HomeMy WebLinkAboutCAG-24-060 Bid Manual Volume II (Plans)WINDSOR HILLS UTILITY IMPROVEMENTS PROJECT
CITY PROJECT: 27-04186
MARCH 2024
COPYRIGHT © 2024 BHC CONSULTANTS, LLC. ALL RIGHTS RESERVEDPath: S:\Cad\Renton\22-10795 Windsor Hills\Design\d Filename: P22-10795_G-1 Plot date: Mar 07, 2024-02:58:10pm CAD User: acariaso. Xref Filename: | X22-10795_Status |G-1
85of1
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.comKING COUNTY
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
DUANE HARTMAN & ASSOCIATES INC. - SURVEY
ASPECT CONSULTING, LLC - GEOTECHNICAL
TENW - TRAFFIC CONTROL AND SURFACE RESTORATION
KING COUNTY
PROJECT LOCATION
405
5
Seattle
Redmond
2
522
90
202
18
169
167
Skykomish
Maple Valley
Bellevue
Renton PREPARED BY:
IN ASSOCIATION WITH:
LOCATION MAP VICINITY MAP
520
NTS NTS
PROJECT MANAGER
KATIE MEDINA, P.E. Kmedina@rentonwa.gov 425-430-7335
JARED McDONALD, P.E. Jmcdonald@rentonwa.gov 425-430-7293
CITY OF RENTON
NE 4TH STW I N D S O R W A Y N E
B R O N S O N W A Y N EGRANDEY W A Y
B R O N S O N PLNEWINDSOR PL NEEDMONDS AVE NEI-405S U N S E T B L V D N E
BRONSON WAY NE
B R O N SO NW A Y N EPROJECT
LOCATION
Bid Documents
Volume 2 of 2
CAG-24-060
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-2.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
INDEX OF DRAWINGS G-2
2 86
M. McCrosky, P.E.
P. Simon
R. Dorn, P.E.
R. Ochiltree, P.E.
N/A
27-04186
INDEX OF DRAWINGS
SHEET
NO.DRAWING TITLEDWG
NO.
GENERAL
1 G-1 COVER SHEET AND VICINITY MAP
2 G-2 INDEX OF DRAWINGS
3 G-3 GENERAL AND SURFACE WATER DRAINAGE NOTES
4 G-4 WATER AND WASTEWATER NOTES
5 G-5 LEGENDS AND ABBREVIATIONS
6 G-6 SURVEY CONTROL AND NOTES
7 G-7 ALIGNMENT TABLES 1 OF 2
8 G-8 ALIGNMENT TABLES 2 OF 2
9 G-9 EROSION CONTROL KEY PLAN
10 G-10 WATER KEY PLAN
11 G-11 STORMWATER KEY PLAN
12 G-12 CONSTRUCTION SEQUENCING, GENERAL REQUIREMENTS, AND POTHOLING DATA
13 G-13 TRENCH DAM DETAIL
EROSION CONTROL
14 EC-1 TESC NOTES
15 EC-2 BRONSON WAY NE TESC PLANS STA 1+00 TO 8+25
16 EC-3 BRONSON WAY NE TESC PLANS STA 8+25 TO 17+50
17 EC-4 BRONSON WAY NE TESC PLAN STA 17+50 TO 22+50 GRANDEY WAY TESC PLAN STA 29+80 TO 34+00
18 EC-5 GRANDEY WAY TESC PLANS STA 34+00 TO 42+50
19 EC-6 GRANDEY WAY TESC PLAN STA 42+50 TO 47+00 BRONSON PLACE NE TESC PLAN STA 80+00 TO 83+25
20 EC-7 BRONSON PLACE NE TESC PLAN STA 54+00 TO 57+50 WINDSOR PLACE NE TESC PLAN STA 80+00 TO 83+25
21 EC-8 WINDSOR PLACE NE TESC PLAN STA 83+25 TO 88+01 WINDSOR WAY NE TESC PLAN STA 60+00 TO 64+50
22 EC-9 WINDSOR WAY NE TESC PLANS STA 64+50 TO 73+50
23 EC-10 WINDSOR PLACE NE TESC PLAN STA 73+50 TO 75+76 BRONSON WAY NE TESC PLAN STA 800+00 TO 802+10
24 EC-11 DITCH TESC PLAN
WATER
25 W-1 BRONSON WAY NE WATER MAIN PLAN AND PROFILE STA 0+80 TO 4+50
26 W-2 BRONSON WAY NE WATER MAIN PLAN AND PROFILE STA 4+50 TO 8+25
27 W-3 BRONSON WAY NE WATER MAIN PLAN AND PROFILE STA 8+25 TO 13+00
28 W-4 BRONSON WAY NE WATER MAIN PLAN AND PROFILE STA 13+00 TO 17+50
29 W-5 BRONSON WAY NE WATER MAIN PLAN AND PROFILE STA 17+50 TO 22+50
30 W-6 GRANDEY WAY NE WATER MAIN PLAN AND PROFILE STA 29+80 TO 34+00
31 W-7 GRANDEY WAY NE WATER MAIN PLAN AND PROFILE STA 34+00 TO 38+50
32 W-8 GRANDEY WAY NE WATER MAIN PLAN AND PROFILE STA 38+50 TO 42+50
33 W-9 GRANDEY WAY NE WATER MAIN PLAN AND PROFILE STA 42+50 TO 47+00
34 W-10 BRONSON PL NE WATER MAIN PLAN AND PROFILE STA 49+80 TO 54+00
35 W-11 BRONSON PL NE WATER MAIN PLAN AND PROFILE STA 54+00 TO 57+50
36 W-12 WINDSOR PL NE WATER MAIN PLAN AND PROFILE STA 79+80 TO 83+25
37 W-13 WINDSOR PL NE WATER MAIN PLAN AND PROFILE STA 83+25 TO 88+00
38 W-14 WINDSOR WAY NE WATER MAIN PLAN AND PROFILE STA 59+80 TO 64+50
39 W-15 WINDSOR WAY NE WATER MAIN PLAN AND PROFILE STA 64+50 TO 69+50
40 W-16 WINDSOR WAY NE WATER MAIN PLAN AND PROFILE STA 69+50 TO 73+50
41 W-17 WINDSOR WAY NE WATER MAIN PLAN AND PROFILE STA 73+50 TO 75+76
42 W-18 VUEMONT PL NE WATER MAIN STA 700+00 TO 702+00
43 W-19 1" WATER SERVICE CONNECTION DETAILS FOR 5/8" x 3/4" AND 1" METERS
44 W-20 WATER SERVICE CONNECTION DETAILS FOR 1 1/2" METER
45 W-21 1 1/2" METER MATERIAL LIST
46 W-22 WATER MAIN CONNECTIONS DETAILS
47 W-23 WATER MAIN POLYPIGGING PLAN
STORMWATER
48 SD-1 BRONSON WAY NE STORM DRAIN PLAN AND PROFILE STA 1+00 TO 4+50
49 SD-2 BRONSON WAY NE STA 4+50 TO 8+25
50 SD-3 BRONSON WAY NE STA 8+25 TO 13+00
51 SD-4 BRONSON WAY NE STA14+25 TO 18+50
52 SD-5 BRONSON WAY NE STA17+50 TO 22+50
53 SD-6 GRANDEY WAY NE STA 30+00 TO 34+00
54 SD-7 GRANDEY WAY NE STA 8+00 TO 13+00
55 SD-8 GRANDEY WAY NE STA 38+50 TO 42+50
56 SD-9 GRANDEY WAY NE STA 42+50 TO 47+00
57 SD-10 BRONSON PL NE STA 80+00 TO 83+25
58 SD-11 BRONSON PL NE STA 54+00 TO 57+50
59 SD-12 WINDSOR PL NE STA 80+00 TO 83+25
60 SD-13 WINDSOR PL NE STA 83+25 TO 88+00
61 SD-14 WINDSOR WAY NE STA 60+00 TO 64+50
62 SD-15 WINDSOR WAY NE STA 64+50 TO 69+50
63 SD-16 WINDSOR WAY NE STA 69+50 TO 73+50
64 SD-17 WINDSOR WAY NE STA 73+50 TO 75+76
65 SD-18 VUEMONT PL NE STA 700+00 TO 702+00 AND STORM STRUCTURE TABLE
66 SD-19 GRANDEY WAY DITCH PLAN AND PROFILE
67 SD-20 BRONSON WAY NE DITCH PLAN AND PROFILE
68 SD-21 BRONSON WAY NE DITCH PLAN AND PROFILE
69 SD-22 STORMWATER DETAILS
RESTORATION
70 R-1 RESTORATION KEY PLAN
71 R-2 BRONSON WAY NE RESTORATION PLAN STA 1+00 TO 7+00
72 R-3 BRONSON WAY NE RESTORATION PLAN STA 7+00 TO 13+00
73 R-4 BRONSON WAY NE RESTORATION PLAN STA 13+00 TO 19+50
74 R-5 BRONSON WAY NE RESTORATION PLAN STA 19+50 TO 22+50
75 R-6 GRANDEY WAY NE RESTORATION PLAN STA 38+00 TO 44+50
76 R-7 GRANDEY WAY NE RESTORATION PLAN STA 31+50 TO 38+50
77 R-8 WINDSOR WAY NE RESTORATION PLAN STA 61+00 TO 67+00
78 R-9 WINDSOR WAY NE RESTORATION PLAN STA 67+00 TO 72+50
79 R-10 WINDSOR WAY NE RESTORATION PLAN STA 72+50 TO 76+00
80 R-11 WINDSOR PL NE RESTORATION PLAN STA 80+50 TO 84+00
81 R-12 BRONSON PL NE RESTORATION PLAN STA 51+00 TO 57+00
82 R-13 DRIVEWAY DETAILS
TRAFFIC CONTROL
83 TC-1 WINDSOR WAY NE TRAFFIC CONTROL PLAN
84 TC-2 WINDSOR PL & BRONSON PL NE TRAFFIC CONTROL PLAN
85 TC-3 BRONSON WAY NE TRAFFIC CONTROL PLAN
86 TC-4 GRANDEY WAY NE TRAFFIC CONTROL PLAN
SHEET
NO.DRAWING TITLEDWG
NO.
GENERAL NOTES SURFACE WATER DRAINAGE NOTES (CONT.)
SURFACE WATER DRAINAGE NOTES
1. NOT USED
2. NOT USED
3. ALL STORM DRAINAGE IMPROVEMENTS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE LATEST
EDITION OF THE CITY OF RENTON SURFACE WATER DESIGN MANUAL (RENTON SWDM), RENTON MUNICIPAL CODE
(RMC), AND THE STANDARD SPECIFICATIONS FOR ROAD, BRIDGE AND MUNICIPAL CONSTRUCTION PREPARED BY
WSDOT AND THE AMERICAN PUBLIC WORKS ASSOCIATION (APWA).
4. NOT USED
5. NOT USED
6. NOT USED
7. ALL UTILITY TRENCH BACKFILL AND ROADWAY SUBGRADE SHALL BE COMPACTED TO 95% MAXIMUM DRY DENSITY
PER SECTION 2-03.3(14)D - COMPACTION AND MOISTURE CONTROL TESTS OF THE WSDOT STANDARD
SPECIFICATIONS.
8. NOT USED.
9. ALL PIPE AND STRUCTURES SHALL BE STAKED FOR SURVEY LINE AND GRADE PRIOR TO THE START OF
CONSTRUCTION. WHERE SHOWN ON THE PLANS OR WHERE DIRECTED BY THE CITY, THE EXISTING MANHOLES,
CATCH BASINS, OR INLETS SHALL BE ADJUSTED TO THE GRADE AS STAKED.
10. NOT USED
11. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH THE
CURRENT STATE OF WASHINGTON STANDARD SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL
INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS
PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH
OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. ALL PIPE BEDDING AND BACKFILL
SHALL BE AS SHOWN ON THE CITY STANDARD PLAN 220.00, 220.10, AND 220.20.
12. NOT USED.
13. ALL DRAINAGE STRUCTURES SUCH AS CATCH BASINS AND MANHOLES SHALL BE FITTED WITH DUCTILE IRON,
BOLT-LOOKING LIDS PER THE CITY STANDARD PLAN 204.10, 204.20, 204.30, 204.40, AND 204.50. STRUCTURES SHALL
HAVE:
·RECTANGULAR OR ROUND, SOLID LIDS WHEN NOT COLLECTING RUNOFF, AND OUTSIDE OF THE ROADWAY.
·ROUND, SOLID LIDS WHEN NOT COLLECTING RUNOFF, AND LOCATED WITHIN THE ROADWAY, BUT OUTSIDE OF
THE CURB/GUTTER LINE.
·ROUND, SOLID LIDS DISPLAYING THE CITY LOGO WHEN WITHIN THE PUBLIC RIGHT-OF-WAY OR IN AN EASEMENT
TO THE CITY. PRIVATE STRUCTURE LIDS OUTSIDE PUBLIC RIGHT-OF-WAY AND EASEMENTS TO THE CITY SHALL
NOT DISPLAY THE CITY LOGO.
14. NOT USED
15. LIDS OF MANHOLES/CATCH BASINS WITHIN PUBLIC RIGHT-OF-WAY SHALL NOT BE ADJUSTED TO FINAL GRADE UNTIL
AFTER PAVING. ALL MANHOLE/CATCH BASINS RIMS SHALL BE ADJUSTED TO BE FLUSH WITH FINAL FINISHED GRADES,
UNLESS OTHERWISE SHOWN.
16. NOT USED.
17. ROCK FOR EROSION PROTECTION OF ROADSIDE DITCHES, WHERE REQUIRED, SHALL BE OF SOUND QUARRY ROCK
PLACED TO A MINIMUM DEPTH OF ONE (1) FOOT AND SHALL MEET THE FOLLOWING SPECIFICATIONS:
·4 - 8 INCH ROCK / 40 - 70% PASSING.
·2 - 4 INCH ROCK / 30 - 40% PASSING; AND
·LESS THAN 2 INCH ROCK / 10 - 20% PASSING.
18. NOT USED
19. THE END OF EACH STORM DRAIN STUB SHALL BE CAPPED. A CLEANOUT TOPPED WITH A BOLT-LOCKING LID MARKED
"STORM" OR "DRAIN" SHALL BE LOCATED AT THE PROPERTY LINE OR AT THE POINT OF CONNECTION OF A PRIVATE
STORM DRAINAGE CONVEYANCE SYSTEM PER THE CITY STANDARD PLAN 227.00.
20. ALL STORM SYSTEM EXTENSIONS SHALL BE STAKED FOR LINE AND GRADE BY A SURVEYOR LICENSED IN
WASHINGTON STATE, AND CUT SHEETS SHALL BE PROVIDED TO THE CITY PRIOR TO CONSTRUCTION.
21. ALL NEWLY-INSTALLED AND NEWLY-REHABILITATED (PUBLIC AND PRIVATE) STORM CONVEYANCE SYSTEMS SHALL
BE INSPECTED BY MEANS OF REMOTE CCTV ACCORDING TO THE CITY STANDARD PLAN 266.00. CCTV INSPECTIONS
AND REPORTS SHALL BE SUBMITTED TO THE CITY PRIOR TO RECEIVING APPROVAL TO INSTALL PROJECT CURBS,
GUTTERS AND/OR PAVEMENT.
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE
CITY OF RENTON PUBLIC WORKS DEPARTMENT AND THE 2023 EDITION OF THE WSDOT/APWA STANDARDS AND
SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS &
SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON WEEKDAYS UNLESS
OTHERWISE APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT, REFER TO SP 1-08.0(2).
3. THE CITY OF RENTON AND BHC CONSULTANTS, LLC ASSUME NO RESPONSIBILITY FOR EXISTING UTILITY LOCATIONS
AND ELEVATIONS. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION AND ELEVATION SO AS TO AVOID
DAMAGE OR DISTURBANCE PRIOR TO COMMENCEMENT OF ANY CONSTRUCTION. THE INFORMATION IS PROVIDED
FOR CONTRACTORS CONVENIENCE ONLY. THERE MAY BE DISCREPANCIES AND OMISSIONS.
4. BEFORE ANY CONSTRUCTION ACTIVITY OCCURS, THE CONTRACTOR SHALL MEET WITH THE CITY FOR A
PRE-CONSTRUCTION CONFERENCE. A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING CONSTRUCTION.
REFER TO SP 1-07.6 and 1-08.0(1).
5. THE CONTRACTOR SHALL FOLLOW CONSTRUCTION SEQUENCING AND GENERAL REQUIREMENTS ON DWG G-12. THE
CONTRACTOR MAY PROPOSE ALTERNATIVES FOR THE CITY'S APPROVAL.
6. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY IN ADVANCE OF BACKFILLING ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE OVER ALL
OTHER PLANS.
8. NOT USED.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS-BUILT DRAWING OF THE STORM, WATER, AND
SEWER IMPROVEMENTS, WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR
LICENSED PROFESSIONAL SURVEYOR, REFER TO SP 1-05.4
10. THE CONTRACTOR SHALL VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION BY CALLING THE
UNDERGROUND LOCATE LINE AT 1-800-424-5555 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION,
REFER TO SP 1-7.17
11. A PROJECT GEOTECHNICAL ENGINEERING REPORT IS AVAILABLE FOR CONTRACTOR REFERENCE AS NOTED IN THE
CONTRACT BIDDING DOCUMENTS.
12. OVERHEAD ELECTRICAL POWER, TELEPHONE, CABLE TV, AND OTHER OVERHEAD LINES ARE GENERALLY NOT
SHOWN. THE LINES THAT ARE SHOWN ARE LOCATED BY POINT-TO-POINT, POLE OR TOWER TO POLE OR TOWER.
DETERMINE THE EXTENT OF HAZARDS OR IMPACTS ON CONSTRUCTION ACTIVITIES CREATED BY OVERHEAD OR
UNDERGROUND ELECTRICAL POWER, TELEPHONE, CABLE TV, AND OTHER LINES IN ALL AREAS, AND FOLLOW
PROCEDURES DURING CONSTRUCTION AS REQUIRED BY LAW AND REGULATIONS. PRIOR TO CONSTRUCTION, MEET
WITH UTILITY OWNERS TO DETERMINE THE EXTENT OF HAZARDS AND TAKE WHATEVER PRECAUTIONS AND
REMEDIAL MEASURES THAT MAY BE REQUIRED TO PROTECT PERSONS AND PROPERTY AND TO AVOID DISRUPTION
OF SERVICE.
13. MANHOLES, CATCH BASINS, AND OTHER STRUCTURES ARE GENERALLY SHOWN ON PLAN AND PROFILE DRAWINGS
SYMBOLICALLY. CONSTRUCT MANHOLES, CATCH BASINS, AND OTHER STRUCTURES AS SHOWN ON DETAIL
DRAWINGS AND AS SPECIFIED.
14. ALL UTILITIES SHALL BE SUPPORTED AND MAINTAINED DURING CONSTRUCTION (INCLUDING THOSE IDENTIFIED AS
ABANDONED OR TO BE ABANDONED).
15. CONTRACTOR SHALL PROTECT PUBLIC AND PRIVATE PROPERTY. PROPERTY DISTURBED DURING CONSTRUCTION
TO BE RESTORED TO EXISTING CONDITIONS UNLESS OTHERWISE SPECIFIED BY THE CITY. THE CONTRACTOR IS
RESPONSIBLE FOR IDENTIFYING AND DOCUMENTING ANY DAMAGE THAT IS PRE-EXISTING OR CAUSED BY OTHERS.
REFER TO SS 1-07.16 AND SP 1-07.16.
16. PROTECTION OF THE ENVIRONMENT: NO CONSTRUCTION RELATED ACTIVITY SHALL CONTRIBUTE TO THE
DEGRADATION OF THE ENVIRONMENT, ALLOW MATERIAL TO ENTER SURFACE OR GROUND WATERS, OR ALLOW
PARTICULATE EMISSIONS TO THE ATMOSPHERE, WHICH EXCEED STATE OR FEDERAL STANDARDS. ANY ACTIONS
THAT POTENTIALLY ALLOW A DISCHARGE TO STATE WATERS MUST HAVE PRIOR APPROVAL OF THE STATE OF
WASHINGTON, DEPARTMENT OF ECOLOGY.
17. ALL DISTANCES SHOWN ON THE DRAWINGS AND DESCRIBED IN THE SPECIFICATIONS SHALL BE INTERPRETED TO REFER TO
THE HORIZONTALLY AND VERTICALLY PROJECTED PLANES UNLESS OTHERWISE INDICATED. LINEAL FOOTAGE OF PIPING
SHOWN ON THE DRAWINGS REFERS TO HORIZONTAL LENGTH. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE
STARTING WORK AND SHALL IMMEDIATELY NOTIFY THE ENGINEER OF ANY DISCREPANCIES.
18. SYSTEM OPERATION AND SERVICES SHALL BE MAINTAINED DURING CONSTRUCTION. SOME DWGS HAVE SPECIFIC
SEQUENCING REQUIREMENTS TO MAINTAIN SERVICE. SEE NOTE 12 ON DWG G-12.
19. ALL EXCAVATIONS ADJACENT TO POWER POLES OR OTHER RELATED FACILITIES (VAULTS, HANDHOLES, ETC.) SHALL COMPLY
WITH WAC 296-155, PART N, EXCAVATION, TRENCHING AND SHORING. POLE PROTECTION/ SUPPORTING SYSTEMS USED
WHILE EXCAVATING SHALL COMPLY WITH WAC 155-655 GENERAL PROTECTION REQUIREMENTS, ITEM (9) AND SHALL NOT
AFFECT THE STRUCTURAL INTEGRITY OF POLES WHILE THE SYSTEMS ARE IN PLACE OR AFTER THE SYSTEMS HAVE BEEN
REMOVED.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FULL RESTORATION OF ALL EXISTING FEATURES DISTURBED DURING
CONSTRUCTION TO THEIR ORIGINAL CONDITION UNLESS OTHERWISE INDICATED BY THE ENGINEER. ALL MATERIALS USED
FOR THE CONSTRUCTION SHALL BE NEW AND UNDAMAGED, AND CATALOG CUTS FOR ALL MATERIALS SHALL BE
APPROVED IN WRITING BY THE CITY PRIOR TO BRINGING ANY MATERIALS ON SITE.
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-3.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
GENERAL AND SURFACE WATER DRAINAGE
NOTES G-3
3 85
M. McCROSKY, P.E.
P. SIMON
R. OCHILTREE, P.E.
N/A
27-04186
22. ALL STORM SYSTEMS AND CONNECTIONS TO EXISTING MAINS SHALL BE TESTED IN ACCORDANCE WITH SECTION
7-04.3(1) OF THE WSDOT STANDARD SPECIFICATIONS AND IN THE THE PRESENCE OF A REPRESENTATIVE OF THE
CITY. STORM DRAIN STUBS SHALL BE TESTED FOR ACCEPTANCE AT THE SAME TIME THE MAIN STORM IS TESTED.
23. FOR ALL DISTURBED PERVIOUS AREAS (COMPACTED, GRADED, LANDSCAPED, ETC.) OF THE DEVELOPMENT
SITE, TO MAINTAIN THE MOISTURE CAPACITY OF THE SOIL EITHER STOCKPILE AND REDISTRIBUTE THE
EXISTING DUFF LAYER AND NATIVE TOPSOIL OR AMEND THE SOIL WITH COMPOST IN ACCORDANCE WITH
STANDARD PLAN 264.00.
24. ISSUANCE OF THE BUILDING OR CONSTRUCTION PERMITS BY THE CITY DOES NOT RELIEVE THE
CONTRACTOR OF THE CONTINUING LEGAL OBLIGATION AND/OR LIABILITY CONNECTED WITH STORMWATER
DISPOSAL. THE CITY DOES NOT ACCEPT ANY OBLIGATION FOR THE PROPER FUNCTIONING AND
MAINTENANCE OF THE STORM SYSTEM PROVIDED DURING CONSTRUCTION.
25. ADEQUATE SAFEGUARDS, SAFETY DEVICES, PROTECTIVE EQUIPMENT, FLAGGERS, AND ANY OTHER
ACTIONS NEEDED TO PROTECT THE LIFE, HEALTH, AND SAFETY OF THE PUBLIC, AND TO PROTECT
PROPERTY IN CONNECTION WITH THE PERFORMANCE OF WORK SHALL BE PROVIDED. ANY WORK WITHIN
THE TRAVELED RIGHT-OF-WAY THAT MAY INTERRUPT NORMAL TRAFFIC FLOW SHALL REQUIRE A TRAFFIC
CONTROL PLAN APPROVED BY THE CITY. ALL SECTIONS OF THE WSDOT STANDARD SPECIFICATIONS 1-10
TEMPORARY CONTROL SHALL APPLY.
26. PROJECTS LOCATED WITHIN THE CITY'S AQUIFER PROTECTION AREA (APA) SHALL COMPLY WITH SPECIAL
REQUIREMENT #6 OF THE RENTON SWDM AND AQUIFER PROTECTION REGULATIONS (RMC 4-3-050).
27. PLACEMENT OF SURFACE APPURTENANCES (CATCH BASIN/MANHOLE LIDS, CLEANOUTS, INLETS, ETC.) IN
THE STREET TRAVEL LANE WHEEL PATH, INTERSECTIONS OF SIDEWALK OR CROSSWALK SHALL BE FITTED
WITH A NON-SLIP OR NON-SKID LID PER ADA REQUIREMENTS.
28. NOT USED.
29. MINIMUM COVER OVER STORM DRAINAGE PIPE SHALL CONFORM TO TABLE 4.2.1.A2 OF THE RENTON SWDM.
30. NOT USED
GENERAL NOTES (CONT.)
21. THESE DRAWINGS AND THE IDEAS AND DESIGNS INCORPORATED HEREIN SHALL NOT BE USED, IN WHOLE OR IN
PART, FOR ANY OTHER PROJECT WITHOUT WRITTEN AUTHORIZATION OF CITY OF RENTON AND BHC
CONSULTANTS, LLC.
22. CITY OF RENTON AND WSDOT STD PLANS REFERENCED ON THE DWGS ARE INCLUDED IN THE CONTRACT BIDDING
DOCUMENTS. SOME RENTON STANDARD PLANS HAVE BEEN MODIFIED FOR THE PROJECT. ANY OTHER STD
PLANS REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS CAN BE
OBTAINED FROM THE CITY OF RENTON.
WATER NOTES WASTEWATER NOTES
1. EXISTING WATER MAINS, HYDRANTS AND SERVICES SHALL REMAIN OPERATIONAL THROUGHOUT THE COURSE OF
CONSTRUCTION. ABANDONMENT AND/OR REMOVAL OF EXISTING WATER MAINS SHALL TAKE PLACE ONLY AFTER
THE NEW MAIN HAS BEEN INSTALLED, TESTED, AND APPROVED BY THE CITY OF RENTON. REFER TO CONSTRUCTION
SEQUENCING AND GENERAL REQUIREMENTS ON DWG G-12.
2. MAIN SHUTDOWNS SHALL BE BY CITY MAINTENANCE STAFF ONLY. CONNECTIONS TO EXISTING MAINS SHALL ALSO
BE PERFORMED BY CITY FORCES, EXCEPT WET TAPS, WHICH MUST BE MADE BY CITY-APPROVED WET TAP
CONTRACTORS. CONTRACTOR SHALL PROVIDE TWO WEEK ADVANCED NOTICE TO CITY FOR SCHEDULING OF
CONNECTIONS AND SHUTDOWNS. ALL NECESSARY EXCAVATION AND MATERIALS ARE TO BE SUPPLIED BY THE
CONTRACTOR AND BE ON-SITE PRIOR TO CITY NOTIFICATIONS. REFER TO SP 7-09.3(19)A.
3. VERIFY LOCATION AND DEPTH OF EXISTING WATER MAINS AT ALL CONNECTION POINTS PRIOR TO CONSTRUCTION.
THE CONTRACTOR SHALL FIELD VERIFY THE OUTSIDE DIAMETER (O.D.) OF ALL EXISTING CAST-IRON PIPES AND
PROVIDE THE PROPER LONG-BODY ADAPTERS AND TRANSITION COUPLINGS FOR THE FINAL CONNECTIONS BY CITY
FORCES. CONNECTIONS TO ALL DUCTILE IRON PIPES SHALL BE MADE WITH LONG-BODY SOLID SLEEVES (MJ).
REFER TO SP 7-09.3(19)A.
4. ALL CONNECTIONS TO EXISTING WATER MAINS SHALL BE MADE ONLY AFTER ALL THE NEW WATER MAINS AND
APPURTENANCES HAVE SUCCESSFULLY CLEANED WITH POLYPIGS, PASSED ALL PRESSURE TESTS, DISINFECTED
WITH CHLORINE SOLUTION, HAVE RECEIVED SATISFACTORY BACTERIOLOGICAL TEST LAB REPORTS, AND ARE
THOROUGHLY FLUSHED. A SUGGESTED POLYPIGGING PLAN IS INCLUDED ON W-23. REFER TO SP 7-09.3(23) &
7-09.3(24)
5. NEW WATER MAIN PIPE MATERIALS SHALL BE DOUBLE THICK CEMENT-LINED DUCTILE IRON PIPE, THICKNESS CLASS
52. ALL DUCTILE IRON PIPES AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE-TYPE, POLYETHYLENE
PLASTIC. REFER TO SP 9-30.1(1) & SP 9-30.1(2).
6. ALL WATER PIPES, FITTINGS, AND VALVES SHALL HAVE RESTRAINED JOINTS PER SPECIFICATIONS. ALL MECHANICAL
JOINT FITTINGS AND VALVES SHALL HAVE WEDGE-TYPE RETAINER GLANDS EQUAL TO MEGALUG SERIES 1100. ALL
FITTINGS AND VALVES SHALL ALSO HAVE CONCRETE THRUST BLOCKS PER COR STANDARD PLANS. REFER TO SP
9-30.2(6).
7. RESTRAINED-JOINT DUCTILE IRON PIPE SHALL HAVE A POSITIVE METAL TO METAL CONTACT LOCKING SYSTEM
WITHOUT THE USE OF GRIPPING TEETH. THE USE OF GASKETS FOR PUSH-ON PIPE WITH INTEGRALLY MOLDED
STEEL OR METAL TEETH (E.G. FIELD LOK GASKET, FAST GRIP GASKET, TALON RJ GASKET) SHALL NOT BE ALLOWED
AS SUBSTITUTE FOR RESTRAINED-JOINT PIPES. REFER TO SP 9-30.2(6).
