RECORD NUMBER
SUB-00636-4
Project Name: Central Maintenance Facility
Status: Pending CoR
Approval
Title: Oil Water Separator Vault #2 Creator: Nick Boydston
Bid Item/
Reference ID:
Bid Item 9 Creation Date: 12/07/2023
Drawing No: NA Due Date: 30 calendar days
Specification
Section:
33 05 15 Subcontractor/
Supplier
Jensen Precast
Description:
Deferred submittal of structural calculations and drawings for Oil Water Separator vault
#2 showing outrigger loading requirements are met.
Submittal Attachments (Line Items)
No. Name Upload Date Doc Type Line Item Status
001 231207-SUB00635-RV0-
330515_SITE_COR Vault Calcs-4.pdf
12/07/2023 Calculations,
Drawings
Pending CoR Approval
Record - General Comments
Comment Date Created By Company
12/26/2023 D. Thompson King County
Comment Text
Structural calculations and drawings stamped by professional engineer, attached.
September 18, 2023 Project No. 22-444
DESIGNED BY:CHECKED BY:
KATE KATTELMAN JEFF VONHANDORF
(KDK)(JJV)
ALL PAGES ALL PAGES
2
8
10
12
BUOYANCY CALCULATIONS 14
DESIGN CALCULATIONS
CENTRAL MAINTENANCE
FACILITY
RENTON SHOP
OIL WATER SEPERATOR #2
RENTON, WASHINGTON
Designed by:
Designed for:
PUYALLUP, WA
PRECAST LID CALCULATIONS
PRECAST END WALL CALCULATIONS
PRECAST SIDE WALL CALCULATIONS
PRECAST BASE SLAB CALCULATIONS
PRETEK GROUP PO BOX 751471, DAYTON, OH 45475 800.241.0925
SEPTEMBER 21, 2023
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Clear Span:6.00 Ft Concrete Lid Thickness = 9.0 in
Location:RENTON, WASHINGTON Total Length:6.46 Ft Bearing Width =2.75 in
Engineer:(KDK)Cover:0.50 Ft Concrete Weight =150 pcf
Date:9/18/2023 Load Factors Loading:Outrigger Loading Backfill Weight =135 pcf
Strength Reduction Factors Dead Load, D 1.3 Hydrostatic:0.00 Ft Sat. Backfill Weight =151 pcf
φ = 0.90 Bending Self Weight, D 1.3
φ = 0.85 Shear Live Load, LL 2.171
Design Slab Beam- Maximum Bending & Shear
Dead load
Wcover =0.07 k/ft Ws Total = 0.18 k/ft Total Service Load
Wself =0.11 k/ft Wu Total = 0.23 k/ft Total Factored Load
Live load
Outrigger Loading
Distributed Live Load =7.81 k/ft Distributed Factored Live Load =16.96 k/ft
Total Service Moment Ms =12.53 ft-k (see attached sheet)
Total Factored Moment Mu =26.49 ft-k (see attached sheet)
Total Factored Shear Load, Vs =11.90 k @ 0.48 Ft from end of clear span
FACTORED BENDING CRACK CONTROL
Fy= 60 ksi fs,max = 98 / (dc x A)^(1/3) <= 0.6 Fy
f'c =7000 psi fs,max =32.7 ksi
wire centroid from face =1.73 in b / N = s =6 in. o.c.
Reinforcing Bars = #6 @ 6 in. o.c. = 0.88 in^2/ft dc =1.5 in
d = 7.27 in A = 18.0 in^2
As = 0.88
a = 0.7425 fs = 31.5 ksi Ok
fMn =27.43 ft-k Ok
Mu = 26.49 ft-k
MMinimum Reinf. = 6.89 ft-k
SHEAR
fVc = 0.85 x 0.0316 * 2 (f'c)^(1/2) x 12'' x d
=12.40 k
Vu =11.90 k Ok
LID CALCULATIONS, LIVE LOAD PERPENDICULAR
AASHTO 8.16.3.2
AASHTO 8.16.6
AASHTO 5.7.3.2
AASHTO 16.7.4.7
AASHTO 8.16.1.2.2 AASHTO Table 3.22.1A
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Span:6.00 Ft Lay Length =3.98 Ft
Location:RENTON, WASHINGTON Rise:11.00 Ft Lid Thickness =0.75 Ft
Engineer:(KDK)Max. Cover:0.50 Ft Loading:
Min Cover:0.00 Ft
I. Properties
Design Specification =AASHTO STANDARD SPECIFICATIONS
FOR HIGHWAY BRIDGES, 17TH EDITION
Backfill Material =SW95
II. Distribution of Wheel Loads Backfill Unit Weight =120 psf
The distribution of wheel loads through the earth cover is found by using the larger of:Cover Material =SW95
Section 3.24.3.2
Wheel loads distributed over a width equal to 4' + 6%span
Section 6.4.2
Wheel loads shall be distributed through cover with a width
equal to 1.75 x cover
III. Impact
Per AASHTO section 3.8.2.3, the dynamic load effects of vehicles shall be considered
by increasing the load as follows:
for less than or equal to 1'-0" cover, impact = 30%
for cover between 1'-0" and 2'-0", impact = 20%
for cover between 2'-0" and 3'-0", impact = 10%
IV. Minimum Reinforcement
FLEXURAL
Minimum reinforcement per AASHTO section 16.8.5.8
As, min = 0.002 x (Agross) = 0.24 sq in/ft
TEMPERATURE & SHRINKAGE
Per AASHTO section 8.20
As, min = 0.13 sq in/ft
V. Live Load Calculation Example
Axle Weight:51 kips Cover at Axle:0.50 Ft
D =Distribution width of wheel load
=4' AXLE SPACING + (2) 6' AXLES + 1.75*COVER
=16+13.125
=16.875 Ft
IM =Impact factor
=30.0 %
Live Load Factor =2.171
Pult= (1+IM)(LL)(2*AXLE WEIGHT)
=286.18 k
wult = Pult / D
=16.96 k/ft
SLAB UNIT LIVE LOAD CALCULATIONS (TRUCK PERPENDICULAR)
Outrigger
Loading
SINGLE-SPAN BEAM ANALYSIS
For Simple, Propped, Fixed, or Cantilever Beams
Job Name:RENTON SHOP - OIL WATER SEPERATOR #2 Subject:TRAFFIC PERPENDICULAR, FAC
Job Number:22-444 Originator:(KDK)Checker:JJV
Controlling case for Moment
Input Data: c
e
Beam Data:Simple Beam b
Span Type?Simple a
Span, L =6.0000 ft.Propped Beam +P +M +we
Modulus, E =4768.962 ksi +wb
Inertia, I =729.00 in.^4 Fixed Beam +w
E,I L
Beam Loadings:Cantilever Beam RL x RR
Full Uniform:Nomenclature
w =0.1800 kips/ft.
Start End Results:
Distributed:b (ft.)wb (kips/ft.)e (ft.)we (kips/ft.)Reactions:
#1:RL =4.45 k RR =4.45 k
#2:ML =N.A.MR =N.A.
#3:Maximum Moments:
#4:+M(max) =12.53 ft-k @ x =3.00 ft.
#5:-M(max) =0.00 ft-k @ x =0.00 ft.
#6:Maximum Deflections:
#7:-D(max) =-0.019 in.@ x =3.00 ft.
#8:+D(max) =0.000 in.@ x =0.00 ft.
D(ratio) =L/3789
Point Loads:a (ft.)P (kips)
#1:3.0000 7.81
#2:
#3:
#4:
#5:
#6:
#7:
#8:
#9:
#10:
#11:
#12:
#13:
#14:
#15:
Moments:c (ft.)M (ft-kips)
#1:
#2:
#3:
#4:
-5.0
-4.0
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Shear (kips)x (ft.)
