SANITARY SEWER NOTES AND
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND
THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND
MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET
OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION,
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PLANNING/BUILDING/PUBLIC WORKS
DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO BEGINNING
ANY WORK WITHIN PUBLIC RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTIUTIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE.
4. A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO
STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL
NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY
A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL
CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE.
6. B SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON. PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS.
8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN
PROGRESS.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE
SANITARY SEWER SYSTEM, WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL
ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE
AVERAGE DEPTH OF 6 INCHES. MAXIMUM DEPTH OF 8 INCHES. THOROUGHLY TAMPING EACH
LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR
ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS
TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS OTHERWISE APPROVED
BY UTILITY SPECIFICATIONS.
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND
FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS
OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE
BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON-SITE EROSION AFTER THE
COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA
STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE
RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL INCLUDE NECESSARY LEVEUNG OF THE
TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND
COMPACTION OF REQUIRED BEDDING MATERIAL, T0 UNIFORM GRADE
THAT
E ENTIRE LENDT
H
OF THE PIPE WILL 8E SUPPORTED ON A UNIFORMLYDENSE UNYIELDING BASE. PIPE BEDDING
SHALL BE PEA GRAVEL 6 INCHES THE PIP
ABOVE AND BELOW E E.
15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034,
SDR 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER
UTILITY.
16. IN UNIMPROVED AREAS,
MANHOLE
TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES
ABOVE FINISHED GRADE
OR MUST
HAVE MINIMUM 2'
DIAMETER CONCRETE RING POURED AT
GRADE. IN PAVED AREA,
COVER MUST SLOPE IN ALL
DIRECTIONS TO MATCH PAVING.
by:
mrc
m
n
a
o
Mi
a
a
m
o
;+;
m
0
o -
SANITARY SEWER NOTES AND
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND
THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND
MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET
OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION,
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PLANNING/BUILDING/PUBLIC WORKS
DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO BEGINNING
ANY WORK WITHIN PUBLIC RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTIUTIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE.
4. A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO
STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL
NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY
A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL
CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE.
6. B SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON. PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS.
8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN
PROGRESS.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE
SANITARY SEWER SYSTEM, WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL
ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE
AVERAGE DEPTH OF 6 INCHES. MAXIMUM DEPTH OF 8 INCHES. THOROUGHLY TAMPING EACH
LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR
ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS
TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS OTHERWISE APPROVED
BY UTILITY SPECIFICATIONS.
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND
FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS
OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE
BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON-SITE EROSION AFTER THE
COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA
STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE
RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL INCLUDE NECESSARY LEVEUNG OF THE
TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND
COMPACTION OF REQUIRED BEDDING MATERIAL, T0 UNIFORM GRADE
THAT
E ENTIRE LENDT
H
OF THE PIPE WILL 8E SUPPORTED ON A UNIFORMLYDENSE UNYIELDING BASE. PIPE BEDDING
SHALL BE PEA GRAVEL 6 INCHES THE PIP
ABOVE AND BELOW E E.
15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034,
SDR 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER
UTILITY.
16. IN UNIMPROVED AREAS,
MANHOLE
TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES
ABOVE FINISHED GRADE
OR MUST
HAVE MINIMUM 2'
DIAMETER CONCRETE RING POURED AT
GRADE. IN PAVED AREA,
COVER MUST SLOPE IN ALL
DIRECTIONS TO MATCH PAVING.
SURFACE WATER DRAINAGE
NOTES AND SPECIFICATIONS
1. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRE -CONSTRUCTION MEETING
MUST BE HELD WITH THE CITY OF RENTON PLAN RENEWER.
2. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE 2012 STANDARD SPECIFICATIONS FOR
ROAD, BRIDGE AND MUNICIPAL CONSTRUCTION PREPARED BY WSDOT AND THE AMERICAN PUBLIC
WORKS ASSOCIATION (APWA), AS AMENDED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT.
3. THE SURFACE WATER DRAINAGE SYSTEM SHALL BE CONSTRUCTED ACCORDING TO THE APPROVED
PLANS, WHICH ARE ON FILE IN THE PUBUC WORKS DEPARTMENT. ANY DEVIATION FROM THE
APPROVED PLANS WILL REQUIRE WRITTEN APPROVAL FROM THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT, SURFACE WATER UTILITY SECTION.
4. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS
IN PROGRESS.