8. ALL WATER MAINS 10 INCH DIAMETER AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH
GRADE AND ALL WATERMAIN 12 INCH DIAMETER AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH
GRADE, UNLESS OTHERWISE SHOWN ON THE PLANS. WHERE UTILITY CONFLICTS OCCUR, WATER MAINS ARE TO BE
LOWERED OR RAISED BY PIPE JOINT DEFLECTION OR VERTICAL BENDS AS DIRECTED BY THE ENGINEER TO CLEAR
CONFLICTS. PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER’S SPECIFICATION FOR SIZE
OF PIPE USED. REFER TO SP 7-09.3(15).
9. AT UTILITY CROSSINGS MAINTAIN MINIMUM VERTICAL SEPARATION OF 18 INCHES FROM SANITARY SEWER OR
STORM DRAIN PIPE AND 12 INCHES FROM OTHER UTILITIES, MEAUSRED WALL TO WALL, UNLESS OTHERWISE
SHOWN ON THE PLANS. WHERE WATER MAIN CROSSES ABOVE OR BELOW SANITARY SEWER OR STORM DRAIN PIPE,
ONE FULL LENGTH OF WATER PIPE SHALL BE CENTERED FOR MAXIMUM JOINT SEPARATION.
10. ALL WATER MAIN VERTICAL BENDS SHALL INCLUDE VERTICAL THRUST BLOCKING PER COR STANDARD PLAN 330.3.
ALL WATER MAIN HORIZONTAL BENDS SHALL INCLUDE HORIZONTAL THRUST BLOCKING PER COR STANDARD PLAN
330.1.
11. CONTRACTOR TO PROVIDE END CAPS, PLUGS, TEMPORARY BLOW-OFF ASSEMBLIES AND TEMPORARY CONCRETE
THRUST BLOCKING, FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-INS TO EXISTING WATER SYSTEM.
REFER TO SP 7-09.3(23).
12. NEW WATER MAINS, HYDRANTS, AND SERVICE LATERALS SHALL BE PRESSURE TESTED AT A STATIC PRESSURE OF
150 PSI ABOVE WORKING PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A
MAXIMUM OF 5 PSI PRESSURE DROP DURING THE ENTIRE TEST PERIOD. THE QUANTITY OF WATER LOST FROM THE
MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN SP 7-09.3(23). ALL PRESSURE TESTING
SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. REFER TO SP 7-09.3(23).
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-4.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WATER AND WASTEWATER
NOTES G-4
4 85
M. McCROSKY, P.E.
R. NICOLAS
R. OCHILTREE, P.E.
N/A
27-04186
1. PROVIDE AS-BUILT INFORMATION SHOWING ALL INVERT AND RIM ELEVATIONS OF MANHOLES AND SIDE SEWER
VERTICAL AND HORIZONTAL LOCATIONS.
2. INSTALL SEWER MAINS AND SERVICES A MINIMUM 2 FEET FROM PARALLEL GAS LINES WHERE CONFLICT OCCURS.
3. AT UTILITY CROSSINGS MAINTAIN MINIMUM TYPICAL VERTICAL SEPARATION OF 18 INCHES FROM WATER AND 12
INCHES FROM OTHER UTILITIES, MEAUSRED WALL TO WALL, UNLESS OTHERWISE SHOWN ON THE PLANS. NOTIFY
ENGINEER IF TYPIAL VERTICAL SEPARATION CAN NOT BE MET. 6-INCH ETHAFOAM PAD MAY BE USED IF APPROVED
BY THE CITY OF RENTON.
4. ALL SIDE SEWER COUPLINGS SHALL BE “FERNCO STRONG-BACK” OR APPROVED EQUAL.
G GENERAL
EC EROSION CONTROL
W WATER
SD STORMWATER
R RESTORATION
TC TRAFFIC CONTROL
AASHTO AMERICAN ASSOCIATION OF STATE HIGHWAY
TRANSPORTATION OFFICIALS
AB ANCHOR BOLT
AC ASPHALT CONCRETE
ACP ASPHALT CONCRETE PAVEMENT
ADA AMERICANS WITH DISABILITIES ACT
ADS ADVANCED DRAINAGE SYSTEMS (PIPE)
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
APWA AMERICAN PUBLIC WORKS ASSOCIATION
AVE AVENUE
BF BLIND FLANGE
BGS BELOW GROUND SURFACE
BO BLOW-OFF
BOT BOTTOM
BSM BIORETENTION SOIL MIX
CB CATCH BASIN
CDF CONTROLLED DENSITY FILL
CED CEDAR
CF CUBIC FEET
CFS CUBIC FEET PER SECOND
CHLK CHAIN LINK FENCE
CI CAST IRON
C/L, CL CENTERLINE
CLR CLEAR
CMP CORRUGATED METAL PIPE
CO CLEANOUT
CONC CONCRETE
CPE CORRUGATED POLYETHYLENE PIPE
CPLG COUPLING
CRZ CRITICAL ROOT ZONE
CSBC CRUSHED SURFACING BASE COURSE
CSTC CRUSHED SURFACING TOP COURSE
CTR CENTER
CULV CULVERT
D DEPTH, DOUBLE, DRAIN
DI DUCTILE IRON
DHA DUANE HARTMAN & ASSOCIATES
DIA DIAMETER
DR DRIVE
DT DECIDUOUS TREE
DWG DRAWING
DWY DRIVEWAY
E EAST, EASTING, ELECTRICAL
EA EACH
EC EROSION CONTROL
EL, ELEV ELEVATION
EP EDGE OF PAVEMENT
EW EACH WAY
EX EXISTING
FCA FLANGED COUPLING ADAPTER
FF FINISHED FLOOR
FG FINISH GRADE
FH FIRE HYDRANT
FL FLANGE
FM FORCE MAIN
FT FEET, FOOT
G GAS
GALV GALVANIZED
GPM GALLONS PER MINUTE
GPS GLOBAL POSITIONING SYSTEM
GRAV GRAVEL
H HORIZONTAL
HDPE HIGH DENSITY POLYETHYLENE
HMA HOT MIX ASPHALT
HP HORSEPOWER
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
IPS IRON PIPE SIZE
JB JUNCTION BOX
L LENGTH
LF LINEAR FEET
LT LEFT
MAP MAPLE
MAX MAXIMUM
MB MAILBOX
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MJ MECHANICAL JOINT
MMA METHYL METHACRYLATE
MON MONUMENT
MPE MEDIUM DENSITY POLYETHYLENE
MUTCD MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES
N NORTH, NORTHING
NAD NORTH AMERICAN DATUM
NAVD NORTH AMERICAN VERTICAL DATUM
NE NORTHEAST
NIC NOT IN CONTRACT
NO. NUMBER
NTS NOT TO SCALE
NW NORTHWEST
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OHWM ORDINARY HIGH WATER MARK
OP OVERHEAD POWER
OPG OPENING
P POWER
PE PLAIN END
PED XING PEDESTRIAN CROSSING
PKWY PARKWAY
P/L PROPERTY LINE
PLS PROFESSIONAL LAND SURVEYOR
PP POLYPROPYLENE PIPE
PRV PRESSURE REDUCING VALVE
PS PUMP STATION
PSE PUGET SOUND ENERGY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PVC POLYVINYL CHLORIDE C-900 PIPE
PVMT PAVEMENT
PWR POWER
RCW REVISED CODE OF WASHINGTON
RD ROAD
REQ'D REQUIRED
RET RETAINING
RJ RESTRAINED JOINT
ROW RIGHT OF WAY
RPBA REDUCED PRESSURE BACKFLOW
ASSEMBLY
RPM REVOLUTIONS PER MINUTE,
RAISED PAVEMENT MARKER
RT RIGHT
S SOUTH, SLOPE, SOCKET, SINGLE
SCH SCHEDULE
SCO SEWER CLEANOUT
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SDR STANDARD DIMENSION RATIO
SE SOUTHEAST
SERV SERVICE
SF SILT FENCE, SQUARE FEET
SMH SEWER MANHOLE
SS SANITARY SEWER
SSMH SANITARY SEWER MANHOLE
SST STAINLESS STEEL
ST STREET
STA STATION
STD STANDARD
STL STEEL
SW SOUTHWEST
SWPPP STORMWATER POLLUTION
PREVENTION PLAN
SYM SYMMETRICAL
T TELEPHONE
TBM TEMPORARY BENCHMARK
TDH TOTAL DYNAMIC HEAD
TELJB TELEPHONE JUNCTION BOX
TELR TELEPHONE RISER
TESC TEMPORARY EROSION AND
SEDIMENT CONTROL
THK THICK
TV TELEVISION (CABLE)
TVJB TELEVISION (CABLE)
JUNCTION BOX
TVR TELEVISION (CABLE) RISER
TYP TYPICAL
U/C UNDER CONSTRUCTION
UD UNDERDRAIN
UGP UNDERGROUND POWER
UGT UNDERGROUND TELEPHONE
UNO UNLESS NOTED OTHERWISE
V VENT, VERTICAL
W/ WITH
W WATER, WEST, WIDTH
WAC WASHINGTON ADMINISTRATIVE CODE
WM WATER METER
WS WATER SURFACE
WSDOT WASHINGTON STATE DEPARTMENT OF
TRANSPORTATION
WSRN WASHINGTON STATE REFERENCE
NETWORK
YRS YEARS
ABBREVIATIONS
X
LIMITS OF CONSTRUCTION WITHIN
PERMANENT EASEMENT
CENTERLINE STATIONING
TO BE REMOVED OR ABANDONED
PIPE
DIRECTION OF FLOW (PLAN)
CHAIN LINK FENCE
SILT FENCE
TEMPORARY CONSTRUCTION FENCE
STRAW WATTLE
CATCH BASIN INLET PROTECTION
CATCH BASIN TYPE 2 W/ GRATE
CATCH BASIN TYPE 2 W/ SOLID LID
CATCH BASIN TYPE 1 W/ GRATE
BIRD CAGE OVERFLOW STRUCTURE
STORM CULVERT END
VALVE
FIRE HYDRANT
WATER METER
PRESSURE REDUCING VALVE
COUPLING
FLANGE FITTING
MECHANICAL JOINT FITTING
RESTRAINED JOINT FITTING
CONCRETE THRUST BLOCK
SLOPE
DIRECTION OF FLOW
CAP
PLUG
POLYPIGGING STATION
AIR/VACUUM RELEASE ASSEMBLY
SEWER MANHOLE
o-o o-o o-o
LEGEND
EXISTING PROPOSED
WATER MANHOLE
FIRE HYDRANT
WATER VALVE
WATER METER
WATER VAULT
POST INDICATOR VALVE
POWER POLE W/ LIGHT
POWER POLE
POWER POLE ANCHOR
JUNCTION BOX
STREET LIGHT VAULT
CABLE TV VAULT
POWER VAULT
POWER/TELEPHONE JUNCTION BOX
STREET LIGHT VAULT
TELEPHONE VAULT
TELEPHONE MANHOLE
DHA SURVEY CONTROL
MONUMENT IN CASE
STORM/SANITARY SEWER MANHOLE
STORM DRAIN CATCH BASIN (TYPE I)I
STORM DRAIN CATCH BASIN (TYPE I)
YARD DRAIN
STORM CULVERT
WHEEL CHAIR RAMP
GAS METER
GAS VALVE
MAILBOX
SIGN
ROCKERY
POT HOLE
CONCRETE
PLAT LOT LINE
STREET R/W LINE
STREET R/W CENTERLINE
CONTOUR
FENCING
UNDERGROUND STORM LINE
UNDERGROUND SEWER LINE
CONIFER TREE
DECIDUOUS TREE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
LEGENDS AND
ABBREVEATIONS G-5
5 85
M. McCROSKY, P.E.
P. SIMON
R. OCHILTREE, P.E.
N/A
27-04186
DESIGNATIONS
SECTION
TITLE
A
-SCALE: 1/2" = 1'-0"
TITLE
DETAIL
TITLE
1
M-1SCALE: 1/2" = 1'-0"
TITLE
4/M-1
DETAIL/SECTION CALLOUT
1
PHOTO
NUMBER
DIRECTION
OF PHOTO
PHOTO REFERENCE
1
M-1 DRAWING
REFERENCE
A
M-1
SECTION LETTER
DRAWING NUMBER WHERE
SECTION IS DRAWN, DASH IF
SECTION APPEARS ON SAME
SHEET AS CUT
DASH IF SECTION IS TAKEN ON THE SAME
DRAWING, DRAWING NUMBER IF SECTION
IS TAKEN ON A DIFFERENT SHEET
SECTION, ELEVATION OR
PROFILE REFERENCE LETTER
DETAIL NUMBER
DRAWING NUMBER WHERE DETAIL IS
REFERENCED, DASH IF DETAIL
APPEARS ON THE SAME SHEET AS
SHEET REFERENCED
ELEVATION
LETTER
DRAWING NUMBER WHERE
ELEVATION IS DRAWN, DASH
IF ELEVATION APPEARS ON
SAME SHEET AS REFERENCED
A
M-1
PIPING DESIGNATIONS
PIPING IS IDENTIFIED BY ITS SIZE FOLLOWED BY PIPING SYSTEM AS FOLLOWS:
NEW PIPING:
EXISTING PIPING:
FOR NEW PIPING MATERIAL, FITTINGS, AND VALVES, SEE SPECIFICATIONS.
PIPING SYSTEM DESIGNATIONS FOR EXISTING PIPING INDICATE TYPE OF
SERVICE AND TYPE OF MATERIAL IF KNOWN. CONTRACTOR SHALL VERIFY ALL
EXISTING PIPE MATERIAL AND NOT RELY ON THIS DESIGNATION PRIOR TO
CONSTRUCTION.
PIPE SIZE
PIPING SYSTEM
EQUIPMENT DESIGNATIONS
EQUIPMENT IS IDENTIFIED AS FOLLOWS:
BOXED NUMBER DESIGNATES NEW EQUIPMENT TO BE SUPPLIED BY THE
CONTRACTOR:
UNBOXED NUMBER DESIGNATES EXISTING EQUIPMENT:
EQUIPMENT LIST IS INCLUDED FOR THE CONVENIENCE OF THE ENGINEER AND
CONTRACTOR, AND IS NOT INTENDED TO REPRESENT PRECISE LISTING OF ALL
EQUIPMENT AND DEVICES TO BE PROVIDED UNDER THIS CONTRACT.
XX-XXXX
8" W
XX-XXXX
8" W
DI GENERAL PIPE MATERIAL
DRAWING
REFERENCE
DETAIL NUMBER OR
SECTION LETTER
DRAWING REFERENCE
SEE R - DRAWINGS FOR RESTORATION SPECIFIC LEGEND.
NOTE
2+00
#
UNDERGROUND SEWER LATERAL LINE
(APROXIMATE LOCATION PER GIS)
UNDERGROUND WATER LINE
UNDERGROUND POWER LINE
UNDERGROUND NATURAL GAS LINE
UNDERGROUND TELEPHONE
UNDERGROUND CABLE TV LINE
UNDERGROUND FIBER OPTIC
OVERHEAD POWER LINE
LANE DELINEATIONS
DITCH
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-6.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
SURVEY CONTROL
AND NOTES G-6
6 85
M. McCrosky
P. Simon
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
SURVEY NOTES
SURVEY CONTROL
PT # SURVEY PT # DESCRIPTION NORTHING EASTING ELEVATION
1 1 MON IN CASE 181819.119 1305917.511 223.30
2 2 MON IN CASE 182293.286 1305907.472 247.20
3 3 REBAR/CONTROL CAP 181637.250 1305103.058 169.81
4 5 SCRIBED X 181637.301 1304474.387 122.28
5 6 SCRIBED X 181873.303 1304990.056 131.52
6 10 MAG NAIL/WASHER 181618.964 1306079.113 248.23
7 11 MAG NAIL/WASHER 181803.706 1306100.663 255.43
8 12 MAG NAIL/WASHER 181773.924 1305649.786 191.25
9 13 MAG NAIL/WASHER 181465.485 1305413.305 190.82
10 14 REBAR CONTROL CAP 181392.471 1305141.120 194.22
11 15 REBAR CONTROL CAP 181220.273 1304835.806 191.14
12 16 MAG NAIL/WASHER 180849.891 1304813.388 193.38
13 17 MAG NAIL/WASHER 181454.170 1304898.582 178.10
14 18 MAG NAIL/WASHER 182269.838 1305312.044 157.05
15 19 MAG NAIL/WASHER 182315.181 1305146.125 142.28
16 20 MAG NAIL/WASHER 182313.180 1304921.540 117.12
17 21 REBAR/CONTROL CAP 182130.996 1304970.591 114.24
18 22 MAG NAIL/WASHER 182069.184 1305115.024 131.51
19 23 MAG NAIL/WASHER 181472.124 1304413.897 125.08
20 24 MAG NAIL/WASHER 181314.536 1304477.880 144.41
21 25 MAG NAIL/WASHER 182065.805 1305567.432 171.64
22 26 MON IN CASE 182305.268 1305619.856 211.48
23 27 MAG NAIL/WASHER 182495.846 1305541.458 219.55
24 40 MAG NAIL/WASHER 181903.877 1305365.386 158.84
25 42 SCRIBED X 181322.086 1305018.983 192.93
26 43 MAG NAIL/WASHER 181723.615 1304690.202 125.73
27* 44 REBAR CONTROL CAP 180586.655 1304611.727 173.67
28 45 SCRIBED X 181814.454 1305383.172 160.57
29 46 REBAR CONTROL CAP 181734.055 1305460.777 169.50
30 47 TACK IN HUB 182059.632 1305159.048 137.35
31 48 TACK IN HUB 182038.776 1305208.637 138.48
32 80 REBAR CONTROL CAP 180717.094 1304783.081 190.95
33 81 MAG NAIL/PACE WASHER 182158.261 1305357.177 153.46
UTILITIES MAPPING:
ALL EXISTING UTILITIES SHOWN HEREIN ARE TO BE VERIFIED HORIZONTALLY AND VERTICALLY PRIOR
TO ANY CONSTRUCTION. ALL EXISTING FEATURES INCLUDING BURIED UTILITIES ARE SHOWN AS
INDICATED BY RECORD LOCATION OR FIELD TIED AS A RESULT OF A UTILITY PAINT-OUT DURING THE
COURSE OF THE FIELD SURVEY. DUANE HARTMAN & ASSOCIATES, INC. (DHA) AND BHC
CONSULTANTS, LLC ASSUME NO LIABILITY FOR THE ACCURACY OF THE RECORD INFORMATION. FOR
THE FINAL LOCATION OF THE EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION, CONTACT
THE UTILITY OWNER/AGENCY AND UTILITIES UNDERGROUND CENTER (800/424-5555)
TOPOGRAPHIC MAPPING:
THE MAP SHOWN HEREON IS THE RESULT OF A TOPOGRAPHIC SURVEY BY DUANE HARTMAN &
ASSOCIATES, INC. (DHA) COMPLETED IN APRIL 2022. DHA AND BHC CONSULTANTS, LLC ASSUME NO
LIABILITY, BEYOND SAID DATE, FOR ANY FUTURE SURFACE FEATURE MODIFICATIONS OR
CONSTRUCTION ACTIVITIES THAT MAY OCCUR WITHIN OR ADJOINING THE PERIMETER OF THIS
SURVEY. CONTACT DHA (425) 483-5355 FOR SITE UPDATES AND VERIFICATIONS.
NOTE:
·PROPERTY LINES SHOWN HEREON GENERATED FROM KING COUNTY RECORDS, AND ARE
CONSIDERED APPROXIMATE IN LOCATION.
·SANITARY AND STORM SEWER MANHOLE LOCATION SHOWN HEREIN ARE FROM CENTER OF LID.
CENTER OF STRUCTURES ARE TO BE VERIFIED PRIOR TO ANY CONSTRUCTION.
HORIZONTAL DATUM:
WASHINGTON STATE COORDINATE SYSTEM, NORTH ZONE NAD83(91), US FEET UTILIZING RTK GPS
FIELD PROCEDURES EXTENDED FROM WSDOT LOCAL CONTROL POINTS.
CONTOUR INTERVAL: TWO (2) FOOT CONTOURS
VERTICAL DATUM:
NORTH AMERICAN VERTICAL DATUM 1988 (NAVD88), US FEET.
* POINT 27 LOCATED NORTH OF INTERSECTION
VUEMONT PL NE AND BRONSON WAY NE.
1
2 3A45
6
7
9
1011 12
13141516A16B17
18 3B8BRONS
ON BRONSON WAY NEB
R
O
N
S
O
N
32
12
11
25
10
9
6 7
1
2
8
29
21
22
23
33
14
15
16
1718
5
24
28
3
13
26
4
19
20
BRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E 4
T
H S
T
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NE
27
30
31VUEMONT PL NES U N S E T B L V D N E
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-7-8.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
ALIGNMENT TABLES
1 OF 2 G-7
7 85
M. McCrosky
R. Nicolas
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
NOTES:
1. SEE DWG G-8 FOR ALIGNMENT TABLES.BRONS
ON
B
R
O
N
S
O
N
W
A
Y N
E
B
R
O
N
S
O
N
VUEMONT PL NEBRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E
4
T
H
S
T
S U N S E T B L V D N E
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NE
1+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9
+
0
0
10+00
11+00
1
2
+
0
0
1
3
+
0
0
14+00
15+00 16+00 1 7 +0 0
1 8 +0 0 19+0020+0021+0022+0030+00 31+0032+0033+003 4 +0 0
35+00
36+00
3
7
+
0
0
38+0039+0040+0041+004
2
+
0
0
4
3
+
0
0
44+00
45+00 46+00
47+00
50+00
51+005
2
+
0
0
53+00
54+00
55+00
5 6 +0 0
57+00
88+01
79+80
80+00
81+0082+008 3 +0 0
8 4 +0 085+0086+00
87+00
8 8 +0 0
75+7659+50
60+00
61+0062+00
63+0064+0065+0066+006
7
+
0
0
6
8
+
0
0
69+00
7
0
+
0
0
71+0072+00
73+00
74+00
75+0020+00
21+0021+7543+0040+00
41+00
4 2 +0 043+00
9 0 +0 0
91+00
91+50
L73
C33
L74 L75
L76L77
C34
C35L78
L79
L80
L81
C 36C37
C38
L82
L
8
3
C39
C40L84L85L86
L87
L88C41
C42
C43
C44C45L 8 9L90 L91L92
L93
C46C 4 7
C48
L94
L95
L96
L97
L98
L99
L100
L101
L102
L103
L104
L105
L106L107
L108
800+00
801+00
8
0
2
+
0
0
8
0
3
+
0
0 804+00
805+00
8
0
6
+
0
0700+00701+00702+00702+90
L118
L119
C61
C62
C63
L120
C64
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-7-8.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
ALIGNMENT TABLES
2 OF 2 G-8
8 85
M. McCrosky
R. Nicolas
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
NOTES:
1. SEE DWG G-7 FOR ALIGNMENT PLAN.
BRONSON - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L74
L75
C33
L76
C34
C35
L73
L77
BEGIN
STATION
0+80.00
4+97.23
5+56.64
10+25.12
10+53.95
18+04.01
19+51.85
20+26.03
BEGIN
NORTHING
180,740.51
181,157.70
181,217.11
181,586.64
181,598.22
182,227.27
182,301.85
182,299.78
BEGIN
EASTING
1,304,796.94
1,304,802.36
1,304,803.13
1,305,048.05
1,305,074.45
1,305,320.03
1,305,202.33
1,305,128.18
END
STATION
4+97.23
5+56.64
10+25.12
10+53.95
18+04.01
19+51.85
20+26.03
22+22.29
END
NORTHING
181,157.70
181,217.11
181,586.64
181,598.22
182,227.27
182,301.85
182,299.78
182,294.30
END
EASTING
1,304,802.36
1,304,803.13
1,305,048.05
1,305,074.45
1,305,320.03
1,305,202.33
1,305,128.18
1,304,932.00
DISTANCE
417.23
59.41
28.83
74.18
196.26
BEARING
N0°44'42"E
N0°44'23"E
N66°19'32"E
S88°24'02"W
S88°24'02"W
RADIUS
409.30
477.50
124.77
TANGENT
263.68
477.50
83.98
CURVE
LENGTH
468.48
750.06
147.84
DELTA
65°34'50"
90°00'00"
67°53'19"
GRANDEY - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L78
C36
L79
C37
L80
L81
C38
BEGIN
STATION
29+80.00
32+16.39
34+90.82
34+91.02
37+67.73
37+67.75
40+83.98
BEGIN
NORTHING
181,243.74
181,274.95
181,464.00
181,464.20
181,683.19
181,683.19
181,810.17
BEGIN
EASTING
1,304,824.39
1,304,590.07
1,304,424.33
1,304,424.33
1,304,567.24
1,304,567.26
1,304,856.87
END
STATION
32+16.39
34+90.82
34+91.02
37+67.73
37+67.75
40+83.98
47+05.40
END
NORTHING
181,274.95
181,464.00
181,464.20
181,683.19
181,683.19
181,810.17
182,319.50
END
EASTING
1,304,590.07
1,304,424.33
1,304,424.33
1,304,567.24
1,304,567.26
1,304,856.87
1,305,124.85
DISTANCE
236.39
0.20
0.02
316.23
BEARING
N82°24'48"W
N0°04'01"W
N66°19'32"E
N66°19'32"E
RADIUS
190.95
238.80
461.50
TANGENT
167.01
156.24
368.08
CURVE
LENGTH
274.44
276.71
621.42
DELTA
82°20'47"
66°23'33"
77°09'00"
BRONSON PL - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L82
C39
C40
L83
BEGIN
STATION
49+80.00
50+88.92
56+32.68
57+06.43
BEGIN
NORTHING
181,927.24
181,970.97
182,427.97
182,494.90
BEGIN
EASTING
1,305,331.25
1,305,431.00
1,305,553.16
1,305,559.69
END
STATION
50+88.92
56+32.68
57+06.43
57+54.57
END
NORTHING
181,970.97
182,427.97
182,494.90
182,527.22
END
EASTING
1,305,431.00
1,305,553.16
1,305,559.69
1,305,595.37
DISTANCE
108.92
48.14
BEARING
N66°19'32"E
N47°49'51"E
RADIUS
301.60
50.00
TANGENT
381.20
45.43
CURVE
LENGTH
543.76
73.75
DELTA
103°17'58"
84°30'54"
WINDSOR PL - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L92
L93
L91
C46
L89
C47
L90
C48
BEGIN
STATION
79+80.00
80+00.00
81+01.61
81+73.90
83+05.38
83+07.96
84+91.79
86+95.79
BEGIN
NORTHING
182,305.48
182,305.35
182,304.70
182,303.97
182,235.41
182,233.04
182,054.18
181,850.21
BEGIN
EASTING
1,305,587.36
1,305,607.36
1,305,708.96
1,305,781.25
1,305,885.04
1,305,886.07
1,305,921.81
1,305,917.97
END
STATION
80+00.00
81+01.61
81+73.90
83+05.38
83+07.96
84+91.79
86+95.79
88+01.04
END
NORTHING
182,305.35
182,304.70
182,303.97
182,235.41
182,233.04
182,054.18
181,850.21
181,749.69
END
EASTING
1,305,607.36
1,305,708.96
1,305,781.25
1,305,885.04
1,305,886.07
1,305,921.81
1,305,917.97
1,305,944.36
DISTANCE
20.00
101.61
72.29
2.58
204.00
BEARING
S89°37'59"E
S89°37'59"E
S89°25'18"E
S23°40'48"E
S1°04'46"W
RADIUS
114.60
425.39
191.00
TANGENT
74.05
93.37
54.00
CURVE
LENGTH
131.48
183.82
105.25
DELTA
65°44'11"
24°45'34"
31°34'25"
WINDSOR WAY - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L84
L85
C41
L86
C42
L87
C43
L88
C44
C45
BEGIN
STATION
59+50.00
61+43.27
61+57.14
62+52.38
64+11.19
68+99.76
69+14.11
72+12.45
72+14.32
73+61.37
BEGIN
NORTHING
181,227.06
181,302.52
181,308.94
181,344.14
181,379.06
181,665.13
181,677.75
181,820.63
181,820.60
181,749.69
BEGIN
EASTING
1,304,757.97
1,304,935.90
1,304,948.20
1,305,036.26
1,305,191.18
1,305,569.00
1,305,575.83
1,305,820.93
1,305,822.80
1,305,944.36
END
STATION
61+43.27
61+57.14
62+52.38
64+11.19
68+99.76
69+14.11
72+12.45
72+14.32
73+61.37
75+76.14
END
NORTHING
181,302.52
181,308.94
181,344.14
181,379.06
181,665.13
181,677.75
181,820.63
181,820.60
181,749.69
181,656.32
END
EASTING
1,304,935.90
1,304,948.20
1,305,036.26
1,305,191.18
1,305,569.00
1,305,575.83
1,305,820.93
1,305,822.80
1,305,944.36
1,306,125.33
DISTANCE
193.27
13.87
158.81
14.35
1.87
BEARING
N67°01'14"E
N62°25'38"E
N77°17'42"E
N28°24'15"E
S88°54'14"E
RADIUS
299.25
573.00
272.90
143.85
191.00
TANGENT
48.03
260.24
166.05
80.67
120.35
CURVE
LENGTH
95.24
488.56
298.34
147.05
214.78
DELTA
18°14'06"
48°51'10"
62°38'14"
58°34'08"
64°25'43"
SD3 - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L94
L95
L96
L97
BEGIN
STATION
20+00.00
20+12.90
20+44.12
21+40.50
BEGIN
NORTHING
182,105.43
182,098.73
182,082.53
182,051.94
BEGIN
EASTING
1,305,085.77
1,305,096.79
1,305,123.47
1,305,214.87
END
STATION
20+12.90
20+44.12
21+40.50
21+74.56
END
NORTHING
182,098.73
182,082.53
182,051.94
182,042.49
END
EASTING
1,305,096.79
1,305,123.47
1,305,214.87
1,305,247.59
DISTANCE
12.90
31.22
96.38
34.06
BEARING
S58°43'34"E
S58°43'34"E
S71°29'40"E
S73°53'41"E
RADIUS TANGENT
CURVE
LENGTH DELTA
SD-06 - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L103
L104
L105
L106
L107
L108
BEGIN
STATION
40+00.00
40+12.50
40+43.67
40+59.28
41+77.86
42+50.13
BEGIN
NORTHING
181,872.44
181,865.30
181,847.51
181,838.90
181,761.04
181,689.89
BEGIN
EASTING
1,305,301.82
1,305,312.08
1,305,337.68
1,305,350.70
1,305,440.13
1,305,452.85
END
STATION
40+12.50
40+43.67
40+59.28
41+77.86
42+50.13
43+00.13
END
NORTHING
181,865.30
181,847.51
181,838.90
181,761.04
181,689.89
181,651.92
END
EASTING
1,305,312.08
1,305,337.68
1,305,350.70
1,305,440.13
1,305,452.85
1,305,485.39
DISTANCE
12.50
31.17
15.61
118.57
72.28
50.00
BEARING
S55°12'19"E
S55°12'19"E
S56°30'24"E
S48°57'09"E
S10°08'36"E
S40°35'34"E
RADIUS TANGENT
CURVE
LENGTH DELTA
SD-05 - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L98
L99
L100
L101
L102
BEGIN
STATION
90+00.00
90+27.65
90+59.30
90+68.95
91+19.96
BEGIN
NORTHING
181,658.11
181,634.42
181,607.34
181,598.85
181,557.68
BEGIN
EASTING
1,305,096.40
1,305,110.65
1,305,127.03
1,305,131.64
1,305,161.76
END
STATION
90+27.65
90+59.30
90+68.95
91+19.96
91+50.09
END
NORTHING
181,634.42
181,607.34
181,598.85
181,557.68
181,531.59
END
EASTING
1,305,110.65
1,305,127.03
1,305,131.64
1,305,161.76
1,305,176.82
DISTANCE
27.65
31.65
9.66
51.01
30.13
BEARING
S31°02'34"E
S31°09'53"E
S28°31'46"E
S36°11'10"E
S29°59'19"E
RADIUS TANGENT
CURVE
LENGTH DELTA
BRONSON WAY - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L118
C61
C62
L119
C63
BEGIN
STATION
800+00.00
800+68.77
802+13.49
803+98.89
804+68.65
BEGIN
NORTHING
180,537.96
180,598.25
180,705.23
180,847.30
180,911.35
BEGIN
EASTING
1,304,607.47
1,304,640.54
1,304,736.14
1,304,851.62
1,304,879.27
END
STATION
800+68.77
802+13.49
803+98.89
804+68.65
806+00.00
END
NORTHING
180,598.25
180,705.23
180,847.30
180,911.35
181,024.15
END
EASTING
1,304,640.54
1,304,736.14
1,304,851.62
1,304,879.27
1,304,945.89
DISTANCE
68.77
69.76
BEARING
N28°44'32"E
N23°20'42"E
RADIUS
317.84
337.74
520.87
TANGENT
73.64
95.10
66.02
CURVE
LENGTH
144.72
185.40
131.35
DELTA
26°05'18"
31°27'09"
14°26'53"
VUEMONT PL - CONSTRUCTION CENTERLINE ALIGNMENT
SEGMENT
L120
C64
BEGIN
STATION
700+00.00
702+31.84
BEGIN
NORTHING
180,482.19
180,593.72
BEGIN
EASTING
1,304,709.09
1,304,505.84
END
STATION
702+31.84
702+90.11
END
NORTHING
180,593.72
180,642.38
END
EASTING
1,304,505.84
1,304,480.13
DISTANCE
231.84
BEARING
N61°14'38"W
RADIUS
50.00
TANGENT
32.95
CURVE
LENGTH
58.27
DELTA
66°46'35"
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
EROSION CONTROL KEY PLAN G-9
9 85
M. McCrosky
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186GRANDEY WAYBRONSON WAY NEWI
NDS
OR WA
Y N
E
BR
ONS
ON PLA
CE NE BRONSON WAY NEWINDSOR PLACE NE
EDMONDS AVE NE
BRONSON WAY NE
SUN SET BL VD NEVUEMONT PL NEB
R
O
N
S
O
N W
A
Y N
E
NE 4TH ST
1
2 3A45
6
7
9
1011 12
13141516A16B17
18 3B8BRONS
ON
B
R
O
N
S
O
N W
A
Y N
E
B
R
O
N
S
O
N
BRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E 4
T
H S
T
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NE
S U N S E T B L V D N EVUEMONT PL NEE
C-10
EC-2 EC-4E
C-5
EC-3EC-5EC-6
EC-4E C -7
EC-7EC-8
E
C-
6
EC-9EC-10EC-9EC-2
EC-8EC-3EC-11EC-11EC-11
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-10.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WATER KEY PLAN G-10
10 85
M. McCrosky
P. Simon
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
1
2 3A45
6
7
9
1011 12
13141516A16B17
18 3B8BRONS
ON BRONSON WAY NEB
R
O
N
S
O
N
VUEMONT PL NEBRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E 4
T
H S
T
S U N S E T B L V D N E
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NE
W-18
W-1 W-6W
-7
W-3W-8W-9
W-5W -1 1
W-12W-13W-
1
0
W-16W-17W-15W-2
W-14W-4
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
STORMWATER KEY PLAN G-11
11 85
M. McCrosky
P. Simon
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186GRANDEY WAYBRONSON WAY NEWI
NDS
OR WA
Y N
E
BR
ONS
ON PLA
CE NE BRONSON WAY NEWINDSOR PLACE NE
EDMONDS AVE NE
BRONSON WAY NE
SUN SET BL VD NEVUEMONT PL NEB
R
O
N
S
O
N W
A
Y N
E
NE 4TH ST
1
2 3A45
6
7
9
1011 12
13141516A16B17
18 3B8BRONS
ON BRONSON WAY NEB
R
O
N
S
O
N
BRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E 4
T
H S
T
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NE
S U N S E T B L V D N EVUEMONT PL NES
D-18
SD-1 SD-6S
D-7
SD-3SD-8SD-9
SD-5S D -1 1
SD-12SD-13
S
D-
1
0
SD-16SD-17SD-15SD-2
SD-14SD-4
CONSTRUCTION SEQUENCING AND GENERAL REQUIREMENTS
1. WORK SHALL BE SEQUENCED AT THE CONTRACTOR’S DISCRETION. HOWEVER, THE CONTRACTOR SHALL MINIMIZE
IMPACT TO THE NEIGHBORHOOD BY MAINTAINING INTERSECTIONS USED BY THE COMMUNITY FOR INGRESS AND
EGRESS AND BY LIMITING WORK TO A SINGLE STREET AS FEASIBLE.
