RECORD DRAWINGS
THESE AS —BUILT DOCUMENTS HAVE BEEN PREPARED
FROM THE CONTRACTOR'S REDLINED MARK—UPS OF THE
CONSTRUCTION DOCUMENTS. THE ENGINEER REVIEWING
THESE RECORD DRAWINGS HAS NOT WITNESSED ALL THE
ELEMENTS OF CONSTRUCTION AND IS NOT RESPONSIBLE
FOR ERRORS OR OMISSIONS IN DATA OR CERTIFY THE
ACCURACY OF THE INFORMATION PROVIDED BY THE
CONTRACTOR'S AS —BUILT REDLINES.
400
Z
CD
o i=
r7
U ZD
Lj
390
W
r CD
0 W
UJI CD
4
(N LL
�*'Ifj
370
360
350
340
m!�
A /
/ A 84+40.60, 12.35' RT /
o FIRE HYDRANT ASSEMBLY /
0
d m
o 1-10m"
u7
Z
Q
84+40
0
0 00
FUTURE CURB ALIGNMENT
(PER C21005145)
0
0
So
STA 84+41.54, 5.83' RT STA 83+38.19, 7.08' LT
FIRE HYDRANT CONNECTION (1)-12" 11.25° BEND, (MJ)
PER COR STD 310.1 AND 310.3 (1)—THRUST BLOCK
(1)-12"x6" TEE, (MJxFL)
(1)-6" GV, (FLxMJ)
(1)—THRUST BLOCK
1
0 10' 20' 40'
1 inch = 20 ft. HORZ
0 5' 10' 20'
1 inch = 10 ft. VERT N0.
84+00 83+60 83+20
•j
0
(3) m 565 M S11
5400 4/
71/ o \
I
I
N ,
LC7
STA 83+03.94, 3.32' LT
CONNECT TO EX 8" W �31
PER COR STD 300.2
(1)-8"x8" TEE, (FLxFL)
(2)-8" GV, (FLxMJ)
(1)-8" ADAPTER (FLxMJ)
(2)-8" SLEEVE, (MJ)
(1)—THRUST BLOCK
(1)-12"x8" REDUCER (MJxPE)
(1)-12" SLEEVE (MJ)
8" AND 12" SPOOLS
AS REQUIRED
—BUILT 10/ 10/23 RVEYED:
DESIGNED:
BG
DRAWN:
DC, JYL
CHECKED:
CB
REVISION BY DATE APPR APPROVED:
TJE
AS -BUILT 04199
SCALE:
HomzONf N D 1983/11991
AS SHOWN
ONE INCH DATUM
AT FULL SCALE
IF NOi ONE INCH
SCALE ACCORDINGLY
NOTES
1. RESTORE UTILITY TRENCH TO EX GRADE IN ACCORDANCE WITH RMC
9-10-11 TRENCH RESTORATION AND STREET OVERLAY REQUIREMENTS.
DOCUMENT EX GRADE PRIOR TO CONSTRUCTION.
2. ALL WATER FITTINGS AND VALVES WITH MECHANICAL JOINT (MJ) END(S)
SHALL HAVE A WEDGE —TYPE RETAINER GLAND EQUAL TO MEGALUG SERIES
1100.
3. CONCRETE THRUST BLOCKS ARE REQUIRED ON ALL WATER FITTINGS PER
COR STD. PLANS 330.1, 330.2 AND 330.3.
4. WHERE NEW WATER MAIN CROSSES A NON —POTABLE PIPE, ONE FULL
LENGTH OF WATER PIPE SHALL BE USED WITH THE PIPE CENTERED FOR
MAXIMUM JOINT SEPARATION UNLESS OTHERWISE STATED.
5. WATER MAIN PIPE DEFLECTION SHALL NOT EXCEED ONE HALF OF PIPE
MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE.
6. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT —LINED (DOUBLE
THICKNESS) DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C151
AND C104 STANDARDS.
LEGEND
ROW LINE
w w
WATER < 12"
�W�W�
WATER > 12"
Fs FS
FIRE SERVICE
N
VALVE
THRUST BLOCK
li
FIRE HYDRANT
SLEEVE
I • E
POLYPIGGING STATION
FLAG NOTES
O1 EX FIRE HYDRANT TO BE REPLACED. EX FIRE HYDRANT SHALL REMAIN
OPERATIONAL UNTIL NEW WATER MAIN AND FIRE HYDRANT ARE ACCEPTED
AND OPERATIONAL. EX FIRE HYDRANT, FIRE HYDRANT VALVE, AND VALVE
BOX SHALL BE REMOVED AFTER ABANDONMENT OF EX WATER MAIN. EX
HYDRANT TO BE REPLACED SHALL BE SALVAGED TO COR WATER SHOPS.
V�
z
SLLJ
L
LLJ
O
rr
In
2
Z_
a
rr
LLJ
a
w
F____
U)
LL
O
C/)
z
S
�� J.
��' Z� w�SN�1
W
0
f
1q)ff
�
�
a
0
• Call 814ISTER�'�
��`rs10NAL
1601 5th Avenue, Suite 1600
w
� ® two business days ���ti�
Seattle, WA 98101
W— 419 911
before you dig
10/16/2023
.2.kpffff.com
www
www.kpff2.582.com
• CITY OF
CITY OF RENTON
11/15/2022
RENTON
RENTON SUNSET GARDENS
�
�
•
OFF -SITE WATER MAIN IMPROVEMENTS
DRAWING NO:
Planning/Building/Public Works
Dept.
WATER UTILITY PLAN & PROFILE -
C303
z
JEFFERSON AVE NE (RESIDENTIAL)
LU
SHEET: G.
11 14