5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND
FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS
OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE
BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
6. ALL SEDIMENTATION/EROSION FACILITIES MUST BE IN OPERATION PRIOR TO CLEARING AND
BUILDING CONSTRUCTION, AND THEY MUST BE SATISFACTORILY MAINTAINED UNTIL CONSTRUCTION
IS COMPLETED AND THE POTENTIAL FOR ON-SITE EROSION HASPASSED.
7. ALL RETENTION/DETENTION FACILITIES MUST BE INSTALLED AND IN OPERATION PRIOR TO OR IN
CONJUNCTION WITH ALL CONSTRUCTION ACTIVITY UNLESS OTHERWISE APPROVED BY THE PUBLIC
WORKS DEPARTMENT. SURFACE WATER UTILITY SECTION.
8. GRASS SEED MAY BE APPLIED BY HYDROSEEDING. THE GRASS SEED MIXTURE, OTHER THAN CITY
OF RENTON APPROVED STANDARD MIXES, SHALL BE SUBMITTED BY A LANDSCAPE ARCHITECT AND
APPROVED BY THE PUBLIC WORKS DEPARTMENT, SURFACE WATER UTIUTY SECTION.
9. ALL PIPE AND APPURTENANCES SHALL BE WD ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE WITH SECTION 7-02.3(1) OF THE CURRENT STATE OF WASHINGTON STANDARD
SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING
OF THE: TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT
AND COMPACTION OF REQUIRED BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE
LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE. UNYIELDING BASE. ALL PIPE
BEDDING SHALL BE APWA CLASS 'C°, WITH THE EXCEPTION OF PVC PIPE. ALL TRENCH BACKFILL
SHALL BE COMPACTED TO MINIMUM 954 FOR PAVEMENT AND STRUCTURAL FILL AND 90%
OTHERWISE PER ASTM D-1557-70. PEA GRAVEL BEDDING SHALL BE 6 INCHES OVER AND UNDER
PVC PIPE.
10. GALVANIZED STEEL PIPE AND ALUMINIZED STEEL PIPE FOR ALL DRAINAGE FACILITIES SHALL HAVE
ASPHALT TREATMENT /1 OR BETTER INSIDE AND OUTSIDE.
11. STRUCTURES SHALL NOT BE PERMITTED WITHIN 10 FEET OF THE SPRING LINE OF ANY STORM
DRAINAGE PIPE, OR 15 FEET FROM THE TOP OF ANY CHANNEL BANK.
12, ALL CATCH BASIN GRATES SHALL BE DEPRESSED 0.10 FEET BELOW PAVEMENT LEVEL.
13. OPEN CUT ROAD CROSSINGS THROUGH EXISTING PUBLIC RIGHT OF WAY WILL NOT BE ALLOWED
UNLESS SPECIFICALLY APPROVED BY CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS
ADMINISTRATOR.
14. ROCK FOR EROSION PROTECTION OF ROADSIDE DITCHES, WHERE REQUIRED, SHALL BE 0F
SOUND QUARRY ROCK PLACED TO A DEPTH OF ONE (1) FOOT AND MUST MEET THE FOLLOWING
SPECIFICATIONS:
4 - 8 INCH ROCK / 40 - 70% PASSING;
2 - 4 INCH ROCK / 30 - 40% PASSING; AND
LESS THAN 2 INCH ROCK / 10 - 20% PASSING.
15. ALL BUILDING DOWNSPOUTS AND FOOTINGRAI HA T T THE T
DRAINS SHALL BE VIEWER R 0 E S ORM
DRAINAGE SYSTEM, UNLESS APPROVED DIMENSIONED, THE CITY PLAN REVIEWER OR SURFACE WATER UTILITY
SECTION. L ACCURATELY TOTHECICERTIFIED MP BUILT DRAWING OF THIS DRAINAGE
SYSTEM WILL BE SUBMITTED TO THE COY UPON COMPLETION.