2. DURING LANE OR STREET CLOSURE, THE CONTRACTOR SHALL MAINTAIN LOCAL ACCESS TO ALL PROPERTIES IN
THE CLOSED AREA.
3. TOTAL ROAD CLOSURE LASTING MORE THAN TWENTY-FOUR (24) HOURS IS SUBJECT TO THE APPROVAL BY THE CITY
COUNCIL.
4. EMERGENCY SERVICES (253-852-2121) SHALL BE NOTIFIED TWENTY-FOUR (24) HOURS BEFORE ANY STREET OR LANE
CLOSURES.
5. RESIDENTS SHALL BE PROVIDED SEVENTY-TWO (72) HOURS OF NOTICE IF ACCESS TO PROPERTY IS IMPACTED OR IF
THE FRONTAGE ALONG THEIR PROPERTY IS IMPACTED.
6. CONTRACTOR SHALL NOT CLOSE NEIGHBORHOOD ENTRANCES FROM SUNSET BLVD NE, EDMONDS AVE NE AND NE
4TH ST SIMULTANEOUSLY. TO MAINTAIN NEIGHBORHOOD ACCESS, TWO OF THE ENTRANCES MUST BE OPEN DURING
CONSTRUCTION.
7. AT ALL LOCATIONS WHERE THERE IS CONFLICT BETWEEN NEW STORM AND EXISTING WATER, THE CONTRACTOR
SHALL SEQUENCE UTILITY INSTALLATION TO ENSURE WATER SERVICE IS PRESERVED FOR RESIDENTS.
INSTALLATION OF NEW STORM MAY NEED TO OCCUR AFTER NEW WATER MAIN IS OPERATIONAL, WATER SERVICES
HAVE BEEN TRANSFERRED FROM OLD TO NEW MAINS, AND EXISTING WATER MAINS HAVE BEEN ABANDONED.
THERE WILL BE NO ADDITIONAL ALLOWANCE FOR TEMPORARY WATER SERVICES IN THE CASE THAT EXISTING
WATER SERVICES ARE IN CONFLICT WITH THE NEW STORM UNDER THE CONTRACTOR'S SEQUENCING PLAN. THIS
SEQUENCING MAY ALLOW SECTIONS OF ABANDONED WATER MAIN TO BE CUT OUT OF THE WAY TO AVOID
CONFLICTS WITH NEW STORM PIPE ALIGNMENT AND TO MINIMIZE WATER SERVICE DISRUPTIONS FOR RESIDENTS.
THIS SUGGESTED SEQUENCING SHOULD BE FOLLOWED UNLESS THE CONTRACTOR PROVIDES IN WRITING AN
ALTERNATIVE APPROACH FOR MAINTAINING WATER SERVICE. THE ALTERNATIVE APPROACH MUST BE SUBMITTED
TO THE CITY PROJECT MANAGER 5 WORKING DAYS PRIOR TO THE ALTERNATIVE APPROACH WORK BEGINNING.
8. ALL NEW WATER MAIN PIPE AND FITTINGS SHALL BE FLUSHED AND CLEANED VIA FOAM POLYPIG PRIOR TO
DISINFECTION AND TESTING. SUGGESTED POLYPIGGING STATION LOCATIONS ARE SHOWN ON DWG W-23.
CONTRACTOR MAY PROPOSE ALTERNATIVE POLYPIGGING STATION LOCATIONS FOR THE CITY’S APPROVAL.
9. THE WINDSOR HILLS NEIGHBORHOOD HAS NARROW ROADWAYS AND LIMITED RESIDENTIAL PARKING. THEREFORE,
WITHIN THE EXISTING RIGHTS-OF-WAY, THE CONTRACTOR SHALL ONLY STAGE ENOUGH CONSTRUCTION MATERIALS
FOR THE CURRENT DAY’S WORK.
10. THE CONTRACTOR SHALL NOT LEAVE STOCKPILED MATERIAL ON CITY STREETS OUTSIDE OF WORK HOURS.
11. PRIOR TO EVERY WEEKEND, THE CONTRACTOR SHALL PATCH THE CONSTRUCTION SITE WITH HMA, STEEL PLATES,
ETC. AND LEAVE THE SITE IN A CLEAN AND ORDERLY CONDITION. ANY TRAFFIC DETOURS SHALL BE MAINTAINED IN
ACCORDANCE WITH THE APPROVED TRAFFIC CONTROL PLAN.
12. SD-4, SD-5, SD-6, SD-7, SD-8, SD-9, SD-10, SD-15, SD-16, SD-17, SD-19, SD-20, AND SD-21, W-4, W-5,W-7, W-8, W-10, W-15,
AND W-16 HAVE SPECIFIC SEQUENCING REQUIREMENTS. SEE THOSE SHEETS FOR NOTES.
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-12.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
CONSTRUCTION SEQUENCING, GENERAL REQUIREMENTS,
AND POTHOLING DATA G-12
12 85
M. McCROSKY, P.E.
P. SIMON
R. OCHILTREE, P.E.
N/A
27-04186
POTHOLING TABLE
POTHOLE
NUMBER DRAWING
ASPHALT
OVERLAY
THICKNESS
(IN)
UTILITY
TYPE
UTILITY
SIZE (IN)
UTILITY
MATERIAL
PIPE
DIRECTION
TOP OF
UTILITY FROM
GRADE (IN)
1 SD-1 4 FIBER OPTIC 14D x 23W CONCRETE N & S 36
2 SD-1 4 GAS 4 STEEL WRAP N & S 38
3A W-6 N/A SEWER 8 CONCRETE E & W 74
3B W-6 6 GAS 1 PE N & S 30
4 SD-6 6 GAS 1 PE N & S 32
5 SD-19 5 SEWER 24 CONCRETE SE & NW 24
6 W-11 5 GAS 2 PE E & W 48
7 W-11 3 FIBER OPTIC 1 PVC E & W 34
8 SD-12 8 GAS 0.5 PE E & W 22
9 SD-15 5 GAS 2 STEEL WRAP SW & NE 32
10 SD-16 5 GAS 2 STEEL WRAP SW & NE 38
11 W-1 8 FIBER OPTIC 14D x 23W CONCRETE N & S 10
12 W-1 5 GAS 4 STEEL WRAP N & S 38
13 SD-5 8 POWER 2 PVC N & S 25
14 W-5 8 POWER 2 PVC N & S 23
15 W-5 8 GAS 2 STEEL N & S 44
16A W-17 6 POWER COULD NOT LOCATE AFTER DIGGING TO 8-FEET BELOW GRADE
16B W-17 4 POWER 2 CABLE N & S 61
17 W-18 N/A GAS 2 STEEL WRAP SW & NE 38
18 W-18 N/A FIBER OPTIC 14D x 23W CONCRETE N & S 30
POTHOLING TABLE NOTE:
UTILITY POTHOLE DATA IS PROVIDED FOR REFERENCE ONLY. CONTRACTOR TO VERIFY LOCATION, DEPTH AND SIZE OF EXISTING
UTILITIES. REPORT ANY DISCREPANCIES TO THE OWNER.
CONSTRUCTION SEQUENCE FOR WATER MAIN IMPROVEMENTS
1. THE CONTRACTOR MUST COMPLETE THE INSTALLATION OF EACH IDENTIFIED SEGMENT OF PIPES, INCLUDING
HYDRANTS, WATER SERVICE LINES, METER SETTERS AND RELATED APPURTENANCES AND PERFORM THE
POLYPIGGING, PRESSURE TESTING AND DISINFECTION OF THE INSTALLED SECTION OF PIPES AND HAVE IT
CONNECTED PER PLANS AND SPECIFICATIONS TO THE ACTIVE WATER SYSTEM BEFORE THE INSTALLATION OF THE
NEXT SEGMENT OF PIPES.
2. ALL WATER SERVICE TRANSFERS MUST BE COMPLETED FOR EACH SEGMENT OF THE NEW PIPES BEFORE THE
INSTALLATION OF THE NEXT SECTION OF PIPES
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_G-13.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
TRENCH DAM DETAIL G-13
13 85
M. McCROSKY, P.E.
R. NICOLAS
R. OCHILTREE, P.E.
N/A
27-04186
NOTES:
1. INSTALL TRENCH DAMS WHERE
EXISTING SLOPE IS GREATER THAN
OR EQUAL TO 10%. SPACE EVERY 25'
MINIMUM.
2. ADJUST SPACING AS REQUIRED TO
AVOID FITTINGS, VALVES AND
STRUCTURES.
SECTION A-A
A
A
ELEVATION
DETAIL
TRENCH DAM
1
TYPNTS
2'12"VARIES12"6"6"
FINISH GRADE,
SURFACING VARIES,
SEE RESTORATION DWGS FINISH GRADE
TYP TRENCH
WALL
PIPE, DIA VARIES
TYP BOTTOM OF PIPE
TRENCH
CONTROLLED
DENSITY FILL
DUCTILE IRON PIPE TO BE
WRAPPED IN POLYWRAP
PRIOR TO PLACEMENT OF CDF
WEIGHTS
HEIGHT "H" WEIGHT
6" RISER 450 LBS
12" RISER 900 LBS
24" RISER 1,800 LBS
36" RISER 2,700 LBS
44" RISER 3,750 LBS
B
AA
6"2'6"
B 6"2'6"3'PLAN VIEW
4""H"6"3'-8" MAXSECTION A-A
OPENING CAST
AS REQUIRED
FRAME AND GRATE
PER COR STD PLAN
204.00 AND 204.30
SECTION B-B
SPECIFICATIONS:
1. CONCRETE MINIMUM
COMPRESSION STRENGTH:
F'c = 5,000 PSI @ 28 DAYS.
2. REINFORCING STEEL" ASTM A615,
Fy = 60,000 PSI
DETAIL
YARD DRAIN
2
NTS
NOTES:
1. INSTALL YARD DRAIN RIMS WITH
SLIGHT DEPRESSION TO COLLECT
STORMWATER ON SIDEWALKS.
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-1.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO TESC NOTES EC-1
14 85
R. Ochiltree, P.E.
P. Simon
R. Dorn, P.E.
R. Ochiltree, P.E.
N/A
27-04186
EROSION AND SEDIMENT CONTROL (ESC) STANDARD PLAN NOTES:
THE FOLLOWING IS A LISTING OF GENERAL NOTES THAT SHALL BE INCORPORATED IN THE EROSION AND SEDIMENT CONTROL (ESC) PLAN SET. ALL THE NOTES
ON THE LIST MAY NOT PERTAIN TO EVERY PROJECT. THE APPLICANT OR OWNER, HEREBY REFERRED TO AS APPLICANT, MAY STRIKE OUT IRRELEVANT NOTES
IF NOT APPLICABLE TO THE PROJECT. HOWEVER, THE APPLICANT SHALL NOT RENUMBER NOR EDIT THE REMAINING NOTES. IF ADDITIONAL NOTES ARE
NEEDED FOR SPECIFIC ASPECTS, THEY SHALL BE ADDED AFTER THE ESC STANDARD PLAN NOTES.
1. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRE-CONSTRUCTION MEETING SHALL BE HELD AMONG THE CITY OF RENTON,
HEREBY REFERRED TO AS THE CITY, THE APPLICANT, AND THE APPLICANT'S CONTRACTOR.
2. THE APPLICANT IS RESPONSIBLE FOR OBTAINING THE WASHINGTON STATE DEPARTMENT OF ECOLOGY (ECOLOGY) CONSTRUCTION STORMWATER
GENERAL PERMIT, IF IT IS REQUIRED FOR THE PROJECT. THE APPLICANT SHALL PROVIDE THE CITY COPIES OF ALL MONITORING REPORTS PROVIDED TO
ECOLOGY ASSOCIATED WITH THE CONSTRUCTION STORM WATER GENERAL PERMIT.
3. THE ESC PLAN SET SHALL INCLUDE AN ESC CONSTRUCTION SEQUENCE DETAILING THE ORDERED STEPS THAT SHALL BE FOLLOWED FROM
CONSTRUCTION COMMENCEMENT TO POST-PROJECT CLEANUP IN ORDER TO FULFILL PROJECT ESC REQUIREMENTS.
4. THE BOUNDARIES OF THE CLEARING LIMITS, SENSITIVE AREAS AND THEIR BUFFERS, AND AREAS OF VEGETATION PRESERVATION AND TREE RETENTION
AS PRESCRIBED ON THE PLAN(S) SHALL BE CLEARLY DELINEATED BY FENCING AND PROTECTED IN THE FIELD IN ACCORDANCE WITH APPENDIX D OF THE
CITY OF RENTON SURFACE WATER DESIGN MANUAL (RENTON SWDM) PRIOR TO THE START OF CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO
DISTURBANCE BEYOND THE CLEARING LIMITS SHALL BE PERMITTED. THE CLEARING LIMITS SHALL BE MAINTAINED BY THE APPLICANT/ESC SUPERVISOR
FOR THE DURATION OF CONSTRUCTION.
5. STABILIZED CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE
PROJECT. ADDITIONAL MEASURES, SUCH AS CONSTRUCTED WHEEL WASH SYSTEMS OR WASH PADS, MAY BE REQUIRED TO ENSURE THAT ALL PAVED
AREAS ARE KEPT CLEAN AND TRACK-OUT TO ROAD RIGHT OF WAY DOES NOT OCCUR FOR THE DURATION OF THE PROJECT. IF SEDIMENT IS TRACKED
OFFSITE, PUBLIC ROADS SHALL BE CLEANED THOROUGHLY AT THE END OF EACH DAY, OR MORE FREQUENTLY DURING WET WEATHER, AS NECESSARY TO
PREVENT SEDIMENT FROM ENTERING WATERS OF THE STATE.
6. WASHOUT FROM CONCRETE TRUCKS SHALL BE PERFORMED OFF-SITE OR IN DESIGNATED CONCRETE WASHOUT AREAS ONLY. DO NOT WASH OUT
CONCRETE TRUCKS ONTO THE GROUND, OR TO STORM DRAINS OR OPEN DITCHES. ON-SITE DUMPING OF EXCESS CONCRETE SHALL ONLY OCCUR IN
DESIGNATED CONCRETE WASHOUT AREAS.
7. ALL REQUIRED ESC BMPS SHALL BE CONSTRUCTED AND IN OPERATION PRIOR TO LAND CLEARING AND/OR CONSTRUCTION TO PREVENT
TRANSPORTATION OF SEDIMENT TO SURFACE WATER, DRAINAGE SYSTEMS AND ADJACENT PROPERTIES. ALL ESC BMPS SHALL BE MAINTAINED IN A
SATISFACTORY CONDITION UNTIL SUCH TIME THAT CLEARING AND/OR CONSTRUCTION IS COMPLETE AND POTENTIAL FOR ON-SITE EROSION HAS PASSED.
ALL ESC BMPS SHALL BE REMOVED AFTER CONSTRUCTION IS COMPLETED AND THE SITE HAS BEEN STABILIZED TO ENSURE POTENTIAL FOR ON-SITE
EROSION DOES NOT EXIST. THE IMPLEMENTATION, MAINTENANCE, REPLACEMENT, ENHANCEMENT, AND REMOVAL OF ESC BMPS SHALL BE THE
RESPONSIBILITY OF THE APPLICANT.
8. ANY HAZARDOUS MATERIALS OR LIQUID PRODUCTS THAT HAVE THE POTENTIAL TO POLLUTE RUNOFF SHALL BE DISPOSED OF PROPERLY.
9. THE ESC BMPS DEPICTED ON THIS DRAWING ARE INTENDED TO BE MINIMUM REQUIREMENTS TO MEET ANTICIPATED SITE CONDITIONS. AS
CONSTRUCTION PROGRESSES AND UNEXPECTED OR SEASONAL CONDITIONS DICTATE, THE APPLICANT SHALL ANTICIPATE THAT MORE ESC BMPS WILL BE
NECESSARY TO ENSURE COMPLETE SILTATION CONTROL ON THE PROPOSED SITE. DURING THE COURSE OF CONSTRUCTION, IT SHALL BE THE
OBLIGATION AND RESPONSIBILITY OF THE APPLICANT TO ADDRESS ANY NEW CONDITIONS THAT MAY BE CREATED BY THE ACTIVITIES AND TO PROVIDE
ADDITIONAL ESC BMPS, OVER AND ABOVE MINIMUM REQUIREMENTS, AS MAY BE NEEDED, TO PROTECT ADJACENT PROPERTIES AND WATER QUALITY OF
THE RECEIVING DRAINAGE SYSTEM.
10. APPROVAL OF THIS PLAN IS FOR ESC ONLY. IT DOES NOT CONSTITUTE AN APPROVAL OF STORM DRAINAGE DESIGN, SIZE NOR LOCATION OF PIPES,
RESTRICTORS, CHANNELS, OR STORMWATER FACILITIES.
11. ANY DEWATERING SYSTEM NECESSARY FOR THE CONSTRUCTION OF STORMWATER FACILITIES SHALL BE SUBMITTED TO THE CITY FOR REVIEW AND
APPROVAL.
12. ANY AREAS OF EXPOSED SOILS, INCLUDING ROADWAY EMBANKMENTS, THAT WILL NOT BE DISTURBED FOR TWO DAYS DURING THE WET SEASON
(OCTOBER 1ST THROUGH APRIL 30TH) OR SEVEN DAYS DURING THE DRY SEASON (MAY 1ST THROUGH SEPTEMBER 30TH) SHALL BE IMMEDIATELY
STABILIZED WITH THE APPROVED ESC COVER METHODS (E.G., SEEDING, MULCHING, PLASTIC COVERING, ETC.) IN CONFORMANCE WITH APPENDIX D OF
THE RENTON SWDM.
13. WET SEASON ESC REQUIREMENTS APPLY TO ALL CONSTRUCTION SITES BETWEEN OCTOBER 1ST AND APRIL 30TH, UNLESS OTHERWISE APPROVED BY
THE CITY.
14. ANY AREA NEEDING ADDITIONAL ESC MEASURES, NOT REQUIRING IMMEDIATE ATTENTION, SHALL BE ADDRESSED WITHIN SEVEN (7) DAYS.
15. THE ESC BMPS ON INACTIVE SITES SHALL BE INSPECTED AND MAINTAINED AT A MINIMUM OF ONCE A MONTH OR WITHIN 24 HOURS FOLLOWING A STORM
EVENT. INSPECTION AND MAINTENANCE SHALL OCCUR MORE FREQUENTLY AS REQUIRED BY THE CITY.
16. BEFORE COMMENCEMENT OF ANY CONSTRUCTION ACTIVITY, CATCH BASIN INSERTS PER THE CITY STANDARD PLAN 216.30 SHALL BE PROVIDED FOR ALL
STORM DRAIN INLETS DOWNSLOPE AND WITHIN 500 FEET OF A DISTURBED OR CONSTRUCTION AREA, UNLESS THE RUNOFF THAT ENTERS THE INLET WILL
BE CONVEYED TO A SEDIMENT POND OR TRAP. ALL CATCH BASIN INSERTS SHALL BE PERIODICALLY INSPECTED AND REPLACED AS NECESSARY TO
ENSURE FULLY FUNCTIONING CONDITION.
17. AT NO TIME SHALL SEDIMENT ACCUMULATION EXCEED 2/3 OF THE CAPACITY OF THE CATCH BASIN SUMP. ALL CATCH BASINS AND CONVEYANCE LINES
SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING OPERATION SHALL NOT FLUSH SEDIMENT-LADEN WATER INTO THE DOWNSTREAM SYSTEM.
18. ANY PERMANENT STORMWATER FACILITY LOCATION USED AS A TEMPORARY SETTLING BASIN SHALL BE MODIFIED WITH THE NECESSARY ESC BMPS AND
SHALL PROVIDE ADEQUATE STORAGE CAPACITY. IF THE TEMPORARY FACILITY IS TO ULTIMATELY FUNCTION AS AN INFILTRATION SYSTEM IN ITS
PERMANENT STATE, THE TEMPORARY FACILITY SHALL BE ROUGH GRADED SO THAT THE BOTTOM AND SIDES ARE AT LEAST THREE FEET ABOVE THE FINAL
GRADE OF THE PERMANENT FACILITY.
19. AREAS DESIGNATED ON THE PLAN(S) CONTAINING EXISTING STORMWATER FACILITIES OR ON-SITE BMPS (AMENDED SOILS, BIORETENTION, PERMEABLE
PAVEMENT, ETC.) SHALL BE CLEARLY FENCED AND PROTECTED USING ESC BMPS TO AVOID SEDIMENTATION AND COMPACTION DURING CONSTRUCTION.
20. PRIOR TO THE BEGINNING OF THE WET SEASON (OCTOBER 1ST), ALL DISTURBED AREAS SHALL BE INSPECTED TO IDENTIFY WHICH ONES SHALL BE
SODDED OR SEEDED IN PREPARATION FOR THE WINTER RAINS. DISTURBED AREAS SHALL BE SODDED OR SEEDED WITHIN ONE WEEK OF THE BEGINNING
OF THE WET SEASON. AN EXHIBIT OF THOSE AREAS TO BE SODDED OR SEEDED AND THOSE AREAS TO REMAIN UNCOVERED SHALL BE SUBMITTED TO THE
CITY FOR REVIEW.
21. PRIOR TO FINAL CONSTRUCTION ACCEPTANCE, THE PROJECT SITE SHALL BE STABILIZED TO PREVENT SEDIMENT-LADEN WATER FROM LEAVING THE
PROJECT SITE, ALL ESC BMPS SHALL BE REMOVED, AND STORMWATER CONVEYANCE SYSTEMS, FACILITIES, AND ON-SITE BMPS SHALL BE RESTORED TO
THEIR FULLY FUNCTIONING CONDITION. ALL DISTURBED AREAS OF THE PROJECT SITE SHALL BE VEGETATED OR OTHERWISE PERMANENTLY STABILIZED.
AT A MINIMUM, DISTURBED AREAS SHALL BE SODDED OR SEEDED AND MULCHED TO ENSURE THAT SUFFICIENT COVER WILL DEVELOP SHORTLY AFTER
FINAL APPROVAL. MULCH WITHOUT SEEDING IS ADEQUATE FOR AREAS TO BE LANDSCAPED BEFORE OCTOBER 1ST.
