HomeMy WebLinkAboutS-393308Utility Specifications
Sanitary Sewer Notes and Specifications
THESE NOTES SHALL APPEAR ON PROJECTS FOR THE WASTEWATER UTILITY.
1. All work and work material shall be in conformance with the standards and specifications
of the City of Renton Planning/Building/Public Works Department and the latest edition
of the WSDOT/APWA Standards and Specifications, as approved and modified by the
City of Renton in the Renton Standard Plans & Specinca(Jons. A set of approved plans
shall be kept on site at all times during construction.
2. The hours of work in the street right of way shall be per City specifications on weekdays
unless otherwise approved in writing by the Planning/Building/Public Works Department.
An approved traffic control plan must be obtained prior to beginning any work within
public right of way.
3. All locations of existing utilities shown are approximate and it shall be the contractors
responsibility to verify the true and correct location so as to avoid damage or
disturbance.
4. A pre -construction Conference and a 24 hour notice shall be required prior to starting
new Construction. It shall be the contractor's responsibility to secure all necessary
permits prior to starting construction. (Inspection will be accomplished by a
representative of the City Of Renton.) It shall be the Contractors responsibility to notify
the Public Works inspector 24 hours in advance of backfilling all construction.
5. Contractor is solely responsible for the means, methods and sequences of construction
and for the Safety of workers and others on the Construction site.
6. It shall be the responsibility of the contractor to obtain street use and any other related
permits prior to any construction.
7. Plans approved by the City of Renton, Public Works Department shall take precedence
over all other plans.
8. A copy of these approved plans must be on the job site whenever Construction is in
progress.
9. The contractor shall provide the City of Renton with an as -built drawing of the sanitary
sewer system, which has been stamped and signed by a licensed professional engineer
or licensed professional surveyor.
10. Backfill shall be placed Equally on both sides of the pipe in layers with a loose average
depth of 6 inches, maximum depth of 8 inches, thoroughly tamping each layer to 95
percent of maximum density, These compacted layers must extend for one pipe
diameter on each side of the pipe or to the side of the trench. Materials to Complete the
fill over pipe shall be the same as described.
11. Open cut road crossings for utility trenches on existing traveled roadway shall be
backfilled with crushed rock and mechanically compacted unless otherwise approved by
12. Datum for Vertical Control shall be North American vertical Datum 1988 Meters, and for
Horizontal Control shall be North American Datum 1983/1991 Meters unless otherwise
approved by the City of Renton Public Works Department. Reference benchmark and
elevations are noted on the plans.
13. All disturbed areas shall be seeded and mulched or otherwise stabilized to the
satisfaction of the Department for the prevention of on-site erosion after the completion
of construction.
14. All pipe and appurtenances shall be laid on a properly prepared foundation in
accordance with the standards and Specfications of the City of Renton
Planning/Building/Public Works Department and the latest edition of the WSDOT/APWA
Standards and Specifications, as approved and modified by the City of Renton in the
Renton Standard Plans & Specifications. This shall include necessary leveling of the
trench bottom or the top of the foundation material, as well as placement and
compaction of required bedding material, to uniform grade so that the entire length of
the pipe will be supported on a uniformly dense, unyielding base. Pipe bedding shall be
pea gravel 6 inches above and below the pipe.
15. Sanitary sewer pipe shall be polyvinyl chloride (PVC) rubber gasketed ASTM D 3034,
SDR 35, or ductile iron class 50, unless otherwise approved by the Wastewater Utility.
16. In unimproved areas, manhole to extend minimum 6 inches and maximum 12 inches
above finished grade or must have minimum T diameter concrete Ting poured at grade.
In paved area, cover must slope in all directions to match paving.
7'
L
T_
PORTION OF THE NE 1/4 OF THE NW 1/4
SECTION 14, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M.
CITY OF RENTON, STATE OF WASHINGTON
NOT TO SCALE
MANHOLE FRAIE Alp COVER
SEE Sm. PLAN til
ADaXSl]ENT RINGS (2" MIN.)
SEE MOM 6
MORTAR JpNT(S) (3/6' MMI.)
SEE NOTE 5
CONE (ECCENTRIC)
MIBBER GASKETED MNTS IN
ACCORDANCE WITH ASM C -N3
STEPS - POLYPROPYLENE STEPS
SHALL K INCLUDED
CONCRETE RISER BY PIPE INC.,
TRY APPFIOIiD EQUAL,
LADDER-POIWROPULDNE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIS -'C
CONCRETE SHELF
PRECAST BASE SECTION
OR CAST IN SHELF.
'A' IS. 'C' 'D'I E'
48" MH 46" 6' MIN. 5 -MIN 24' MIN. 21' LD.
54" MH 59' 8"
MIN. $ 5 MIN 24" MIN 24` D
60' MH 60" 18"
MIK 42" MIN 30 1.0. 1
NOTES,
I. STEPS To BE POLYPROPYLENE SAFETY STEPS,
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASING SHALL BE PER STD. PLAN 401.
