HomeMy WebLinkAboutW-425512Z ti O Z O M v m PROFILE MATERIALS OA TEE MAIN LINE TEE WITH 4" SIDE OUTLET (MJxFL) WITH PLUG (MJ) 4" GATE VALVE WITH 2" SQUARE OPERATING NUT AND VALVE OPERATING NUT EXTENSION AS REQUIRED OB GATE VALVE PER STD PLAN 330.1 OC VALVE BOX AND LID VALVE BOX AND LID PER STD PLAN 330.8 OD FLANGE 4"x2" TAPPED FLANGE (FLxFIPT) OE PIPE 2" BRASS OR BRONZE NIPPLE, LENGTH TO FIT OF BEND 2" 90° BRASS BEND (FIPT x PACK JOINT), FORD C14-77-Q-NL OR EQUAL OG ADAPTER 2"x2 Y2" BRASS ADAPTER (FIPTxMNST) C CAP 2 Y2" CAP (FNST) WITH GASKET, NOT VENTED METER BOX, ARMORCAST A6001640PCX18, WITH METER BOX LID, ARMORCAST A6001947RCI-H7, TO READ OI METER BOX AND LID "RENTON WATER", EXPANSION JOINTS MUST BE INSTALLED 12" MINIMUM ON BOTH SIDES OF METER BOX O BLOCKING CONCRETE BLOCKING PER STD PLAN 330.1 STD. PLAN - 340.1 •• PUBLIC WORKS 2" BLOW -OFF ASSEMBLY APPROVED: "` DEPARTMENT (PERMANENT) 6/28/2( Martin Pastwh, DATE Public Works Adminirtra°r a a a EXISTING WATER MAIN 8,+ TESTING CONNECTION POLYPIG STATION PER STD PLAN 300.7 (1) VERTICAL CROSS (MJxFL) (1) BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG (1) BLIND FLANGE ON BOTTOM (1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY WITH TEMPORARY THRUST BLOCKING TEMPORARY BLOCKING NEW DI WATER MAIN CONNECTION TO EXISTING MAIN (BY CITY FORCES) (1) TEE (MJxFL) (2) DI SPOOLS (2) LONG BODY DI SLEEVES (MJ) OR COUPLING ADAPTERS (ROMAC 501 OR EQUAL) (2) GATE VALVES (FLxMJ) (1) ADAPTER (FLxMJ) (1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY WITH CONCRETE THRUST BLOCKING PER STD PLAN 330.1 FINAL CONNECTION UPON COMPLETION OF POLYPIGGING, HYDROSTATIC TESTING, AND DISINFECTION, REMOVE TEMPORARY THRUST BLOCKING AND TEMPORARY BLOW -OFF ASSEMBLIES FINAL CONNECTION (BY CITY FORCES) (2) DI SPOOLS (1) LONG BODY DI SLEEVE (MJ) NEW DI WATER MAIN NOTES: 1. ALL CONNECTIONS TO EXISTING WATER MAINS WILL BE CONDUCTED BY CITY FORCES AS SPECIFIED IN SECTION 5-14.2 OF THE CITY OF RENTON WATER UTILITY CONSTRUCTION STANDARDS 2. LONG BODY DI SLEEVE FOR CONNECTION FROM DI TO DI PIPE AND FROM DI TO CI PIPE WITH SAME OUTSIDE DIAMETER 3. COUPLING ADAPTORS FOR CONNECTION FROM DI TO CI PIPE WITH DIFFERENT O.D. AND FROM DI TO AC OR TO STEEL PIPE PUBLIC WORKS CONNECTION TO WATER MAIN DEPARTMENT CUT -IN TEE AND TWO VALVES STD. PLAN - 300.2 DATE METERED BACKFLOW ASSEMBLY (TO BE OBTAINED FROM CITY) (1) 21/2" CONTROL VALVE (1) CONSTRUCTION METER (1) RPBA METER SUPPORT (BY CONTRACTOR) NSF 61 SUPPLY HOSE HYDRANT ON EXISTING WATER MAIN TEMPORARY BLOW -OFF ASSEMBLY (1) 2" GALVANIZED PIPE (1) 2" 90° BEND (1) 2" GATE VALVE II POLYPIG POLYPIG STATION (1) VERTICAL CROSS (MJxFL), SIZE TO MATCH WATER MAIN (1) BLIND FLANGE WITH 2" TAP ON TOP OF CROSS (1) TEMPORARY BLOW -OFF ASSEMBLY (1) BLIND FLANGE ON BOTTOM OF CROSS (1) PLUG (MJ) ON END OF CROSS WITH TEMPORARY THRUST BLOCKING NOTES: 1. THE BACKFLOW PREVENTION ASSEMBLY AND SUPPLY HOSE MUST BE DISCONNECTED DURING HYDROSTATIC PRESSURE TESTING OF THE NEW WATER MAIN. 2. POLYPIG AND ALL DEBRIS SHALL BE REMOVED FROM SUMP OF VERTICAL CROSS VIA SANITARY METHOD PRIOR TO DISINFECTION OF NEW WATER MAIN. 3. UPON REMOVAL OF POLYPIG, REMOVE TEMPORARY BLOW -OFF ASSEMBLY AND INSTALL 2" PLUG. 4. THE NEW WATER MAIN SHALL BE CONNECTED TO THE EXISTING SYSTEM ONLY AFTER NEW WATER MAIN IS POLYPIGGED, DISINFECTED AND SATISFACTORY BACTERIOLOGICAL SAMPLE RESULTS ARE OBTAINED. 