22. ROCKERIES ARE CONSIDERED TO BE A METHOD OF BANK STABILIZATION AND EROSION CONTROL. ROCKERIES SHALL NOT BE CONSTRUCTED TO SERVE
AS RETAINING WALLS. ALL ROCKERIES IN CITY ROAD RIGHTS-OF-WAY SHALL BE CONSTRUCTED IN ACCORDANCE WITH CITY STANDARDS. ROCKERIES
OUTSIDE OF ROAD RIGHTS-OF-WAY SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-2-4.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE TESC PLANS
STA 1+00 TO 8+25 EC-2
15 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE BELOWKEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 8+25EC-2MATCHLIN
E STA 4+50 - SEE ABOVE 4+50M A T C H L IN E S T A - S E E D W G 8 0 2 +1 0
E C -1 0
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED TO BE
INSTALLED BEFORE CONSTRUCTION. AS CONSTRUCTION
PROGRESSES, CONTRACTOR SHALL INSPECT, MAINTAIN, REPAIR,
IMPROVE AND INCREASE MEASURES AS REQUIRED TO MAINTAIN
WATER QUALITY STANDARDS IN BOTH NEW AND EXISTING DRAINS.
o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX
1
2
11 12
1+00
2+00 3+00 4+008
0
3
+
0
0
804+00
805+00
BRONSON WAY NE
NE 4TH ST
o -o
o -oBRONSON WAY NEBRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-105 +0 0
6 +0 0
7+00
8+00
30+00
5
9
+
5
0
60+00
6
1
+
0
03+004 +0 0 5+00BRONSON WAY NE
WI
NDS
OR WAY
NEGRANDEY WAY
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-2-4.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE TESC PLANS
STA 8+25 TO 17+50 EC-3
16 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE BELOWMATCHLINE STA - SEE DWG 8+25EC-213+00MATCHLI
NE STA
-
SEE DWG 17+50EC-4MATCHLINE STA - SEE ABOVE13+00NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED TO BE
INSTALLED BEFORE CONSTRUCTION. AS CONSTRUCTION
PROGRESSES, CONTRACTOR SHALL INSPECT, MAINTAIN, REPAIR,
IMPROVE AND INCREASE MEASURES AS REQUIRED TO MAINTAIN
WATER QUALITY STANDARDS IN BOTH NEW AND EXISTING DRAINS.
o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-109+00
10+00
11+00
12+00
1 3 +0 030+0031+00
32+00
33+00
33+5990+0091+00BRO NSON WAY NE
13+00
14+00
15+00
1 6 +0 0
1 7 +0 0
5
0
+
0
0
5
1
+
0
0 50+0051+0052+0040+0041+00BRONSON PL
ACE NEBRONSON WAY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-2-4.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE TESC PLAN STA 17+50 TO 22+50
GRANDEY WAY TESC PLAN STA 29+80 TO 34+00 EC-4
17 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"
M A T C H L IN E S T A - S E E D W G 1 7 +5 0
E C -3
M ATCHLINE STA - SEE DW G 34+00EC-5o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED TO BE
INSTALLED BEFORE CONSTRUCTION. AS CONSTRUCTION
PROGRESSES, CONTRACTOR SHALL INSPECT, MAINTAIN, REPAIR,
IMPROVE AND INCREASE MEASURES AS REQUIRED TO MAINTAIN
WATER QUALITY STANDARDS IN BOTH NEW AND EXISTING DRAINS.
XX BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-1013
14
1518+0019+00
2 0 +0 0
2 1 +0 0
2 2 +0 046+0047+0025+002 5 +7 5
SUNSET BLVD NEB R O N S O N W A Y N E GRANDEY WAY3A
4
3B5+006+0030+00
3 1 +0 0
3 2 +0 0
33+00
3
4
+
0
059+5060+00
3+00
4+005 +0 0
6 +0 0
7+00
8
+
0
0
600+00600+71W IN D S O R W A Y N E
G R A N D E Y W A Y
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-5-6.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY TESC PLANS
STA 34+00 TO 42+50 EC-5
18 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE BELOWM
A
T
C
H
LIN
E S
T
A
- S
E
E D
W
G
34+00
W
-6
KEY MAP
SCALE: 1" = 400'-0"38+50MATCHLINE STA - SEE DWG 38+50SD-7MATCHLINE STA - SEE DWG 42+50SD-9o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX34+003 5 +0 0
36+00
37+00
3
8+
00100+00100+75G R A N D E Y W A Y
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-1039+00
40+00
41+00
4 2 +0 0200+00200+75GRANDEY WAY
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-5-6.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY TESC PLAN STA 42+50 TO 47+00
BRONSON PLACE NE TESC PLAN STA 80+00 TO 83+25 EC-6
19 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 42+50EC-5KEY MAP
SCALE: 1" = 400'-0"MATCHLI
NE STA
-
SEE DWG
5
4
+0
0
EC-
7
o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX
5
19+0020+0043+00
44+00 4 5 +0 0
4 6 +0 0
4 7 +0 0
G R A N D E Y W A Y BRONSON WAY NENOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-101 5 +0 0 16+0050+00
51+00
52+00
5 3 +0 0
5 4 +0 0
52+0053+00
54+00 55+00BRONSON PLACE NE
B R O N S O N W A Y N E
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-7-10.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024 RLO BRONSON PLACE NE TESC PLAN STA 54+00 TO 57+50
WINDSOR PLACE NE TESC PLAN STA 80+00 TO 83+25 EC-7
20 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 54+00EC-6KEY MAP
SCALE: 1" = 400'-0"
M A T C H L I N E S T A
- S E E D W G
8 3 +2 5
E C -8
o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX
67
54+00
55+00
5 6 +0 0
5
7
+
0
0
90+00
90+75
B R O N S O N P L A C E N E
WINDSOR PLACE NENOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-108
54+0055+0079+80 80+00 81+00
82+00
83+0057+0656+0057+007 0 +0 0
71+0072+0090+0090+75WINDSOR PLACE NE
BRONSON PLACE NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-7-10.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR PLACE NE TESC PLAN STA 83+25 TO 88+01
WINDSOR WAY NE TESC PLAN STA 60+00 TO 64+50 EC-8
21 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"MATCHLI
NE STA - SEE DWG 83+25EC-7MATCHLINE STA - SEE DWG 64+50EC-9o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
TREE PROTECTION
XX
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-108 4 +0 0
85+00 86+00
87+00
8 8 +0 088+01
73+007 2 +0 0
7 3 +0 0
74+00 75+00 75+75
85+0086+004
0
0
+
0
0
4
0
1
+
0
0
5 0 0 +0 0
5 0 1 +0 0
WINDSOR PLACE NE
5+006+0030+00
59+50
60+00
61+00
62+00
63+00
64+00
4+0065+00 66+00BRONSON WAY NEWINDSOR WAY NEo-oo-oo-o
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-7-10.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR WAY NE TESC PLANS
STA 64+50 TO 73+50 EC-9
22 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"MAT
CHL
I
NE
S
T
A
-
S
E
E
ABOVE
M A T C H L IN E S T A - S E E D W G 7 3 +5 0
E C -1 0
6
9
+
5
0MATCHLINE STA - SEE DWG 64+50EC-8MATCHLINE STA - SEE BELOW69+50o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-1010 87+007 0 +0 0
7 1 +0 0 72+00
7
3
+
0
0 75+0075+758 2 +0 0
8
3
+
0
0
8 4 +0 0
8 5 +0 0
8 6 +0 0
400+00401+00500+00501+00WINDSOR WAY NE
9
65+00
66+00
67+00
6 8 +0 0
6 9 +0 0
8 0 +0 0
8 1 +0 043+00300+00300+75WINDSOR WAY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-7-10.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR PLACE NE TESC PLAN STA 73+50 TO 75+76
BRONSON WAY NE TESC PLAN STA 800+00 TO 802+10 EC-10
23 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 73+50EC-9MATCHLINE STA - SEE DWG 802+10EC-2o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
POTHOLE INFORMATION ON DWG G-12
XX
NOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES REQUIRED
TO BE INSTALLED BEFORE CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, CONTRACTOR SHALL
INSPECT, MAINTAIN, REPAIR, IMPROVE AND INCREASE
MEASURES AS REQUIRED TO MAINTAIN WATER QUALITY
STANDARDS IN BOTH NEW AND EXISTING DRAINS.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NEEC-7EC-6EC-2EC-2E C -3 EC-3EC-4
EC-4EC-5E C -5 EC-6EC-7
EC-8E C -8
E C-9
E C -9
E
C-10
EC-10EDMONDS AVE NE16A
16B
88+00
88+01 7 5 +7 6
74+00
7 5 +0 0
WINDSOR PLACE NE
17
18
800+00 801+00
802+00
00701+00BRONSON WAY NE
VUEMONT PL NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_EC-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO DITCH TESC PLANS EC-11
24 85
B. Ochiltree, P.E.
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186520+00
21+00
GRANDEY WAYo-oo-oNOTES:
1. EC SHEETS SHOW MINIMUM TESC MEASURES TO BE
INSTALLED PRIOR TO CONSTRUCTION. AS
CONSTRUCTION PROGRESSES, ADDITIONAL TESC
MEASURES SHALL BE INSTALLED TO PROTECT BOTH
NEW AND EXISTING DRAINS.
o-o
LEGEND:
CATCH BASIN INSERT PER COR STD. PLAN 216.30
STRAW WATTLES PER COR STD. PLAN 213.40
SILT FENCE PER COR STD. PLAN 214.00
AND STAKE AND WIRE FENCE
PER COR STD PLAN 212.00
POTHOLE INFORMATION ON DWG G-12
TREE PROTECTION
XX
1 0 +0 0
1 1 +0 0
3 2 +0 0
3 3 +0 0
33+599
1
+
5
090+009
1
+
0
0
B R O N S O N W A Y N E o-oo-oo-oo-o14+0015+0050+004 0 +0 0
41+00
4
2
+
0
0
43+00
300+00
BRONSON WAY NEo-o o-o
o-oo-oo-oo-oo-o
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON WAY NE WATER MAIN PLAN AND PROFILE
STA 0+80 TO 4+50 W-1
25 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 4+50 W-2MATCHLINE STA - SEE DWG 4+50 W-2
KEY MAP
SCALE: 1" = 400'-0"
M A T C H L IN E S T A - S E E D W G 8 0 2 +1 0
W -1 8
EX GRADE AT C/L
RIGHT OF WAY
200
195
190
185
180
175
170
200
195
190
185
180
175
170
EX 8" W EX 14" FO, IE 190.62±CONNECT TO EX 8" DI3'MIN8" W
DI EX GASEX GASEX W1" WS1" WS1" WS1" WSFIRE HYDRANT ASSEMBLY1" WS1" WS1" WSEX 6" W
ESTIMATED45° HORIZONTAL BENDEX 4" GAS, IE 188.82±11.25° HORIZONTAL BENDEX GRADE AT C/L
RIGHT OF WAY
MAINTAIN POSITIVE
SLOPE TO STA 1+25 INSTALL 6" DI FOR FH
ASSEMBLY W/ 12" MIN
CLR BELOW EX 6" W
8" W IE 187.65±
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD POLYPIGGING STATIONDEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 325 LF - 8" RJ DI W WITH POLYWRAP
1+00 2+00 3+00 4+00
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY EXACT LOCATION PRIOR
TO STARTING WORK. ANY DISCREPANCIES FOUND IN THE
FIELD FROM THOSE SHOWN HERE SHALL BE REPORTED TO
THE OWNER PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX, AND
BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND
1" SERVICE LINE AND SETTER WITH NEW PRV IN SEPARATE
METER BOX, PER DETAIL 1, DWG W-19
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE WITH NEW PRV IN SEPARATE METER
BOX (TYP) AND SETTER PER DETAIL 1, DWG W-20
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2" SERVICE
LINE AND SETTER PER COR STANDARD PLAN 320.2.
PROTECT EXISTING SURVEY MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING SURVEY MONUMENT IS
DISTURBED. OWNER TO REPLACE.
CONTRACTOR TO FURNISH MATERIALS.
INSTALL POLYPIG STATION
PER COR STANDARD PLAN 300.7.
SEE SUGGESTED POLYPIGGING
PLAN, DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
1
2
11 12
8
0
3
+
0
0
804+00
805+00
1
5
3
BRONSON WAY NE
NE 4TH ST
6
INSTALL
1 - 8" CAP, MJ,
ON EX 8" DI
TYPE C 7 TYPE C 7 TYPE A 7
TYPE A7
TYPE B 7
1
TYPE C7
STA 1+26.39, OFFSET 7.83' RT
CONNECT TO EXISTING 8" DI W/
1 - 8" SOLID SLEEVE, RJ x RJ
1 -8" DI SPOOL, LF AS REQ'D
SEE DETAIL 1/W-22 FOR CONNECTION DETAIL
1
TYPE C 7
STA 0+87.9
OFFSET 0.34' RT
10
STA 1+00
OFFSET 17.10' RT
10
2
STA 3+93.8
OFFSET 0.53' RT
10
STA 3+70.61, OFFSET 2.98' LT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY-24.86' LT
6
1
STA 1+31.36',
OFFSET 1.25' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 1+54.52
OFFSET 3.34' LT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
16 LF - 8" DI
8 LF - 8" DI
12STA 1+39.21,
OFFSET 0.30' LT
9 LF - 8" DI
216 LF - 8" DI
154 LF - 8" DI
FOR RESTORATION,
SEE R-SHEETS, TYP
SEGMENT 1 W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLINE STA - SEE DWG 8+25W-3DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON WAY NE WATER MAIN PLAN AND PROFILE
STA 4+50 TO 8+25 W-2
26 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 4+50 W-1MATCHLINE STA - SEE DWG 8+25 W-3MATCHLINE STA - SEE DWG 4+50W-1KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
195
190
185
180
175
170
165
195
190
185
180
175
170
165
200 200
EX GRADE AT C/L
RIGHT OF WAY
EX GRADE AT C/L
RIGHT OF WAY
IE 183.92±EX WEX 8" SD, IE 185.8±EX 4" WEX GAS1" WS8" x 8" TEE8" x 8" TEE12" MIN
6" MIN W/
ETHAFOAM
PAD 1" WS1" WS11.25° HORIZONTAL BEND45° HORIZONTAL BEND45° HORIZONTAL BEND12" SD, IE 189.8±MAINTAIN POSITIVE
SLOPE TO STA 1+25 EX 8" SS, IE 171.7±3'MIN8" W
DI FIRE HYDRANT ASSEMBLYIE 184.33±
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 374 LF - 8" RJ DI W WITH POLYWRAP
5 +0 0
6 +0 0
7+00
8+00
3
DEFLECT PIPE MAXIMUM 9" PER
18' OF HORIZONTAL LENGTH
6 6
WI
NDS
OR WAY
NEGRANDEY WAY NETYPE C7
TYPE C 7
1
1
1
TYPE C7
FOR CONTINUATION,
SEE DWG W-14
11 STA 5+86.1,
OFFSET 0.58' LT
10 STA 5+56.7,
OFFSET
0.55' RT
11 STA 6+30.8,
OFFSET 6.14' LT
10 STA 7+48.9,
OFFSET 0.60' RT
STA 7+87.1,
OFFSET 6.55' LT
1- 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK2
STA 6+07.7, OFFSET 6.68' LT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 5+82.6, OFFSET 3.66' LT
1 - 8" x 8" TEE, FL x FL
W/ THRUST BLOCK
2 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
SEE W-6 FOR FITTING
CALLOUTS ON GRANDEY WAY
6
26 LF - 8" DI
1 5 8 L F - 8" DI
5 9 L F - 8 " D I
75 LF -8" DI26 LF
-
8"
DI
24 LF - 8" DI
STA 8+06.1,
OFFSET 11.82' LT
1- 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 7+63.5, OFFSET 6.06' LT
1 - 8"x6" TEE, FL x FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL X RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY,
OFFSET 24.79' RT
STA 5+24.7, OFFSET 3.0' LT
1 - 8" x 8" TEE, FL x FL
W/ THRUST BLOCK
2 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
SEE W-14 FOR FITTING
CALLOUTS ON WINDSOR WAY
FOR CONTINUATION,
SEE DWG W-6
B RO NS O N W AY NE
FOR
RESTORATION,
SEE R-SHEETS,
TYPSEGMENT 2SEGMENT 1
SEGMENT 3
5+00 6+00 7+00 8+00
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY EXACT LOCATION PRIOR
TO STARTING WORK. ANY DISCREPANCIES FOUND IN THE
FIELD FROM THOSE SHOWN HERE SHALL BE REPORTED TO
THE OWNER PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX, AND
BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND
1" SERVICE LINE AND SETTER WITH NEW PRV IN SEPARATE
METER BOX, PER DETAIL 1, DWG W-19
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE WITH NEW PRV IN SEPARATE METER
BOX (TYP) AND SETTER PER DETAIL 1, DWG W-20
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2" SERVICE
LINE AND SETTER PER COR STANDARD PLAN 320.2.
PROTECT EXISTING SURVEY MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING SURVEY MONUMENT IS
DISTURBED. OWNER TO REPLACE.
CONTRACTOR TO FURNISH MATERIALS.
INSTALL POLYPIG STATION
PER COR STANDARD PLAN 300.7.
SEE SUGGESTED POLYPIGGING
PLAN, DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLINE STA - SEE DWG 13+00W-4DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON WAY NE WATER MAIN PLAN AND PROFILE
STA 8+25 to 13+00 W-3
27 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 8+25 W-2MATCHLINE STA - SEE DWG 8+25W-2MATCHLINE STA - SEE DWG 13+00 W-4
7
KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
9+00
10+00
11+00
12+00
1 3 +0 0
5
B RONSON WAY NE
BRONSON WAY NE
DEFLECT PIPE MAXIMUM
9" PER 18' OF
HORIZONTAL LENGTH
DEFLECT PIPE
MAXIMUM 9" PER 18' OF
HORIZONTAL LENGTH
7
TYPE A
TYPE C7
7TYPE A
TYPE B7
7TYPE A
TYPE A
7 TYPE A7TYPE B
6
STA 8+82.8, OFFSET 8.07' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK STA 9+66.7, OFFSET 8.97' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
10 STA 10+54.1,
OFFSET 0.19' RT
10 STA 10+25.4,
OFFSET 0.25' RT
3
STA 11+21.6, OFFSET 11.57' RT
1 - 8" x 6" TEE, FL x FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 14.61' RT
STA 11+32.6, OFFSET 12.93' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
283 LF - 8" DI
156 LF - 8" DI
248 LF - 8" DI
11 LF - 8" DI
FOR RESTORATION,
SEE R-SHEETS, TYP
SEGMENT 1
175
170
165
160
155
150
175
170
165
160
155
150
180
185
180
185
EX GRADE AT C/L
RIGHT OF WAY1" WS11.25° HORIZONTAL BEND11.25° HORIZONTAL BEND11.25° HORIZONTAL BENDEX WEX WEX WEX WFIRE HYDRANT ASSEMBLY1" WS1" WS1" WS1" WS1" WS1" WS1" WS12" SD, IE 172.1412" SD, IE 167.25EX SD12"MINMAINTAIN POSITIVE
SLOPE TO STA 1+25EX SS, IE 167.7±8" W
DI 3'MIN8" W, IE 173.70
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
APPROX 475 LF - 8" RJ DI W WITH POLYWRAP
9+00 10+00 11+00 12+00 13+
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY EXACT LOCATION PRIOR
TO STARTING WORK. ANY DISCREPANCIES FOUND IN THE
FIELD FROM THOSE SHOWN HERE SHALL BE REPORTED TO
THE OWNER PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX, AND
BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND
1" SERVICE LINE AND SETTER WITH NEW PRV IN SEPARATE
METER BOX, PER DETAIL 1, DWG W-19
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE WITH NEW PRV IN SEPARATE METER
BOX (TYP) AND SETTER PER DETAIL 1, DWG W-20
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2" SERVICE
LINE AND SETTER PER COR STANDARD PLAN 320.2.
PROTECT EXISTING SURVEY MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING SURVEY MONUMENT IS
DISTURBED. OWNER TO REPLACE.
CONTRACTOR TO FURNISH MATERIALS.
INSTALL POLYPIG STATION
PER COR STANDARD PLAN 300.7.
SEE SUGGESTED POLYPIGGING
PLAN, DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLI
NE STA
-
SEE DWG 17+50W-5DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON WAY NE WATER MAIN PLAN AND PROFILE
STA 13+00 TO 17+50 W-4
28 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 13+00W-3MATCHLINE STA - SEE DWG 17+50 W-5MATCHLINE STA - SEE DWG 13+00 W-3
KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
165
160
155
150
145
140
165
160
155
150
145
140
170 170
EX GRADE AT C/L
RIGHT OF WAY
IE 151.8
6" IE 149.911.25° HORIZONTAL BEND11.25° HORIZONTAL BENDEX WEX WEX WEX 4" WEX WFIRE HYDRANT ASSEMBLY18" SD, 153.06EX 18" SD, IE 154.89SEE PLAN NOTE8" x 8" TEE12" SD, IE 149.61" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WS12" SD, IE 152.012" MIN
MAINTAIN
POSITIVE
SLOPE TO
STA 1+25 EX SS, IE 144.52±8" W
DIEX 8" SS, IE 148.45±MAINTAIN
POSITIVE
SLOPEEX 8" SS, IE 146.32±22.5° HORIZONTAL BEND3'-0"MIN12"MIN12" MINEX 6" SD, IE UNKNOWN8" W IE 155.08
PROVIDE 6" MINIMUM CLR
ABOVE PROPOSED STORM
W/ ETHAFOAM PAD
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTHFIRE HYDRANT ASSEMBLYEX SD
ESTIMATED
DEPTH
APPROX 460 LF - 8" RJ DI WITH POLYWRAP EX 8" SS+00 14+00 15+00 16+00 17+00
6
5
3
B R O N S O N W A Y N E
BRONSON PL
ACE NE7 TYPE A
7 TYPE A
7
TYPE C
7 TYPE C
7 TYPE B
7TYPE B1
1
1
TYPE A
7 TYPE B
7 TYPE B
7
TYPE A
7
STA 13+74.9, OFFSET 12.59' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
TYPE B7
TYPE C7
STA 15+77.5, OFFSET 10.57' RT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY, +
OFFSET 31.89' RT
FOR CONTINUATION, SEE DWG W-10
STA 15+10.1,
OFFSET 6.85' RT
10
STA 17+38.5, OFFSET 9.94' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
2
STA 15+36.6, OFFSET 14.46' RT
1 - 8" x 8" TEE, FL x FL
W/ THRUST BLOCK
3 - 8" GATE VALVE, FL x RJ
SEE W-10 FOR FITTING
CALLOUTS ON BRONSON PL NE
STA 15+46.2, OFFSET 16.32' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 14+28.97,
OFFSET 0.0'
10
DEFLECT PIPE MAXIMUM 9" PER
18' OF HORIZONTAL LENGTH
1 6 5 L F - 8 " D I
3 3 L F - 8 " D I166 LF - 8" DI
8 LF -
8" DI
FOR RESTORATION,
SEE R-SHEETS, TYP
EX WATER SHALL BE
ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE
ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP
EXISTING STORM AS REQUIRED
SEGMENT 4S E G M E N T 1
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY EXACT LOCATION PRIOR
TO STARTING WORK. ANY DISCREPANCIES FOUND IN THE
FIELD FROM THOSE SHOWN HERE SHALL BE REPORTED TO
THE OWNER PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX, AND
BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND
1" SERVICE LINE AND SETTER WITH NEW PRV IN SEPARATE
METER BOX, PER DETAIL 1, DWG W-19
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE WITH NEW PRV IN SEPARATE METER
BOX (TYP) AND SETTER PER DETAIL 1, DWG W-20
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2" SERVICE
LINE AND SETTER PER COR STANDARD PLAN 320.2.
PROTECT EXISTING SURVEY MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING SURVEY MONUMENT IS
DISTURBED. OWNER TO REPLACE.
CONTRACTOR TO FURNISH MATERIALS.
INSTALL POLYPIG STATION
PER COR STANDARD PLAN 300.7.
SEE SUGGESTED POLYPIGGING
PLAN, DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON WAY NE WATER MAIN PLAN AND PROFILE
STA 17+50 TO 22+50 W-5
29 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
M A T C H L IN E S T A - S E E D W G 1 7 +5 0
W -4
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 17+50 C-5
EX GRADE AT C/L
RIGHT OF WAY
13
14
1518+0019+00
2 0 +0 0
2 1 +0 0
2 2 +0 0
7
6
3
1
2
B R O N S O N W A Y N E
SUNSET BLVD NEGRANDEY WAY NE7 TYPE C
7 TYPE C
7 TYPE C
7 TYPE C 7TYPE B
7TYPE B
7 TYPE A
7 TYPE C
FOR CONTINUATION,
SEE DWG W-9
7 TYPE A
7TYPE C
10
STA 18+94.1, OFFSET 7.12' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 18+75.3, OFFSET 8.13' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
10
STA 20+26.5,
OFFSET 1.16' RT10
STA 20+26.3,
OFFSET 0.0'10
STA 20+31.4, OFFSET 5.63' RT
1 - 8" x 8" TEE FL x FL
W/ THRUST BLOCK
3 - 8" GATE VALVE, FL x RJ
SEE W-9 FOR FITTING
CALLOUTS ON GRANDEY WAY
1
STA 19+08.4, OFFSET 6.40' LT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 19+52.2,
OFFSET 0.0'
STA 22+2.5,
OFFSET 0.19' LT10
INSTALL 1 - 6" CAP,
MJ ON EX 6" CI
39 LF - 8" DI
8 LF -
8" DI
1 3 5 L F - 8 " D I
1 2 1 L F - 8 " D I
20 LF -
8" DI
20 LF -8" DI
54 LF - 8" DI78 LF
-
8"
DI
1 - 1" AIR AND VACUUM RELEASE
VALVE ASSEMBLY
PER COR STD PLAN 340.3
STA 18+44.8, OFFSET 7.86' RT
CLEAR 3' x 3' AREA OF HEDGE AS
REQUIRED FOR CONSTRUCTION
OF ASSEMBLY
STA 18+24.4, OFFSET 11.6' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 18+4.2,
OFFSET 0.17' LT
FOR RESTORATION,
SEE R-SHEETS, TYP
REMOVE EX 6"
GATE VALVE
AND INSTALL
BLIND FLANGE
ON EX TEE
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
STA 22+21.6, OFFSET 7.17' LT
CONNECT TO EX 12" CI WATER MAIN W/
1 - 12" x 8" TAPPING TEE AND AND VALVE, FL x RJ
W/ THRUST BLOCK
SEE DETAIL 2/W-22 FOR CONNECTION DETAILSSEGMENT 2S E G M E N T 1
1 - 8" SOLID SLEEVE, RJ RJ
STA 21+84.55, OFFSET 6.62' LT
STA 21+73.5, OFFSET 6.67' LT
1 - 8" 45° VERTICAL BENDS, RJxRJ
W/ VERTICAL THRUST BLOCK
STA 21+66.90, OFFSET 6.65' LT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 8" NIPPLE, LF AS REQUIRED
1 - 8" ADAPTER, FL x RJ
1 - 8" 45° VERTICAL BEND, FL x RJ
W/ VERTICAL THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY,
OFFSET 23.33' RT
STA 21+77.6
OFFSET 6.65' LT
12
21+00 22+00
135
130
125
120
115
110
105
135
130
125
120
115
110
105
EX GRADE AT C/L
RIGHT OF WAY
6" IE 115.85±EX WEX WEX WEX 2" GAS, IE 114.08±1" WS1" WS12" SD, IE 114.44FIRE HYDRANT ASSEMBLYCONNECT TO EX 12" CI WEX SDMAINTAIN
POSITIVE
SLOPE EX 8" SS,IE 105.41±8" W
DI EX 2" P, IE 116.00±45° VERTICAL BEND8" SOLID SLEEVEIE 112.95
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD POLYPIGGING STATIONPROVIDE 6" MINIMUM
CLR W/ ETHAFOAM PAD
CONTRACTOR TO VERIFY45° VERTICAL BENDAPPROX 175 LF - 8" RJ DI W WITH POLYWRAP
160
155
150
145
140
135
130
160
155
150
145
140
135
130
EX GRADE AT C/L
RIGHT OF WAY
IE 134.12±22.5° HORIZONTAL BEND11.25° HORIZONTAL BEND45° HORIZONTAL BEND22.5° HORIZONTAL BENDEX WEX WEX WEX WEX WEX W8" x 8" TEE1" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WSMAINTAIN
POSITIVE
SLOPEEX 8" SS, IE 142.92±8" W
DI1" AIR VAC ASSEMBLYMAINTAIN
POSITIVE
SLOPE
TRENCH DAM, TYP
PER DETAIL 1/G-13
3'-0"MINDEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 310 LF - 8" RJ DI W WITH POLYWRAP
18+00 19+00 20+00
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY EXACT LOCATION PRIOR
TO STARTING WORK. ANY DISCREPANCIES FOUND IN THE
FIELD FROM THOSE SHOWN HERE SHALL BE REPORTED TO
THE OWNER PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR STANDARD
PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX, AND
BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND
1" SERVICE LINE AND SETTER WITH NEW PRV IN SEPARATE
METER BOX, PER DETAIL 1, DWG W-19
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE WITH NEW PRV IN SEPARATE METER
BOX (TYP) AND SETTER PER DETAIL 1, DWG W-20
TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2" SERVICE
LINE AND SETTER PER COR STANDARD PLAN 320.2.
PROTECT EXISTING SURVEY MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING SURVEY MONUMENT IS
DISTURBED. OWNER TO REPLACE.
CONTRACTOR TO FURNISH MATERIALS.
INSTALL POLYPIG STATION
PER COR STANDARD PLAN 300.7.