16. ISSUANCE OF THE BUILDING OR CONSTRUCTION PERMITS BY THE CITY OF RENTON DOES NOT
RELIEVE THE OWNER OF THE CONTINUING LEGAL OBLIGATION AND/OR LIABILITY CONNECTED WITH
STORM SURFACE WATER DISPOSITION. FURTHER, THE CITY OF RENTON DOES NOT ACCEPT ANY
OBLIGATION FOR THE PROPER FUNCTIONING AND MAINTENANCE OF THE SYSTEM PROVIDED
DURING CONSTRUCTION.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SAFEGUARD. SAFETY
DEVICES, PROTECTIVE EQUIPMENT, FLAGGERS, AND ANY OTHER NEEDED ACTIONS TO PROTECT
THE LIFE. HEALTH. AND SAFETY OF THE PUBLIC. AND TO PROTECT PROPERTY IN CONNECTION
WITH THE PERFORMANCE OF WORK COVERED BY THE CONTRACT. ANY WORK WITHIN THE
TRAVELED RIGHT OF WAY THAT MAY
INTERRUPT NORMAL TRAFFIC FLOW SHALL REQUIRE A TRAFFIC CONTROL PLAN APPROVE BY THE
PUBLIC WORKS DEPARTMENT, TRANSPORTATION SYSTEMS DIVISION. ALL SECTIONS OF THE
INSECT STANDARD SPECIFICATIONS 1-07-23 TRAFFIC CONTROL SHALL APPLY.
18. SPECIAL DRAINAGE MEASURES WILL BE REQUIRED IF THE PROJECT LOCATION IS WITHIN THE
AQUIFER PROTECTION AREA (APA).
AS-S&T NOTC
THIS CONSTRUCTION RECORD DRAWING IS A COPY OF A CAD FILE PREPARED BY BARGHAUSEN
CONSULTING ENGINEERS AND HAS BEEN EDITED TO REFLECT FIELD VERIFIED INVERT AND RIM
CALL 2 WORKING DAYS ELEVATIONS OF THE STORM, SANITARY SEWER AND WATER MAIN SYSTEMS. FIELD VERIFIED INVERT AND
EBIRIM ELEVATIONS WERE OBTAINED BY DEACON AND NORTHWEST CONSTRUCTION IN AUGUST 220/7, A
D
BEFORE YOU G. FIELD SURVEY BY BARCHAIISEN CONSULTING ENGINEERS WAS ALSO CONDUCTED IN OCTOBER 2017.
THE ON-SITE PRIVATE STORM DRAINAGE FACILITIES AND PUBUC/PRNATE WATER AND SEWER SYSTEMS
O WERE INSTALLED IN ACCORDANCE WITH THE APPROVED PUNS AND THE DOCUMENTED FIELD
z Hil REVISIONS AND FUNCTION AS INTENDED.
VERnCAL DATIM
CITY OF RENTON, NAVD 88
BENCR
CITY OF REENTON CONTROL
POINT NO. 1864 WAS HELD
FOR ELEVATION, BEING
19.488 FEET (NAVD88)
AS -BUILT
wATd PLM OENEMIXm¢ xtiMNuXMNR3m
L auwoMAxoRumEasMNILaE NArmmMrcawlmnxumrmmonovTlR:anaFxenoxvuvcw�u
nAXDAm sPE6R'AInNRaosPEOALPRw6MX6A1p wsom/APWAnaNAmsICdICATIW{sIAT¢EmIXON K
aMMm[D6YTxEanarRFNlaI. ASETaYmArrRwmPlMlssxuLlFlNerArTHFOamEvmrmxsmurnox
MwrmDNss. AMXidNORC110xD01xfld4sxAURE HBDmpI1roTIRF1TMFam161MK1101111NmNIM[Idl
AlmaRo[w[aPm Puu.xllevtielNFmRSFomwDAuxFOF¢¢.areaRu¢nrnromxsMucRox.
2 ALLF[6TIN6 UIIMR¢4NLLRFMAM WsdVKF WNNDCMISTALKIIDNUIiF%DNERN54NDIm. 1NFmmRALIgISNW
ExL LamaussssmvmFrunmrmGTIpMRFraueRD»RxsaravAnox.
!. AMMArFANLSFISEDrORTNFCd6RIUC110Nawal¢SFSIEMIMPROYER4R59WlRFxFwANDLRMMAGm.IlD
'eYTaaD CV¢'TmALLMATERWSSXaIREAPPROV®IX WRITING RY1MFmY0F pmiOxepDRTO.NNGNGAxI
MATdWSUxENF.
