HomeMy WebLinkAboutR-408211IN S. W. 114 OF S. W. 114 OF SECTION 04, T. 23 N., R. 05 E. W. M. CITY OF RENTON, STATE OF WASHINGTON 0 N Nz- w w 3 EXISTING WATER LINE PLAN VIEW TESTING DETAIL H -...ICAL CROSS(MJxFL) FOR POLYPIGGING ONE BLIND FLANGE ON TOP WITH 2"TAP & 2"PLUG ONE BLIND FLANGE ON BOTTOM ONE (MJ) PLUG WITH 2" TAP & 2" TEMPORARY BLOW -OFF TEMPORARY BLOCK CUT -IN (BY CITY FORCES) TEE (FLxFL) W/ CONC. BLOCK 1- GATE VALVES (FLxMJ) 2- SOLID SLEEVES (MJ) OR RO-MAC COUPLINGS 1- PLUG (MJ) W/2"TAP & TEMP. BLOW -OFF TEMP. BLOCK EXISTING WATER LINE EXISTING WATER LINE FINAL CONNECTION DETAIL AFTER ALL TESTING, CLEANING BY POLYPIG, AND DISINFECTION, REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT WITH SLEEVE (MJ) & 0.1. SPOOLS FINAL CONNECTION BY CITY FORCES EXISTING WATER LINE 1 -' PUBLIC WORKS DEPARTMENT CONNECTION TO WATER MAIN CUT IN -LINE TEE & ONE VALVE STD. PLAN - 300.2 MARCH 2O10 Encompass ENGINEERING & SURVEYING Western Washington Division 165 NE Juniper Street, Suite 201 ■ IssaQuah, WA 98027 - Phone: (425) 392-0250 Eastern Washington Division k D 0 o I 11-1/4' BEND 22-1/2" BEND 45' BEND immm CI ) CAP TEE 190' BEND THRUST BLOCK BEARING AREA IN SQUARE FEET (SEE NOTES) FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS SOIL FIRM SILT OR FIRM SILTY SAND COMPACT SAND COMPACT SAND & GRAVEL 90' 45' BEND it 1/4' 90' 45-BEND 11 1/4' 90' 45' BEND 11 1/4' FITTING BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG do 22 1/2' BEND BEND BEND 4 7.0 4.2 4.2 1.7 2.9 2.1 2.1 I'D 2.2 1.6 1.6 1.0 6 t3.3 9.4 9.4 .7 4.7 4,7 1.9 5.0 3.5 3.5 1.4 8 23.3 16.7 16'7 6.7 11.7 8.4 8.4 3.4 8.8 6.3 6.3 2.5 12" 53.0 37.5 37.5 1 15.0 126.5 18.8 18.8 7.5 20.0 14.0 14.0 5.6 AREAS CALCULATED ON 300 PSI TEST PRESSURE. 3'-0" MIN. COVER FOR WATERMAIN LESS THAN 12'. 4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER. MAX. HEIGHT OF THRUST BLOCK (FT) = 0.5 x DEPTH OF TRENCH MIN. HEIGHT OF THRUST BLOCK (FT) = O.D. PIPE + 1.0' THRUST BLOCK BE AREA REFERS TO FACE OF BLOCK M IN SQUARE FEET 7L4" 1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND FOR SOIL TYPES DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER. 2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND. 3. ALL POURED THRUST BLOCKS SHALL BE BACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING SHALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH. 4. ALL BLOCKING SHALL BE CONCRETE CL 5 (1-1/2'). 5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA POSSIBLE, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOINT BOLTS OR GLANDS REASONABLE ACCESS 10 BOLTS AND GLANDS SHALL BE PROVIDED. PUBIC WOCONCRETE BLOCKING FOR STD. PLAN - 330.2 RK� 4 � � HORIZONTAL AND DOWNWARD llEl'AR'1'ML•'N'I' A o VERTICAL BENDS MARCH 2O10 EXISTING WATER LINE TESTING DETAIL EXISTING WATER LINE FINAL CONNECTION DETAIL PLAN VIEW TICAL CROSSCMJxFL) FOR POLYPIGGING BLIND FLANGE ON TOP WITH 2'TAP b 2'PLUG BLIND FLANGE