SEE SUGGESTED POLYPIGGING
PLAN, DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
M ATCHLINE STA - SEE DW G 34+00W -7DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
GRANDEY WAY NE WATER MAIN PLAN AND PROFILE
STA 29+80 TO 34+00 W-6
30 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 34+00 W-7
KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
3A
4
3B5+006+0030+00
3 1 +0 0
3 2 +0 0
33+00
3
4
+
0
0
7
7
6
3
G R A N D E Y W A Y N EBRONSON WAY NEW IN D S O R W A Y N E
TYPE B
7TYPE A
TYPE C
TYPE C7
TYPE C 7
TYPE C 7
TYPE B
7TYPE A7
TYPE B7
TYPE C 7
1
1
FOR CONTINUATION,
SEE W-1
2
1
STA 32+16,
OFFSET 0.0'
10
STA 32+46.4, OFFSET 7.16', LT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 32+80, OFFSET 5.92' LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 32+91.6, OFFSET 4.27', RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 33+80.5, OFFSET 5.95, RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
12
5 LF - 8" DI
STA 30+13.4
OFFSET 4.87' LT
2 3 7 L F - 8 " D I
CONTRACTOR TO REMOVE AND
WASTEHAUL EX WATER MAIN AS
REQUIRED FOR INSTALLATION OF
STORM LINE, CAP/PLUG OPEN ENDS
PER SP 7-09.3(26)
18 LF
8" DI
17 LF - 8" DI
15 LF - 8" DI
85 LF - 8" DI
FOR
CONTINUATION,
SEE W-14
SEE DWG W-2 FOR
STATION AND FITTING
LABELS ALONG
BRONSON WAY NE
STA 33+08.4, OFFSET 4.20' LT
1 - 8" SOLID SLEEVE, RJ x RJ
DEFLECT PIPE MAX
9" PER 18' OF
HORIZONTAL
LENGTH
FOR RESTORATION,
SEE R-SHEETS, TYP
STA 32+63.5, OFFSET 6.02', LT
1 - 8" x 6" TEE, FL x FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 24.79' RTSEGMENT 1S E G M E N T 3
S E G M E N T 2
190
185
180
175
170
165
160
190
185
180
175
170
165
160
SEE DWG W-2
FOR TEE
EX GRADE AT C/L
RIGHT OF WAY
EX WEX WEX W1" WS1" WS1" WS8" x 8" TEEMAINTAIN
POSITIVE
SLOPEPOLYPIGGINGSTATION
TRENCH DAM,
PER DETAIL 1/G-13, TYP8" SOLID SLEEVEEX GASAPPROX 147 LF - 8" RJ DI W WITH POLYWRAP
170
165
160
155
150
145
140
170
165
160
155
150
145
140
EX GRADE AT C/L
RIGHT OF WAY
EX GASEX GASEX W11.25° HORIZONTAL BEND45° HORIZONTAL BEND22.5° HORIZONTAL BENDFIRE HYDRANT ASSEMBLY1" WS1" WS1" WSMAINTAIN
POSITIVE
SLOPE EX 8" SS, IE 145.68±3'MIN8" W
DI 1" WSAPPROX 155 LF - 8" RJ DI W WITH POLYWRAP
150
145
140
135
130
125
120
150
145
140
135
130
125
120
EX GRADE AT C/L
RIGHT OF WAY
EX 1" GASEX W22.5° HORIZONTAL BEND1" WS1" WS1" WSMAINTAIN
POSITIVE
SLOPEEX 8" SS, IE 137.48±12"MIN12" SD, IE 144.268" W, IE 143.09
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
APPROX 96 LF - 8" RJ DI W WITH POLYWRAP
30+00 31+00 32+00 33+00 34+
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLINE STA - SEE DWG 38+50W-8DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
GRANDEY WAY NE WATER MAIN PLAN AND PROFILE
STA 34+00 TO 38+50 W-7
31 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 38+50 W-8
M
A
T
C
H
LIN
E S
T
A
- S
E
E D
W
G
34+00
W
-6
MATCHLINE STA - SEE DWG 34+00 W-6
KEY MAP
SCALE: 1" = 400'-0"
STA 35+35.5, OFFSET 6.61', RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
EX GRADE AT C/L
RIGHT OF WAY+00 35+00 36+00 37+00 38+00
140
135
130
125
120
115
110
140
135
130
125
120
115
EX GRADE AT C/L
RIGHT OF WAYEX WEX SD, IE 118.24EX WEX WEX W22.5° HORIZONTAL BEND22.5° HORIZONTAL BEND22.5° HORIZONTAL BEND (ROTATED)22.5° HORIZONTAL BEND45° HORIZONTAL BENDFIRE HYDRANT ASSEMBLY12" SD, IE 119.271" WS1" WS1" WS1" WS12" MINEX 8" SS, IE 121.44±EX 8" SS, IE 119.24±EX 8" SS, IE 115.68EX 8" SS, IE 114.22±MAINTAIN
POSITIVE
SLOPE
MAINTAIN
POSITIVE
SLOPE
12" MIN 12" SD, IE 118.878" W, IE 117.10±
PROVIDE 6" MIN CLR W/
ETHAFOAM PAD
8" W
DI
INSTALL 6" DI FOR FH
ASSEMBLY W/ 12" MIN
CLR BELOW EX 6" W
TRENCH DAM,
PER DETAIL 1/G-13, TYP
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
EX 6" WATER,
ESTIMATEDEX 8" SS, IE 121.35±APPROX 445 LF - 8" RJ DI W WITH POLYWRAP22.5° VERTICAL BEND22.5° VERTICAL BEND (ROTATED)3'MIN8" W, IE 117.07±
PROVIDE 6" MIN CLR W/
ETHAFOAM PAD EX 8" SS, ESTIMATED34+003 5 +0 0
36+00
37+00
3
8
+
0
0
7
10
3
5
6
G R A N D E Y W A Y N E
TYPE C
1
TYPE C 7
TYPE C7
TYPE C7
TYPE B 7
STA 36+31.0, OFFSET 5.28', RT
1 - 8" 22.5° BEND, RJ x RJ
ROTATE AS REQUIRED
W/ VERTICAL THRUST BLOCK
STA 34+61.2, OFFSET 3.84', RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 34+90.7,
OFFSET 0.30' RT
2
STA 37+67.4,
OFFSET 0.37' RT
10
STA 36+60.6, OFFSET 9.58', RT
1 - 8"x6" TEE, FL x FL W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1- 8" ADAPTER, FL X RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 23.91' LT
STA 37+7.45, OFFSET 9.03', RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
1
77 LF - 8" DI7 7 L F - 8 " D I6 2 L F - 8 " D I
29 LF
8" DI
430 L
F - 8" DI
45 LF - 8" DI
3 0 L F - 8" DI
12" SD, IE 117.69
6" W, IE 116.69
PROVIDE 6" MIN CLR W/
ETHAFOAM PAD, DEFLECT PIPE
MAX 9" PER 18" OF HORIZ LENGTH
FOR RESTORATION,
SEE R-SHEETS, TYP
STA 37+33.5, OFFSET 6.01, LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
23 LF - 8" DI
8 LF- 8" DI
8'-6 1/4"S E G M E N T 2
1 - 8" 22.5° VERTICAL BEND,
RJ x RJ, W/ VERTICAL
THRUST BLOCK
STA 35+60.08,
OFFSET 9.82' RT
1 - 8" 22.5° VERTICAL BEND,
RJ x RJ, W/ VERTICAL
THRUST BLOCK
STA 36+22.73,
OFFSET 6.88' RT
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
GRANDEY WAY NE WATER MAIN PLAN AND PROFILE
STA 38+50 TO 42+50 W-8
32 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 42+50 W-9MATCHLINE STA - SEE DWG 38+50 W-7MATCHLINE STA - SEE DWG 42+50W-9MATCHLINE STA - SEE DWG 38+50W-7KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
39+00
40+00
41+00
4 2 +0 0
3
GRANDEY WAY NE
TYPE C 7
TYPE C 7
TYPE C 7
TYPE C 7
TYPE B7
TYPE B7
TYPE C 7
TYPE B 7
2
STA 40+16.0,
OFFSET 0.14' RT 10
STA 41+62.9, OFFSET 3.16', LT
1 - 8" x 6" TEE, FL x FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 26.14' RT
STA 41+76.5, OFFSET 2.17', RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
DEFLECT PIPE MAXIMUM 9" PER
18' OF HORIZONTAL LENGTH
14 LF
8" DI
FOR RESTORATION,
SEE R-SHEETS, TYP
EX WATER SHALL BE ABANDONED
IN PLACE AND PROPOSED WATER
SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM
STRUCTURE IS INSTALLED
EX WATER SHALL BE
ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE
ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE
IS INSTALLED
8'-6 1/4"S E G M E N T 2
39+00 40+00 41+00 42+00
140
135
130
125
120
115
140
135
130
125
120
115
EX GRADE AT C/L
RIGHT OF WAYEX WEX WEX WEX W11.25° HORIZONTAL BEND1" WS1" WS1" WS1" WS1" WS1" WS1" WS1" WS12" SD, IE 122.0212" SD, IE 125.5612" MIN FIRE HYDRANTASSEMBLYMAINTAIN
POSITIVE
SLOPE 3'MIN8" W
DI
6" W, IE 127.12
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 400 LF - 8" DI W WITH POLYWRAP
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
S D-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
GRANDEY WAY NE WATER MAIN PLAN AND PROFILE
STA 42+50 TO 47+00 W-9
33 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 42+50W-8MATCHLINE STA - SEE DWG 42+50 W-8
KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
S E G M E N T 2
SEGMENT 15
19+0020+0043+00
44+00 45+00
4 6 +0 0
4 7 +0 03
6
6
1
G R A N D E Y W A Y N E BRONSON WAY NETYPE C7 TYPE A7
TYPE A7
TYPE B7
TYPE B7
TYPE C7
TYPE B 7
1
2
STA 43+45.5, OFFSET 5.33', LT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
DEFLECT PIPE
MAXIMUM 9" PER 18' OF
HORIZONTAL LENGTH
FOR CONTINUATION,
SEE DWG W-5
STA 46+84.3,
OFFSET 0.61' RT
STA 46+85.4,
OFFSET 0.32', RT
10
10
STA 46+21.0, OFFSET 8.21' LT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 25.90' LT
FOR CONTINUATION,
SEE DWG W-5
5
167 LF - 8" DI
272 LF - 8" DI
6 LF - 8" DI
6 LF - 8" DI
STA 46+74.3, OFFSET 6.66' LT
1 - 8" SOLID SLEEVE, RJ x RJ
12 STA 46+68.3
OFFSET 7.25' LT
4 7 L F - 8 " DI
FOR RESTORATION,
SEE R-SHEETS, TYP
SEE DWG W-5 FOR
FITTINGS CALLOUT ON
BRONSON WAY NE
140
135
130
125
120
115
140
135
130
125
120
115
SEE DWG
W-5 FOR
TEE IE
EX GRADE AT C/L
RIGHT OF WAYEX WEX WEX WEX WEX 6" W11.25° HORIZONTAL BEND1" WS1" WS1" WS1" WS1" WS1" WS1" WSEX 18" SD, IE 125.1018" SD, IE 124.75FIRE HYDRANTASSEMBLY8" x 8" TEEMAINTAIN
POSITIVE
SLOPE
EX 4" W
DEFLECT PIPE MAX 9"
PER 18' OF HORIZ LENGTH
INSTALL 6" DI FOR FH
ASSEMBLY W/ 12" MIN
CLR BELOW EX 4" W
8" W, IE 127.61
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD3'MIN8" W
DI POLYPIGGING STATION8" SOLID SLEEVEEX 8" SS, ESTIMATEDDEFLECT PIPE
MAX 9" PER 18 OF
HORIZ LENGTH
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
APPROX 424 LF - 8" DI W WITH POLYWRAP
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
43+00 44+00 45+00 46+00 47+00 W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
S D-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-10-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON PL NE WATER MAIN PLAN AND PROFILE
STA 50+00 TO 54+00 W- 10
34 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 54+00 W-11MATCHLI
NE STA
-
SEE DWG
5
4
+0
0
W-
1
1
KEY MAP
SCALE: 1" = 400'-0"
FOR CONTINUATION,
SEE DWG W-4
EX GRADE AT C/L
RIGHT OF WAY
175
180
170
165
185
190
195
175
180
170
165
185
190
195
12" SD, IE 181.8612" SD, IE 177.151" WS1" WSEX MH06318" W, IE 183.36
PROVIDE 6" MIN
CLR W/
ETHAFOAM PAD
8" W, IE 178.92
PROVIDE 6" MIN CLR
W/ ETHAFOAM PADEX WEX SD, ESTIMATEDEX SD, ESTIMATED1" WSAPPROX 100 LF - 8" DI W WITH POLYWRAPEX 6" SS1 5 +0 0 16+0050+00
51+00
52+00
5 3 +0 0
5 4 +0 0
6
BRONSON PLACE NE
B R O N S O N W A Y N E
CUT IN AND INSTALL:
SSMH, TYPE 1 - 48"
STANDARD PLAN 400.1
STA 52+11.0, OFFSET 1.22 LT
TYPE C7
TYPE C7
TYPE C7
TYPE A7
TYPE A
7
TYPE B
7
TYPE C 7
1
TYPE A 7
TYPE A7
FOR CONTINUATION,
SEE W-4
STA 50+90.0,
OFFSET 0.32' RT 10
STA 51+56.4,
OFFSET 3.98' LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 51+43.8, OFFSET 8.36' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 51+89.2, OFFSET 4.54' LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 52+7.8, OFFSET 11.52' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK STA 54+59.2, OFFSET 29.4' RT1 - 8" 22.5° BEND, RJ x RJSTA 54+68.3, OFFSET 43.1 RTSTA 50+8.2,
OFFSET 0.36' RT
10
2
1
DEFLECT PIPE
MAXIMUM 9"
PER 18' OF
HORIZONTAL
LENGTH
SEE DWG W-4 FOR
FITTING CALLOUTS
35 LF
-
8"
DI
5 LF
8" DI
STA 50+33.23, OFFSET 14.62' LT
1 - 8" SOLID SLEEVE, RJ x RJ
STA 50+36.9,
OFFSET 11.26' LT12
85 LF - 8" DI 1 8 L F
8 " D I32 LF - 8" DI
6" SS
SDR-35 PVC
±25 LF
MATCH EX
SLOPE
6" SS
SDR-35 PVC
±12 LF
MATCH EX
SLOPE
6" SS
SDR-35 PVC
±22 LF
MATCH EX
SLOPE
2 6 4 L F - 8 " D I
25 LF
8" DI
STA 50+62.6, OFFSET 12.01' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
FOR RESTORATION,
SEE R-SHEETS, TYP
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
CAP/PLUG OPEN ENDS OF EXISTING
WATER PER 7-09.3(26)SEGMENT 4SEGM ENT 150+00 51+00 52+00 53+
175
170
165
160
155
150
145
175
170
165
160
155
150
145
SEE DWG W-4
FOR TEE IE 12" SD, IE 158.5412" SD, IE 157.5145° HORIZONTAL BEND45° HORIZONTAL BEND45° HORIZONTAL BEND45° HORIZONTAL BENDEX GASEX GASEX W8" x 8" TEE1" WS1" WS1" WS1" WS1" WS12"MIN12"MINM A I N T A I N P O S I T I V E
S L O P E
EX 8" SS, 157.85±EX 8" SS, IE 161.33±12"MINPOLYPIGGING STATION45° HORIZONTAL BENDDEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
8" W
DI 3'MINEX MH0630EX 6" SS
EX 6" SSSSMH TYPE 1 - 48"RIM EL 169.13IE 162.81± - 6" PVC OUT (SW)IE 162.91± - 6" PVC IN (SE)IE 162.91± - 6" PVC IN (NE)8" COUPLING8" COUPLINGTRENCH DAM, TYP
PER DETAIL 1/G-138" SOLID SLEEVEAPPROX 300 LF - 8" DI W WITH POLYWRAP
CONTRACTOR TO
CONFIRM PIPE SIZE AND
MATERIAL PRIOR TO
STARTING SEWER WORK
+00 54+
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-10-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
BRONSON PL NE WATER MAIN PLAN AND PROFILE
STA 54+00 TO 57+50 W- 11
35 85
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 54+00 W-10MATCHLINE STA - SEE DWG 54+00W-10KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY
190
195
200
205
210
215
220
225
190
195
200
205
210
215
220
225
IE 205.36±
PROVIDE 12" MIN
CLR BELOW EX 2"
AND 4" WATEREX WEX GASEX WEX GAS22.5° HORIZONTAL BEND, ROTATED11.25° HORIZONTAL BENDEX 2" GAS, IE 211.03EX 1" T, IE 211.83FIRE HYDRANT ASSEMBLY22.5° HORIZONTALBEND8" x 8" TEE12" SD, IE 211.2412" x 8" TEE,CONNECT TOEX 12" CI1" WS1" WS (2)1" WS1" WS1" WSEX 6" SD, IE 209.09EX 8" SS, IE 202.94TEE
IE 210.86
(CONTRACTOR
TO CONFIRM)12"MINMAINTAIN POSITIVE
SLOPE TO STA 56+00
GRADE AT PIPE
CENTERLINE POLYPIGGINGSTATION1" AIR VAC ASSEMBLY8" W
DI12" SD, IE 207.023'MIN6" IE 209.33±DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
EX 2" W
TRENCH DAM, TYP
PER DETAIL 1/G-138" SOLID SLEEVEPOLYPIGGING STATION6" SD, IE 207.338" W, IE 209.18
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
8" W,
IE 209.49
APPROX 228 LF - 8" DI W WITH POLYWRAP
54+00
55+00
5 6 +0 0
5
7
+
0
0
90+00
90+75
67
5
4
B R O N S O N P L A C E N E
TYPE C
TYPE C7
TYPE A7
1
1
1
1
1
STA 55+8.2, OFFSET 14.3' RT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 40.54' RT
STA 55+28.6, OFFSET 3.30' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCKSTA 54+59.2, OFFSET 29.4' RT
1 - 8" 22.5° BEND, RJ x RJ
ROTATE AS REQUIRED W/
VERTICAL THRUST BLOCK
6
STA 54+68.3, OFFSET 43.1 RT
1 - 8" x 8" TEE, FL x FL
W/ THRUST BLOCK
3 - 8" GATE VALVE, FL x RJ
FOR CONTINUATION, SEE DWG W-12
STA 56+33.4,
OFFSET 0.58' LT
10
STA 57+5.9,
OFFSET 0.86' LT 10
2
1
2 4 L F - 8 " D I4 2 L F - 8 " D I1 3 1 L F - 8 " D I
1 - 1" AIR AND VACUUM
RELEASE VALVE ASSEMBLY
PER COR STD PLAN 340.3
STA 55+99.7, OFFSET 7.59' LT
STA 57+95.1,
OFFSET 12.26' RT 11
WINDSORPLACE NE12 STA 54+75.49
OFFSET 37.25' RT26 LF8"
DI
STA 54+71.9, OFFSET 40.21' RT
1 - 8" SOLID SLEEVE, RJ x RJ
1
5 LF
8" DI
18 LF - 8" DI
STA 57+95.1,
OFFSET 12.26' RT11
7
5 LF - 12" DI
5 LF - 12" DI
FOR RESTORATION,
SEE R-SHEETS, TYP
SEE DET 3/W-22
FOR STA/OFFSET
12
SE
G
M
ENT 4
S E G M E N T 5
STA 56+56.4, OFFSET 10.59' LT
1- 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
CONNECT TO EX 12" CI AND CUT IN:
1 - 12" x 8" TEE, FLXFL
W/ THRUST BLOCK
2 - 12" GATE VALVES, FL x RJ
1 - 8" GATE VALVE, FL x FL
2 -12" SOLID SLEEVE, RJ x RJ
2 - 12" DI SPOOL
SEE DETAIL 3/W-22 FOR
CONNECTION DETAIL AND
ADDITIONAL FITTING CALLOUTS
TYPE A7
+00 55+00 56+00 57+00
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
M A T C H L I N E S T A
- S E E D W G
8 3 +2 5
W -1 3
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-12-13.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR PL NE WATER MAIN PLAN AND PROFILE
STA 79+80 TO 83+25 W-12
36 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 83+25 W-13
KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAY80+00 81+00 82+00 83+00
8
79+80 80+00 81+00
82+00
83+0090+0090+756
3
1
WINDSOR PLACE NE
BRONSON PLACE NE7TYPE C
7TYPE C
FOR CONTINUATION,
SEE DWG W-10
1
1
FOR CONTINUATION,
SEE DWG W-11
7 TYPE C
7 TYPE C
7TYPE C
7TYPE C
7TYPE C
7TYPE C
7TYPE A
1
10
STA 81+01.3,
OFFSET 0.33' RT
6
STA 80+66.9, OFFSET 7.01' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
SEE DWG W-11 FOR
FITTING CALLOUTS
10 STA 81+73.7,
OFFSET 0.28' RT
STA 82+39.6,
OFFSET 21.6' LT 10
STA 82+59.7, OFFSET 30.91' LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
11 STA 83+05.6,
OFFSET 0.17' RT
10
STA 82+74.3,
OFFSET 49.8' LT
STA 82+86.9, OFFSET 33.43' LT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 83+18.9, OFFSET 13.8' LT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 14.2' LT
10 STA 80+12.5,
OFFSET 0.0' RT
226 LF
8" D I206 LF - 8" DI
1 - 1" AIR AND VACUUM
RELEASE VALVE
ASSEMBLY PER COR
STD PLAN 340.3
STA 83+05
OFFSET 54.09' LT
COORDINATE WITH CITY
STAFF FOR LOCATION OF
ASSEMBLY PRIOR TO
CONSTRUCTION
35 LF - 8" DI
41 LF - 8" DIFOR RESTORATION,
SEE R-SHEETS, TYP
SEGMENT 4SEGMENT 5225
220
215
210
205
200
225
220
215
210
205
200
SEE DWG W-11
FOR TEE IEEX GASEX WEX GAS45° HORIZONTAL BEND8" x 8" TEE1" WSEX GRADE AT C/L
RIGHT OF WAY
MAINTAIN
POSITIVE
SLOPE
EX GRADE PIPE C/L
TRENCH DAM, TYP
PER DETAIL 1/G-13
225
230
220
235
240
245
225
230
220
235
240
245
EX WEX WEX WEX W12" SD, IE 238.61EX GAS45° HORIZONTAL BENDFIRE HYDRANT ASSY45° HORIZONTALBENDEX GAS1" WS1" WS1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
MAINTAIN
POSITIVE
SLOPE
STA 82+84 1" WS1" AIR VAC ASSY8" W, IE 240.37
PROVIDE 6"
MIN CLR W/
ETHAFOAM PAD
DEFLECT PIPE
MAXIMUM 9" PER
18' OF HORIZONTAL
LENGTH
EX GRADE AT
PIPE C/L
3'MIN8" W
DI 1" WSAPPROX 320 LF - 8" RJ DI W WITH POLYWRAP
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLI
NE STA - SEE DWG 83+25W-12DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-12-13.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR PL NE WATER MAIN PLAN AND PROFILE
STA 83+25 TO 88+00 W-13
37 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 83+25 W-12
EX GRADE AT C/L
RIGHT OF WAY
8 4 +0 0
85+00 86+00
87+00
8 8 +0 088+01
WINDSOR PLACE NE
WINDSOR WAY NE4
67TYPE B
7 TYPE C
7 TYPE C
7TYPE C
7 TYPE C 7 TYPE C
7 TYPE C 7TYPE C
1
1111
7 TYPE C
STA 87+31.4, OFFSET 8.68' RT
1 - 8" x 8" TEE, FL x FL
W/ THRUST BLOCK
2 - 8" GATE VALVE, FL x RJ
7TYPE C
STA 83+36.9, OFFSET 4.06' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 84+21.0, OFFSET 4.78' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 84+04.9,
OFFSET 9.04' LT 10
STA 84+91.8,
OFFSET 0.07' LT 10
STA 87+33.7, OFFSET 9.07' RT
1 - 8" x 6" TEE, FL x FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x FL
1- 8" ADAPTER, FL x RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT
ASSEMBLY - 25.12' LT
FOR CONTINUATION,
SEE DWG W-16
2
FOR CONTINUATION,
SEE DWG W-17
STA 87+26.6,
OFFSET 2.39' RT 10
7 TYPE C
STA 86+95.8,
OFFSET 0.29' LT
10
5
48 LF - 8" DI 4 8 L F - 8 " D I
310 LF - 8" DI
5 LF - 8" DI
5 LF - 8" DI
STA 87+29.7, OFFSET 18.51' RT12
STA 87+30.5, OFFSET 13.59' RT
1 - 8" SOLID SLEEVE, RJ x RJ
FOR RESTORATION,
SEE R-SHEETS, TYP
SEGMENT 4
SEGMENT 3225
230
220
215
235
240
210
SEE DWG W-16
FOR TEEEX WEX GASEX WEX GASEX WEX W12" SD, IE 213.3345° HORIZONTAL BEND1" WSEX WFIRE HYDRANT ASSEMBLY8" x 8" TEE1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
SEE DWG W-16
FOR PROFILE
CONTINUATIONEX 8" SS12"MINEX 6" CI W
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 180 LF - 8" RJ DI W WITH POLYWRAP
84+00 85+00 86+00 87+00
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE225
230
220
235
240EX WEX GASEX GASEX WEX WEX GASEX W12" SD, IE 229.0711.25° HORIZONTAL BEND11.25° HORIZONTAL BEND1" WS1" WS1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
MAINTAIN
POSITIVE
SLOPE TO
STA 82+94 8" W
DI 3'MIN1" WSAPPROX 226 LF - 8" RJ DI W WITH POLYWRAP
MATCHLINE STA - SEE DWG 64+50W-15DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR WAY NE
STA 59+80 TO 64+50 W-14
38 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"
FOR CONTINUATION SEE DWG W-2
EX GRADE AT C/L
RIGHT OF WAY MATCHLINE STA - SEE DWG 64+50 W-155+006+0059+50
60+00
61+00
62+00
63+00
64+00WINDSOR WAY NE
6
6
3BRONSON WAY NE1.5" COPPER
7TYPE B
7TYPE C
TYPE B 7
TYPE C 8
1
1
1
1
1
TYPE C7
FOR
CONTINUATION,
SEE DWG W-2
STA 61+43.3,
OFFSET 0.0'
11
STA 61+57.1,
OFFSET 0.0'10
STA 62+52.7,
OFFSET 0.0'
10
STA 62+89.2, OFFSET 2.02' LT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 64+30.7, OFFSET 9.94 RT
1 - 8"x6" TEE, FLx FL
W/ THRUST BLOCK
1 - 8" GATE VALVE, FL x RJ
1- 8" ADAPTER, FL X RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT
ASSEMBLY - 26.49' LT
2
STA 60+40.7,
OFFSET 68.54' RT
1 - 8" 45° BEND, RJ x RJ
W/ THRUST BLOCK
STA 61+44.7, OFFSET 4.35' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 63+28, OFFSET 9.1' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
DEFLECT PIPE MAXIMUM 9" PER
18' OF HORIZONTAL LENGTH
25 LF - 8" DI
G
R
A
NDEY
W
AY NE
1 5 6 L F - 8 " D I143 LF - 8" DI
40 LF - 8" DI
103 LF - 8" DI
FOR CONTINUATION,
SEE DWG W-6
STA 59+77.6,
OFFSET 57.27' RT
1 - 8" SOLID SLEEVE,
RJ x RJ
STA 64+11.5,
OFFSET 0.14' LT
10
12
FOR RESTORATION,
SEE R-SHEETS, TYP
TYPE C7
SEE W-2 FOR
FITTINGS CALLOUT
SEG
MENT 2 SEGMENT 1S E G M E N T 3
SEG
MENT 2 SEGMENT 15 LF - 8" DI
STA 59+81.2, OFFSET 58.88' RT
POLYPIGGING STATION
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
195
190
185
180
175
195
190
185
180
175
200
205
200
205
SEE DWG W-2
FOR TEE EX WEX GASEX WEX 4" WEX WEX GASEX 4" WEX SD, IE 191.2245° HORIZONTAL BEND22.5° HORIZONTAL BEND22.5° HORIZONTALBEND11.25° HORIZONTAL BENDFIRE HYDRANT ASSEMBLY1" WS1" WS1" WS1" WS1.5" WS12" SD, IE 190.96EX GRADE AT C/L
RIGHT OF WAY
12" MINEX 8" SSEX 8" SS, IE 185.07±MAINTAIN
POSITIVE
SLOPE12" MINPOLYPIGGING STATION8" SOLID SLEEVE8" x 8" TEE3'MIN8" W
DI DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
GRADE AT PIPE
CENTERLINE EX W1" WSAPPROX 480 LF - 8" RJ DI W WITH POLYWRAP
60+00 61+00 62+00 63+00 64+00 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
MATCHLINE STA - SEE DWG 69+50W-16DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR WAY NE
STA 64+50 TO 69+50 W-15
39 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 69+50 W-16MATCHLINE STA - SEE DWG 64+50W-14KEY MAP
SCALE: 1" = 400'-0"
EX GRADE AT C/L
RIGHT OF WAYMATCHLINE STA - SEE DWG 64+50 W-14
9
65+00
66+00
67+00
6 8 +0 0
6 9 +0 0
WINDSOR WAY NE
6
5
2" COPPER
7 TYPE A
7TYPE C
7 TYPE C
7 TYPE A 7 TYPE C
7
TYPE C
7 TYPE A 7 TYPE A
7TYPE C
7 TYPE A 7 TYPE C
7TYPE A
7TYPE B 7 TYPE C
7TYPE A
1
1
3
2
STA 69+14.5,
