HomeMy WebLinkAboutT-4001100 O
lr
F
L-867 LIGHT FIXTURE OR 1/4" THICK
BLANK PLATE AND NEOPRENE GASKET
EXTERIOR THREADED GROUND LUG
ATTACHMENT
APPROXIMATE 4" CONCRETE SURROUND
CAST -IN-PLACE OR PRECAST
#6 AWG BARE COPPER �\
SAFETY GROUND
5/8" z 8' MIN GROUND / °
ROD, SECURE TO �
GROUND WIRE VIA
EXOTHERMIC WELD
INTERIOR THREADED GROUND LUG ATTACHMENT
STAINLESS STEEL BOLTS WITH ANTI -SEIZE COMPOUND #10 AWG STRANDED SEE SPECIFICATION REQUIREMENTS
BOND TO METAL UD FOR HANDHOLE SELECTION
12' OF CABLE NEATLY COILED
IN TURF AREAS, �¢ IN HANDHOLE
GRADE AWAY g PLACE SEALANT BETWEEN LID AND
FROM HH BOX FOR 2 -PIECE CONSTRUCTION
L-867 BASE CAN, CLASS 1, SIZE B 24"
HIGH, UNLESS NOTED OTHERWISE.^ y/ a GRS OR PVC CONDUITS AS REQ'D.
° - 2 -WAY OR 3 -WAY AS REQUIRED. IF TERM -A -DUCTS NOT USED:
GROUT AROUND INCOMING CONDUITS
FOR WALL
\� o BUSHINGS ON GRS. PENETRATIONS.PROVIDE
a / THREADED HUB BELL
X� `_. \�� 2" PVC SCH. 40
1, 2, OR 3 ... _
CONNECTIONS AS / \/ 2/ MIN C�OMPAOCTEDIN LE
DRAIN
REQUIRED OR NOTED
�GRAVEL OR SAND
TYPICAL L-887 BASE CAN DETAIL 1
SCALE: NTS E4.0
2" DEEP DRAIN GRAVEL,
COMPACTED
COMPACT NATIVE SOIL WITH
VIBRATORY PLATE
V GROUND ROD, 5/8" x 8',
EXTEND 6" ABOVE
HANDHOLE FLOOR
TYPICAL HANDHOLE DETAIL 2
SCALE: NTS E4.0
l COMPACTED
BACKFILL
PLASTIC WARNING
TAPE BURIED 6"
ABOVE CONDUIT
SAND BACKFILL
2" SCHED. 40 PVC
CONDUIT UNO BURIED
18" MINIMUM, OR
AS NOTED
2" SAND BEDDING
CLEARANCE, PARALLEL OR CROSSING, 6"
FROM ELECTRICAL, 12" FROM
TELEPHONE/GAS/WATER MINIMUM -
TYPICAL SINGLE
BURIED CONDUIT DETAIL 3
SCALE: NTS E4.0
RESTORE PAVING TO
MATCH EXISTING
`PLASTIC WARNING TAPE
18.0" MIN
RESTORE PAVING TO �� j� COMPACTED CRUSHED
BACKFILL
MATCH EXISTING 30" AGGREGATE P-209
CONCRETE ENCASEMENT P610
TAPLASTIC WARNING /RIED 6//\\� � \�// 3.0"
ABOVE CONDUIT 5,p� PLASTIC WARNING TAPE NOTE.
SAND BACKFILL 3'0SCID 40 PVC CONDUIT: BURIED 21.0" MIN. DUCTBANK IS
18.0" MIN SAND BEDDING SURROUNDED BY CONCRETE
6 \� COMPACTED CRUSHED 3.0" 3.0" (3.0" MIN). INDIVIDUAL CONDUITS SEPARATED FROM EACH
2" SCHED. 40 PVC TE P-209 OTHER BY 2.0" MIN (TYP ALL DIRECTIONS). CONDUIT SIZE
CONDUIT BURIED 18" 3.0" R- NOTED ON PLANS.