5. THE INTERIORS OF ALL PIPES AND FITTINGS TO BE USED IN FINAL CONNECTION MUST BE SWABBED OR SPRAYED WITH A 5-6% AVAILABLE CHLORINE SOLUTION. STD. PLAN - 300.7 PUBLIC WORKS APPROVED: DEPARTMENT POLYPIGGING NEW WATER MAINS 6/28/2023 Mahn Pastuch" DATE Pnehr work: namm:v"« WATER PLAN GENERAL NOTES Standard Plan No. 300 1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CITY OF RENTON PUBLIC WORKS STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION. 2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION. 3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND "CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF RENTON PRIOR TO BRINGING ANY MATERIALS ON -SITE. 4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND C 104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS PER ANSI/AWWA C110/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE, POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS. 5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS AND 48 INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60 INCHES. ANY DEVIATIONS MUST BE APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFLICTS OCCUR, THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER. PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST METHOD (MDD) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MDD. 6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAY BE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO CONCRETE BLOCKING. 7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIOR TO BEING FLUSHED, DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND REMOVE PLUGS, CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT / BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITYTESTING. 8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP DURING THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, FLUSHED, AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR. 9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION. ti�Y o STD. PLAN - 300.0 a� PUBLIC WORKS WATER PLAN GENERAL NOTES DEPARTMENT MARCH 2O10 F NCO UNDERGROUND LOCATOR SERVICE CALL BEFORE YOU DIG! 8/ NO. 1114' AND 22 Y2 ° BENDS FPIPE CLAMP AND ANCHOR ROD i A _A 45' BEND PIPE CLAMP AND ANCHOR ROD oL L�`� yp va o A A 90° BEND PIPE CLAMP AND ANCHOR ROD MINIMUM DIMENSIONS PIPE SIZE BEND VOLUME (CF) A D L 4" 11 Y4 BLOCKING NOT REQUIRED 22 Y2* 45° 90° 16 2.5' 3/4' 2.0' 11 Y4 BLOCKING NOT REQUIRED 22 Y2' 6" 45° 13 2.3' %11 2.0' 90° 43 3.5' %11 2.0' 11 Ya° BLOCKING NOT REQUIRED 221/z° 8" 45° 33 3.2' 3/4" 2.0' 90° 86 4.4' 3j4' 2.0' 11Y/4° BLOCKING NOT REQUIRED 10" 22 YZ 13 2.3' 3j4' 2.0' 45° 64 4.0' %11 2.0' 90° 141 5.2' 1" 3.5' 11 Ya BLOCKING NOT REQUIRED 22 Y2* 20 2.7' 3/q' 2.0' 12" 45° 111 4.8' 3/q" 2.0' 90° 206 5.9' 1 Y$' 4.0' * D =ANCHOR ROD DIAMETER MINIMUM DIMENSIONS BASED ON FOLLOWING