£ AIL WATERMAM PIPE MATFRM¢sIMLLNEo3AFNfNNEDDUCfIIEIRax vNF,TNIpd�pABurmAwwacsss ANDc
100.MrtIONI EPUSNOXmMEDMXXAIIOM[. CASEIMIN d1011LiItFMdI PIENIxN¢SNMINEtlA56 }m A5
Id ANMIAWWA C11M1CUWASL10ffi..Pll WC111EXONMEMD XmN65NALLEE WRIJPFD IMX&MLNAR.IUEF-rwE
6. MMIMIIMfpVfRX¢MroPOF ward MaMroNxmImQUDEsxiusNEssda¢FORPIFdFARnFAd10NDIdIlEA9
AKOptlld¢FOR PIPEdAMEfd OF124NMIMDLM6FA MAMMUAI WVERmRALL WMFIIMAN66WllREmDd011¢
AxrDduTNMMusr¢McROYwnTxEarvaRmroxvRaxroaRUTqurndL wlarununTARXucrsamd
TllsrRONMof nIEwATd MMNvwl MAnlusDnAtraxE6ANrroaEaNaNMX.ysarmrovNOymEMN✓MV,ImWN
MCENEFIECIMINsxAUXDEE11EFmoxF11AIF0EPPEYa1VEM111Rds�X'ATRMrgISEMaPPFVEEa. AUTMR01
uo.YULsxAueEElNnracRoro%vemmrMARr4uM DRY'DEN81YMOnFRMR®WrxEMDdIaoPRaLTnT¢T
MEiI%DIMmI W R64NNAYS,ROAOWgsMWmFR4,ROMWAYPRISAAANNOMVEw'AY;IOm%PMIONIfMmINNNIaVm
ARFM ALLPNE mNECOMeAcildsXML%%M00.
£ mxmHF&oOENGPoR WAId MaM65MALL RE msMXm, dnAMm AI®MIUREVINIMIINACWRMIAiWI1XOlY0f
NxTdl nAxoAro D[Ta¢AXDEPEOFlUTx1NRAmsxAMREIXnAxm arAuosrcALAraolwRmxra.MN%,Nrnxss
AXD WfiF d XmRAMR. MEFM-UKd/OREIMILal PR000CT MAYN RFOVIRFDONALLM®411NALIOINIEIXald110NT0
mNd[rt Nrcgxs.
1. ALLXEW WATERMMNPDRSMDNTRNG65Mal HAW A ROAM PIPE PIG RUNTNROII611 H P VBm10RIUM
DNIMFCIm,MDTFsim. tlfANING,IAtESSURE ANOPUNIYTEATIN65Xa1MDdEEWTxF»Es[D¢dAxouNodTxF
swERNaex DFA alrOreExFox unurr WSPEero£ Tx[txxnlAna sxAusurwr,,Nmeueee AFMe9s PXxs,
fDRPORAT10N 6TOP6, RlOW-0iFASREMMId AND1NmnRE6TRAIM(BioE11NGNN1E511N6ANDPWwACFPTAM[E ND
TDXNECIIDXfiIMLIBEMADEXE{VlFFX1HENEW MYX OR RETWFm1NFXEW Wn-TAPVNYETDANEXmMOM.VN{MIR
1MENFW PAIR%MASREd FOAMxY6Gm, 06MF[Lliq ftBEHm,ANDPaXFDROd PM85UREAppmRnrT¢11X6.
£ IJkVY WATER MMISYIIIUMN6 M MIERA¢6HALLRE MM ATAnAM1R¢SUIXOF160PNAROVEVAX
PRE6IAMF WRXAMINMUNOFMPSIIEnPR®IIREfOR 120MdV1¢ WIINAMARRRM10F69PRESSUEDROPUVMW
1NEENdWlF6TPdN0.UroN6MNfACTORYfAMPIETld10FINE PRFSMIREIFn,RO VINSNRMM:D6fiKim,NV6N®,
ANDIXd WATd$AM/l¢SIULLRETARm FOI mRITI1FnIN6RYIHEPLXUC WONBRI,PE[mA.
9.T1EmNiM[[WN X0 REMMEM EM WAMUxM MDMMXIEWwD:DdARIRiNRAT1FAnNENM M
WYS PRXIRro MAKWGCOWIFGTld6roliff f10SINIG WAlER5Y6DM.IHE WXdACigISMALLLWEFTXFEI%IMG WAId
NMIAfA XIiIN6SATTXEmxxM.TIMroMM.POR[dNk%XGTx[x[C¢TRRfO➢AA0%AMMIDYdRmUP�TM
THEXIMLCONNECTON. IHFmNIMI'IOXSIWLf1D'AYMA REMWFNLSII%OIIMATWMS,a%P0.04IDENId1XGA1N
MLMATERW4RMDIBXDmRTxEcnvaRExrmrovwoxMTxEroxMrnOnTOTIa FI%IRIswATd smNA Tx[
mXdACfORFMALLPRWNFAN[IIISfaILXRGDW. CONCRNF BWORNG,NOmA1xFiE5UNA{FREMdtOTI1H.
by
Date
by.
