heating Water Return Schedule Design data obtained from the
HX Heat Exchanger (sched)mechanical prints' schedule of
HZ Hertz, cycle per second equipment.
I.D.Inside Diameter SCR Silcon Controlled Rectifier
in.inches Speed Controller
in.w.g.inches of water gauge SF Supply Fan
Kfactor Correction factor to the free area need to SFD Smoke/Fire Damper
calculate CFM.SP Static Pressure
KW Kilowatts Spec(s)Specifications
LAT Leaving Air Temperature sq.ft.square feet
LWG Low Wall Grille Submittals Submitted data on equipment
LWR Low Wall Register (subs)capabilities.
LWT Leaving Water Temperature Suct.Suction
MAU Make-up Air Hangling Unit SWG Sidewall Grille
MAX Maximum Flow Requirements for DDC SWR Sidewall Register
MBH Mega BTUs per hour (1MBH=1,000BTUH)TAB Test; Adjust; and Balance
MIN Minimum Flow Requirements for DDC Tach Tachometer
N/A Not Available Tech Technician
N/S Not Shown or Specified TSP Total Static Pressure: Difference
OA Outside Air between the entering and leaving
OBD Opposed Blade Damper static pressure of a fan.
O.D.Outside Diameter TP Traverse or Test Point
PD Pressure Drop. TU Terminal Unit
PH Phase UH Unit Heater
PHC Preheat Coil VAV Variable Air Volume; box that
Prim.Primary contains a motorized damper that
PSI Pounds per Square Inch modulates airflow.
RA Return Air VD Volume Damper
RAT Return Air Temperature VFD Variable Frequency Drive
RF Return Fan Velgrid Instrument that reads used to read
RH Relative Humidity velocity in feet per minute.
RHC Reheat Coil VP Velocity Pressure
RPM Revolutions per Minute VVT Variable Volume Terminal
RTU Roof Top Unit W.C.Water Column
RVA Rotating Vane Anemometer -reads W.G.Water Gauge
air velocity in feet per minute WB Wet Bulb
SA Supply Air
2715 Sunset Lane NE, Renton, WA 98056 Page 1 of 2
N NEUDORFER ENGINEERS, LLC.
Consulting Engineers
5516 1st Avenue South
Seattle, Washington 98108
(206) 621-1810 Fax (206) 343-9820
Sunset Terrace
Stair 1 Pressurization
Confidence Testing
SPF-1 Certification Given
RED YELLOW WHITE X
CONFIDENCE TEST X REPAIRS
Occupancy Address:2715 Sunset Lane NE
Renton WA 98056
Occupancy Name:Sunset Terrace
Building Owner:iCAP Equity Phone Number:(425) 278-9023
Responsible Person:Jami Stevenson Phone Number:
Building Owner Address:3535 Factoria Blvd SE #500
Bellevue, WA 98006
Date of Inspection:5/25/23
Inspection
Frequency/Type:New Construction
Testers Name
(Please Print):Antonio Amort
NEBB Certification
Number:21988
Central station
monitoring?Yes X No Monitoring
Company Name:Fire Protection Inc.
Primary Component:System Make:Honeywell
System Model:Gamewell E3 Series
System Location:Level 1
Identification
Number:
PROBLEMS FOUND: (If additional room is needed, please add a separate sheet)
CORRECTIONS MADE: Date Corrected: __________Corrected By: ______________________________
(If additional room is needed, please add a separate sheet)
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Bellevue Fire Department Fire Code standards, and that
Discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
Signature of Tester:__________________________Phone #(206) 715-5085
Testing Agency:Neudorfer Engineers, LLC.
Mailing Address:5516 1st Avenue South, Seattle Washington
Building Representative (signature) _____________________________________________________
2715 Sunset Lane NE, Renton, WA 98056 Page 2 of 2
Measurements Taken
Floor Pressure
(inches)
Floor Pressure
(inches)
Floor Door Force
(Pounds)
Floor Door Force
(Pounds)
*See attached sheet for pressure measurements.