Shear Diagram
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Moment (ft-kips)x (ft.)
Moment Diagram
SINGLE-SPAN BEAM ANALYSIS
For Simple, Propped, Fixed, or Cantilever Beams
Job Name:RENTON SHOP - OIL WATER SEPERATOR #2 Subject:TRAFFIC PERPENDICULAR, FAC
Job Number:22-444 Originator:(KDK)Checker:JJV
Controlling case for Moment
Input Data: c
e
Beam Data:Simple Beam b
Span Type?Simple a
Span, L =6.0000 ft.Propped Beam +P +M +we
Modulus, E =4768.962 ksi +wb
Inertia, I =729.00 in.^4 Fixed Beam +w
E,I L
Beam Loadings:Cantilever Beam RL x RR
Full Uniform:Nomenclature
w =0.2340 kips/ft.
Start End Results:
Distributed:b (ft.)wb (kips/ft.)e (ft.)we (kips/ft.)Reactions:
#1:RL =9.18 k RR =9.18 k
#2:ML =N.A.MR =N.A.
#3:Maximum Moments:
#4:+M(max) =26.49 ft-k @ x =3.00 ft.
#5:-M(max) =0.00 ft-k @ x =0.00 ft.
#6:Maximum Deflections:
#7:-D(max) =-0.040 in.@ x =3.00 ft.
#8:+D(max) =0.000 in.@ x =0.00 ft.
D(ratio) =L/1805
Point Loads:a (ft.)P (kips)
#1:3.0000 16.96
#2:
#3:
#4:
#5:
#6:
#7:
#8:
#9:
#10:
#11:
#12:
#13:
#14:
#15:
Moments:c (ft.)M (ft-kips)
#1:
#2:
#3:
#4:
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Shear (kips)x (ft.)
Shear Diagram
0.0
5.0
10.0
15.0
20.0
25.0
30.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Moment (ft-kips)x (ft.)
Moment Diagram
SINGLE-SPAN BEAM ANALYSIS
For Simple, Propped, Fixed, or Cantilever Beams
Job Name:RENTON SHOP - OIL WATER SEPERATOR #2 Subject:TRAFFIC PERPENDICULAR, FAC
Job Number:22-444 Originator:KDK Checker:JJV
Controlling case for Shear
Input Data: c
e
Beam Data:Simple Beam b
Span Type?Simple a
Span, L =6.0000 ft.Propped Beam +P +M +we
Modulus, E =4768.962 ksi +wb
Inertia, I =729.00 in.^4 Fixed Beam +w
E,I L
Beam Loadings:Cantilever Beam RL x RR
Full Uniform:Nomenclature
w =0.2340 kips/ft.
Start End Results:
Distributed:b (ft.)wb (kips/ft.)e (ft.)we (kips/ft.)Reactions:
#1:RL =12.01 k RR =6.35 k
#2:ML =N.A.MR =N.A.
#3:Maximum Moments:
#4:+M(max) =23.55 ft-k @ x =2.00 ft.
#5:-M(max) =0.00 ft-k @ x =0.00 ft.
#6:Maximum Deflections:
#7:-D(max) =-0.035 in.@ x =2.75 ft.
#8:+D(max) =0.000 in.@ x =0.00 ft.
D(ratio) =L/2081
Point Loads:a (ft.)P (kips)
#1:2.0000 16.96
#2:
#3:
#4:
#5:
#6:
#7:
#8:
#9:
#10:
#11:
#12:
#13:
#14:
#15:
Moments:c (ft.)M (ft-kips)
#1:
#2:
#3:
#4:
-10.0
-5.0
0.0
5.0
10.0
15.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Shear (kips)x (ft.)
Shear Diagram
0.0
5.0
10.0
15.0
20.0
25.0
0.000.360.721.081.441.802.162.522.883.243.603.964.324.685.045.405.76Moment (ft-kips)x (ft.)
Moment Diagram
Tabulation of Single-Span Beam Shear, Moment, Slope, and Deflection for 50 Equal Segments
Point #x (ft.)Shear (k)
1 0.0000 12.01
2 0.1200 11.98
3 0.2400 11.95
4 0.3600 11.92
5 0.4800 11.90
6 0.6000 11.87
7 0.7200 11.84
8 0.8400 11.81
9 0.9600 11.78
10 1.0800 11.76
11 1.2000 11.73
12 1.3200 11.70
13 1.4400 11.67
14 1.5600 11.64
15 1.6800 11.61
16 1.8000 11.59
17 1.9200 11.56
18 2.0400 -5.43
19 2.1600 -5.46
20 2.2800 -5.48
21 2.4000 -5.51
22 2.5200 -5.54
23 2.6400 -5.57
24 2.7600 -5.60
25 2.8800 -5.62
26 3.0000 -5.65
27 3.1200 -5.68
28 3.2400 -5.71
29 3.3600 -5.74
30 3.4800 -5.77
31 3.6000 -5.79
32 3.7200 -5.82
33 3.8400 -5.85
34 3.9600 -5.88
35 4.0800 -5.91
36 4.2000 -5.93
37 4.3200 -5.96
38 4.4400 -5.99
39 4.5600 -6.02
40 4.6800 -6.05
41 4.8000 -6.07
42 4.9200 -6.10
43 5.0400 -6.13
44 5.1600 -6.16
45 5.2800 -6.19
46 5.4000 -6.21
47 5.5200 -6.24
48 5.6400 -6.27
49 5.7600 -6.30
50 5.8800 -6.33
51 6.0000 -6.35
1.44 -0.0942 -0.0024
2.88 -0.0936 -0.0047
Moment (ft-k)Slope or Rotation (deg.)Deflection (in.)