MINIMUM, OR AS CONCRETE ENCASEMENT P610
NOTED 2" SPACING MINIMUM FOR SAME VOLTAGE,
2" SAND BEDDING 3.0" 6" SPACING MINIMUM FOR DIFFERENT VOLTAGE
CLEARANCE, PARALLEL OR r NOTE: SERVICE
CROSSING, 6" FROM ELECTRICAL, 3'O" SCHD 40 PVC CONDUIT: BURIED 21.0" MIN.
2" SPACING MINIMUM FOR SAME VOLTAGE, SAND BEDDING DUCTBANK IS SURROUNDED BY CONCRETE 30 MIN).TYPICAL MULTIPLE CONCRETE
12" FROM TELEPHONE/GAS/WATER (
MINIMUM SERVICE IVIG MINIMUM FOR DIFFERENT VOLTAGE 3.0" 3.0" CONDUIT SIZE NOTED ON PLANS. ENCASED DUCTBANK DETAIL B
SCALE: NTS E4.0
TYPICAL MULTIPLE
BURIED CONDUIT DETAIL 4
SCALE: NTS E4.0
FRANGIBLE COUPLING
AND DISCONNECT PLUG -
ELEVATED BASE PLATE THREADED
UGHT GROUND LUG ATTACHMENT
L-867 BASE PLATE
#6 600V GREEN
INSULATED, TYP.
L-823 PRIMARY
CONNECTOR -
°
L-867 BASE CAN,10
EXISTING OR NEW E4.0
PROVIDE 3' SLACK MIN.
FOR ALL CONNECTIONS
NEW TRANSFORMER, SIZE
AS REQUIRED BY
MANUFACTURER
TRANSFORMER SUPPORT
STAND
TYPICAL LIGHT DETAIL 7
SCALE: NTS E4.0
TYPICAL SINGLE CONCRETE
ENCASED DUCTBANK DETAIL 5
SCALE: NTS E4.0
1/2" CHAMFER
4'
4" 4-
4'
g" DUCT MARKERS TO HAVE
DIRECTION ARROWS AS
24" REQUIRED TO REFLECT
4" DUCT INSTALLATION.
q" n
# — X 1/2" WIDE X 1/4" DEEP
INSCRIPTION (TYP.)
f INDICATES QUANTITY
24" ------- X INDICATES SIZE
TYPICAL DUCT MARKER DETAIL 8
SCALE: NTS E4.0
PROVIDE WEDGE UNDER FIXTURE OR BLANK LID TO
PROTECT CABLE
PROVIDE SPIRAL WRAPPED WARNING TAPE OR TAPE
FLAGS 10' O.C., FULL EXPOSED LENGTH
PROVIDE CONDUIT OR PIPE WHERE EXPOSED TO
TRAFFIC, PVC OR HDPE FOR FOOT TRAFFIC, STEEL
FOR VEHICLE TRAFFIC
L-824 5KV CABLE, NEW, USED, OR
SALVAGED, #8 OR #6 AWG
SPLICE IN TRENCH
L-823 PRIMARY CONNECTOR
— EXISTING LIGHT, SIGN, OR HH
TEMPORARY AIRFIELD
CABLE DETAIL 9
SCALE: NTS E4.0
CALL 48 HOURS
BEFORE YOU DIG
1-800-424-5555
NOTE:- .L
IF "L" DOES NOT MEASURE 1"
ADJUST SCALES ACCORDINGLY.
T-400110 R-400159
Z
O
rc
8
6
z
�§
Rt
Lw
<_ zoilli
q�
WIWI
Z
Qz
ra
CO
05
^ s
LE
z
O
Q
F
c J
J
in
J =
F
W
�
W
�
U
z
O �
�
z
F
En
N
N
M
Q
0
U
z j
ir
w
o
w
J
W
U
O^
V)
SCALE AS
NOTED
`� DCR
SHEET "`
E4.0
H.
MFA
OF SlEm
DATE
JANUARY, 2013
"o` 23-2010-007