CONDITIONS: • PIPE RESTRAINED MINIMUM 36' ON EACH SIDE OF BEND • SAFE BEARING LOAD = 1,000 SF L • CONCRETE STRENGTH = 3,000 PSI • CONCRETE WEIGHT = 150 PCF A • HYDROSTATIC PRESSURE = 200 PSI • TRENCH = TYPE 2 FLAT BOTTOM TRENCH WITH LIGHTLY CONSOLIDATED BACKFILL PER ANSI/AWWA C150/A21.50 L ° ' • FACTOR OF SAFETY = 1.5 • SOIL FRICTIONAL RESISTANCE BASED ON COHESIVE I_ -I GRANULAR SOIL (GC+SC), SAND, GRAVEL, CLAY MIXTURE f A CONCRETE BLOCKING DESIGN MUST BE ADJUSTED FOR NOTES: VARIANCES IN ANY OF THESE CONDITIONS. 1. NO CHANGE IN PIPE DIRECTION OR DIAMETER SHALL OCCUR WITHIN 36' OF THE VERTICAL BEND. BENDS, TEES, REDUCERS, ETC. BEYOND THE 36' LIMIT MAY BE RESTRAINED BY STANDARD CONCRETE BLOCKING PER STD PLANS 330.1 AND 330.2. 2. FITTINGS SHALL BE POLYWRAPPED AFTER INSTALLATION OF PIPE CLAMPS AND ANCHOR RODS PRIOR TO POURING CONCRETE BLOCKING. 3. PIPE CLAMPS AND ANCHOR RODS SHALL BE INSTALLED PER STD PLAN 330.4. 4. JOINT RESTRAINT SHALL BE MEGALUG SERIES 1100 OR EQUAL. 5. WATER MAIN SHALL NOT BE PRESSURIZED UNTIL ALL TRENCHING WITHIN 100' OF VERTICAL BEND IS BACKFILLED AND COMPACTED TO MINIMUM T COVER. 6. 90° VERTICAL BENDS SHALL ONLY BE INSTALLED WHERE GIVEN PRIOR APPROVAL BY THE CITY. 7. ALL CONCRETE SHALL BE MECHANICALLY MIXED. JOB SITE MIXING, HAND -MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT ALLOWED. 8. BACKFILL TRENCH BEYOND 90° VERTICAL BLOCK WITH CRUSHED SURFACING TOP COURSE MATERIAL COMPACTED TO 95% MDD. CRUSHED BACKFILL SHALL EXTEND 20' BEYOND BLOCK OR TO FIRM BEARING TRENCH WALL, WHICHEVER IS LESS. 9. CONCRETE BLOCKING SHALL BE LEFT OPEN OR SHEETED FOR MINIMUM 24 HOURS. SURVEYED: 8Y OTHERS DESIGNED: ROLL/ HEA VR/N DRAWN: MARY MOORS CHECKED: HOLL/ HEA VR/N BY DATE APPR APPROVED: HOLL/ HEA VR/N CONCRETE BLOCKING STD. PLAN - 330.3 PUBLIC WORKS APPROVED: DEPARTMENT FOR VERTICAL FITTINGS WITH RESTRAINED JOINTS 6/28/z( o ei:"w�:i,: enm„.r.,..,. DATE 4.2.1 PIPE SYSTEMS -DESIGN CRITERIA FIGURE 4.2.1.B PIPE ANCHOR DETAIL A�111,-1_ 6n MiN 2'M/ry i e.v. a _ CONCRETE BLOCK A CONCRETE BLOCK ANCHOR vie v.. o e`o_ p v p v P. v CONCRETE SECTION A -A FOOTING NTS KEYEDINTO UNDISTURBED SOIL AS SHOWN 2021 Surface Water Design Manual SCALE: AS NOTED ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY C5 6" MIN. STRAP -FOOTING ANCHOR -(TYPICAL) NTS z 6" MIN. A NOTE: FOR SOLID WALL HDPE, PIPE MUST BE FREE TO SLIDE INSIDE A 4' LONG SECTION OF PIPE ONE SIZE DIAMETER LARGER. 6" MIN. v .. . hr�`a Yr. VMIN. kiv .'v11v 2 x PIPE DIA. r MIN. SECTION B-B NTS VERnCAL• NAVD 1988 HORIZONTAL: NAD 1983/1991 DATUM 4-15 1" MIN. DIAMETER STEEL ROD (STRAP) CLAMPED SECURELY TO PIPE. CONCRETE FOOTING KEYEDINTO UNDISTURBED SOIL AS SHOWN 7/23/2021 CITY OF RENTON Planning/Building/Public Works Dept. 5/S/25 CIVIL ENGINEERING LANDSCAPE ARCHITECTURE 'Con PLANNING �zw� DESIGN SURVEYING 12100 NE 195th St, Suite 300 Bothell, Washington 98011 425.885.7877 W-425512 IN COMPLIANCE WITH CITY OF RENTON STANDARDS TOWNS ON 12TH 3916 & 3926 NE 12TH ST, RENTON, WA 98056 WA TER STANDARD DETAILS O O O DATE: O FI0/111202J ELOBo PAGE: DRAWING NO: C6.32 SHEET: OF, 59 93 CONSTRUCTION RECORD DRA WINGS