0.00 -0.0944 0.0000
7.16 -0.0893 -0.0117
8.59 -0.0871 -0.0139
4.31 -0.0926 -0.0071
5.74 -0.0912 -0.0094
12.83 -0.0779 -0.0201
14.24 -0.0741 -0.0220
10.00 -0.0844 -0.0160
11.42 -0.0814 -0.0181
18.45 -0.0601 -0.0271
19.84 -0.0547 -0.0285
15.65 -0.0698 -0.0238
17.05 -0.0652 -0.0255
23.33 -0.0360 -0.0320
22.68 -0.0294 -0.0328
21.24 -0.0488 -0.0299
22.62 -0.0426 -0.0310
20.70 -0.0109 -0.0343
20.03 -0.0051 -0.0345
22.02 -0.0230 -0.0335
21.36 -0.0169 -0.0340
18.01 0.0112 -0.0343
17.33 0.0162 -0.0339
19.36 0.0005 -0.0346
18.69 0.0060 -0.0345
15.27 0.0301 -0.0322
14.58 0.0344 -0.0314
16.65 0.0211 -0.0335
15.96 0.0257 -0.0329
12.48 0.0460 -0.0283
11.77 0.0494 -0.0271
13.88 0.0384 -0.0304
13.18 0.0423 -0.0294
9.63 0.0585 -0.0230
8.91 0.0612 -0.0215
11.06 0.0527 -0.0258
10.35 0.0557 -0.0245
6.73 0.0679 -0.0167
5.99 0.0697 -0.0149
8.18 0.0636 -0.0200
7.46 0.0658 -0.0183
3.77 0.0739 -0.0095
3.02 0.0748 -0.0076
5.26 0.0713 -0.0132
4.51 0.0727 -0.0113
0.76 0.0764 -0.0019
0.00 0.0765 0.0000
2.27 0.0756 -0.0057
1.52 0.0761 -0.0038
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Top Slab Thickness =9.0 in
Location:RENTON, WASHINGTON End Wall Thickness =12.0 in
Engineer:(KDK)Cover:0.50 Ft Traffic Surcharge = 100 psf
Date:9/18/2023 Water Table Depth:0.00 Ft At-rest Pressure Above Water Table = 45 psf
At-rest Pressure Below Water Table = 45 psf
Design End Wall
End wall Height =13.17 Ft
Soil Cover on Top of Wall =0.50 Ft
Soil weight =135 pcf
Ptop = 0.023 ksf
Pbottom = 0.615 ksf
PLive Load surcharge = 0.100 ksf
W1= 0.296 k
W2= 3.901 k
Wsurcharge= 1.317 k
V1= 0.148 k
V2= 2.600 k
Vsurcharge= 0.658 k
Max. Moment Mu =12.48 ft-k
Max. Shear Load, Vu =4.60 k
BENDING f'c =7000 psi
rebar cover =1.5 in
bar size and spacing =# 5 @ 12 in
d =10.19 in
As =0.307
a =0.2577
fMn =13.88 ft-k Ok
Mu = 12.48 ft-k
MMinimum Reinf. = 12.25 ft-k
SHEAR
fVc = 0.90 x 0.0316 * 2 (f'c)^(1/2) x 12" x d
=18.40 k
dshear = 10.19 in
Vu =4.60 k Ok
END WALL CALCULATIONS
CHECK SHEAR CAPACITY OF STEEL PLATE
Botton slab plate =9.75'' x 1.5'' x 0.375''
Max. Spacing between steel plate =5.00 Ft
Shear Load from wall =4.60 k/ft (from endwall calculation)
Shear Load on steel plate =23.00 k
Steel plate design shear capacity ɸRn =ɸ*0.6*FvAb (check 1 )
Ab=L*t
L=9.750 in Fv =36 ksi
t=0.375 in ɸ=0.75
ɸRn =59.23 k Ok
Steel plate design shear capacity ɸRn =ɸ*0.6*FvAse (check 2 )
Ase=L*w
L=9.750 in Fv =36 ksi
w=1.500 in ɸ=0.75
ɸRn =236.93 k Ok
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Top Slab Thickness =9.0 in
Location:RENTON, WASHINGTON Side Wall Thickness =12.0 in
Engineer:(KDK)Cover:0.50 Ft Traffic Surcharge = 100 psf
Date:9/18/2023 Water Table Depth:0.00 Ft At-rest Pressure Above Water Table = 45 psf
At-rest Pressure Below Water Table = 45 psf
Design Side Wall
Side wall Height =13.17 Ft
Side Wall Length =17.17 Ft
Soil Cover on Top of Wall =0.50 Ft
Soil weight =135 pcf
Ptop = 0.023 ksf
Pbottom = 0.615 ksf
PLive Load surcharge = 0.100 ksf
W1= 0.30 k
W2= 3.90 k
Wsurcharge= 1.32 k
V1= 0.15 k
V2= 2.60 k
Vsurcharge= 0.66 k
Max. Moment Mu =17.69 ft-k (Spanning Horizontally between each endwall)
Max. Shear Load, Vu =4.60 k
BENDING f'c =7000 psi
rebar cover =1.5 in
bar size and spacing =# 5 @ 8 in
d =10.19 in
As =0.460
a =0.3865
fMn =20.69 ft-k Ok
Mu = 17.69 ft-k
MMinimum Reinf. = 12.25 ft-k
SHEAR
fVc = 0.90 x 0.0316 * 2 (f'c)^(1/2) x 12" x d
=18.40 k
dshear = 10.19 in
Vu =4.60 k Ok
SIDE WALL CALCULATIONS - SPANNING HORIZONTALLY BETWEEN END WALLS
CHECK SHEAR CAPACITY OF STEEL PLATE
Botton slab plate =9.75'' x 1.5'' x 0.375''
Max. Spacing between steel plate =5.00 Ft
Shear Load from wall =4.60 k/ft (from endwall calculation)
Shear Load on steel plate =23.00 k
Steel plate design shear capacity ɸRn =ɸ*0.6*FvAb (check 1 )
Ab=L*t
L=9.750 in Fv =36 ksi
t=0.375 in ɸ=0.75
ɸRn =59.23 k Ok
Steel plate design shear capacity ɸRn =ɸ*0.6*FvAse (check 2 )
Ase=L*w
L=9.750 in Fv =36 ksi
w=1.500 in ɸ=0.75
ɸRn =236.93 k Ok
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Span,Rise:
Location:RENTON, WASHINGTON Designer:(KDK)Checker:JJV
Input Data:
c
Beam Data:e
b
Length, L =8.00 ft.a
Width, W =1.00 ft. +P
Thickness, T =0.83 ft. +wb +we +M +w
Modulus, E =4769.0 ksi
Subgrade, K =40 pci T
Inertia, I =0.048 ft.^4
E,I L
Beam Loadings: x
Nomenclature
Full Uniform:
w =0.0000 kips/ft. Results:
Start End Beam Flexiblity Criteria:
Distributed:b (ft.)wb (kips/ft.)e (ft.)we (kips/ft.) for b*L <= p/4 beam is rigid
#1: for p/4 < b*L < p beam is semi-rigid
#2: for b*L >= p beam is flexible
#3: for b*L >= 6 beam is semi-infinite long
#4:
#5:b =0.151 b = ((K*W)/(4*E*144*I))^(1/4)
#6:b*L =1.21 b*L = Flexibility Factor
Point Loads:a (ft.)P (kips)Beam is semi-rigid
#1:0.5000 13.98
#2:7.5000 13.98
#3: Max. Shears and Locations:
#4:+V(max) =12.16 k @ x =7.50 ft.
#5:-V(max) =-12.16 k @ x =0.50 ft.
#6:
#7: Max. Moments and Locations:
#8:+M(max) =0.46 ft-k @ x =0.50 ft.
#9:-M(max) =-20.60 ft-k @ x =4.00 ft.
#10:
#11: Max. Deflection and Location:
#12:D(max) =-0.636 in. @ x =0.00 ft.
Moments:c (ft.)M (ft-kips) Max. Soil Pressure and Location:
#1:Q(max) =3.665 ksf @ x =0.00 ft.