OFFSET 0.16' RT
10
10
9
1
DEFLECT PIPE MAXIMUM 9" PER
18' OF HORIZONTAL LENGTH
STA 69+00,
OFFSET 0.18' RT
STA 66+56.9, OFFSET 11.69' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
230 LF - 8" DI
19 LF
8" DI
308 LF - 8 " DI
FOR RESTORATION,
SEE R-SHEETS, TYP
STA 66+75.7, OFFSET 10.2' RT
1 - 8" x 6" TEE, FL x FL
W/ THRUST BLOCK
2 - 8" GATE VALVE, FL x RJ
1 - 8" ADAPTER, FL x RJ
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 27.10' LT
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
SEGMENT 3
195
190
185
180
175
170
165
195
190
185
180
175
170
165 EX WEX 15" SD, IE 172.87EX W12" SD, IE 173.861" WS2" WS1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
12"MIN3'MINEX 8" SD, IE 176.598" W IE 175.37
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
65+00 66+00 67+00 68+00 69+00
195
190
185
180
175
170
200
195
190
185
180
175
170
200
EX WEX WEX GASEX W11.25° HORIZONTAL BEND1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAYFIRE HYDRANT ASSEMBLY3'MINEX 4" W
INSTALL 6" DI FOR FH
ASSEMBLY W/ 12" MIN
CLR BELOW EX 4" W
DEFLECT PIPE
MAXIMUM 9" PER 18' OF
HORIZONTAL LENGTH
APPROX 495 LF - 8" RJ DI W WITH POLYWRAP
195
190
185
180
175
200
205
195
190
185
180
175
200
205
EX GASEX WEX W1" WS1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAYEX 8" SSEX 6" SS12"MIN8" W
DI W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NENOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR WAY NE
STA 69+50 TO 73+50 W-16
40 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 69+50 W-15MAT
CHL
I
NE
S
T
A
-
S
E
E
DWG
6
9
+
5
0
W-
1
5
M A T C H L IN E S T A - S E E D W G 7 3 +5 0
W -1 7
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 73+50 W-17
EX GRADE AT C/L
RIGHT OF WAY
10 87+007 0 +0 0
7 1+00 72+00
7
3
+
0
0
WINDSOR WAY NE WINDSOR PLACE NE6
SEE DWG W-13
FOR CALLOUTS
7 TYPE A
7 TYPE A
7 TYPE A
7 TYPE A
7TYPE A
7TYPE A
7 TYPE B 7 TYPE C
7 TYPE B
7TYPE A
11
1
STA 69+86.1, OFFSET 5.87' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 70+79.6, OFFSET 7.78' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 71+53.6, OFFSET 4.82' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK STA 73+16.7, OFFSET 5.25' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 72+98,
OFFSET 28.5' LT 10
STA 72+12.8,
OFFSET 0.22' LT
11
STA 73+22.4, OFFSET 7.38' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
2
DEFLECT PIPE MAXIMUM 9"
PER 18' OF HORIZONTAL LENGTH
9 1 L F - 8 " D I
7 2 L F - 8 " D I
149 LF - 8" DI
31 LF - 8" DI6 LF - 8" DI
FOR CONTINUATION
SEE DWG W-13
EX WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL
BE ONLINE AND OPERATIONAL BEFORE
STORM STRUCTURE IS INSTALLED
S E G M E N T 3 SEGMENT 4195
190
185
180
175
195
190
185
180
175
200 200
205 205
EX WEX GASEX W22.5° HORIZONTAL BEND11.25° HORIZONTAL BEND1" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
MAINTAIN
POSITIVE
SLOPE3'MIN8" W
DI
DEFLECT PIPE MAX
9" PER 18' OF
HORIZ LENGTH
APPROX 150 LF - 8" RJ DI W WITH POLYWRAP
195
200
190
185
205
210
215
195
200
190
185
205
210
215
EX WEX GAS, IE 202.82EX W11.25° HORIZONTAL BEND12" SD, IE 192.0312" SD, IE 202.411" WS1" WS1" WSEX GRADE AT C/L
RIGHT OF WAY
TRENCH DAM, TYP,
PER DETAIL 1/G-13
APPROX 150 LF - 8" RJ DI W WITH POLYWRAP
8" W IE 201.24
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
8" W IE 190.86
PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
205
210
215
220
225
230
235
205
210
215
220
225
230
235
IE 218.19±EX W22.5° HORIZONTAL BEND12" SD, IE 213.21FIRE HYDRANT ASSEMBLY8" x 8" TEE1" WS11.25° HORIZONTAL BENDEX 6" SS, IE 204.24±POLYPIGGING STATION8" SOLID SLEEVEINSTALL 6" DI FOR FH
ASSEMBLY W/ 1' CLR
BELOW EX 6" W
APPROX 100 LF - 8" RJ DI W WITH POLYWRAP
73+0070+00 71+00 72+00 W-11W-10W-1W-2W -3W-4W-5W-6W-7W -8 W-9W-12
W-13W -14
W -1 5
W-16
W-17W-18SD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13SD -1 4
S D -1 5
SD-16
SD-17SD-18W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NENOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
WINDSOR WAY NE
STA 73+50 TO 75+76 W-17
41 85
M. McCrosky, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 73+50 W-16MATCHLINE STA - SEE DWG 73+50W-16KEY MAP
SCALE: 1" = 400'-0"
STA 74+07.91, OFFSET 6.34' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
EX GRADE AT C/L
RIGHT OF WAY
16A
16B
7 5 +7 6
74+00
7 5 +0 0
WINDSOR PLACE NE 6
STA 75+50.61, OFFSET 10.45' RT
CONNECT TO EXISTING 16" DI W/
1 - 16" x 8" TAPPING TEE AND VALVE, FL x RJ
W/ THRUST BLOCK
SEE DETAIL 4/W-22 FOR CONNECTION DETAIL
5
INSTALL 1 - 6" CAP, MJ
ON EX 6" CI
REMOVE EX 6" GATE VALVE AND
INSTALL BLIND FLANGE ON EX TEE
3
17TYPE C
7 TYPE C
7 TYPE C EDMONDS AVE NESTA 74+44.54, OFFSET 6.35' RT
1 - 8" 11.25° BEND, RJ x RJ
W/ THRUST BLOCK
STA 74+76.4,
OFFSET 0.48' LT
10
STA 73+63,
OFFSET 0.66' LT 10
STA 74+67.1, OFFSET 5.39' RT
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - FIRE HYDRANT ASSEMBLY - 24.73' LT
STA 75+27.6, OFFSET 12.02' RT
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
STA 75+56,
OFFSET 0.52' LT 10
2
84 LF - 8" DI
37 LF - 8" DI 23 LF
8" DI
64 LF - 8" DI
SEGMENT 4
230
235
240
245
250
255
260
235
240
245
250
255
260
EX WEX W22.5° HORIZONTAL BENDFIRE HYDRANT ASSEMBLY1" WS1" WSTEE
IE 246.32±
EX GRADE AT C/L
RIGHT OF WAY POLYPIGGING STATION8" SOLLID SLEEVECONNECT TO EX 16" DIEX P, IE 246.6±INSTALL 6" DI FOR FH
ASSEMBLY W/ 12" CLR
BELOW EX 6" W
EX 6" W
TRENCH DAM, TYP,
PER DETAIL 1/G-13
APPROX 100 LF - 8" RJ DI W WITH POLYWRAP
74+00 75+00
220
225
230
235
240
245
250
220
225
230
235
240
245
250
EX GAS11.25° HORIZONTAL BENDEX GRADE AT C/L
RIGHT OF WAY EX W1" WS11.25° HORIZONTAL BEND3'MIN8" W
DI
DEFLECT PIPE
MAX 9" PER 18' OF
HORIZ LENGTH
APPROX 99 LF - 8" RJ DI W WITH POLYWRAP W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NENOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-18.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
VUEMONT PL NE
STA 700+00 TO 702+00 W- 18
M. McCrosky
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
STA 800+36, OFFSET 3.2' RT
CONNECT TO EX 10" DI
AND CUT-IN:
1- 10" x 8" TEE, FL x FL
W/ THRUST BLOCK
1- 10" GATE VALVE, FL x RJ
1- 10" ADAPTER, FL x MJ
2- 10" SOLID SLEEVE, RJ x RJ
1- 8" GATE VALVE, FL x RJ
2- 10" SPOOL, LF AS REQUIRED
3 LF - 8" DI
1- 8" 45° BEND ROTATED
VERTICAL, FL x RJ
W/ THRUST BLOCK
7 LF - 8" DI
2 LF - 8" DI
1- 8" 45° BEND ROTATED
VERTICAL, RJ x RJ
W/ THRUST BLOCK
CONNECT TO EX 8" DI
1- 8" SOLID SLEEVE, RJ x RJ
1- 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1- 8" MJ PLUG
W/ THRUST BLOCK
1- 6" GATE VALVE, FL x RJ
11 LF 8" DI
STA 701+62,
OFFSET 4.95' RT
CONNECT TO EXISTING
6" HYDRANT STUB W/:
1 - 8" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1 - 6" GATE VALVE, FL x RJ
1 - 6" SOLID SLEEVE, RJ x RJ
1- 6" DI SPOOL, LF AS REQUIRED
STA 701+72, OFFSET 10.4' RT
CONNECT TO EXIST 6" STEEL
1- 6" 90° BEND, RJ x RJ
W/ THRUST BLOCK
2- 6" DI SPOOL, LF AS REQUIRED
1- 6" COUPLING, DI RJ x STEEL
1- 10" x 6" TEE, RJ x FL
W/ THRUST BLOCK
1- 10" MJ PLUG
W/ THRUST BLOCK
1- 6" GATE VALVE, FL x RJ
STA 700+98, OFFSET 33.6' LT
CONNECT TO EX 6" CI
1- 6" x 6" TEE, RJ x RJ
W/ THRUST BLOCK
1- 6" DI SPOOL, LF AS REQUIRED
1- 6" COUPLING, DI RJ x CI
11 LF - 6" DI W
KEY MAP
SCALE: 1" = 400'-0"
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-18.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024 42 85
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 802+10W-11
-NTS
DETAIL 2
-NTS
DETAIL
INSTALL
1 - 6" CAP,
MJ, ON EX 6" CI
INSTALL 1 - 6" CAP,
MJ, ON EX STEEL
SEE DETAIL 3/-
NEW 8" DI W
EX 6" DI
EX HYDRANT
6" CAP
EX 6" STEEL
DEAD-MAN ANCHOR BLOCK
PER STD PLAN 330.4
EX 8" DI
EX 10" DI
EX 6" STL (TO BE ABANDONED)
EX 6" STL W TO BE
ABANDONED IN PLACE
EX 6" STL
NEW 8" DI W
NEW 10" DI W
AFTER TESTING AND DISINFECTION
OF NEW PIPES, REMOVE 2 EX 10"
BLIND FLANGES AND EX CONCRETE
BLOCKING AND CONNECT TO
EX 10"x10" CROSS WITH:
2- 10" GATE VALVE, FLxRJ
2- 10" DI SPOOL, LF AS REQUIRED
1- 10"x8" REDUCER, RJxRJ
3
-NTS
DETAIL
DEAD-MAN ANCHOR BLOCK
PER STD PLAN 330.4
BRONSON WAY NE
VUEMONT PL NE17
18
6
STA 701+12,
OFFSET 0.28' RT
1
1
1
2
6
1
11
INSTALL
1 - 8" CAP,
MJ, ON EX 8" DI
REMOVE EX
GATE VALVE
47 LF - 10" DI
STA 800+69,
OFFSET 0.14' RT 10
STA 800+50,
OFFSET 0.84' RT 10
2
SEE
DETAIL 1/-
SEE
DETAIL 2/-
67 LF - 8" DI
EX 14" FO IE 166.3±
EX 2" GAS IE 175.9±
NOTES:
1. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITIES PRIOR TO STARTING
CONSTRUCTION.
2. SEE DWG G-4 FOR WATER GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
3. ALL WORK ON THE EXISTING WATER SYSTEM, INCLUDING
CONNECTIONS TO EXISTING MAINS, REMOVAL OF
EXISTING PIPES, PIPE CAPS, AND ABANDONMENT OF
EXISTING PIPES, WATER SERVICES, OR OTHER SYSTEM
COMPONENTS SHALL BE PERFORMED BY CITY FORCES
WITH THE DIRECT SUPPORT OF THE CONTRACTOR. SEE
DRAWING W-22 FOR NOTES REGARDING CONNECTIONS
TO EXISTING WATER MAIN.
CONSTRUCTION NOTES:
CAUTION: POTENTIAL UTILITY CONFLICT.
CONTRACTOR SHALL POTHOLE AND FIELD VERIFY
EXACT LOCATION PRIOR TO STARTING WORK. ANY
DISCREPANCIES FOUND IN THE FIELD FROM THOSE
SHOWN HERE SHALL BE REPORTED TO THE OWNER
PRIOR TO STARTING WORK.
ABANDON EXISTING WATER MAIN IN PLACE.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.1.
INSTALL FIRE HYDRANT ASSEMBLY PER COR
STANDARD PLAN 310.2.
REMOVE AND SALVAGE HYDRANT TO CITY SHOPS.
CLOSE VALVE, REMOVE AND WASTEHAUL VALVE BOX,
AND BACKFILL WITH CSTC. RESTORE SURFACE PER
RESTORATION DWGS R-1 - R-12.
CONTRACTOR TO INSTALL NEW METER BOX AND 1"
SERVICE LINE PER DETAIL 1, DWG W-19. TYPE AS
NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND
1-1/2" SERVICE LINE AND SETTER PER DETAIL 1, DWG
W-20. TYPE AS NOTED ON THE PLANS.
CONTRACTOR TO INSTALL NEW METER BOX AND 2"
SERVICE LINE AND SETTER PER COR STANDARD
PLAN 320.2.
PROTECT EXISTING MONUMENT AND ADJUST
MONUMENT CASE AFTER FINAL PAVING.
NOTIFY ENGINEER WHEN EXISTING MONUMENT IS
DISTURBED. OWNER TO REPLACE.
INSTALL POLYPIG STATION PER
COR STANDARD PLAN 300.7. SEE
SUGGESTED POLYPIGGING PLAN,
DWG W-23.
1
2
3
4
5
6
7
8
9
10
11
12 W-11W-10W-1W-2W -3 W-4W-5W-6W-7W -8 W-9W-12
W-13W -1 4
W -1 5
W -1 6
W
-17
W-18BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-19.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
1" WATER SERVICE CONNECTION DETAILS
FOR 5/8" x 3/4" AND 1" METERS W-19
M. McCrosky
P. Simon
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
MATERIAL LIST
ITEM CONFIGURATION
TYPE
METER SIZE
5/8" x 3/4" 1"
APPROVED MODELS
1 REGULATOR
ADAPTER
A,B NOT USED
C RA-X-NL or SCH 80 PVC NIPPLES, THREADED
2 TUBING 1" TYPE "K" SOFT COPPER TUBING
3 METER SETTER A, B, C
1" SETTER, QUICK
JOINT INLET AND
OUTLET, PADLOCK
WINGS ON INLET
ANGLE BALL VALVE,
SINGLE CHECK VALVE
ON OUTLET, FORD
VBH74-15W-44-44-Q-NL
, A.Y. MCDONALD
721-415WCQQ 44, OR
MUELLER B-24701-6AN,
INSTALL CENTERED
AND SQUARED IN
METER BOX. PROVIDE
ADAPTERS FOR
5/8"x3/4" METERS,
FORD A24-GT-117-NL
OR APPROVED EQUAL
1" SETTER, QUICK
JOINT INLET AND
OUTLET, PADLOCK
WINGS ON INLET
ANGLE BALL VALVE,
SINGLE CHECK VALVE
ON OUTLET, FORD
VBH74-15W-44-44-Q-NL
, A.Y. MCDONALD
721-415WCQQ 44, OR
MUELLER B-24701-6AN,
INSTALL CENTERED
AND SQUARED IN
METER BOX
4 WATER METER
A, B, C RE-INSTALL EXISTING AMI WATER METER
WITH RADIO AND BATTERY UNIT
5 METER BOX A, B, C METER BOX, ARMORCAST A6001946PCX18 OR
APPROVED ALTERNATE
6 METER BOX LID
A, B, C METER BOX LID, ARMORCAST A6001969RCI-H7,
TO READ "RENTON WATER"
7 METER BOX LID
A, B, C METER BOX LID, ARMORCAST A6001969,
STANDARD MARKING
8
PRESSURE
REDUCING
VALVE
ASSEMBLY
A, B
1" PRV ASSEMBLY
WITH INTERNAL
BYPASS AND
STRAINER, ZURN
WILKINS 600xl SERIES
OR APPROVED EQUAL
(FNPT)
1" PRV ASSEMBLY
WITH INTERNAL
BYPASS AND
STRAINER, ZURN
WILKINS 600xl SERIES
OR APPROVED EQUAL
(FNPT)
C
3/4" PRV ASSEMBLY
WITH INTERNAL
BYPASS AND
STRAINER, ZURN
WILKINS 600xl SERIES
OR APPROVED EQUAL
(FNPT)
9 PIPE
A, B 1" BRASS NIPPLE (MNPT), LENGTH TO FIT
C NOT USED
10 SHUTOFF
VALVE
A, B 1" BRONZE BALL VALVE, ZURN, WILKINS 850XL
SERIES OR APPROVED EQUAL
C NOT USED
11 BEND
A, B (FNPT) x PACK JOINT (FNPT) x PACK JOINT
C NOT USED
12
BEND A, B, C
1" 90° BRASS BEND,
FORD L-44-44-Q-NL OR
EQUAL
1" 90° BRASS BEND,
FORD L-44-44-Q-NL OR
EQUAL
(PACK JOINT X PACK
JOINT)
(PACK JOINT X PACK
JOINT)
13 COUPLER A, B, C
COUPLER (PACK
JOINT x PACK JOINT),
FORD C4#-4#-Q-NL,
CONTRACTOR TO
PROVIDE OUTLET
COMPATIBLE WITH
EXISTING SERVICE
PIPE MATERIAL AND
SIZE
COUPLER (PACK
JOINT x PACK JOINT),
FORD C4#-4#-Q-NL,
CONTRACTOR TO
PROVIDE OUTLET
COMPATIBLE WITH
EXISTING SERVICE
PIPE MATERIAL AND
SIZE
14 GRAVEL
A, B, C CSTC CSTC
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-19.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024 43 85
AS SHOWN
27-04186
NOTES:
1. TYPES A & B: CONTRACTOR TO REMOVE AND WASTEHAUL EXISTING METER BOX
AND SETTER ONCE CUSTOMER SIDE SERVICE IS TRANSFERRED TO NEW MAIN.
2. CONTRACTOR TO LEAVE EACH CUSTOMER SIDE SERVICE EXPOSED FOR CITY
REPRESENTATIVE TO VISUALLY INSPECT AND DOCUMENT EXISTING SERVICE
LINE MATERIAL.
FOR 5/8" x 3/4" AND 1" METERS
WITH NEW 3/4" OR 1" PRV
1
NTS
DETAIL
12"
MIN
9" TO 12"
24" TO 30"
3" MIN
6"
SIDEWALK
3" MIN
12"
MIN
9" TO 12"
24" TO 30"
3" MIN
6"
3" MIN
2" TO 6"
TYPE B
TYPE A
9" TO 12"
SIDEWALK
METER
BOX
PRV
BOX EX SERVICE
TO BUILDINGBACK OFSIDEWALK1" BALL CORPORATION STOP
WITH BALL VALVE, AWWA
TAPERED THREAD (CC) INLET,
QUICK JOINT OUTLET, FORD
FB1000-4-Q-NL OR A.Y.
MCDONALD 74701BQ
PROPOSED MAIN
LOOP DOWN TO CENTERLINE OF
WATER MAIN TO PROVIDE SLACK
IN SERVICE LINE TO METER
SIDEWALK
6" TO 9"PROPERTY
LINE
CITY PIPING PRIVATE PIPING
EX SERVICE LINE PROTECT EX
CUSTOMER-SIDE
SERVICE LINE
INSTALL NEW PRV ASSEMBLY IN
EXISTING METER BOX AT TIME OF
TRANSFER OF SERVICE FROM
OLD MAIN TO PROPOSED MAIN
6"TYPE C - PLAN214
3
4
6
5
12
11
1312
2
914
11
9
7
10 5
8
2
2
12
12
12
2
2
1" BALL CORPORATION STOP
WITH BALL VALVE, AWWA
TAPERED THREAD (CC) INLET,
QUICK JOINT OUTLET, FORD
FB1000-4-Q-NL OR A.Y.
MCDONALD 74701BQ
PROPOSED MAIN
PROPERTY
LINE
CITY PIPING PRIVATE PIPING
BACK OFSIDEWALK3
14
4
6 5
2
8 7
12
9
11
14
9
10
12
13
5
11
2
1" BALL CORPORATION
STOP WITH BALL VALVE,
AWWA TAPERED THREAD
(CC) INLET, QUICK JOINT
OUTLET, FORD
FB1000-4-Q-NL OR A.Y.
MCDONALD 74701BQ
LOOP DOWN TO CENTERLINE OF
WATER MAIN TO PROVIDE SLACK
IN SERVICE LINE TO METER
LOOP DOWN TO CENTERLINE OF
WATER MAIN TO PROVIDE SLACK
IN SERVICE LINE TO METER
PROPOSED
MAIN
5
6
4
3
2 12
TYPE C - METER BOX SECTION
SIDEWALK
PROTECT EX
CUSTOMER-SIDE
SERVICE LINE
EX SINGLE CHECK VALVE
CRIMP OR CAP EX
CITY-SIDE
SERVICE LINE
EX ANGLE BALL VALVE
2
12
12
2
13
1
1 8
MAIN
22.5°22.5°2
2
22.5°14
14
TYPE C - PRV BOX SECTION
2
24" TO 30"
EX CURB,
VARIES
EX CURB,
VARIES
EX CURB,
VARIES
EX CURB,
VARIES
EX METER BOX AND LID
1" WATER SERVICE CONNECTION
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-20.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKS03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WATER SERVICE CONNECTION DETAILS
FOR 1 1/2" METER W-20
M. McCrosky
P. Simon
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-20.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKS03/08/2024
ISSUED FOR BID MTM 03-2024
RLO
44 85
AS SHOWN
27-04186
NOTES:
1. TYPES A & B: CONTRACTOR TO REMOVE AND WASTEHAUL EXISTING METER BOX
AND SETTER ONCE CUSTOMER SIDE SERVICE IS TRANSFERRED TO NEW MAIN.
2. SEE DWG W-21 FOR MATERIAL LIST.
3. CONTRACTOR TO LEAVE EACH CUSTOMER SIDE SERVICE EXPOSED FOR CITY
REPRESENTATIVE TO VISUALLY INSPECT AND DOCUMENT EXISTING SERVICE
LINE MATERIAL.
24" TO 30"
9" TO 12"
MAIN
6"6" TO 9"3" MIN3"
MIN
TYPE A
3"
MIN
2" TO 6"
MAIN
24" TO 30"
9" TO 12"
MAIN
24" TO 30"
24" TO 30"
9" TO 12"
12"
MIN
6"6" TO 9"3" MIN3"
MIN
TYPE B
3"
MIN
PROPERTY
LINE
PROPERTY
LINE
CITY PIPING PRIVATE PIPING
CITY PIPING PRIVATE PIPINGBACK OFSIDEWALKBACK OFSIDEWALK4
2 6
5
3
1
4"18
8
6
9
12
13 11
14 12
15
6 8
6
8
6
8
17
6
7
16
22
SIDEWALK
FINISHED
GRADE
2 4
1
METER
BOX
PRV
BOX
8" TO 10"8
8
8
6
6
6
EX SERVICE LINE
PROTECT EX
CUSTOMER-SIDE
SERVICE LINE
INSTALL NEW PRV ASSEMBLY IN
EXISTING METER BOX AT TIME OF
TRANSFER OF SERVICE FROM
OLD MAIN TO PROPOSED MAIN
4 FINISHED
GRADE
5
3
1
4"
2 6
SIDEWALK1311
8
6
8
18 8
6
9
12
10
SIDEWALK
PROTECT EX
CUSTOMER-SIDE
SERVICE LINE
EX SINGLE CHECK VALVE
CRIMP OR CAP EX
CITY-SIDE SERVICE
LINE
EX ANGLE
BALL VALVE
8
68
FINISHED
GRADE
19
1519
6
17
4
2 6
5
3
1
4"
SIDEWALK
12
9
6
18
8
6
6
6
8
7
14
2 2
8
18
17
6
15
16
13
11
10
MAIN
TYPE C - PLAN
TYPE C - METER BOX SECTION
TYPE C -PRV BOX SECTION
WATER SERVICE CONNECTION
FOR 1 1/2" METER
1
NTS
DETAIL
7
12
18
18
10
7
EX CURB,
VARIES
EX CURB,
VARIES
EX CURB,
VARIES
EX CURB,
VARIES
EX METER BOX AND LID
FINISHED
GRADE
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-21.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024
1 1/2" METER MATERIAL LIST W-21
M. McCrosky
S. Olsoe
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
MATERIAL LIST
ITEM CONFIGURATION
TYPE
METER SIZE
1.5"
APPROVED MODELS
1 TEE A,B,C 2" TAPPED REDUCING TEE
(MJxFIPT)
2 PIPE A,B,C 2" BRASS NIPPLE (MIPT), LENGTH
AS REQUIRED
3 VALVE
2" GATE VALVE (FIPT) WITH
SQUARE OPERATING NUT AND
EXTENSION PER STD PLAN 330.7
4 VALVE BOX
A, B, C VALVE BOX AND LID PER STD
PLAN 330.7
5 COUPLING A, B, C
2" x 1 1/2" BRASS COUPLING (MIPT
x PACK JOINT), FORD C44-76-Q-NL
OR EQUAL
6 TUBING
A, B, C 1 1/2" TYPE "K" SOFT COPPER
TUBING
7 BEND
A,B
1.5" 90° BRASS BEND (FNPT X
PACK JOINT), FORD L14-66-Q-NL
OR EQUAL
C NOT USED
8 BEND
A, B, C
1.5" 90° BRASS BEND (PACK JOINT
X PACK JOINT), FORD L44-66-Q-NL
OR EQUAL
9 METER SETTER
A, B, C
1 1/2" VERTICAL METER SETTER
WITH BYPASS, FLANGED ANGLE
BALL VALVE AND PADLOCK WINGS
ON INLET, ANGLE CHECK VALVE
ON OUTLET, AND BALL VALVE ON
BYPASS WITH PADLOCK WINGS,
FORD VBH86-12B-11-66-Q-NL, A.Y.
MCDONALD 730B-612WDFF665, OR
MUELLER B-2427N (1 1/2"),
BYPASS NOT PERMITTED ON
IRRIGATION METERS
10 METER SPREADER
A, B, C 13 3/16" RIGID METER SPREADER
(TEMPORARY)
11 WATER METER A, B, C EXISTING AMI WATER METER WITH
RADIO AND BATTERY UNIT
12 METER BOX
A, B, C
17"X30" METER BOX, ARMORCAST
A6001640PCX18 OR APPROVED
ALTERNATE
13 METER BOX LID
A, B, C
METER BOX LID, ARMORCAST
A6001947RCI-H7, TO READ
"RENTON WATER"
14 METER BOX LID
A, B, C METER BOX LID, ARMORCAST
A6001947, STANDARD MARKING
15
PRESSURE
REDUCING VALVE
ASSEMBLY
A, B, C
1.5" PRV ASSEMBLY WITH
INTERNAL BYPASS AND STRAINER,
ZURN WILKINS 600xl SERIES OR
APPROVED EQUAL (FNPT)
16 SHUTOFF VALVE
A,B
1.5" BRONZE BALL VALVE, ZURN,
WILKINS 850XL SERIES OR
APPROVED EQUAL
C NOT USED
17 COUPLER A, B, C
1 1/2" COUPLER (PACK JOINT x
PACK JOINT), FORD C4#-6#-Q-NL
OR EQUAL, OUTLET COMPATIBLE
WITH EXISTING SERVICE LINE SIZE
AND MATERIAL
18 GRAVEL
A, B, C CSTC TO SUPPORT METER BOX,
METER BYPASS TO BE EXPOSED
19 REGULATOR
ADAPTOR
A,B NOT USED
C RA-X-NL or SCH 80 PVC NIPPLES,
THREADED
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-21.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKSISSUED FOR BID MTM 03-2024
RLO
03/08/2024 45 85
AS SHOWN
27-04186
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-22.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKS03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WATER MAIN CONNECTION DETAILS W-22
46 85
M. McCROSKY, P.E.
J. LIRA
R. OCHILTREE, P.E.
N/A
27-04186
WATER CONNECTION GENERAL NOTES:
1. SEE CONSTRUCTION SEQUENCING PLAN, DWG G-12 FOR MORE
INFORMATION.
2. TESTING CONNECTIONS ARE PROVIDED FOR REFERENCE ONLY.
CONTRACTOR SHALL SUBMIT CONSTRUCTION SEQUENCING AND
TESTING PLAN PRIOR TO STARTING WORK.
3. POLYPIGGING NEW WATER MAINS SHALL BE PER COR STD. PLAN 300.7.
SEE POLYPIGGING PLAN, DWG W-23.
4. ALL FINAL CONNECTIONS TO EXISTING WATER MAIN SHALL BE BY CITY
FORCES. SEE SPECIAL PROVISIONS SECTION 7 09.3(19)A.
5. CONTRACTOR TO POTHOLE EXISTING MAINS PRIOR TO INSTALLATION
OF TESTING CONNECTION TO CONFIRM EXISTING MAIN DEPTH AND
SIZE. REPORT ANY DISCREPANCIES TO OWNER.
1 0'-0"±
TEMPORARY
BLOCKING
FOR CONTINUATION
SEE DWG W-1
8" W
DI
66'-0"±
EX HYDRANT FOR FILLING NEW DI
WATER MAIN, SEE POLYPIGGING
PLAN, DWG W-23
8" W
DI
1 - 8" DI SPOOL, LF AS REQ'D
1 - 8" 45° BEND, RJ x RJ,
W/ THRUST BLOCK
1 - 8" DI SPOOL, LF AS REQ'D
1 - 8" SOLID SLEEVE, RJ x RJ
NE 4TH ST/BRONSON WAY NE
WATER MAIN CONNECTION
1
W-1SCALE: 1" = 10'-0"
DETAIL
INSTALL 1 - 8" CAP,
MJ ON EX 8" DI
REMOVE EX
MAIN AS REQ'D
NOTE:
1. LONG BODY DI SLEEVE FOR
CONNECTION FROM DI TO DI PIPE.
FINAL CONNECTIONTESTING CONNECTION
POLYPIG STATION
PER COR STD
PLAN 300.7
REMOVE
EX VALVE BOX
BRONSON WAY NE/SUNSET BLVD NE
WATER MAIN CONNECTION
2
W-5SCALE: 1" = 10'-0"
DETAIL
POLYPIG STATION
PER COR STD
PLAN 300.7
8" W
DI
SEE NOTE 2
FINAL CONNECTIONTESTING CONNECTION
INSTALL 1 - 6" CAP, MJ
ON EX 6" CI
REMOVE EX MAIN AS REQ'D
REMOVE EXISTING GATE VALVE AND
INSTALL BLIND FLANGE ON EXISTING TEE
1 - 8" SOLID SLEEVE,
RJ x RJ
1 -12" x 8" TAPPING TEE
AND VALVE, FL x RJ
PER COR STD PLAN 300.6
TEMPORARY
BLOCKING
NOTES:
1. LONG BODY DI SLEEVE FOR CONNECTION
FROM DI TO DI PIPE.
2. 8" DI STUB ACROSS SUNSET TO BE
INSTALLED BY CONTRACTOR. ALL PIPE
SHALL BE SWABBED AND INSTALLED
UNDER SUPERVISION OF CITY
INSPECTOR. COORDINATE
INSTALLATION WITH CITY.SEE WATER
CONNECTIONS GENERAL NOTE 4.