ON BOTTOM (MJ) PLUG WITH 2' TAP 6 2' TEMPORARY BLOW -OFF 'ORARY BLOCK LINGS /C E AFTER ALL TESTING, CLEANING BY POLYPIG, AND DISINFECTION, REMOVE TEMP. BLOCK 6 BLOW -OFF L CONNECT WITH SLEEVE (MJ) a D.I. SPOOLS FINAL CONNECTION BY CITY FORCES EXISTING WATER LINE PUBLIC WORKS CONNECTION TO WATER MAIN CUT S7D' PLAN - 300.3 DEPARTMENT IN -LINE TEE & TWO VALVES �t t MARCH 2O10 407 Swiftwater Blvd. - Cle Elum, WA 98922 ■ Phone: (509) 674-7433 N0. AS-BUILTS REVISION 13"x24" PLASTIC METER BOX EQUAL TO MID -STATES PLASTIC, INC. BCF SERIES MSBCF 1324-18 WITH 1.75" THICK DUCTILE IRON DIAMOND PLATE COVER EQUAL TO LAID -SLATES PLASTICS, INC. MSCBC-1324-R WITH READER LID AND 2" DRILLED HOLE FOR TOUCHREAD PIT LID (SEE DETAIL A -A) 9" MIN, 12" MAX FINISH GRADE I 0 36" MIN COVER "' t) 22-1 /2' City I al r<r. PIPING r,r.. U. J I IN UNIMPROVED RIGHT OF J I WAY INSTALL METER BOX AT PROPERTY LINE NTH 12" � Of w LONG COPPER TAILPIECE. w 0. a I SIDEWALK $ I CL TOUCHREAD WATER METER TO BE SUPPLIED BY THE 12" z a CITY 3 �' _ TYPE "K" SOFT o -1 zl� COPPER TUBING N'? NEW DUCTILE IRON WATERMAIN IF SERVICE LINE TO HOUSE IS 3/4" OR 1" TO BE INSTALLED IN THE FUTURE GALVANIZEC INSTALL FORD C14-33 OR 44 FIPT PP LNG x COMPRESSION COUPLING LOOP DOWN TO CENTERLINE OF WATER MAIN TO PROVIDE SLACK IN COPPER COPPERSETTER FOR 5/8"x3/4" METER: FORD SERVICE LINE TO METER. VBH72-15W-44-33G, OR McDONALD BRASS: 21-215WC0033, OR MUELLER: 3/4-8-2470-2 WITH ANGLE BALL VALVE ON INLET AND SINGLE CHECK VALVE ON OUTLET CORPORATION STOP WITH BALL VALVE. FORD COPPERSETTER FOR 1" METER: FORD VBH72-15W-44-44G, OR TAPERED THREAD (CC). QUICK JOINT MCDONALD BRASS: 21-415WC0044, OR MUELLER: 1-B-2470-2 (3/4" FB10DO-3-0) OR AY MCDONALD 4701B BOTH INLET AND OUTLET WITH QUICK JOINT. PADLOCK WINGS ON (I- FB1000-4-0) OR AY MCDONALD 4701B INLET ANGLE BALL VALVE AND SINGLE CHECK VALVE ON OUTLET. ALL FITTINGS SHALL BE WITH OUICK JOINT. NOTE: ALL METER BOXES INSTALLED WITHIN CONCRETE OR PAVED DRIVEWAYS SHALL BE CAST-IRON EQUAL TO OLYMPIC FOUNDARY. EXPANSION JOINTS MUSH BE INSTALLED ON BOTH SIDES OF METER BOX. A- A DRILL 2" DIA. HOLE FOR AMR (AUTOMATIC METER READ) TOUCHREAD DEVICE 2-1/2" MIN. FROM NEAREST r AND FRONT EDGE OF PIT LID I TYPICAL RIB NOTE: THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS THE NUT TO TIGHTEN AGAINST THE OPEN SIDE OF MORE THAN ONE RIB. PUBLIC WORKS 34" AND 1" WATER SERVICE STD. PLAN - 320.1 DEPARTMENT NOVEMBER 2009 - INSIDE HOUSE PREFERRED CONFIGURATION Ga 5 � 3 10 8 10 4 FLOW # ITEM AMT 1 90' GALVANIZED STEEL ELBOW 4 EA. 2 3/4" PACKING JOINT COUPLING W/MALE IRON PIPE 2 EA. THREAD FOR COPPER PIPE SERVICE: FORD C84-33 OR EQUIVALENT FOR GALVANIZED PIPE SERVICE:FORD C85-33 OR EQUIVALENT 3 PRESSURE REDUCING VALVE W/STRAINER - 3/4" 1 EA. WITH UNION COUPLINGS AT INLET AND OUTLET, WILKINS 600 SERIES OR EQUAL (WITH INTERNAL BYPASS AND STRAINER) 4 3/4" CLOSE UNION - BRASS (M X F) 1 EA. 5 3/4" BRASS