#2:
#3:
#4:
BASE SLAB DESIGN CALCULATIONS
Subgrade
Check Base Slab Shear Strength (@ distance d from inside face of leg unit leg):
As =0.20 in2/ft f'c = 7.0 ksi
b =12 in
de =0.69 ft
Vu =-11.08
Mu =-10.09 ft*k/ft
Vude/Mu =0.755
Vc = 0.079 √(f'c)bde < 0.126√(f'c)bde OK
fVc =18.64675 per LRFD 5.14.5.3 fVc = 0.9*(0.0676√f'c+4.6AsVude/bdeMu)bde
OK
Check Base Slab Moment Capacity @ Midspan:
Mu =20.6 ft*k/ft As =0.20 in2/ft #4 @ 12.00 in in top of slab
a = 0.16 in de =8.25 in
fMn =7.2 ft*k/ft
Longitudinal Base Slab Reinforcement
Maximum spacing of reinforcing bars shall be 1.5 times the depth or 18" (5.10.3.2)
Smax = 18''
Shrinkage and temperature reinforcement per section 5.10.8:b =12''
As > 1.3bh/[2*(b+h)fy] =0.06 in2/ft h = 10''
fy =60 ksi
Provide #4 @ 12 in top only, bottom not exposed to temperature variations
As =0.2 in2/ft OK
k/ft @ x=0.800
Project:RENTON SHOP - OIL WATER SEPERATOR #2 Clear Span:6.00 Ft Water Table Height: 0.00 Ft
Location:RENTON, WASHINGTON Clear Rise:13.92 Ft Max. Cover: 0.50 Ft
Engineer:(KDK)Base Extension: 0.00 Ft Min. Cover: 0.00 Ft
Skin Friction Above Water Table: 128 PSF Note: Water Table Height
Skin Friction Below Water Table: 67 PSF measured from top of vault
(Negative = below top of vault)
Vault Data:Thickness
Description / Width Length Volume (per foot)Unit Weight Weight
Top Slab 0.75 FT 8.00 FT 6.00 CF 150 LB/CF 0.90 K/F
Walls 1.00 FT 13.92 FT 27.83 CF 150 LB/CF 4.18 K/F
Base Slab 0.83 FT 8.00 FT 6.67 CF 150 LB/CF 1.00 K/F
Soil over Top Slab 0.25 FT 8.00 FT 2.00 CF 120 LB/CF 0.24 K/F
Soil over Base Ext.0.00 FT 15.75 FT 0.00 CF 120 LB/CF 0.00 K/F
Interior 6.00 FT 13.92 FT 83.50 CF 0 LB/CF 0.00 K/F
Downward / Resisting Forces:
Vault Structure (self weight)6.08 K/F
Soil over Vault 0.24 K/F
Soil over Base Extension 0.00 K/F
Skin Friction above Water Table 0.00 K/F
Skin Friction below Water Table 1.04 K/F
Total 7.35 K/F
Upward Bouyant Forces:
Concrete Area 2.53 K/F
Void Area 5.21 K/F
Total 7.74 K/F
Factor of Safety for Bouyancy:1.0 OK
VAULT BUOYANCY CALCULATIONS
AS-BUILT
LAYOUT PLAN
TOP SECTION
A
DESIGN NOTES:
1. THIS STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE AMERICAN
ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
STANDARD: SPECIFICATION FOR HIGHWAY BRIDGES, SEVENTEENTH EDITION
(2002), ASTM C-857, AND ACI-318-02.
2. DESIGN LOADS:
LIVE LOAD: HS25-44 + 50.7 KIP (75 PSI OVER A 26-INCH BY 26-INCH AREA)
OUTRIGGER LOADING
SOIL WEIGHT = 135 PCF
DEPTH OF OVERBURDEN = 6" MAX
3. CONCRETE 28 DAY COMPRESSIVE STRENGTH: 7,000 PSI (MIN)
4. CONCRETE SHIPPING STRENGTH 70%: 3,500 PSI (MIN)
5. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
6. CEMENT: ASTM C-150 SPECIFICATIONS
7. WELDING STEEL STRENGTH = 70 KSI
8. HYDROSTATIC PRESSURE: WATER TABLE AT TOP OF VAULT
BACKFILL NOTES:
MECHANICAL TAMPERS OR APPROVED COMPACTING EQUIPMENT
NOT EXCEEDING 1 TON SHALL BE USED ON ALL BACKFILL MATERIAL
THAT IS DIRECTLY ADJACENT TO THE STRUCTURAL ELEMENTS AND
OVER THE TOP OF THE STRUCTURE UNTIL THERE IS AT LEAST 1' OF
COVER OVER THE TOP. BACKFILL MATERIAL IN STRUCTURAL
BACKFILL ZONE SHALL BE PLACED IN 8" LIFTS (MAXIMUM) BEFORE
BEING COMPACTED. AT NO TIME SHALL HEAVY CONSTRUCTION OR
BACKFILLING EQUIPMENT IN EXCESS OF 8 TON BE PERMITTED OVER
THE STRUCTURE OR WITHIN 3' OF ANY STRUCTURAL ELEMENT
WITHOUT AT LEAST 2' OF COVER OVER THE STRUCTURE UNLESS THE
STRUCTURE IS DESIGNED FOR LESS COVER.
NO BACKFILL UNTIL THE WHOLE VAULT IS ASSEMBLED.
DURING BACKFILLING, AT NO TIME SHALL THERE BE MORE THAN 24"
DIFFERENCE BETWEEN BACKFILL HEIGHT ON EACH SIDE OF THE
VAULT8'-0" VAULT OVERALL6'-0"INSIDE CLEAR1'-0" WALL(TYP.)13'-11" INSIDE CLEAR15'-6" OVERALL9"LID10"BASEELEVATION A
℄ 18"Ø OPENING FOR
12"Ø PIPE IE 318.554'-0"℄ 12"Ø OPENING FOR 8"Ø
PIPE IE 318.22
℄ 16"Ø OPENING FOR
12"Ø PIPE IE 324.90
TOP WALL CONNECTION
(SEE DETAIL ON SHEET P2)
INTERNAL/VAULT
ELEV. 314.11
T/VAULT
ELEV. 328.78
B/VAULT
ELEV. 313.28
2'-10"2'-10"
LAYOUT PLAN
BOTTOM SECTION
B1 BASE
SW2A & SW2B
SW1A & SW1B EW1
17'-2" (SIDE WALL TYP.)8'-0" (END WALL TYP.)C℄ 16"Ø OPENING FOR
12"Ø PIPE IE 324.9011'-312"℄ 18"Ø OPENING FOR
12"Ø PIPE IE 318.55
SW1A
(SW2A BEYOND)
SW1B
(SW2B BEYOND)
EW1 EW2
T1 TOP RING
L1 - LID L1 - LIDL1 - LID WEIR
SW2A
SW2B
SW1A
SW1B
10'-0"3'-2"T1 TOP RING
19'-2" (BASE SLAB)
BOTTOM WALL CONNECTION
(SEE DETAIL ON SHEET P2)
END WALL CONNECTION
(SEE DETAIL ON SHEET P2)
EW2
℄ 12"Ø OPENING FOR 8"Ø
PIPE IE 318.224'-538"EW1
EW2
OIL WATER SEPARATOR (OWS-2)
19'-2" VAULT OVERALL
17'-2" INSIDE CLEAR
BBAFFLEWEIR
BAFFLE
4'-1114"1'-6"TOP RINGL3"x 3"x 14" BEARING ANGLE
W/ 34"x6" H.C.A. @ 1'-0" O.C.
L3"x 3"x 14" BEARING ANGLE
W/ 34"x6" H.C.A. @ 1'-0" O.C.13'-2"1'-0"
(TYP.)
NOTE:
CUSTOMER TO VERIFY PIPE
LOCATIONS AND OPENING SIZES
PRIOR TO PRODUCTION OF PRECAST
SIDE WALL CONNECTION
(SEE DETAIL ON SHEET P2)
PRODUCT DETAIL
PRODUCT QTY APPROX HANDLING WEIGHT
T1 1 9,722 LBS
SW1A,SW2A 2 25,750 LBS
SW1B,SW2B 2 8,080 LBS
EW1,EW2 2 15,800 LBS
B1 1 19,160 LBS
L1 3 4,140 LBS
WEIR 1 6,200 LBS
BAFFLE 1 5,930 LBS
0 2' 4'8'
ELEVATION B
0 2' 4'8'
ELEVATION C
0 2' 4'8'
8'-0"
AFTERBAY
℄1'-312"2'-10"9"(TYP.)2
2
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P1DATE ENG
SEPTEMBER 21, 2023
INSTALLATION NOTES (BY OTHERS):
1. WALL PANELS WILL NEED TO BE BRACED TO FLOOR PANELS DURING INSTALLATION
2. AFTER INSTALLATION OF PANELS ALL RECESS POCKETS & VOIDS WILL NEED TO BE
GROUTED WITH A NON-SHRINK 4,000 PSI GROUT
3. AFTER INSTALLATION OF PANELS ALL SEAMS/JOINTS WILL NEED TO BE SEALED WITH
CS1900 SEALANT AND PAINTED WITH CS1800 COATING. SEE PANEL SEAM DETAIL.
