Loading...
HomeMy WebLinkAboutW-399001V J w N EX. CB 5� TOP 40.27 6" IE 38.9 (E) ExO n 23 TOPE 4030 N o 60PE 1390 (W) 6" IF 400 (EW) SS N90'00'00.00"E w EX. 8" PVC SEWER -- -- -- 115.25 C I I 3 I I I I � J � GLASS AWNING S SS CONTRACTOR SHALL FIELD VERIFY LOCATION — w 3 OF ALL UNDERGROUND AND OVERHEAD UTILITIES THAT COULD BE AFFECTED BY TRENCHING FOR NEW FIRE SERVICE LINE. FIELD VERIFICATION SHALL BE DONE BY POTHOLING. ANY CONFLICTS EXISTING SSMH LOCATION SHALL BE REPORTED TO ENGINEER IMMEDIATELY AND INFORMATION TO BE 0 FIELD VERIFIED PRIOR L LI 1n EX. 12" D.I. WATER MAIN TO CONSTRUCTION w GORTONA — > BUILDING REMOVE CURBS AND LANDSCAPING AS Q EX SOME! (NOT FOUND) REQUIRED FOR INSTALLATION OF NEW FIRE S ; ABANDON 6- C.I. ORRECORDDRAWINGS BUILDING #724 SERVICE. RESTORE TO ORIGINAL CONDITIONS Q WATER MAIN 2 STORY MASONARY W/ w 3s.ot cALc'D NO APPARENT BASEMENT g J J PROTECT EXISTING STREET BUILDING 80( FF=41.0 LIGHT, POLE, STRUCTURES, N AND ELECTRICAL RUNS. o TORY MASON, N CONNECT TO EXISTING W/BASEMENT WATER MAIN ( ) FF -41.55 1-12"x4" TAPPING TEE MJxFL 1-4" GATE VALVE (FLx MJ) 4" DETECTOR DOUBLE CHECK VALVE SS 3 1—CONCRETE BLOCKING ASSEMBLY INSIDE BUILDING PER SEE DETAIL 300.1 ON SHEET C2.0 STD PLAN 360.5. SEE SHEET C2.0 REMOVE CURBS AND LANDSCAPING AS REQUIRED FOR INSTALLATION OF NEW FIRE SERVICE. RESTORE TO ORIGINAL CONDITIONS o � WALL MOUNTED FDC W 42 LF 4" WA SAWCUT, PATCH, AND REPAIR (CL 52 DI PIPE) 3 EXISTING PAVEMENT AND PROTECT EXISTING WATER METER FIRE SERVICE AT UNDERLYING CONCRETE 3' MIN. COVER PANELS. SEE DETAIL 110.1 TENANT ENTRY PRIMARY ENTRY PIV PER STD PLAN 360.5, ON SHEET C2.0. 5.0' MIN. SEE SHEET C2.0. 24" v ASPHALT PATCH REQUIRED BEHIND FACE OF CURB W µ PER WSDOT STD SPEC 2-09.4 AWNING c� n I I O i N90'00'00.00'W EX. 06 PROTECT EXISTING3 TOP 40.30 _FIBER OPTIC LINES 8" IE 39.1 (W) I T,o CECIL irASSOMATES PO BOX 598 BOTHELL, WA 98011 (206) 484-3495 www.ceciinassoc.com SD SD S. 3RD STREET EX SDMH TOP 41.10 6" IF 37.1 (NE) 6" IF 36.9 (SE) CTR CHANNEL 36.5 (EW) 4 PERMIT SUBMITTAL RJC11/17/181RJC N 1" = 10' R12W1: NAD wi1991 3 PERMIT SUBMITTAL RJC 0/31 1 RJC m. RJC 2 PERMIT SUBMITTAL RJC 19/26/171 RJC V6 I oxEIx� I 1 PERMIT SUBMITTAL RJC 9 8 17 RJC -NLL� DATUM JCF NO. REVISION BY DATE I APPR RJC g"E"4O*iO'N"V CITY OF ' RENTON Planning/Building/Public Works Dept. 11:7_1��[NPPlh CONTRACTOR SHALL PROVIDE ADEQUATE TRAFFIC CONTROL IN ORDER TO KEEP ONE LANE OF TRAFFIC OPEN AT ALL TIMES. A TRAFFIC CONTROL PLAN SHALL BE SUBMITTED TO THE CIN INSPECTOR PRIOR TO STARTING SITE WORK. CONTRACTOR SHALL CALL FOR UTILITY LOCATES, AND SHALL POTHOLE ALONG THE PROPOSED WORK AREA TO IDENTIFY LOCATION AND DEPTH OF ALL EXISTING UTILITIES PRIOR TO BEGINNING CONSTRUCTION. THE ENGINEER SHALL IMMEDIATELY BE NOTIFIED OF ANY DISCREPANCIES BETWEEN THE FOUND UTILITIES AND THE UTILITIES SHOWN ON THE PLANS. NOTE: 1. THE MINIMUM VERTICAL CLEARANCE FROM THE EXISTING SANITARY SEWER IS 18 INCHES. THE MINIMUM VERTICAL CLEARANCE FROM GAS, ELECTRIC, TELEPHONE, AND FIBER OPTIC IS 12 INCHES. IF THE MINIMUM CLEARANCE CANNOT BE OBTAINED, THE APPLICANT IS TO OBTAIN CITY APPROVAL PRIOR TO INSTALLATION OF THE FIRE LINE. 2. ALL CONCRETE BLOCKING FOR HORIZONTAL BENDS, TEES, AND VERTICAL BENDS SHALL BE PER COR STD. PLANS 330.2 AND 330.3. 3. ALL MECHANICAL JOINT FITTINGS AND VALVES SHALL HAVE RESTRAINED GLANDS EQUAL TO MEGALUG SERIES 1100 OR ROMAC ROMAGRIP. 4. CEMENT CONCRETE CURB RESTORATION SHALL BE PER COR STD. PLAN 101. 5. CEMENT CONCRETE SIDEWALK RESTORATION SHALL BE COR STD. PLAN 102. rl T N CALL BEFORE HORIZ. 0 Scale®O YOU In Feet UD=MUND RV811ICE A W W-399001 IN COMPLIANCE WITH CITY OF RENTON STANDARDS W REGIONAL FIRE AUTHORITY tZl DEVELOPMENT ENGINEERINGO APPROVED CJ IFitz-James 01/26/2018 cJiamas 01/26/2018 7 WATER UTILITY Abdoul Gafour 01 /26/2018 O CORTONA BUILDING 117 18 Z FIRE SERVICE PLAN ° NO NOE" C1.00 0 ma: 1 �, 2 U