4. MANHOLE YCIIONS TO BE OF REINFORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, SPOKE AND CASING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASING To GRADE SHALL RE ACCOMPLISHED WITH A COMBINATION OF
ADJUSTMENT RINGS. BRICKS AND MORTAR Q(LG BRIMS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1/2 BOND. THE USE OF SHIMS IN PROHIBITED
7. SANITARY SEWER MANHOLES SHALL HAW ALL INTERIOR SURFACES, INCLUDING CHANNEUNG,
COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASBER MC-AROSHIELD OR
APPROVED EQUAL', COLOR O COATING SHALL BE MIT.
B. RUBBER GAWETED JOINTS SHALL BE IN CONFORMANCE 'MM ASTM C-443,
9, CHANNEL HEIGHT SHALL RE A MINIMUM OF 3/4 IY THE INSIDE DIAMETER OF THE LARGEST PIPE.
10. CONNECTONS TO MANHOLE SHALL BE MADE USING OPK ADAPTOR, KOR-N-SEAL BOOTS OR
APPROVED EQUAL
11, IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM of IY
ABOVE FINISHED GRADE OR MUST HAW A MINIMUM T DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS, CO ER MUST SLOPE IN ALL DIRECTIONS To MATCH PAYING.
4 jR PUBLIC WORKS @1D. PIJM - lOp]
// DEPARTMENT STANDARD SANITARY MANHOLE
sEPTEMeEa eou
SEAL WIN AN 4000 OR APPROVED
MAL AND CRY SAID AFTER PLAN
PATCH NG NTS
]'-P
] PLL JOIMB BETWEEN TXECONE, I➢JO511%1lFMNG•v,
WNVDE VA
BRIMS AM FRAME SHALL LSIR 11®
l'-P�
CLASSDEPTH OF
ASPHALT TOBE2 BBi
0 AOJOTMEMOF THE FRMIETONRPEF BNM3 BE
HA.1.
ACLOMI.IS,IEll WIRE ACIXARINTNHO AOp6TNEM
RINGS. 9RICK4 AND Nomm 9_Y BIUM WALLED
3. RERACE EXCAVATED MATERIAL WIMAMINIMUM OF POF
BOTOM OF THE UPPER
CLASS W ASPHALT OR TO A DEPTH TUT IS T BKOW THE
ORC OF WMRbFRONRRFHj.
MOTION OF THE UPPER ADJUS11I RING WHICHEVER
OREATFA ORAS AARTYED S V THE FNGIAEER
MTNSLWNT FKU ON A
MINIMUM Or 6" WHICHENR
Is CHRATER
MORTAR .p'NT(6) O/a'
NN) YE
ADJUST. NT NTNG (I- MN.) OR
NOTE 3 AND SPECIN. PROMSo
BRIMS SEE NOW 4
7 -Dain
S`C-ON A -A
1. REMOVEPA%MEMAWAMEM MRI.LLBFORAOMTMCE
] PLL JOIMB BETWEEN TXECONE, I➢JO511%1lFMNG•v,
WHICH IS EIXVI TO THE ONMETER OF THE FUME PUe FOUR
BRIMS AM FRAME SHALL LSIR 11®
FEET. ADlN8i G5TN6FUME TD PAT£MEM BIHLFK£
USING Mass RINGS ON CONCRETE BLCCNs PER TO RAN
0 AOJOTMEMOF THE FRMIETONRPEF BNM3 BE
HA.1.
ACLOMI.IS,IEll WIRE ACIXARINTNHO AOp6TNEM
RINGS. 9RICK4 AND Nomm 9_Y BIUM WALLED
3. RERACE EXCAVATED MATERIAL WIMAMINIMUM OF POF
STAGAMED TO CREATE A RUN NING p'ND OR 12 BCM THIS
CLASS W ASPHALT OR TO A DEPTH TUT IS T BKOW THE
ORC OF WMRbFRONRRFHj.
MOTION OF THE UPPER ADJUS11I RING WHICHEVER
OREATFA ORAS AARTYED S V THE FNGIAEER
PUBLIC WORKS TYPICAL UTILITY COVER - -
DEPARTMP.NT ADAYETMENT FOR
PAVEMENT OR OVERLAY Y MINtI i
"AS -BUILT" NOTE:
"AS—BUILT" IS BASED ON A ACTUAL FIELD SURVEY
BY TOUMA ENGINEERS AND INFORMATION SUPPLIED
BY CONTRACTOR. C1 60068 2
=j�TOUMA ENGINEERS AND T00�"RAN SCALE I"�"NoISM"'r4m)
CITY OF NE 2nd ST SEWER EXTENSION 1e
FIRMS
LSLAND SURVEYORS]PLLC Mw.E , RENTON SEWER DETAILS
255 SW 41st STREET � RENTON, WA 98057 MRu INHT a NAIL slard Plonning/Building/Public Works Dept. 9
PHONE (425) 251-0665 FAX (425) 251-0625 TAX LOT #142305-9092
NO. REVISION BY DATE APPR +^E*R'NONE
S-393308