4. PIPE SEALING/CONNECTION AND FLOOR SLOPE BY OTHERS
5. ALL WELDING DONE BY OTHERS PRIOR TO BACKFILLING
6. STEPS AND/OR LADDERS SUPPLIED AND INSTALLED BY OTHERS.
4-POINT PANEL LIFTING DETAIL
LIFTING AND SETTING TOP AND BOTTOM SLABS, LIFTING FOR WALLS60°4-POINT EDGE PANEL ROTATING AND SETTING DETAIL
ROTATING AND SETTING WALL PANELS
60°TO CRANETO CRANETO CRANEMIN.MIN.
BASE TO WALL SEAM SEAL DETAIL
1.) SET PANEL
2.) CAULK IN WITH CS-1900, ONCE AN OUTER SKIN HAS FORMED PROCEED TO STEP 3
3.) PAINT JOINT 2" 30 MILLS ON EACH SIDE WITH CS-1800
4.) WRAP WITH CS-212. CENTER ON JOINT
2"
(TYP.)
INTERIOR WALL
#2 - CAULK IN WITH CS-1900, ONCE
AN OUTER SKIN HAS FORMED
PROCEED TO STEP 3
EXTERIOR WALL
#4 - WRAP WITH CS-212,
CENTER ON JOINT
BASE
#1 - SET PANELS #3 - PAINT JOINT 2" STRIP 30 MILLS
ON EACH SIDE WITH CS-1800
**IF PANEL GAP IS 0" TO 38"
NO BACKER ROD IS NEEDED**
**IF PANEL GAP IS 38" OR GREATER
BACKER ROD IS NEEDED**
WALL TO WALL SEAM SEAL DETAIL
1.) SET PANEL
2.) CAULK IN WITH CS-1900, ONCE AN OUTER SKIN HAS FORMED PROCEED TO STEP 3
3.) PAINT JOINT 2" 30 MILLS ON EACH SIDE WITH CS-1800
4.) WRAP WITH CS-212. CENTER ON JOINT
2"
(TYP.)
#2 - CAULK IN WITH CS-1900, ONCE
AN OUTER SKIN HAS FORMED
PROCEED TO STEP 3
EXTERIOR WALL
#4 - WRAP WITH CS-212,
CENTER ON JOINT
INTERIOR WALL
#1 - SET PANELS
#3 - PAINT JOINT 2" STRIP 30 MILLS
ON EACH SIDE WITH CS-1800
**IF PANEL GAP IS 0" TO 38"
NO BACKER ROD IS NEEDED**
**IF PANEL GAP IS 38" OR GREATER
BACKER ROD IS NEEDED**
TOP TO WALL SEAM SEAL DETAIL
1.) APPLY BEAD OF CAULKING CENTERED ON WALL EDGE, ONCE DONE PROCEED TO STEP 2
2.) SET PANEL (TOP)
3.) WRAP WITH CS-212. CENTER ON JOINT
TOP
#1 - APPLY BEAD OF CS-1900 CAULKING
CENTERED ON WALL EDGE, ONCE DONE
PROCEED TO STEP 2
#2 - SET TOP PANEL2"(TYP.)INTERIOR WALL
#3 - WRAP WITH CS-212,
CENTER ON JOINT
EXTERIOR WALL
WALL CORNER SEAM SEAL DETAIL
1.) SET PANEL
2.) CAULK IN WITH CS-1900, ONCE AN OUTER SKIN HAS FORMED PROCEED TO STEP 3
3.) PAINT JOINT 2" 30 MILLS ON EACH SIDE WITH CS-1800
4.) WRAP WITH CS-212. CENTER ON JOINT
2"
(TYP.)
INTERIOR WALL
#2 - CAULK IN WITH CS-1900, ONCE
AN OUTER SKIN HAS FORMED
PROCEED TO STEP 3EXTERIOR WALL
#4 - WRAP WITH CS-212,
CENTER ON JOINT
#1 - SET PANELS
#3 - PAINT JOINT 2" STRIP 30 MILLS
ON EACH SIDE WITH CS-1800
**IF PANEL GAP IS 0" TO 38"
NO BACKER ROD IS NEEDED**
**IF PANEL GAP IS 38" OR GREATER
BACKER ROD IS NEEDED**
EXTERIOR WALL
AS-BUILT
TOP WALL CONNECTION
AFTER INSTALLATION OF
BAR PT DUCT TO BE FILLED
W/ GROUT
#6 BAR, 34"Ø STEEL BAR
28" LONG
3"Ø PT DUCT IN
WALL AND TOP SLAB
5"x 5"x 38"
CONNECTION PLATE
14"
14"
7"x 7"x 34" DEEP
RECESS POCKET
L3"x3"x 14" 6" LONG
W/ 2 EA. 34"x 6" H.C.A.
CAST IN BOTH SIDES
14"
FRONT VIEW SIDE VIEW
SIDE VIEW SIDE WALL CONNECTION
PANEL SEAM DETAIL
SEAL ALL JOINTS WITH
CS1900 SEALANT 1ST PAINT SEAMS WITH CS1800
COATING 2ND
BOTTOM AND END WALL CONNECTION
112" DEEP RECESS
POCKET
12"x 12"x 6" SQUARE
BAR 112"x 934"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
14"
514" LONG MIN
SIDE VIEW FRONT VIEW
14"
514" LONG MIN
NELSON STUD AWS
TYPE C (OR EQUAL)
14"
14"
12"x 12"x 6" SQUARE BAR
BUTYL ROPE
112" DEEP x 3"WIDE
HORIZONTAL KEY
OIL WATER SEPARATOR (OWS-2)TO CRANE9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P2DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
17'-2" LONG L3"x3"x 14" W/ 34"x 6"
H.C.A. SPACED @ 12" O.C. MAX.
SIDE VIEW
BEARING ANGLE DETAIL
BILL OF MATERIALS (T1)
ITEM QTY DESCRIPTION
1 2.4 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
2 14 3"Ø x 1'-6" LONG PT DUCT
3 4 RL7 8-TON ERECTION ANCHOR (79149)
P1 2 BEARING ANGLE: 3"x3"x 17'-2" w/ (18) 34"Ø x 6" H.C.A.
T1 - PLAN VIEW
T1 TOP RING - 9,722 LBS
1 PIECE NEEDED
QTYS. ARE PER PIECE
19'-2" OVERALL
8'-0" OVERALL3"Ø PT DUCT
(TYP.)
2
1
BEARING ANGLE (P1)
(TYP.) SEE DETAIL
ELEVATION 1
P3
0 1' 2'4'
1
P3
1'-0"17'-2" OPENING 1'-0"6'-0" OPENING1'-0"1'-0"3 SPACES @ 1'-9" O.C. = 5'-3"(TYP.)1'-412"1'-412"2 SPACES @ 4'-4" = 8'-8" (TYP.)5'-3"5'-3"5"(TYP.)12'-2"3'-6"3'-6"5"(TYP.)12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)2P31'-6"OVERALL3"Ø PT DUCT (TYP.)2 38T RL-7 ERECTION
ANCHOR (TYP.)
PRECAST ANGLE (P1) CAST
FLUSH AS BEARING SHELF
FOR LID PIECES9"14"
BEARING ANGLE
(TYP.) SEE DETAIL
SECTION 2
P3TYPICAL SIDE REINFORCING
9"1'-6"3" SHELF
9"5"
#4 TIES @ 1'-0" O.C.A1(6) #6 BARS SPACED
AS SHOWN (TYP.)