Date
by:
Date
MBUC WORKS�• ALAI( -800.6
DEPARTMENT YtlIAhR W.ANLF4
MARcx Raio
IKEA PROPERTY INC
420 AWtl WOOD ROAD
CONSHOHOCKEN, PA 19428
CONTACT: DWIGHT E. SLATM
CONSTRUCTION MANAGER
P: (610) 834-018Q CELL M0 S49-4623
E: plY RiIIYGY 1R EeR LSLALG4 IG EA&C
ENGINEER
BARGHAUSEN CONSULTING ENGINEERS
18215 72ND AVENUE SOUTH KENT.
WA 98032
CONTACT: JAY GRUBB, PE
(4951741-R919
GENERAL SITE DEVELOPMENT NOTES
1. THE CONTRACTOR SHALL OBTAIN AND HAVE AVAILABLE COPIES OF THE
APPLICABLE GOVERNING AGENCY STANDARDS AT THE JOB SITE DURING THE
RELATED CONSTRUCTION OPERATIONS.
2. CONTRACTOR SHALL ASSURE THAT ALL NECESSARY PERMITS HAVE BEEN OBTAINED
PRIOR TO COMMENCING WORK,
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION,
DIMENSION AND DEPTH OF ALL EXISTING UTILITIES PRIOR TO CONSTRUCTION
WHETHER SHOWN ON THESE PLANS OR NOT. UTILITIES OTHER THAN THOSE
SHOWN MAY EXIST ON THIS SITE. ONLY THOSE UTILITIES WITH EVIDENCE OF
THEIR INSTALLATION VISIBLE AT GROUND SURFACE OR SHOWN ON RECORD
DRAWING PROVIDED BY OTHERS ARE SHOWN HEREON. EXISTING UNDERGROUND
UTILITY LOCATIONS SHOWN ARE APPROXIMATE ONLY AND ARE SUBJECT TO A
DEGREE OF UNKNOWN VARIATION. SOME UNDERGROUND LOCATIONS SHOWN
HEREON MAY HAVE BEEN TAKEN FROM PUBLIC RECORDS. BARGHAUSEN
CONSULTING ENGINEERS, INC. ASSUMES NO LIABILITY FOR THE ACCURACY OF
PUBLIC RECORDS OR RECORDS OF OTHERS. IF CONFLICTS SHOULD OCCUR, THE
CONTRACTOR SHALL CONSULT BARGHAUSEN CONSULTING ENGINEERS, INC., TO
RESOLVE ALL PROBLEMS PRIOR TO PROCEEDING WITH CONSTRUCTION.
3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW ALL OF THE
DRAWINGS AND SPECIFICATIONS ASSOCIATED WITH THE PROJECT WORK SCOPE
PRIOR TO THE INITIATION OF CONSTRUCTION. SHOULD THE CONTRACTOR FIND A
CONFLICT WITH THE DOCUMENTS RELATIVE TO THE SPECIFICATIONS OR THE
RELATIVE CODES, IT IS THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE
PROJECT ENGINEER OF RECORD IN WRITING PRIOR TO THE START OF
CONSTRUCTION. FAILURE BY THE CONTRACTOR TO NOTIFY THE PROJECT ENGINEER
SHALL CONSTITUTE ACCEPTANCE OF FULL RESPONSIBILITY BY THE CONTRACTOR
TO COMPLETE THE SCOPE OF WORK AS DEFINED BY THE DRAWINGS AND IN FULL
COMPLIANCE WITH LOCAL REGULATIONS AND CODES.
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE APPROPRIATE
UTIUTIES INVOLVED PRIOR TO CONSTRUCTION.
5. INSPECTION OF BUILDING AND SITE WORK WILL BE ACCOMPLISHED BY A
REPRESENTANE OF THE CITY OF RENTON. INSPECTION OF SOILS, SUBGRADE.
SUBBASE, PAVEMENTS TRENCH BACKFILL AND GENERAL EXCAVATION WILL BE
ACCOMPLISHED BY A REPRESENTATIVE OF THE OWNER. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE INSPECTOR 24 HOURS IN
ADVANCE OF BACKFILLING ALL CONSTRUCTION.
6. THE CONTRACTOR SHALL PRIOR TO ANY CONSTRUCTION OR DEVELOPMENT
ACTIVITY CONTACT THE AGENCY AND/OR UTILITY INSPECTION PERSONNEL AND
ARRANGE ANY REQUIRED PRE -CONSTRUCTION MEETING(S). CONTRACTOR SHALL
PROVIDE 72 HRS MIN ADVANCE NOTIFICATION TO OWNER, FIELD ENGINEER AND
ENGINEER OF PRE -CONSTRUCTION MEETINGS.