General
Do stair shafts have flush? CFM __________Yes No X
Were measurements taken from atmospheric pressure?Yes X No
Were measurements taken from shaft and the main occupied area?Yes X No
What was static pressure? 0.16”-0.20” in. H2O
Do elevator shaft pressures measure 0.10 in H2O, in 100% automatic sprinklered
building?
Yes No X
All doors operate correctly?Yes X No
System can be operated manually?Yes X No
Does life safety core type building have 0.05 in H2O between pressurized core and
tenant area?
Yes X No
Are gaskets in good condition on stair and elevator doors?Yes X No
Do all dampers, controls work properly on shaft pressurization system?Yes X No
Do stair shaft pressures measure 0.10 in H2O?Yes X No
Additional Measurements, Calculations and Comments:
2715 Sunset Lane NE, Renton, WA 98056 Page 1 of 2
N NEUDORFER ENGINEERS, LLC.
Consulting Engineers
5516 1st Avenue South
Seattle, Washington 98108
(206) 621-1810 Fax (206) 343-9820
Sunset Terrace
Stair 2 Pressurization
Confidence Testing
SPF-2 Certification Given
RED YELLOW WHITE X
CONFIDENCE TEST X REPAIRS
Occupancy Address:2715 Sunset Lane NE
Renton WA 98056
Occupancy Name:Sunset Terrace
Building Owner:iCAP Equity Phone Number:(425) 278-9023
Responsible Person:Jami Stevenson Phone Number:
Building Owner Address:3535 Factoria Blvd SE #500
Bellevue, WA 98006
Date of Inspection:5/25/23
Inspection
Frequency/Type:New Construction
Testers Name
(Please Print):Antonio Amort
NEBB Certification
Number:21988
Central station
monitoring?Yes X No Monitoring
Company Name:Fire Protection Inc.
Primary Component:System Make:Honeywell
System Model:Gamewell E3 Series
System Location:Level 1
Identification
Number:
PROBLEMS FOUND: (If additional room is needed, please add a separate sheet)
CORRECTIONS MADE: Date Corrected: __________Corrected By: ______________________________
(If additional room is needed, please add a separate sheet)
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Bellevue Fire Department Fire Code standards, and that
Discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
Signature of Tester:__________________________Phone #(206) 715-5085
Testing Agency:Neudorfer Engineers, LLC.
Mailing Address:5516 1st Avenue South, Seattle Washington
Building Representative (signature) _____________________________________________________
2715 Sunset Lane NE, Renton, WA 98056 Page 2 of 2
Measurements Taken
Floor Pressure
(inches)
Floor Pressure
(inches)
Floor Door Force
(Pounds)
Floor Door Force
(Pounds)
*See attached sheet for pressure measurements.
General
Do stair shafts have flush? CFM __________Yes No X
Were measurements taken from atmospheric pressure?Yes X No
Were measurements taken from shaft and the main occupied area?Yes X No
What was static pressure? 0.17”-0.20” in. H2O
Do elevator shaft pressures measure 0.10 in H2O, in 100% automatic sprinklered
building?
Yes No X
All doors operate correctly?Yes X No
System can be operated manually?Yes X No
Does life safety core type building have 0.05 in H2O between pressurized core and
tenant area?
Yes X No
Are gaskets in good condition on stair and elevator doors?Yes X No
Do all dampers, controls work properly on shaft pressurization system?Yes X No
Do stair shaft pressures measure 0.10 in H2O?Yes X No
Additional Measurements, Calculations and Comments:
Fan UnitPROJECT:LOCATION:Sunset Terrace Stair Pressurization RENTON, WA
CT-1646-23PROJECT #:
DATE:CONTACT:
AUTHOR:
5/25/2023Tony Amort
Tested By:Tony Amort
Date:5/25/2023
SYSTEM/UNIT: SF-1
Log:SF-1 5/25/2023 Tony Amort The Amps and Volts were recorded from the VFD.