℄ 3"Ø PT DUCT (TYP.)
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)
1'-0"
A2
112"CLR.OIL WATER SEPARATOR (OWS-2)
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)3
LEVEL W/
SIDE SHELF
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
SECTION 3
P3TYPICAL END REINFORCING 1'-6"5"
#4 TIES @ 1'-0" O.C.A3
(6) #6 BARS SPACED
AS SHOWN (TYP.)
℄ 3"Ø PT DUCT (TYP.)
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)
1'-0"
A2
112"CLR.3
P3
3" SHELF(TYP.)9"1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P3DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
EW1 - PLAN VIEW
EW1 END WALL - 15,535 LBS
1 PIECE NEEDED
ELEVATION 1
P4
0 1' 2'4'
REINFORCING DETAIL
(END WALL TYP.)
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
BILL OF MATERIALS (EW1)
ITEM QTY DESCRIPTION
1 3.8 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
2 4 3"Ø x 12" LONG PT DUCT
3 2 RL7 8-TON ERECTION ANCHOR (79149) w/ TENSION BAR
4 2 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042)
6 6 WELD PLATE: 11
2"x 93
4" w/ 3
4"Ø x 6" H.S.A.
QTYS. ARE PER PIECE
1'-0"OVERALL12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)5"(TYP.)BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL
3
2
16
℄ 3"Ø PT DUCT
5 8T RL-24 PLATE
LIFTING INSERT (TYP.)112"CLR.#4 @ 1'-0" (S.D.)
#5 @ 1'-0" (L.D.)2"CLR.A1
A2
MESH CHAIR
OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
A3
#4 @ 1'-0" (L.D.)13'-2" OVERALL8'-0" OVERALL
2 SPACES @ 4'-6" O.C. = 9'-0"2'-9"1'-5"2'-3"3'-6"2'-3"1P42'-3"3'-6"2'-3"
3 SPACES @ 1'-9" O.C. = 5'-3"1'-412"1'-412"3'-4"6'-6"3'-4"4'-1114"4'-0"
BOTTOM SLAB WELD PLATE
934"x 112"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
14"
(USED HERE FOR END WALL CORNER CONNECTION)
WALL WELD PLATE
(TYP.) SEE DETAIL 4
3"Ø x 12" PT
DUCT (TYP.)2
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
WALL WELD PLATE
(TYP.) SEE DETAIL4
3℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
℄ BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL 6
℄ 18"Ø BLOCKOUT FOR
12"Ø PIPE
ADD (1) #5 x 4'-2"
LONG BAR (E.W. T&B)
13'-2"6"1114"
(TYP.)
NOTE: PANEL WILL NOT HANG LEVEL,
ADJUST LIFTING CABLES AS REQUIRED.6'-6"2'-0"
(TYP.)
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P4DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
EW2 - PLAN VIEW
EW2 END WALL - 15,800 LBS
1 PIECE NEEDED
ELEVATION 1
P5
0 1' 2'4'
REINFORCING DETAIL
(END WALL TYP.)
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
BILL OF MATERIALS (EW2)
ITEM QTY DESCRIPTION
1 3.9 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
2 4 3"Ø x 12" LONG PT DUCT
3 2 RL7 8-TON ERECTION ANCHOR (79149) w/ TENSION BAR
4 2 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042)
6 6 WELD PLATE: 11
2"x 93
4" w/ 3
4"Ø x 6" H.S.A.
QTYS. ARE PER PIECE
1'-0"OVERALL12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)5"(TYP.)BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL
3
2
16
℄ 3"Ø PT DUCT
5 8T RL-24 PLATE
LIFTING INSERT (TYP.)13'-2" OVERALL8'-0" OVERALL
2 SPACES @ 4'-6" O.C. = 9'-0"2'-9"1'-5"2'-3"3'-6"2'-3"1P52'-3"3'-6"2'-3"
3 SPACES @ 1'-9" O.C. = 5'-3"1'-412"1'-412"3'-4"3'-4"BOTTOM SLAB WELD PLATE
934"x 112"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
14"
(USED HERE FOR END WALL CORNER CONNECTION)
WALL WELD PLATE
(TYP.) SEE DETAIL 4
3"Ø x 12" PT
DUCT (TYP.)2
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
WALL WELD PLATE
(TYP.) SEE DETAIL4
3℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
℄ BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL 6
13'-2"6"1114"
(TYP.)
2'-0"
(TYP.)112"CLR.#4 @ 1'-0" (S.D.)
#5 @ 1'-0" (L.D.)2"CLR.A1
A2
MESH CHAIR
OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
A3
#4 @ 1'-0" (L.D.)
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P5DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
B1 - PLAN VIEW
B1 BASE - 19,160 LBS
1 PIECE NEEDED
1
P6
19'-2" OVERALL
8'-0" OVERALLNOTE:
BASES SHOWN AS POURED
NOT AS INSTALLED
3 SPACES @ 3'-6" O.C. = 10'-6"
3'-0"4 SPACES @ 3'-6" O.C. = 14'-0"2'-2"
4'-4"4'-4"2'-3"3'-6"2'-3"1114"(TYP.)4'-4"
1'-0"
(TYP.)2'-0"4'-0"2'-0"10'-6"4'-4"
ELEVATION 1
P6
0 1' 2'4'
BILL OF MATERIALS (B1)
ITEM QTY DESCRIPTION
1 4.7 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
5 8 RL24 8-TON PLATE LIFTING INSERT (79042) w/(4) #4 BARS
6 14 WELD PLATE: 112"x 934" w/ 34"Ø x 6" H.S.A.
7 4 RL6 8-TON ANCHOR (79049) w/ (2) RL31 SHEAR BARS E.W.
BOTTOM SLAB WELD PLATE
934"x 112"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
14"
7℄ RL6 8T ANCHOR W/ (2)
RL31 SHEAR BARS E.W.
℄ BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL 6
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
10"OVERALLMARK THIS END "EAST"
TO ENSURE PROPER
FIELD ORIENTATION
BOTTOM SLAB WELD
PLATE (TYP.) SEE DETAIL 6
QTYS. ARE PER PIECE
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)
1 5 8T RL-24 PLATE
LIFTING INSERT (TYP.)
REINFORCING DETAIL
(BASE SLAB TYP.)112"CLR.#4 @ 1'-0" (S.D.)2"CLR.12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)
OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
MESH CHAIR
#4 @ 1'-0" (S.D.)
#4 @ 1'-0" (L.D.)A3
A2
A1
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
5"℄ RL6 8T ANCHOR W/ (2)
RL31 SHEAR BARS E.W.
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P6DATE ENG
SEPTEMBER 21, 2023
9"3'-112"4'-11"
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
17'-2" OVERALL
10'-0"112" KEYFACE VIEW SIDE VIEW
SIDE WALL WELD ANGLE & KEY DETAIL
L3"x3"x 14" 6" LONG
W/ 2 EA. 34"x 6" H.C.A.
412"112"3"
7"x 312"x 34" DEEP
RECESS POCKET
112" KEYOUTSIDE FACE
OF WALL "A"
SW1A - PLAN VIEW
SW1A BOTTOM SIDE WALL - 25,750 LBS
1 PIECE NEEDED
ELEVATION 1
P7
0 1' 2'4'1P74'-6"2'-9"2'-9"2'-7"3 SPACES @ 4'-0" O.C. = 12'-0"2'-7"2'-6"5'-0"2'-6"4'-4"8'-6"4'-4"
4 SPACES @ 3'-6" O.C. = 14'-0"2'-0"1'-2"WALL WELD PLATE
(TYP.) SEE DETAIL4
BILL OF MATERIALS (SW1A)
ITEM QTY DESCRIPTION
1 6.4 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
3 4 RL7 8-TON ERECTION ANCHOR (79149) w/ TENSION BAR
4 9 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042) w/(4) #4 BARS
8 4 WELD ANGLE: 3"x 3"x 6" w/ 34"Ø x 6" H.C.A.