8'-0"
3 8 '-0"
FOR CONTINUATION,
SEE DWG W-5
MJ CAP, RJ
W/ 2" TAP AND
TEMPORARY
BLOW-OFF ASSEMBLY
8 LF +- 8" DI
BRONSON PLACE NE
WATER MAIN CONNECTION
3
W-11SCALE: 1" = 10'-0"
DETAIL5'-0"±8 '-0"±5'-0"±56'-0"±8" W
DI
FOR CONTINUATION,
SEE DWG W-11
1 - 8" 22.5° BEND, RJ x RJ,
W/ THRUST BLOCK
STA 56+59, OFFSET 10.70' LT
POLYPIG STATION PER COR
STD PLAN 300.7
STA 56+67.08', OFFSET 11.34' LT
1 - 8" 45° VERTICAL BEND, RJ x RJ
W/ VERTICAL THRUST BLOCK
STA 56+73.2, OFFSET 12.64' LT
CUT IN:
1 -12" x 8" TEE, FL x FL
W/ THRUST BLOCK
2 - 12" GATE VALVE, FL x RJ
1 - 8" GATE VALVE, FL x FL
2 - 12" SOLID SLEEVE, RJ x RJ
1 - 8" 45° VERTICAL BEND, FL x RJ,
W/ VERTICAL THRUST BLOCK
EX HYDRANT FOR FILLING NEW DI
WATER MAIN, SEE POLYPIGGING
PLAN, DWG W-23
12" W
DI
12" W
DI
1 - 8" SOLID
SLEEVE, RJ x RJ
8" W
DI
12" W
DI
12" W
DI
FINAL CONNECTIONTESTING CONNECTION
7 LF - 8" DI 2 LF± - 8" DI
4 LF± - 8" DI
TEMPORARY BLOCKING
1 - 8" 45° VERTICAL BEND, RJ x RJ
W/ VERTICAL THRUST BLOCK
NOTE:
1. LONG BODY DI SLEEVE FOR
CONNECTION FROM DI TO DI PIPE.
WINDSOR PLACE NE/EDMONDS AVE NE
WATER MAIN CONNECTION
4
W-17SCALE: 1" = 10'-0"
DETAIL
FINAL CONNECTIONTESTING CONNECTION
8 '-0 "±
TEMPORARY
BLOCKING
STA 72+89.4, OFFSET 15.43' LT
POLYPIG STATION PER COR
STD PLAN 300.7
STA 72+96.9, OFFSET 20.64' LT
1 - 16" x 8" TAPPING TEE AND
VALVE, FL x RJ,
PER COR STD PLAN 300.6
65'-0"±
50'-0"±20'
-0"±EX HYDRANT FOR
FILLING NEW DI WATER
MAIN, SEE POLYPIGGING
PLAN, DWG W-23
1 - 8" 22.5° BEND, RJ x RJ
W/ THRUST BLOCK
FOR CONTINUATION,
SEE DWG W-17
8" W
DI
8" W
DI
STA 72+93.2, OFFSET 17.98' LT
1 - 8" SOLID SLEEVE, RJ x RJ
INSTALL 1 - 6" CAP, MJ ON EX 6" CI
REMOVE EX 6" GATE VALVE AND
INSTALL BLIND FLANGE ON EX TEE
REMOVE EX MAIN AS REQ'D
5 LF± - 8" DI
NOTE:
1. LONG BODY DI SLEEVE FOR
CONNECTION FROM DI TO DI PIPE.
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_W-23.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
20123392STATE O F WASHIN
G
T
ONR
E
GI S T E R E DMYATLIASDOM
c
RCOPROF
E
SSIONAL E N G IN EERN
OR
YKS03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WATER MAIN
POLYPIGGING PLAN W-23
47 85
M. McCrosky
J. Lira
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
SEGMENT LAUNCH
LOCATION
RETRIEVAL
LOCATION LENGTH
1 STA 1+39.21
BRONSON WAY NE
STA 22+11.6
BRONSON WAY NE 2,104.9'±
2 STA 30+13.4
GRANDEY WAY
STA 46+63.3
GRANDEY WAY 1,845'±
3 STA 72+89.35
WINDSOR WAY NE
STA 59+81.2
WINDSOR WAY NE 1329.5'±
4 STA 75+41.2±
WINDSOR WAY NE
STA 50+36.9
BRONSON PL NE 1461.5'±
5 STA 56+61.8
BRONSON PL NE
STA 54+75.5
BRONSON PL NE 203.8'±
NOTES:
1. SEE CONSTRUCTION SEQUENCING AND GENERAL REQUIREMENTS,
DWG G-12 FOR MORE INFORMATION.
2. POLYPIGGING LOCATIONS PROVIDED FOR REFERENCE ONLY.
CONTRACTOR SHALL SUBMIT CONSTRUCTION SEQUENCING AND
TESTING PLAN PRIOR TO STARTING WORK.
3. POLYPIG STATIONS WATER MAINS SHALL BE PER COR STD. PLAN
300.7.
4. WHEN HOSE FOR FILLING CROSS THE ROADWAY, CONTRACTOR TO
PROVIDE RAMPS TO PROTECT HOSE FROM VEHICULAR TRAFFIC.
5. SEGMENT ALIGNMENT AND SYMBOLS ARE SCHEMATIC. SEE WATER
PLAN AND PROFILE SHEETS FOR LOCATION OF POLYPIG STATIONS.
LEGEND
POLYPIG STATION
EXISTING HYDRANTS FOR FILLING
AND FLUSHING PROPOSED MAIN
WATER CONNECTION
BETWEEN NEW SEGMENTS
1
-NTS
DETAIL
POLYPIG
STATION
TEMPORARY BLOCKING
SEPARATE
SEGMENT
SEPARATE SEGMENT
8'-0"±
TO BE COMPLETED BY CITY FORCES:
REMOVE POLYPIG STATION AND
TEMPORARY BLOCKING, INSTALL
CONNECTION BETWEEN SEGMENTS WITH:
1 - 8" DI SPOOL, LF AS REQUIRED
1 - 8" SOLID SLEEVE, RJ x RJ
FINAL CONNECTION
TESTING CONNECTION
NOTE:
1. VALVE CONFIGURATION VARIES.
1
2 3A45
6
7
9
1011 12
13141516A16B17
18 3B890+00
90+75
800+00
801+00
8
0
2
+
0
0
8
0
3
+
0
0 804+00
805+00
8
0
6
+
0
0700+00701+00702+00702+90
BRONS
ON BRONSON WAY NEB
R
O
N
S
O
N
BRONSON WAY NEGRANDEY WAYW
IN
D
S
O
R
W
A
Y N
E
N
E
4
T
H
S
T
PLACE NE
WINDSOR PLACE NE
EDMONDS AVE NE
WAY NEVUEMONT PL NES U N S E T B L V D N E
SEGMENT 2
SEGMENT 1
SEGMENT 3
SEGMENT 5
SEGMENT 4
EX HYDRANT
FOR FILLING
SEGMENT 5
EX HYDRANT
FOR FILLING
SEGMENT 4
EX HYDRANT
FOR FILLING
SEGMENT 2
EX HYDRANT
FOR FILLING
SEGMENT 3
EX HYDRANT
FOR FILLING
SEGMENT 1
FOR CONNECTION
BETWEEN SEGMENTS,
SEE DETAIL 1/-
FOR CONNECTION
BETWEEN SEGMENTS,
SEE DETAIL 1/-
FOR CONNECTION
BETWEEN SEGMENTS,
SEE DETAIL 1/-
FOR CONNECTION
BETWEEN SEGMENTS,
SEE DETAIL 1/-
FOR CONNECTION
BETWEEN SEGMENTS,
SEE DETAIL 1/-
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE STORM DRAIN PLAN AND PROFILES
STA 1+00 TO 4+50 SD-1
48 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
CONSTRUCTION NOTES:
CONNECT TO EX CATCH BASIN WITH KOR-N-SEAL
CONNECTION.
1MATCHLINE STA - SEE DWG 4+50 SD-2
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
M A T C H L IN E S T A - S E E D W G 8 02 +1 0
S D -18LEGEND:
POTHOLE INFORMATION ON DWG G-12
XX
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITES PRIOR TO STARTING
CONSTRUCTION.
7. SEE DWG G-3 FOR STORM GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
8. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
9. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
10. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
11. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.
175
205
200
195
190
185
180
175
205
200
195
190
185
180
EX GRADE AT
C/L OF PIPE
ALIGNMENT
IE 190.74 - 8" OUT (SW)70 LF - 8" SD HDPE
S=0.34%EX IE 190.6 - 18" IN (NE)EX IE 190.5 - 18" OUT (NE)IE 190.5 - 8" IN (NE)EX 14" D x 23" W FOIE 191.87EX 10" W, IE 192.53ESTIMATEDEX E, IE 192.72, ESTIMATEDEX CB NO. 134565RIM EL 196.54EX WSCB #1RIM EL 194.89EX 4" GAS, IE 192.12PROVIDE 6" MIN
CLEARANCE W/
ETHAFOAM PAD1 1
2
11 12
1+00
2+00 3+00 4+008
0
3
+
0
0
804+00
805+00
BRONSON WAY NE
NE 4TH ST
8" SD
HDPE
CB #1
TYPE 1 W/ GRATE
STA 1+77
OFFSET 20.38' RT
1 BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE
STA 4+50 TO 8+25 SD-2
49 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 8+25SD-3MATCHLIN
E STA - SEE DWG 4+50SD-1KEY MAP
SCALE: 1" = 400'-0"
FOR CONTINUATION, SEE DWG SD-6
5 +0 0
6 +0 0
7+00
8+00
30+00
5
9
+
5
0
60+00
6
1
+
0
0
BRONSON WAY NE
WI
NDS
OR WAY
NEGRANDEY WAYCB #31
TYPE 1 W/ GRATE
STA 5+04
OFFSET 14.8' LT
SEE DWG SD-6
CB #32
TYPE 2 W/ SOLID LID
STA 5+70
OFFSET 14.4' LT
SEE DWG SD-6
12" SD
PP
12" SD
PP
CB #30
TYPE 1
W/ GRATE
STA 4+74
OFFSET 27.1' RT
SEE DWG SD-6
FOR PLAN AND PROFILE
SEE DWG SD-6
12" SD
PP
SEE R DWGS FOR
RESTORATION
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITES PRIOR TO STARTING
CONSTRUCTION.
7. SEE DWG G-3 FOR STORM GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
8. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
9. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
10. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
11. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE
STA 8+25 TO 13+00 SD-3
50 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 13+00SD-4MATCHLINE STA - SEE DWG 8+25SD-2HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
9+00
10+00
11+00
12+00
1 3 +0 0
BRO NSON WAY NE
CB #2
TYPE 1 W/ GRATE
STA 8+36
OFFSET 14.9' RT
CB #3
TYPE 1 W/ GRATE
STA 8+35
OFFSET 15.2' LT
12" SD
DI
12" SD
DI
CB #5
TYPE 1 W/ GRATE
STA 11+04
OFFSET 15.5' RT
CB #6
TYPE 1 W/ BIRDCAGE INLET
PER COR STD PLAN 234.20
STA 11+04
OFFSET 25.6' RT
12" SD
DI
12" SD
PP
FOR DITCH IMPROVEMENTS
SEE DWG SD-20
12" SD
DI
OUTFALL
IE 166.3
CB #4
TYPE 2 W/ GRATE
STA 11+03
OFFSET 13.7' LT
FOR PLAN AND PROFILE
SEE DWG SD-20
185
180
175
170
165
160
155
185
180
175
170
165
160
155CB #2RIM EL 177.20IE 172.22 - 12" OUT (NW)CB #3RIM EL 176.90IE 171.62 - 12" IN (SE)IE 171.62 - 12" OUT (NE)CB #4RIM EL 169.47IE 167.0 - 12" IN (S)IE 167.0 - 12" IN (W)IE 167.0 - 12" OUT (N)CB #5RIM EL 169.94IE 167.30 - 12" OUT (N)IE 167.30 - 12" IN (S)CB #6RIM EL 170.06IE 167.40 - 12" OUT (N)EX GRADE AT
C/L OF PIPE
ALIGNMENT
271 LF - 12" SD DI
S=1.7%
30 LF - 12" SD PP
S=2.0%
29 LF - 12" SD DI
S=1.0%
10 LF
12" SD DI
S=1.0%EX 8" SS, IE 169.588" W, IE 173.70EX 6" W, IE 173.77ESTIMATEDEX WS1" WSEX 6" W, IE 173.24ESTIMATEDEX 8" SS, IE 168.491" WSEX 8" SS, IE 165.4±EX OHPEX 8" SS, IE 164.78EX OHPEX 8" SS, IE 163.748" W, IE 165.57PROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITES PRIOR TO STARTING
CONSTRUCTION.
7. SEE DWG G-3 FOR STORM GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
8. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
9. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
10. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
11. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE
STA 14+25 TO STA 18+50 SD-4
51 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA
-
SEE DWG 17+50SD-5MATCHLINE STA - SEE DWG 13+00SD-3HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
FOR PROFILE
CONTINUATION
SEE DWG SD-10
KEY MAP
SCALE: 1" = 400'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS INSTALLED. BYPASS
PUMP EXISTING STORM AS REQUIRED.
1
13+00
14+00
15+00
1 6 +0 0
1 7 +0 0
5
0
+
0
0
5
1
+
0
0BRONSON PL
ACE NECB #56
TYPE 2 W/ SOLID LID
STA 16+25
OFFSET 17.1' LT
12" SD
DI
CB #58
TYPE 1W/ GRATE
STA 16+55
OFFSET 14.9' RT
CB #55
TYPE 1 W/ GRATE
STA 15+69
OFFSET 27.8' RT
12" SD
DI
12" SD
DI
12" SD
PP
BRONSON WAY NE
FOR PLAN AND PROFILE
SEE DWG SD-10
CB #54
TYPE 1 W/ GRATE
STA 50+80
OFFSET 15.5' RT
CB #8
TYPE 1 W/ GRATE
STA 14+20
OFFSET 14.8' RT
SEE DWG SD-21
CB #9
TYPE 1 W/ GRATE
STA 14+26
OFFSET 15.6' LT
SEE DWG SD-21
CB #7
TYPE 1 W/ GRATE
STA 14+17
OFFSET 30.1' RT
SEE DWG SD-21
FOR CHANNEL IMPROVMENTS
SEE DWG SD-21
FOR PLAN AND PROFILE
SEE DWG SD-21
CB #57
TYPE 1 W/ GRATE
STA 16+58
OFFSET 15.6' LT
1
170
165
160
155
150
145
140
EX GRADE AT C/L
OF PIPE ALIGNMENT
CB #58RIM EL 151.48IE 149.6 - 12" OUT (W)170
165
160
155
150
145
140CB #54RIM EL 160.90CB #55RIM EL 156.26IE 149.5 - 12" IN (E)IE 149.4 - 12" OUT (S)IE 149.3 - 12" IN (N)IE 150.5 - 12" IN (SE)EX IE 149.3± - 12" CONC OUT (NW)IE 153.1 - 12" OUT (NW)IE 153.1 - 12" IN (SE)CB #57RIM EL 151.32CB #56RIM EL 152.10IE 157.8 - 12" OUT (NW)IE 157.8 - 12" IN (NE)7 3 L F - 1 2 " S D D I
31 LF - 12" SD DI
S=0.3%
32 LF - 12" SD DI
S=0.3%
6 0 L F - 1 2 " S D P P
S =7 .8 %EX 8" SS, IE 144.02EX 6" W, IE 148.31, ESTIMATEDEX 1" WS1" WS8" W, IE 147.90EX 6" W, IE 149.50ESTIMATED8" W, IE 149.60EX 8" SS, IE 144.446" W, IE 150.23EX 6" SD, IE 151.09ESTIMATEDEX 6" SD, IE 153.17ESTIMATEDEX 8" SS, IE 148.728" W, IE 154.52S =3 .6 %1" WSPROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITES PRIOR TO STARTING
CONSTRUCTION.
7. SEE DWG G-3 FOR STORM GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
8. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
9. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
10. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
11. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-1-5.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE
STA 17+50 TO 22+50 SD-5
52 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
M A T C H L IN E S T A - S E E D W G 1 7 +5 0
S D -4
KEY MAP
SCALE: 1" = 400'-0"
PROFILE
VERT
SCALE: HORIZ
A
SD-61" = 20'-0"
1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"PROFILE
VERT
SCALE: HORIZ
B
SD-71" = 20'-0"
1" = 5'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS INSTALLED. BYPASS
PUMP EXISTING STORM AS REQUIRED.
CONNECT EXISTING PIPE TO NEW CATCH BASIN WITH
FABRICATED SAND COLLAR OF SAME MATERIAL AS THE
CONNECTING PIPE.
1
2
LEGEND:
POTHOLE INFORMATION ON DWG G-12
XX
13
14
1518+0019+00
2 0 +0 0
2 1 +0 0
2 2 +0 0
SUNSET BLVD NE12" SD
PVC
CB #20
TYPE 1 W/ GRATE
STA 21+59
OFFSET 16.8' LT
CB #21
TYPE 1 W/ GRATE
STA 21+71
OFFSET 15.0' RT
CB #22
TYPE 2 W/ SOLID LID
STA 21+90
OFFSET 15.8' RT
REMOVE EX CB AND
RESTORE CURB
AND GUTTER
B R O N S O N W A Y N E GRANDEY WAY2
1
130
125
120
115
110
105
100
130
125
120
115
110
105
100
EX GRADE AT
C/L OF PIPE
ALIGNMENT CB #20RIM EL 119.12IE 114.5 - 12" OUT (N)CB #21RIM EL 119.28IE 114.3 - 12" IN (W)IE 114.3 - 12" OUT (S)CB #22RIM EL 118.46IE 114.0 - 12" IN (N)EX IE 113.9 - 8" CMP IN (S)EX IE 113.9 - 8" CMP OUT (N)EX 8" SS, IE 112.148" W, IE 116.026" W, IE 116.10EX 2" P, IE 116.28EX GAS, IE 114.88,ESTIMATED19 LF - 12" SD PVC
S=1.6%
34 LF -
12" SD
PVC
S=0.6%EX 6" WPROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
1 2NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. LOCATION AND DEPTH OF EXISTING UTILITIES SHOWN
ARE APPROXIMATE. CONTRACTOR SHALL VERIFY
LOCATION OF EXISTING UTILITES PRIOR TO STARTING
CONSTRUCTION.
7. SEE DWG G-3 FOR STORM GENERAL NOTES. REFER TO
CONSTRUCTION SEQUENCING AND GENERAL
REQUIREMENTS ON DWG G-12.
8. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
9. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
10. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
11. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18135
130
125
120
115
110
135
130
125
120
115
110 CB #39RIM EL 121.73EX GRADE AT
C/L OF PIPE
ALIGNMENT
IE 119.6 - 12" OUT (N) CB #38RIM EL 121.68S=0.75%8" W, IE 117.11EX SS, IE 115.66EX 1" WS6" W, IE 117.1EX 4" W, IE 118.76, ESTIMATEDIE 119.3 - 12" IN (S)IE 119.3 - 12" IN (E)IE 119.3 - 12" OUT (SW)39 LF
12" SD DI 1145
140
135
130
125
150
145
140
135
130
125
155155
150
IE 144.4 - 12" OUT (SW)CB #34RIM EL 146.488" W, IE 143.09EX GAS, IE 143.26, ESTIMATEDEX 8" SS, IE 139.94CB #35RIM EL 145.75IE 140.6 - 12" IN (NE)IE 143.7 - 12" IN (SW)IE 140.6 -12" OUT (NW)30 LF -
12" SD DI
S=2.0%
EX GRADE AT
C/L OF PIPE
ALIGNMENT
EX 4" W, IE 142.82, ESTIMATEDPROVIDE 6" MIN
CLEARANCE W/
ETHAFOAM PAD
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY NE
STA 30+00 TO 34+00 SD-6
53 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
M ATCHLINE STA - SEE DW G 34+00SD-7MATCHLINE STA - SEE DWG 34+00 SD-7
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
LEGEND:
POTHOLE INFORMATION ON DWG G-12
XX
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN
PLACE AND PROPOSED WATER SHALL BE
ONLINE AND OPERATIONAL BEFORE STORM
STRUCTURE IS INSTALLED. BYPASS PUMP
EXISTING STORM AS REQUIRED.
1
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD
PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER
COR STD PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD
PLAN 220.20
6. EXISTING STORM PIPES SHALL BE REMOVED
WHEN LOCATED WITHIN 30 INCHES OF NEW
STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED
WHERE SHOWN AND PLUGGED AND
ABANDONED IN PLACE PER WSDOT STD SPEC
7-08.3(4) WHEN LOCATED FARTHER THAN 30
INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS
CALCULATED FROM C/L OF STRUCTURE TO C/L
OF STRUCTURE.
3A
4
3B5+006+0030+00
3 1 +0 0
3 2 +0 0
33+00
3
4
+
0
059+5060+00
G R A N D E Y W A YBRONSON WAY NEWIN DSOR W AY NE12" SD
PP
CB #32
TYPE 2 W/ SOLID LID
STA 30+13
OFFSET 17.3' LT
12" SD
PVC
12" SD
DI
CB #34
TYPE 1 W/ GRATE
STA 33+14
OFFSET 15.0' RT
CB #35
TYPE 2 W/ GRATE
STA 33+23
OFFSET 15.2' LT
12" SD
PP
CB #30
TYPE 1 W/ GRATE
STA 4+74
OFFSET 27.1' RT
CB #31
TYPE 1 W/ GRATE
STA 5+04
OFFSET 14.8' LT
CB #33
TYPE 2 W/ GRATE
STA 32+53
OFFSET 16.4' LT
12" SD
PVC
SEE PROFILE A/SD-5
1
1
1
195
190
185
180
175
170
200
195
190
185
180
175
170
200
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #31RIM EL 189.29IE 185.2 - 12" IN (SE)IE 185.2 - 12" OUT (N)CB #30RIM EL 190.48IE 186.2 - 12" OUT (NW)EX IE 189.6 - 4" IN (N)CB #32RIM EL 188.00IE 183.9 - 12" IN (S)IE 180.5 - 12" OUT (W)EX 8" SD, IE 185.44,TO BE ABANDONED8" W, IE 184.4EX 6" W, IE 184.94,ESTIMATED67 LF - 12" SD PP
S=1.5%
51 LF - 12" SD PP
S=1.9%
PROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
190
185
180
175
170
165
160
190
185
180
175
170
165
160
EX GRADE AT
C/L OF PIPE
ALIGNMENT
1" WSEX 1" WSEX 2" GAS, IE 167.42,ESTIMATED242 LF -
12" SD PVC
S=13.8%
TRENCH DAM, TYP
PER DETAIL 1/G-13
170
165
160
155
150
145
170
165
160
155
150
145
140 140
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #33RIM EL 154.40IE 148.9 - 12" IN (E)IE 148.9 - 12" OUT (NW)EX 2" GAS, IE 159.94,ESTIMATED1" WSEX 1" WS1" WSEX 1" WS &EX 4" W, IE 3.14,ESTIMATEDEX 2" GAS, IE 149.15,ESTIMATEDEX 4" W, IE 149.96,ESTIMATED242 LF -
12" SD PVC
S=13.8%11155
150
145
140
135
130
155
150
145
140
135
130
125 125
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #35RIM EL 145.75IE 140.6 - 12" IN (E)IE 143.7 - 12" IN (NE)IE 140.6 - 12" OUT (NW)1" WSEX 1" WSEX GAS, IE 143.341" WS S=12.0%
139 LF
-12" SD PP
75 LF -
12" SD PVC EX 4" W, IE 137.59,ESTIMATEDEX 1" WS1" WSEX 4" W, IE 135.34,ESTIMATEDS=12.4%11BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY NE
STA 8+00 TO 13+00 SD-7
54 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 38+50SD-8M
A
T
C
H
LIN
E S
T
A
- S
E
E D
W
G
34+00
S
D-6
MATCHLINE STA - SEE DWG 38+50 SD-8MATCHLINE STA - SEE DWG 34+00 SD-6
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
CONNECT EXISTING PIPE TO NEW CATCH BASIN WITH
FABRICATED SAND COLLAR OF SAME MATERIAL AS
THE CONNECTING PIPE.
1
234+003 5 +0 0
36+00
37+00
3
8
+
0
0
12" SD
PP
12" SD
DI
CB #37
TYPE 2 W/ GRATE LID
STA 36+01
OFFSET 14.3' LT
12" SD
DI
CB #36
TYPE 2 W/ GRATE
STA 34+54
OFFSET 13.9' LT
CB #38
TYPE 1 W/ GRATE
STA 36+44
OFFSET 16.6' RT
12" SD
DI
CB #39
TYPE 2 W/ GRATE LID
STA 36+67
OFFSET 14.4' LT
G R A N D E Y W A Y
12" SD
DI
SEE PROFILE
B/SD-5
1
1
1
2
135
130
125
120
115
135
130
125
120
115
110 110
105 105
EX GRADE AT
C/L OF PIPE
ALIGNMENTCB #36RIM EL 128.19IE 122.9 - 12" IN (S)IE 122.0 - 12" OUT (N)CB #37RIM EL 121.20IE 119.2 - 12" IN (S)IE 117.3 - 12" IN (N)EX IE 117.3 - 8" OUT (W)CB #39RIM EL 121.72IE 119.3 - 12" OUT (SW)IE 119.3 - 12" IN (E)IE 119.3 - 12" IN (S)6" W, IE 117.1EX 4" WIE 128.14ESTIMATEDEX 6" SS, IE 120.0±EX 4" WIE 122.54ESTIMATEDEX 4" WIE 118.83ESTIMATEDEX 1" WSEX 4" WIE 118.96ESTIMATE8" W, IE 117.391" WSEX 1" WS1" WSEX 1" WSEX 8" SS, IE 112.7±153 LF - 12" SD DI
S=1.8%7 0 L F - 1 2 " S D D I
S =2 .9%
210 LF - 12" SD DI
S=1.2%111TRENCH DAM, TYP
PER DETAIL 1/G-13 2NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD
PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER
COR STD PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD
PLAN 220.20
6. EXISTING STORM PIPES SHALL BE REMOVED
WHEN LOCATED WITHIN 30 INCHES OF NEW
STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED
WHERE SHOWN AND PLUGGED AND
ABANDONED IN PLACE PER WSDOT STD SPEC
7-08.3(4) WHEN LOCATED FARTHER THAN 30
INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS
CALCULATED FROM C/L OF STRUCTURE TO C/L
OF STRUCTURE.BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY NE
STA 38+50 TO 42+50 SD-8
55 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 38+50SD-7MATCHLINE STA - SEE DWG 42+50SD-9HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 38+50 SD-7
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
1
39+00
40+00
41+00
4 2 +0 0
GRANDEY WAY
CB #41
TYPE 1 W/ GRATE
STA 38+74
OFFSET 13.5' LT
12" SD
DI
12" SD
PP
CB #42
TYPE 2 W/SOLID LID
STA 38+74
OFFSET 4.8' RT
CB #43
TYPE 1 W/ GRATE
STA 41+57
OFFSET 15.5' RT
CB #44
TYPE 1 W/ GRATE
STA 41+49
OFFSET 14.7' LT
12" SD
DI
12" SD
PP
CB #40
TYPE 1 W/ GRATE
STA 38+74
OFFSET 16.8' RT
1
140
135
130
125
120
115
110
140
135
130
125
120
115
110
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #42RIM EL 125.45IE 121.8 - 12" OUT (W)IE 121.8 - 12" IN (E)IE 121.8 - 12" IN (SE)IE 121.8 - 12" IN (NW)CB #43RIM EL 130.61IE 125.3 - 12" OUT (W)IE 125.3 - 12" IN (NW)IE 125.7 - 12" IN (SE)285 LF - 12" SD PP
S=1.2%
31 LF
12" SD PP
S=1.3%1" WSEX 1" WSEX 1" WS1" WS1" WS1" WSEX 1" WSEX 1" WS8" W, IE 127.1EX 4" W, IE 127.13ESTIMATEDCB #44RIM EL 130.25NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD
PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER
COR STD PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD
PLAN 220.20
6. EXISTING STORM PIPES SHALL BE REMOVED
WHEN LOCATED WITHIN 30 INCHES OF NEW
STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED
WHERE SHOWN AND PLUGGED AND
ABANDONED IN PLACE PER WSDOT STD SPEC
7-08.3(4) WHEN LOCATED FARTHER THAN 30
INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS
CALCULATED FROM C/L OF STRUCTURE TO C/L
OF STRUCTURE.BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18135
130
125
120
115
110
135
130
125
120
115
110
105105CB #42RIM EL 125.45IE 122.2 - 12" OUT (S)CB #41RIM EL 124.61CB #40RIM EL 124.91IE 122.0 - 12" OUT (N)EX GRADE AT
C/L OF PIPE
ALIGNMENT
12 LF - 12" SD DI
S=2.0%
18 LF - 12" SD DI
S=2.0%EX 8" SS, IE 118.98" W, IE 120.43EX 4" W, IE 121.06, ESTIMATEDIE 121.8 - 12" IN (NW)IE 121.8 - 12" IN (SE)IE 121.8 - 12" OUT (W)IE 121.8 - 12" IN (E)1
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-6-9.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY NE
STA 42+50 TO 47+00 SD-9
56 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 42+50SD-8KEY MAP
SCALE: 1" = 400'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
1
5
19+0020+0043+00
44+00 45+00
4 6 +0 0
4 7 +0 0
G R A N D E Y W A Y BRONSON WAY NECB #46
TYPE 1 W/ GRATE
STA 44+77
OFFSET 15.6' LT
SEE DWG SD-19
18" SD
PP
CB #45
TYPE 1 W/ GRATE
STA 44+64
OFFSET 14.8' RT
SEE DWG SD-19
18" SD
PP
IE 127.0 - 18" OUT (W)
FOR CHANNEL
IMPROVMENTS
SEE DWG SD-19
FOR PLAN AND PROFILE
SEE DWG SD-19
1
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD
PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER
COR STD PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD
PLAN 220.20
6. EXISTING STORM PIPES SHALL BE REMOVED
WHEN LOCATED WITHIN 30 INCHES OF NEW
STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED
WHERE SHOWN AND PLUGGED AND
ABANDONED IN PLACE PER WSDOT STD SPEC
7-08.3(4) WHEN LOCATED FARTHER THAN 30
INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS
CALCULATED FROM C/L OF STRUCTURE TO C/L
OF STRUCTURE.BRONSON B R O N S O N W A Y N E
BR O NSO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-10-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONA L E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON PL NE
STA 50+00 TO 54+00 SD-10
57 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA
-
SEE DWG
5
4
+
0
0
SD-
1
1
175
170
165
160
155
150
145
FOR PROFILE
CONTINUATION
SEE DWG SD-4
KEY MAP
SCALE: 1" = 400'-0"MATCHLINE STA - SEE DWG 54+00 SD-11
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
CONSTRUCTION NOTES:
SEE WATER SHEETS FOR NEW SANITARY MANHOLE
DESIGN.