VALVE VARIABLE 6 12" STANDARD METER BOX W/SOLID COVER 1 EA. CONCRETE: 17 1/4 X 28 5/8 INSIDE DIMENSIONS, EQUAL TO FOG TITE METER SEAL CO. +2 PLASTIC: 13 X 24 j INSIDE DIMENSIONS, EQUAL TO BROOKS METER BOX 7 3/4" GALVANIZED STEEL PIPE, THREADED, LENGTH AS VARIABLE REQUIRED 8 3/4" X 1/4" X 3/4" STD. BRASS TEE 1 EA. 9 1/4" PETCOCK (M X F) 1 EA. 10 1 3/4" BRASS NIPPLE VARIABLE FUNCTION THE FUNCTION OF A PRESSURE REDUCING VALVE IS TO REDUCE HIGH-WATER PRESSURES IN THE SERVICE CONNECTION TO AN ACCEPTABLE RANGE OF 55 TO 75 PSI INSTALLATION OF A PRESSURE REDUCING VALVE IS REQUIRED WHERE THE SERVICE CONNECTION PRESSURE EXCEEDS 80 POUNDS PER SQUARE INCH IN ACCORDANCE TO THE UNIFORM PLUMBING CODE. INSTALLATION THE PRESSURE REDUCING VALVE SHALL BE LOCATED ON THE CUSTOMER'S PROPERTY 'DOWNSTREAM" OF THE METER BOX. RESPONSIBILITY FOR PROPER INSTALLATION, OPERATION, AND MAINTENANCE OF THE VALVE SHALL BE ASSUMED BY THE CUSTOMER. THREE POSSIBLE CONFIGURATIONS FOR INSTALLATION OF THE VALVE ARE SHOWN ABOVE. A BUILDING DEPARTMENT PLUMBING PERMIT IS REQUIRED PRIOR TO INSTALLATION PUBLIC WORKS 3a" & 1" INDIVIDUAL PRESSURE REDUCING STD. PLAN - 340.5 DEPARTMENT VALVE ASSEMBLY ys Tp� MARCH 2O10 SURVEYED: SDM DESIGNED: NEM DRAWN: TLK KMR 05122123 KMR CHECKED: NEM BY DATE APPR APPROVED: NEM SCALE 1" = 20' ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY VERTICAL: NAVD 1988 HORIZONTAL: NAD 1983/1991 DATU M W z r J Q �- j I- 11Y W W 0IO a DIRECTION OF FLOW FEa _3„ (MIN.) 6" MIN. 6"MIN.(TYP.) PLAN UNION (TYP,) TO CITY METER STACKED METER SECTION 6" MIN. FREE BOXES DRAINING GRAVEL NOTES: 1. ALL DOUBLE CHECK VALVE ASSEMBLIES (DCVA'S) MUST BE LISTED ON LATEST LIST OF "BACKFLOW PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASHINGTON DEPARTMENT OF HEALTH. 2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION OF THE INSTALLATION OF THE DCVA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE DCVA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN. 3. THE DCVA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER UTILITY CROSS -CONNECTION CONTROL SPECIALIST, FAX NO. 425-430-7241. 4. DCVA AND METER BOX SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE WATER METER. 34" TO 2" DOUBLE CHECK VALVE STD. PLAN - 340.8 PUBLIC WORKS ASSEMBLY FOR IRRIGATION OR �- DEPARTMENT RESIDENTIAL FIRE SPRINKLER MARCH 2O10 0 Cl T Y OF RENTON Planning/Building/Public Works Dept. M. pg WASkI �6 O 49917 d'Z,G18TER�9��� ANAL LAN�� 5/22/23 AS -BUILT DRAWINGS PLAN THESE AS -BUILT DRAWINGS AND THE INFORMATION SHOWN ACCURATELY REFLECT EXISTING FIELD CONDITIONS AS OF 05/22/23 (DATE SIGNED) BY: KEVIN M. REESE --��- 05/22/23 PROFESSIONAL ENGINEER OR DATE PROFESSIONAL LAND SURVEYOR 00 TQ:) v l , • z 0 0 W-408204 R- 4 0 8211 m IN COMPLIANCE WITH CITY OF RENTON STANDARDS � 28 HUNDRED UNIT L 0 T SUBDIVISION DETAILS 07 C) C-� DATE 1211312021 flELDB00K' N/A PAGE: NIA T y DRAWING N0: 1666.3 oo N SHEET.• 11OF 12