QTYS. ARE PER PIECE
1'-9"4'-0"1'-9"
℄ SIDE WALL WELD
ANGLE SEE DETAIL 8
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)3
REINFORCING DETAIL
(SIDE WALL TYP.)
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)3" KEY412"10'-0"1'-0"OVERALL3
5 8T RL-24 PLATE
LIFTING INSERT (TYP.)
WALL WELD PLATE
(TYP.) SEE DETAIL 4
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)6"SIDE WALL WELD
ANGLE SEE DETAIL 8
1
112"CLR.#4 @ 1'-0" (S.D.)
MESH CHAIR
#5 @ 8" (L.D.)2"CLR.OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
A1
A2 #4 @ 1'-0" (L.D.)
A3
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
9"7'-712"
5'-8"4'-0"
112" DEEP x 9" WIDE CHANNEL
FOR WEIR & BAFFLE WALL
112" DEEP x 9" WIDE CHANNEL ON
INSIDE FACE FOR WEIR & BAFFLE WALL
(TYP. 2 PLACES)
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P7DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
FACE VIEW SIDE VIEW
SIDE WALL WELD ANGLE & KEYWAY DETAIL
L3"x3"x 14" 6" LONG
W/ 2 EA. 34"x 6" H.C.A.
414"112" KEYWAY312"
7"x 312"x 34" DEEP
RECESS POCKET112" KEYWAYOUTSIDE FACE
OF WALL "A"
SW1B - PLAN VIEW
SW1B TOP SIDE WALL - 7,660 LBS
1 PIECE NEEDED
ELEVATION 1
P8
0 1' 2'4'1P8BILL OF MATERIALS (SW1B)
ITEM QTY DESCRIPTION
1 1.9 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
2 3 3"Ø x 12" LONG PT DUCT
3 4 RL7 8-TON ERECTION ANCHOR (79149)
4 2 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042)
8 4 WELD ANGLE: 3"x 3"x 6" w/ 3
4"Ø x 6" H.C.A.
QTYS. ARE PER PIECE
REINFORCING DETAIL
(SIDE WALL TYP.)5"(TYP.)2 ℄ 3"Ø PT DUCT
17'-2" OVERALL
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)3
4'-3"2 SPACES @ 4'-4" O.C. = 8'-8"4'-3"
3 SPACES @ 3'-6" O.C. = 10'-6"3'-4"3'-4"3'-2" OVERALL112" KEYWAY1'-9"1'-5"3 SPACES @ 4'-0" O.C. = 12'-0"2'-7"2'-7"1'-312"1'-10"1'-10"1'-312"℄ WALL WELD PLATE (TYP.)
SEE DETAIL4
℄ 16"Ø BLOCKOUT FOR
12"Ø PVC PIPE
℄ 16"Ø BLOCKOUT FOR
12"Ø PVC PIPE
3"Ø x 12" PT
DUCT (TYP.)2
℄ SIDE WALL WELD
ANGLE SEE DETAIL 8 12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)312"KEYWAY414"3'-2"1'-0"OVERALL3
WALL WELD PLATE
(TYP.) SEE DETAIL4
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)6"SIDE WALL WELD
ANGLE SEE DETAIL 8 1
1'-6"3'-7"1'-6"3'-7"7'-0"
NOTE: PANEL WILL NOT HANG LEVEL,
ADJUST LIFTING CABLES AS REQUIRED.
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.1'-7"℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
112"CLR.2"CLR.A2 #4 @ 1'-0" (L.D.)
OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
MESH CHAIR
#4 @ 1'-0" (S.D.)A3
#5 @ 8" (L.D. BETWEEN BLOCKOUTS)A4
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
#5 @ 4" (L.D. BESIDE BLOCKOUTS)A1
9"3'-112"4'-11"9"7'-712"
112" DEEP x 9" WIDE CHANNEL ON
INSIDE FACE FOR WEIR & BAFFLE WALL
(TYP. 2 PLACES)
112" DEEP x 9" WIDE CHANNEL
FOR WEIR & BAFFLE WALL
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P8DATE ENG
SEPTEMBER 21, 2023
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
17'-2" OVERALL
10'-0"112" KEYFACE VIEW SIDE VIEW
SIDE WALL WELD ANGLE & KEY DETAIL
L3"x3"x 14" 6" LONG
W/ 2 EA. 34"x 6" H.C.A.
412"112"3"
7"x 312"x 34" DEEP
RECESS POCKET
112" KEYOUTSIDE FACE
OF WALL "A"
SW2A - PLAN VIEW
SW2A BOTTOM SIDE WALL - 25,632 LBS
1 PIECE NEEDED
ELEVATION 1
P9
0 1' 2'4'1P94'-6"2'-9"2'-9"2'-7"3 SPACES @ 4'-0" O.C. = 12'-0"2'-278"2'-6"5'-0"2'-6"4'-4"8'-6"4'-4"
4 SPACES @ 3'-6" O.C. = 14'-0"1'-2"2'-0"WALL WELD PLATE
(TYP.) SEE DETAIL4
BILL OF MATERIALS (SW2A)
ITEM QTY DESCRIPTION
1 6.3 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
3 4 RL7 8-TON ERECTION ANCHOR (79149) w/ TENSION BAR
4 9 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042) w/(4) #4 BARS
8 4 WELD ANGLE: 3"x 3"x 6" w/ 34"Ø x 6" H.C.A.
QTYS. ARE PER PIECE
1'-9"1'-9"4'-0"
℄ SIDE WALL WELD
ANGLE SEE DETAIL 8
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)3
REINFORCING DETAIL
(SIDE WALL TYP.)112"CLR.#4 @ 1'-0" (S.D.)
MESH CHAIR
#5 @ 8" (L.D.)2"CLR.OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
A1
A2 #4 @ 1'-0" (L.D.)
A3
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)3" KEY412"10'-0"1'-0"OVERALL3
5 8T RL-24 PLATE
LIFTING INSERT (TYP.)
WALL WELD PLATE
(TYP.) SEE DETAIL 4
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)6"SIDE WALL WELD
ANGLE SEE DETAIL 8
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
9"3'-112"4'-11"9"7'-712"
4'-0"5'-8"
112" DEEP x 9" WIDE CHANNEL
FOR WEIR & BAFFLE WALL
112" DEEP x 9" WIDE CHANNEL ON
INSIDE FACE FOR WEIR & BAFFLE WALL
(TYP. 2 PLACES)
1
4'-538"1'-10"
℄ 12"Ø OPENING FOR 8"Ø PIPE
ADD (1) #5 x 4'-2"
LONG BAR (E.W. T&B)
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P9DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
SW2B - PLAN VIEW
SW2B TOP SIDE WALL - 8,080 LBS
1 PIECE NEEDED
ELEVATION 1
P10
0 1' 2'4'1P10BILL OF MATERIALS (SW2B)
ITEM QTY DESCRIPTION
1 2.0 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
2 3 3"Ø x 12" LONG PT DUCT
3 4 RL7 8-TON ERECTION ANCHOR (79149)
4 2 WELD PLATE: 3"x 6" w/ 34"Ø x 6" H.C.A.
5 4 RL24 8-TON PLATE LIFTING INSERT (79042)
8 4 WELD ANGLE: 3"x 3"x 6" w/ 3
4"Ø x 6" H.C.A.