7. THE CONTRACTOR IS RESPONSIBLE FOR WORKER AND SITE SAFETY AND SHALL
COMPLY WITH THE LATEST OSHA STANDARDS AND REGULATIONS, OR ANY OTHER
AGENCY HAVING JURISDICTION FOR EXCAVATION AND TRENCHING PROCEDURES.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE "MEANS AND METHODS"
REQUIRED TO MEET THE INTENT AND PERFORMANCE CRITERIA OF OSHA. AS WELL
AS ANY OTHER ENTITY THAT HAS JURISDICTION FOR EXCAVATION AND/OR
TRENCHING PROCEDURES.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE
SAFEGUARDS, SAFETY DEVICES, PROTECTIVE EQUIPMENT, FLAGGERS, AND ANY
OTHER NEEDED ACTIONS TO PROTECT THE LIFE, HEALTH, AND SAFETY OF THE
PUBLIC, AND TO PROTECT PROPERTY IN CONNECTION WITH THE PERFORMANCE
OF WORK COVERED BY THE CONTRACTOR. ANY WORK WITHIN THE TRAVELED
RIGHT-OF-WAY THAT MAY INTERRUPT NORMAL TRAFFIC ROW SHALL REQUIRE AT
LEAST ONE BAGGER FOR EACH LANE OF TRAFFIC AFFECTED.
9. PROTECTIVE MEASURES SHALL BE TAKEN BY THE CONTRACTOR TO PROTECT
ADJACENT PROPERTIES, PUBLIC AND PRIVATE, AT ALL TIMES DURING
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF
ALL EXISTING UTILITY SERVICES THAT ARE TO REMAIN OPERATIONAL WITHIN THE
CONSTRUCTION AREA WHETHER SHOWN OR NOT SHOWN ON THE PLANS
10. TWO (2) COPIES OF THESE APPROVED PLANS MUST BE ON THE JOB SITE
WHENEVER CONSTRUCTION IS IN PROGRESS: ONE (1) SET SHALL BE SUBMITTED
TO BARGHAUSEN CONSULTING ENGINEERS., INC., WITH RECORDS OF AS -BUILT
INFORMATION AT COMPLETION OF PROJECT.
11. CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR OBTAINING PERMITS FROM THE
WASHINGTON STATE DEPARTMENT OF NATURAL RESOURCES FOR REMOVING AND
REPLACING ALL SURVEY MONUMENTATION THAT MAY BE AFFECTED BY
CONSTRUCTION ACTIVITY, PURSUANT TO WAC 332-120. APPLICATIONS MUST BE
COMPLETED BY A REGISTERED LAND SURVEYOR. APPUCATIONS FOR PERMITS TO
REMOVE MONUMENTS MAY BE OBTAINED FROM THE WASHINGTON STATE
DEPARTMENT OF NATURAL RESOURCES, OR BY CONTACTING THEIR OFFICE BY
TELEPHONE AT (206) 902-1190.
WASHINGTON STATE DEPARTMENT OF NATURAL RESOURCES
PUBLIC LAND SURVEY OFFICE
111 WASHINGTON STREET S.E.
P.O. BOX 47060
OLYMPIA, WASHINGTON 98504-7060
UPON COMPLETION OF CONSTRUCTION, ALL MONUMENTS DISPLACED, REMOVED,
OR DESTROYED SHALL BE REPLACED BY A REGISTERED LAND SURVEYOR, AT THE
COST AND AT THE DIRECTION OF THE CONTRACTOR, PURSUANT TO THESE
REGULATIONS. THE APPROPRIATE FORMS FOR REPLACEMENT OF SAID
MONUMENTATION SHALL ALSO BE THE RESPONSIBILITY OF THE CONTRACTOR.
CITY OF RENTON
�GH I � DEPARTMENT OF PUBLIC WORKS
mP FZ GENERAL CONSTRUCTION NOTES
IKEA REDEVELOPMENT, F ENTON, WA.
U
Z DEaum cFB DAMb/II/2015 FX.6 IND. 015001266
u' ee• DRANN a
G4TANO ENSOl CYCOIID JSC BGLE N/A PBD NDDK PAOF
A>NnI oweem 6 w. w s > �2-1w42
R-3847102
0
z
inO
7
W
U
in