Unit Data
Fan Manufacturer ILG
Fan Model Number CFS18QD8363
Fan Serial Number 091321M645210
Fan Rotation Clockwise
Fan Discharge Bottom Vertical
Drive Type Belt Drive
Test Data
Motor RPM Actual 801 RPM
Motor VFD Hertz 27.0 Hz
Motor Volts T1-T2 94 Volts
Motor Amps T1 5.48 Amps
Motor Data
Motor Manufacturer Baldor
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1750 RPM
Motor Rated Volts 230/460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor Full Load Amps 13.2/6.6 Amps
Motor Service Factor 1.15
Nominal Efficiency 89.50 %
Power Factor 0.80
Sheave Data
Motor Sheave MFG Not Listed
Motor Sheave Diam.5 OD
Motor Sheave Bore 1 in.
Motor Sheave Type Adjustable
Adj Mtr Sheave Pos Middle
Fan Sheave Diam.9.25 OD
Fan Sheave Bore 1 in.
Number of Belts 2
Belt Size A64
Sheave Center Line 22.50 in.
Motor to Extend 3.00 in.
Motor to Retract 4.00 in.
Neudorfer Engineers
Fan UnitPROJECT:LOCATION:Sunset Terrace Stair Pressurization RENTON, WA
CT-1646-23PROJECT #:
DATE:CONTACT:
AUTHOR:
5/25/2023Tony Amort
Tested By:Tony Amort
Date:5/25/2023
SYSTEM/UNIT: SF-2
Log:SF-2 5/25/2023 Tony Amort The Amps and Volts were recorded from the VFD.
Unit Data
Fan Manufacturer ILG
Fan Model Number CFS18QD8363
Fan Serial Number 091321M645210
Fan Rotation Clockwise
Fan Discharge Bottom Vertical
Drive Type Belt Drive
Test Data
Motor RPM Actual 747 RPM
Motor Volts T1-T2 88 Volts
Motor Amps T1 5.40 Amps
Motor Data
Motor Manufacturer Baldor
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1750 RPM
Motor Rated Volts 230/460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor Full Load Amps 13.2/6.6 Amps
Motor Service Factor 1.15
Nominal Efficiency 89.50 %
Power Factor 0.80
Sheave Data
Motor Sheave MFG Not Listed
Motor Sheave Diam.5 OD
Motor Sheave Bore 1 in.
Motor Sheave Type Adjustable
Adj Mtr Sheave Pos Middle
Fan Sheave Diam.9.25 OD
Fan Sheave Bore 1 in.
Number of Belts 2
Belt Size A64
Sheave Center Line 22.50 in.
Motor to Extend 3.00 in.
Motor to Retract 4.00 in.
Neudorfer Engineers
Date: 5/25/23
R
7
6
5
4
3
2
1
P1
P2
HZ
27 Hz
25 Hz
ATM = Atmosphere
Door force indicates the force measured at the stairwell doors.
A calibrated Shortridge ADM was used to measure pressure.
All pressures were measured in inches of water column.
Notes
Notes:
Notes:
See attached sheets for fan operating data.
Event Level Pressurization Fans Panel Speed Reference
Floor Reference to Atmosphere SPF-1 -
Fan VFD speeds and control program speed reference SPF-2 -
Fire Zone
NA means the data was not applicable.
0.18" / 25 lbs 0.18" / 27 lbs
0.16" / 22 lbs 0.18" / 24 lbs
0.16" / 30 lbs // 0.16" (Outside Egress)0.17" / NA
0.17" / 24 lbs -
0.18" / 25 lbs 0.19" / 27 lbs
0.19" / 25 lbs 0.20" / 25 lbs
0.19" / 25 lbs 0.20" / 28 lbs
0.19" / 25 lbs 0.20" / 27 lbs
0.16" / 25 lbs 0.18" / 25 lbs
0.21" / 22 lbs (Atmosphere)-
+0.10'' to 0.35" W.C. / Door Force +0.10'' to 0.35" W.C. / Door Force
Technician(s): Tony Amort / Alex Lorenzo Project: Sunset Terrace Stairwell 1 and 2 Pressurization - General Alarm
Floor Stair 1 / SPF-1 Stair 2 / SPF-2