QTYS. ARE PER PIECE
REINFORCING DETAIL
(SIDE WALL TYP.)5"(TYP.)2 ℄ 3"Ø PT DUCT
17'-2" OVERALL
℄ 8T RL-7 ERECTION
ANCHOR (TYP.)3
4'-3"2 SPACES @ 4'-4" O.C. = 8'-8"4'-3"
3 SPACES @ 3'-6" O.C. = 10'-6"3'-4"3'-4"3'-2" OVERALL112" KEYWAY1'-9"1'-5"2'-7"2'-7"
℄ WALL WELD PLATE (TYP.)
SEE DETAIL4
3"Ø x 12" PT
DUCT (TYP.)2
℄ SIDE WALL WELD
ANGLE SEE DETAIL 8
12" CHAMFER
RUNNING LENGTH
(BOTH SIDES)
3'-2"
3℄ 8T RL-7 ERECTION
ANCHOR (TYP.)6"SIDE WALL WELD
ANGLE SEE DETAIL 8 1
1'-6"3'-7"1'-6"3'-7"7'-0"
NOTE: PANEL WILL NOT HANG LEVEL,
ADJUST LIFTING CABLES AS REQUIRED.
WALL WELD PLATE
FACE VIEWSIDE VIEW
NELSON STUD AWS
TYPE C (OR EQUAL)
112" DEEP RECESS
POCKET
3"x 6"x 38" STEEL PLATE
W/ 2 EA. 34"x 6" H.C.A.1'-7"℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)5
112"CLR.2"CLR.A2 #4 @ 1'-0" (L.D.)
OUTSIDE SURFACE (MARKED DURING
PRODUCTION TO ENSURE PROPER
INSTALLATION)
MESH CHAIR
#4 @ 1'-0" (S.D.)A3
#5 @ 8" (L.D.)A1
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
FACE VIEW SIDE VIEW
SIDE WALL WELD ANGLE & KEYWAY DETAIL
L3"x3"x 14" 6" LONG
W/ 2 EA. 34"x 6" H.C.A.
414"112" KEYWAY312"
7"x 312"x 34" DEEP
RECESS POCKET112" KEYWAYOUTSIDE FACE
OF WALL "A"312"KEYWAY414"1'-0"OVERALL9"3'-112"4'-11"9"7'-712"
112" DEEP x 9" WIDE CHANNEL ON
INSIDE FACE FOR WEIR & BAFFLE WALL
(TYP. 2 PLACES)
3 SPACES @ 4'-0" O.C. = 12'-0"
WALL WELD PLATE
(TYP.) SEE DETAIL4112" DEEP x 9" WIDE CHANNEL
FOR WEIR & BAFFLE WALL
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P10DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
L1 - PLAN VIEW
L1 PRECAST LID - 4,140 LBS
3 PIECES NEEDED
ELEVATION 1
P11
0 1' 2'4'
1
P11
BILL OF MATERIALS ( L1 )
ITEM QTY DESCRIPTION
1 1.0 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
9 4 MB V-ANCHOR 0.444Ø (MBV6444)
5'-8516" OVERALL
6'-512" OVERALL(DESIGN WIDTH)QTYS. ARE PER PIECE
REINFORCING DETAIL
(PRECAST LID TYP.)1'-834"3'-0"1'-834"℄ MB V-ANCHOR (TYP.)9
1'-6"2'-8 516"1'-6"
MB V-ANCHOR (TYP.)9
5'-8 516"9"OVERALL112"CLR.2"CLR.#6 @ 6" (L.D. ALONG DESIGN WIDTH)A1
#4 @ 1'-0" (S.D.)A3
A2 #4 @ 1'-0" (L.D.)
MESH CHAIR
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P11DATE ENG
SEPTEMBER 21, 2023
AS-BUILT
OIL WATER SEPARATOR (OWS-2)
BILL OF MATERIALS ( BAFFLE, WEIR )
ITEM QTY DESCRIPTION
1 1.5 YD³CONCRETE 7,000 PSI MIX (3,500 PSI STRIP)
3 2 RL7 8-TON ERECTION ANCHOR (79149)
10 4 RL24 8-TON PLATE LIFTING INSERT (79054)
QTYS. ARE PER PIECE
2"CLR.2"CLR.#4 @ 1'-0" (L.D.)A1
#4 @ 1'-0" (S.D.)A3
A2 #4 @ 1'-0" (L.D.)
MESH CHAIR
WEIR - PLAN VIEW
PRECAST WEIR - 6,200 LBS
1 PIECE NEEDED
ELEVATION 1
P12
0 1' 2'4'1P12BAFFLE - PLAN VIEW
PRECAST BAFFLE - 5,930 LBS
1 PIECE NEEDED
ELEVATION 2
P12
0 1' 2'4'10'-6" OVERALL10'-6" OVERALL6'-2" OVERALL 6'-2" OVERALL
1'-7"3'-0"1'-7"3℄ 8T RL-7 ERECTION
ANCHOR (TYP.)1'-7"3'-0"1'-7"3℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
2'-4"1'-138"1'-138"958"958"2'-0"2'-0"10'-6"
3'-0"10"
3'-2"6"8" OVERALL3'-0"10"4'-8"9"9"
10'-6"8" OVERALL2P124"(TYP.)3 ℄ 8T RL-7 ERECTION
ANCHOR (TYP.)4"(TYP.)3 ℄ 8T RL-7 ERECTION
ANCHOR (TYP.)
℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)3'-6"4'-4"2'-8"10
NOTE: PANEL WILL NOT HANG LEVEL,
ADJUST LIFTING CABLES AS REQUIRED.
1'-7"1'-7"2'-2"6'-2"2'-2"℄ 8T RL-24 PLATE
LIFTING INSERTS (TYP.)10
10 8T RL-24 PLATE
LIFTING INSERT (TYP.)
1'-0"4'-2"1'-0"
10 8T RL-24 PLATE
LIFTING INSERT (TYP.)
DESIGN NOTES
1. STEEL REINFORCEMENT: REBAR ASTM A615 GRADE 60
2. CEMENT: ASTM C0150 SPECIFICATIONS
3. WELDING STEEL: 70 KSI & PER ASTM A36
4. ANY REINFORCING CUT AROUND OPENINGS OR
INSERTS MUST BE REPLACED WITH EQUIVALENT
5. LIFT INSERTS SHALL BE INSTALLED AND USED PER
MANUFACTURER'S RECOMMENDATIONS2"CLR.2"CLR.#5 @ 112" (L.D. E.F.
EA. SIDE OF BLOCKOUT)A1
#4 @ 1'-0" (S.D.)A3
A2 #4 @ 1'-0" (L.D. E.F. ABOVE
AND BELOW BLOCKOUT)
MESH CHAIR
SECTION 3
P12PRECAST WEIR REINFORCING
3
P12
4
P12
SECTION 4
P12PRECAST BAFFLE REINFORCING
1
9/21/23 AS BUILT DRAWINGS JJC
DATE DESCRIPTION ENG
1
CENTRAL MAINTENANCE FACILITY
(RENTON SHOP)
LOCALE:RENTON STATE:WA
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NUMBER:
DATE:
2
3
4
5
6
7
KDK
NBD
JJV
22-444
11/16/2022
5415 189TH STREET E
PUYALLUP, WA 98375
PHONE 253-929-1818
PROVIDED BY:
P.O. BOX 351
BELLBROOK, OH 45305
800.241.0925
DESIGNED BY:SPEC: 03 41 33 SPEC SUBPART: 1.04 PROJECT NUMBER: KC PARKS 1122161
DATE:
DESCRIPTION
P12DATE ENG
SEPTEMBER 21, 2023