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
INSTALL YARD DRAIN RIMS WITH SLIGHT
DEPRESSION TO COLLECT STORMWATER ON
SIDEWALKS.
1
2
3
50+00
51+00
52+00
5 3 +0 0
5 4 +0 0
BRONSON PLACE NE
B R O N S O N W A Y N E
12" SD
PVC
CB #54
TYPE 1 W/ GRATE
STA 50+80
OFFSET 15.5' RT
CB #53
TYPE 1 W/ GRATE
STA 52+55
OFFSET 15.3' LT
CB #52
TYPE 1 W/ GRATE
STA 53+54
OFFSET 13.6' RT
YARD DRAIN,
PER DETAIL 2/G-13
12" SD
PP
FOR PLAN AND PROFILE
SEE DWG SD-4
CB #55
TYPE 1 W/ GRATE
BRONSON WAY NE
STA 15+68.65
OFFSET 27.75' RT
1
8" SD
HDPE
10 LF
2 3
175
170
165
160
155
150
145
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #54RIM EL 160.90IE 157.8 - 12" OUT (NW)IE 157.8 - 12" IN (NE)1 7 5 L F - 1 2 " S D P V C
S =5 .1 %EX 8" SSIE 156.378" W, IE 155.541" WSNOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18190
185
180
175
170
165
190
185
180
175
170
165
160160
EX GRADE AT
C/L OF PIPE
ALIGNMENT CB #52RIM EL 183.84IE 178.7 - 12" OUT (SW)IE 178.7 - 12" IN (N)IE 178.7 - 8" IN (NE)CB #53RIM EL 171.07IE 166.7 - 12" OUT (SW)IE 166.7- 12" IN (NE)S =1 1 .7 %8" W, IE 178.92EX 2" GAS, IE 171.41ESTIMATEDEX 4" W, IE 180.31,ESTIMATEDEX 8" SSIE 184.32EX GAS, IE 167.38ESTIMATEDEX WS1" WSEX 8" SS, IE 174.8ESTIMATEDEX 6" SD, IE 184.2ESTIMATED8" W, IE 183.36EX 6" SD, IE 169.8ESTIMATEDPROVIDE 6"
MIN CLR W/
ETHAFOAM
PADTRENCH DAM, TYP
PER DETAIL 1/G-13EX 8" SS,IE 172.1721 0 3 L F -1 2 " S D P P
PROVIDE 6"
MIN CLR W/
ETHAFOAM PAD
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-10-11.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON PL NE
STA 54+00 TO 57+50 SD-11
58 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 54+00SD-10MATCHLINE STA - SEE DWG 54+00 SD-10
KEY MAP
SCALE: 1" = 400'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
CONSTRUCTION NOTES:
CONNECT TO EX CATCH BASIN WITH KOR-N-SEAL
CONNECTION.
INSTALL YARD DRAIN RIMS WITH SLIGHT DEPRESSION
TO COLLECT STORMWATER ON SIDEWALKS.
1
22
210
205
200
215
220
225
195
210
205
200
195
215
220
225
EX GRADE AT
C/L OF PIPE
ALIGNMENT
IE 211.4 - 12" OUT (N) CB # 90RIM EL 213.74CB # 91RIM EL 213.91IE 211.28 - 12" IN (S)IE 211.28 - 12" OUT (W)CB #92RIM EL 214.36IE 211.1 - 12" IN (W)EX IE 211.1 - 12" OUT (N)21 LF - 12" SD DI
S=0.50%
31 LF - 12" SD DI
S=0.50%8" W, IE 209.22EX SS, IE 207.67EX OHPEX 12" SDEX 2" G, IE 210.58ESTIMATEDEX 4" W, IE 210.44ESTIMATEDPROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
67
54+00
55+00
5 6 +0 0
5
7
+
0
0
B R O N S O N P L A C E N E
WINDSOR PLACE NE12" SD
DI
CB #92
TYPE 1 W/ GRATE
STA 56+56
OFFSET 14.2' RT
CB #90
TYPE 1 W/ GRATE
STA 56+36
OFFSET 15.6' LT
CB #91
TYPE 1 W/ GRATE
STA 56+52
OFFSET 16.4' LT
12" SD
DI
12" SD
PP
CB #51
TYPE 2 W/ GRATE
STA 54+96
OFFSET 7.5' LT
CB #50
TYPE 1 W/ GRATE
STA 55+00
OFFSET 58.3 RT12" SD
PP
YARD DRAIN,
PER DETAIL 2/G-13
8" SD
HDPE
1
2
210
205
200
195
190
215
220
210
205
200
195
190
215
220
EX GRADE AT
C/L OF PIPE
ALIGNMENT CB #51RIM EL 209.52IE 202.5 - 12" OUT (E)IE 202.5 - 12" IN (S)IE 206.5 - 8" IN (NE)CB #50RIM EL 215.95IE 211.3 - 12" OUT (SW)IE 213.8 - 8" IN (N)YARD DRAINRIM EL 216.67IE 214.0 - 8" OUT (SW)1 4 3 L F -1 2 " S D P P 8" W, IE 208.47EX 4" W, IE 208.78,ESTIMATEDEX 12" SD, IE 192.2ESTIMATEDEX 2" GAS, IE 204.4, ESTIMATED1" WSEX 1" WS8.4 LF
8" SD HDPE
S=2.0%1" WSEX 1" WSEX 2" G, IE 190.62, ESTIMATEDEX 8" SS, IE 205.95EX 1" WS1" WSEX 8" SS, IE 208.10S =1 3 .4 %
TRENCH DAM, TYP
SEE DETAIL 1/G-13
S =1 6 .6 %
6 6 L F -1 2 " S D P P
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18+00
210
205
200
215
220
210
205
200
215
220
195 195
190 190IE 207.8 - 6" OUT (SW)EX IE 210.7 - 6" IN (E)EX CB NO. 133775RIM 212.19EX GRADE AT
C/L OF PIPE
ALIGNMENT
4 4 L F - 8 " S D H DP E
S =3.0 %EX 4" W, IE 208.90ESTIMATED8" W, IE 209.22CB #51RIM EL 209.52IE 203.8 - 12" OUT (E)IE 203.8 - 12" IN (S)IE 206.5 - 6" IN (NE)EX 6" SD
M A T C H L I N E S T A
- S E E D W G
8 3 +2 5
S D -1 3
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-12-13.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONA L E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR PL NE
STA 80+00 TO 83+25 SD-12
59 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
CONSTRUCTION NOTES:
INSTALL YARD DRAIN RIMS WITH SLIGHT DEPRESSION TO
COLLECT STORMWATER ON SIDEWALKS.
1
8
54+0055+0079+80 80+00 81+00
82+00
83+00WINDSOR PLACE NE
BRONSON PLACE NE12" SD
PP
CB #81
TYPE 1
STA 83+01
OFFSET 15.8' RT
CB #82
TYPE 1
STA 83+13
OFFSET 23.6' LT
YARD DRAIN,
PER DETAIL 2/G-13
CB #83
TYPE 1
STA 82+80
OFFSET 229.2' LT
12" SD
PPFOR PLAN AND PROFILE
SEE DWG SD-11
CB #51
TYPE 2 W/ GRATE
STA 54+96
OFFSET 7.47' LT
CB #50
TYPE 1
STA 55+00
OFFSET 58.3' RT
1
255
250
245
240
235
230
225
245
240
235
255
250
230
225
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #83RIM EL 248.57IE 246.6 - 8" IN (E)IE 244.3 - 12" OUT (S)CB #82RIM EL 243.98IE 238.9 - 12" IN (N)IE 238.9 - 12" OUT (W)YARD DRAINRIM EL 249.24IE 246.7 - 8" OUT (S)CB #81RIM EL 241.78IE 237.0 - 12" IN (E)IE 237.0 - 12" OUT (S)74 LF - 12" SD PP
S=7.3%
41 LF - 12" SD PP
S=4.6%1" WSEX 1" WSEX 2" GAS, IE 246.61EX 8" SS, IE 239.858" W, IE 240.37EX 1/2" GAS5.6 LF - 8" SD HDPE
S=1.8%EX 1" WS1" WS1NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
MATCHLI
NE STA - SEE DWG 83+25SD-12DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-12-13.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR PL NE
STA 83+25 TO 88+00 SD-13
60 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
FOR PROFILE CONTINUATION
SEE DWG SD-16
8 4 +0 0
85+00 86+00
87+00
8 8 +0 088+01
73+00WINDSOR PLACE NE
WINDSOR WAY NE12" SD
PP
CB #80
TYPE 1 W/ GRATE
STA 85+23
OFFSET 14.8' LT
12" SD
PVC
CB #79
TYPE 2 W/ GRATE
STA 86+83
OFFSET 15.2' LT
SEE DWG SD-16
FOR PLAN AND PROFILE
SEE DWG SD-16
CB #78
TYPE 1 W/ GRATE
STA 86+67
OFFSET 24.0' RT
CB #76
TYPE 2 W/ SOLID LID
STA 72+48
OFFSET 21.8' LT
CB #77
TYPE 1 W/ GRATE
STA 72+93
OFFSET 14.6' RT
240
235
230
225
220
215
210
240
235
230
225
220
215
210
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #80RIM EL 229.21IE 224.6 - 12" IN (N)IE 224.6 - 12" OUT (S)221 LF - 12" SD PVC
S=5.6%
160 LF - 12" SD PP
S=6.6%CB #79RIM EL 222.55IE 214.0 - 12" IN (N)
IE 214.0 - 12" OUT (SW)EX 1" WS1" WSEX 8" SSIE 223.5±8" W,IE 233.08EX 1" WSEX GASIE 235.14ESTIMATEDEX 4" WIE 236.08ESTIMATEDEX 1" WSEX GASIE 225.59ESTIMATEDEX GASIE 221.90ESTIMATEDEX GASIE 219.69ESTIMATED1" WS1" WSEX 1" WSEX 1" WSEX 4" W
IE 238.23
ESTIMATED
EX 1" WS1" WSNOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
MATCHLINE STA - SEE DWG 64+50SD-15DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONA L E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR WAY NE
STA 60+00 TO 64+50 SD-14
61 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
CONSTRUCTION NOTES:
INSTALL QUARRY SPALL PAD AT OUTFALL, PER
WSDOT STD SPECIFICATION 8-01.3(11).
15+006+0030+00
59+50
60+00
61+00
62+00
63+00
64+00
4+00WINDSOR WAY NEBRONSON WAY NEG
R
AN
DEY W
AY NE
12" SD
DI
CB #60
TYPE 1 W/ GRATE
STA 62+51
OFFSET 14.7' RT
CB #61
TYPE 1 W/ GRATE
STA 62+96
OFFSET 14.7' RT
12" SD
DI
FOR PLAN AND PROFILE
SEE DWG SD-6
CB #62
TYPE 1 W/ GRATE
STA 62+96
OFFSET 15.7' LT
12" SD
DI - OUTFALL
IE 190.5±
1
SEE R DWGS FOR
RESTORATION
INFORMATION
200
195
190
185
180
200
195
190
185
180
175175
205205
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #60RIM EL 192.56EX IE 192.0 - 4" DI IN (S)IE 191.2 - 12" OUT (E)CB #61RIM EL 193.0IE 191.1 - 12" OUT (E)IE 191.1 - 12" IN (W)CB #62RIM EL 192.88IE 190.8 - 12" IN (N)IE 190.8 - 12" OUT (S)30 LF - 12" SD DI
S=0.7%EX 2" GASIE 189.68ESTIMATED8" W, IE 189.2944 LF - 12" SD DI
S=0.05%EX 8" SS, IE 186.0±EX OHPEX 6" W, IE 190.21,ESTIMATED15 LF -
12" SD DI
S=2.0%
12" SD DI
OUTFALL
IE 190.5±
1
8'1'NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE APPR
OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONA L E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024 RLO WINDSOR WAY NE
STA 64+50 TO 69+50 SD-15
62 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 64+50SD-14MATCHLINE STA - SEE DWG 69+50SD-16MATCHLINE STA - SEE DWG 69+50 SD-16
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS INSTALLED. BYPASS
PUMP EXISTING STORM AS REQUIRED.
CONNECT EXISTING PIPE TO NEW CATCH BASIN WITH
FABRICATED SAND COLLAR OF SAME MATERIAL AS THE
CONNECTING PIPE.
1
2
LEGEND:
POTHOLE INFORMATION ON DWG G-12
XX
9
65+00
66+00
67+00
6 8 +0 0
6 9 +0 0
WINDSOR WAY NE
12" SD
PP
CB #70
TYPE 2 W/ SOLID LID
STA 68+28
OFFSET 15.9' LT
CB #71
TYPE 1 W/ GRATE
STA 68+58
OFFSET 15.0' LT
CB #72
TYPE 1 W/ GRATE
STA 68+52
OFFSET 15.4' RT
12" SD
PP
1
2
185
180
175
170
195
190
185
180
175
170
195
190
165 165
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #70RIM EL 178.98EX IE 172.7 - 12" IN (SE)EX IE 172.6 - 12" OUT (NW)IE 172.9 - 12" IN (NE)CB #71RIM EL 178.24IE 173.5 - 12" OUT (SW)IE 173.5 - 12" IN (NE)IE 173.5 - 12" IN (SE)1 5 6 L F - 1 2 " S D P P
S =6 .9 %29 LF - 12" SD PP
S=2.1%1" WSEX 8" SS, IE 169.89EX 1" WSEX 4" W IE 175.28ESTIMATEDEX 1" WS1" WS1" WS12NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO NVUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
N E 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18185
180
175
170
165
185
180
175
170
165
165165
190190
CB #71RIM EL 178.2431 LF - 12" SD PP
S=1.94%
EX GRADE AT
C/L OF PIPE
ALIGNMENTCB #72RIM EL 178.44IE 173.5 - 12" OUT (SW)IE 173.5 - 12" IN (NE)IE 173.5 - 12" IN (SE)IE 174.0 - 12" OUT (NW)8" W, IE 172.29EX 2" GAS, IE 175.7ESTIMATEDEX 4" W INSIDECB, IE 174.06EX 8" SS, IE 171.771
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR WAY NE
STA 69+50 TO 73+50 SD-16
63 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHL
I
NE
S
T
A
-
S
E
E
DWG
6
9
+
5
0
S
D-
1
5
M A T C H L IN E S T A - S E E D W G 7 3 +5 0
S D -1 7
MATCHLINE STA - SEE DWG 69+50 SD-15
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
HORIZ: 1" = 20'-0"
VERT: 1" = 5'-0"
KEY MAP
SCALE: 1" = 400'-0"
FOR PROFILE CONTINUATION
SEE DWG SD-13
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS INSTALLED. BYPASS
PUMP EXISTING STORM AS REQUIRED.
1
185
180
175
195
190
205
200
185
180
175
195
190
200
EX GRADE AT
C/L OF PIPE
ALIGNMENT
CB #73RIM EL 188.90IE 184.3 - 12" IN (SW)IE 184.3 - 12" OUT (NE)CB #74RIM EL 194.89IE 190.4 - 12" OUT (SW)IE 190.4 - 12" IN (SE)CB #75RIM EL 196.56IE 192.4 - 12" OUT (NW)IE 192.4 - 12" IN (NE)8 2 L F - 1 2 " S D P P
S =7 .4 %
3 6 L F -
1 2 " P P EX 2" GAS, IE 193.52ESTIMATED,TO BE RELOCATEDEX 8" SSIE 189.00EX 4" W, IE 191.75,ESTIMATED8" W, IE 190.97EX 8" SSIE 184.0±ESTIMATEDEX 1" WS1" WSEX 8" SSIE 186.31EX 4" W, IE 191.22,ESTIMATEDEX 8" SSIE 178.13EX GAS, IE 182.57, ESTIMATEEX 1" WS1" WSEX 2" G,
TO BE
RELOCATED11S=5 .6 %
PROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
195
205
200
195
205
200
210 210
215 215
220 220
225 225
EX GRADE AT
C/L OF PIPE
ALIGNMENT CB #76RIM EL 215.96IE 211.8 - 12" OUT (SW)IE 212.9 - 12" IN (N)IE 211.8 - 12" IN (NE)IE 211.8 - 12" IN (SE)IE 214.0 - 12" OUT (SW)IE 214.0 - 12" IN (N)CB #79
RIM EL 222.55
1 4 3 L F -1 2 " S D P V C
7 6 L F - 1 2 " S D P P
S =2.9 %EX 1" WS1" WS8" WIE 219.06EX 4" W, IE 218.89,ESTIMATEDEX GAS, IE 219.18,ESTIMATEDEX 8" SSIE 207.56EX 6" SS, IE 203.2±EX 4" W, IE 211.75, ESTIMATEDEX 1" WS8" W, IE 201.20EX GAS, IE 204.69ESTIMATED1" WSEX 1" WSEX 8" SSIE 215.12EX 2" G,
TO BE
RELOCATED
S =1 3 .6 %
PROVIDE 6"
MIN CLR W/
ETHAFOAM
PAD
TRENCH DAM, TYP,
PER DETAIL 1/G-13 1PROVIDE 6" MIN CLR
W/ ETHAFOAM PAD
10
7 0 +0 0
7 1+00 72+00
7
3
+
0
0
WINDSOR WAY NE WINDSOR PLACE NE12" SD
PP
CB #74
TYPE 1 W/ GRATE
STA 70+91
OFFSET 15.3' LT
CB #75
TYPE 1 W/ GRATE
STA 71+11
OFFSET 15.0' RT
CB #78
TYPE 1 W/ GRATE
STA 86+67
OFFSET 24.0' RT
CB #79
TYPE 2 W/ SOLID LID
STA 86+83
OFFSET 15.2' LT
CB #77
TYPE 1 W/ GRATE
STA 72+93
OFFSET 14.6' RT
12" SD
PVC
12" SD
PP
12" SD
PP
12" SD
PP
CB #76
TYPE 2 W/ SOLID LID
STA 72+48
OFFSET 21.8' LT
CB #73
TYPE 2 W/ SOLID LID
STA 70+12
OFFSET 7.9' LT
FOR PLAN AND PROFILE
SEE DWG SD-13
SEE PROFILE
B/SD-17
SEE PROFILE
A/SD-17
1
1
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-14-17.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO WINDSOR WAY NE
STA 73+50 TO 75+76 SD-17
64 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186MATCHLINE STA - SEE DWG 73+50SD-16KEY MAP
SCALE: 1" = 400'-0"
PROFILE
VERT
SCALE: HORIZ
A
SD-161" = 20'-0"
1" = 5'-0"
PROFILE
VERT
SCALE: HORIZ
B
SD-161" = 20'-0"
1" = 5'-0"
CONSTRUCTION NOTES:
EXISTING WATER SHALL BE ABANDONED IN PLACE AND
PROPOSED WATER SHALL BE ONLINE AND OPERATIONAL
BEFORE STORM STRUCTURE IS INSTALLED. BYPASS
PUMP EXISTING STORM AS REQUIRED.
1
16A
16B
7 5 +7 6
74+00
7 5 +0 0
WINDSOR PLACE NE EDMONDS AVE NEN O S T O R M IM P R O V E M E N T S O N T H IS P L A N
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN 202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE PER
WSDOT STD SPEC 7-08.3(4) WHEN LOCATED FARTHER
THAN 30 INCHES FROM NEW STORM FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA RESTORED
AS SHOWN ON THE RESTORATION SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18225
220
215
210
205
230
200
225
220
215
210
205
230
200CB #76RIM EL 215.96EX GRADE AT
C/L OF PIPE
ALIGNMENT
IE 216.3 - 12" OUT (S) CB #78RIM EL 220.61EX 4" W, IE 212.49 , ESTIMATEDEX 8" SS, IE 204.82IE 211.8 - 12" OUT (SW)IE 211.8 - 12" IN (NE)IE 211.8 - 12" IN (SE)IE 212.9 - 12" IN (N)5 4 L F - 1 2 " S D P P
S =6 .3 %1225
220
215
210
205
230
225
220
215
210
205
230
200200
EX GRADE AT
C/L OF PIPE
ALIGNMENT
IE 214.90 - 12" OUT (N)CB #77RIM EL 220.29CB #76RIM EL 215.96IE 211.8 - 12" OUT (SW)IE 211.8 - 12" IN (NE)IE 212.9 - 12" IN (N)IE 211.8 - 12" IN (SE)EX 8" SS, IE 204.24EX 4" W, IE 212.81ESTIMATED8" W, IE 214.78EX GASIE 215.68ESTIMATED5 8 L F
1 2 " S D P P
S =5 .3 %1
MATCHLINE STA - SEE DWG 802+10SD-1DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-18.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO VUEMONT PL NE STA 700+00 TO 702+00 AND
STORM STRUCTURE TABLE SD-18
65 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
KEY MAP
SCALE: 1" = 400'-0"
STORM STRUCTURE TABLE
STRUCTURE
ID DRAWING STATION CB TYPE
COVER/GRATE
COR STD
CB #1 SD-1 1+77 1 204.20
CB#2 SD-3 8+36 1 204.20
CB #3 SD-3 8+35 1 204.20
CB #4 SD-3 11+03 2 204.20
CB #5 SD-3 11+04 1 204.20
CB #6 SD-3 11+04 1 204.30
CB #7 SD-4 14+17 1 204.30
CB #8 SD-4 14+20 1 204.20
CB #9 SD-4 14+26 1 204.20
CB #20 SD-5 21+59 1 204.20
CB #21 SD-5 21+71 1 204.20
CB #22 SD-5 21+90 2 204.50
CB #30 SD-6 4+74 1 204.20
CB #31 SD-6 5+04 1 204.20
CB #32 SD-6 30+13 2 204.50
CB #33 SD-6 32+53 2 204.20
CB #34 SD-6 33+14 1 204.20
CB #35 SD-6 33+23 2 204.20
CB #36 SD-7 34+54 2 204.20
CB #37 SD-7 36+01 2 204.30
CB #38 SD-7 36+44 1 204.30
CB #39 SD-7 36+67 2 204.30
CB #40 SD-8 38+74 1 204.20
CB #41 SD-8 38+74 1 204.20
CB #42 SD-8 38+74 2 204.50
CB #43 SD-8 41+57 1 204.20
CB #44 SD-8 41+49 1 204.20
CB #45 SD-9 44+64 1 204.30
CB #46 SD-9 44+77 1 204.30
CB #50 SD-11 55+00 1 204.20
CB #51 SD-11 54+96 2 204.50
CB #52 SD-10 53+54 1 204.20
CB #53 SD-10 52+55 1 204.20
CB #54 SD-4 50+80 1 204.20
CB #55 SD-4 15+69 1 204.20
CB #56 SD-4 16+25 2 204.50
CB #57 SD-4 16+58 1 204.30
CB #58 SD-4 16+55 1 204.30
CB #60 SD-14 62+51 1 204.30
CB #61 SD-14 62+96 1 204.20
CB #62 SD-14 62+96 1 204.20
CB #70 SD-15 68+28 2 204.50
CB #71 SD-15 68+58 1 204.30
CB #72 SD-15 68+52 1 204.30
CB #73 SD-16 70+12 2 204.50
CB #74 SD-16 70+91 1 204.20
CB #75 SD-16 71+11 1 204.20
CB #76 SD-13 72+48 2 204.50
CB #77 SD-13 72+93 1 204.20
CB #78 SD-13 86+67 1 204.20
CB #79 SD-13 86+83 2 204.20
CB #80 SD-13 85+23 1 204.20
CB #81 SD-12 83+01 1 204.30
CB #82 SD-12 83+13 1 204.20
CB #83 SD-12 82+80 1 204.30
17
18
800+00 801+00
802+00
700+00701+00702+00BRONSON WAY NE
VUEMONT PL NEN O S T O R M IM P R O V E M E N T S O N T H IS P L A N
BRONSON B R O N S O N W A Y N E
B RO N SO N
VUEM
ONT PL NE
BRONSON WAY NE
G R A N D E Y W A Y N E
W IN D S O R
NE 4TH STSUNSET BLVD NEPL NEWINDSOR PL NEEDMONDS AVE NEWAY NEW AY NESD-11SD-10SD-1SD-2S D -3 SD-4SD-5SD-6SD-7S D -8 SD-9SD-12
SD-13S D -1 4
S D-1 5
S D -1 6
S
D-17
SD-18
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-19.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO GRANDEY WAY DITCH
PLAN AND PROFILE SD-19
66 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
LEGEND:
POTHOLE INFORMATION ON DWG G-12
XX520+00
21+00
CB #45
TYPE 1 W/ GRATE
STA 20+13
CB #46
TYPE 1 W/ GRATE
STA 20+46
18" SD
PP
18" SD
PP
REMOVE EX CB
GRANDEY WAYCB #47
TYPE 2 W/ GRATE
STA 21+42.4
2 3
LIMITS OF
CONSTRUCTION
1 4
6
8
8
7
CONSTRUCTION NOTES:
PROTECT EXISTING BLOCK WALL IN-PLACE WITH
TEMPORARY SHORING AS NECESSARY.
REMOVE EXISTING BROKEN CONCRETE ROCKERY
AND LOOSE SOILS IN EXISTING DITCH TO PREPARE
TRENCH SUBGRADE AND SIDEWALLS.
WITHIN PRIVATE PROPERTY SURFACE
RESTORATION SHALL BE 12-INCHES OF TOPSOIL
AND HYDROSEED PER SECTION 8-02 ROADSIDE
RESTORATION.
REMOVE PORTIONS OF EX 24" CMP AND EX 12"
CONC SD SO THAT EX SD PIPES ARE FLUSH
WITHIN NEW CB #47. CONNECT USING
KOR-N-SEAL CONNECTIONS OR EQUAL.
CONNECT EX PIPE TO NEW CATCH BASIN WITH
FABRICATED SAND COLLAR OF SAME MATERIAL
AS THE CONNECTING PIPE.
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
PROTECT EXISTING FENCES OR REMOVE, RETAIN,
AND REINSTALL AS NECESSARY.
PRESERVE AND PROTECT TREES.
1
2
3
4
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN
202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR
STD PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM
FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE
PER WSDOT STD SPEC 7-08.3(4) WHEN LOCATED
FARTHER THAN 30 INCHES FROM NEW STORM
FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS
CALCULATED FROM C/L OF STRUCTURE TO C/L OF
STRUCTURE.
5
6
7
8
20+00 21+00
145
140
135
130
125
120
115
145
140
135
130
125
120
115
IE 124.6 - 18" IN (E)CB #46RIM EL 131.06IE 125.2 - 18" OUT (W)IE 128.0 - 18" IN (E)EX GRADE AT
C/L OF PIPE
ALIGNMENT
33 LF - 18" SD PP
S=1.9%CB #47RIM 141.0IE 136.0 - 18" OUT (W)EX IE 138.7 - 12" CONC IN (E)EX IE 137.3 - 24" CMP IN (S)9 7 L F - 1 8 " S D P P
S = 8 .3 %EX 124.6 - 18" OUT (W)EX 18" OUTFALL
IE 122.7 8" WIE 127.61EX 24" SS, IE 127.18RIGHT OF WAYEX 12" SD
IE 138.7
(INSIDE EX 24" SD)EX 24" SD IE 137.3P/LEX BLOCK WALL
FINAL
GRADE
PROVIDE 6" MIN
CLEARANCE W/
ETHAFOAM PAD
1
CB #45RIM EL 130.65EX 6" W, IE 127.24ESTIMATED4
5
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-20.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE DITCH
PLAN AND PROFILE SD-20
67 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
CONSTRUCTION NOTES:
INSTALL QUARRY SPALL PAD AT OUTFALL, PER
WSDOT STD SPECIFICATION 8-01.3(11).
PROVIDE MINIMUM 1-FOOT DITCH FREEBOARD
ABOVE BIRDCAGE INLET.
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
1
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN
202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM
FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE
PER WSDOT STD SPEC 7-08.3(4) WHEN LOCATED
FARTHER THAN 30 INCHES FROM NEW STORM
FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.
2
3
9
1
+
5
090+009
1
+
0
0
REMOVE VEGETATION AND
INSTALL QUARRY SPALL DITCH,
MATCH EXISTING GRADES AND
SLOPE TO DRAIN TO CB #6
CB #4
TYPE 2 W/ GRATE
STA 90+30
CB #5
TYPE 1 W/ GRATE
STA 90+59
CB #6
TYPE 1 W/ BIRDCAGE INLET
PER COR STD PLAN 234.20
STA 90+69
12" SD
DI
B R O N S O N W A Y N E
LIMITS OF CONSTRUCTION
1
176
1
7
4
1
7
21703
90+00 91+00
165
160
155
150
170
175
180
CB #4RIM EL 169.47IE 167.0 - 12" OUT (N)IE 167.0 - 12" IN (S)IE 167.0 - 12" IN (W)29 LF - 12" SD DI
S=1.0%
EX GRADE AT
C/L OF PIPE
ALIGNMENT CB #5RIM EL 169.94IE 167.3 - 12" OUT (N)IE 167.3 - 12" IN (S)CB #6RIM EL 169.90IE 167.4 - 12" OUT (N)10 LF - 12" SD DI
S=1.0%
QUARRY SPALL DITCH,
PER DETAIL 2/SD-228" W, IE 165.57EX 8" SS, IE 163.74OUTFALL
IE 166.3
18 LF - 12" SD DI
S=3.9%
FINAL
GRADE
1 EX 6" W, IE 166.06ESTIMATED8'1'EX GRADE
RIGHT OF WAY
EX
GRADE
2
3
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-21.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024
RLO BRONSON WAY NE DITCH
PLAN AND PROFILE SD-21
68 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
CONSTRUCTION NOTES:
PROTECT EXISTING FENCES OR REMOVE, RETAIN,
AND REINSTALL AS NECESSARY.
REMOVE EXISTING BROKEN CONCRETE LINING,
LOOSE SOILS, AND VEGETATION IN EXISTING
DITCH TO PREPARE TRENCH SUBGRADE AND
SIDEWALLS.
WITHIN PRIVATE PROPERTY SURFACE
RESTORATION SHALL BE 8-INCHES OF CSBC.
REMOVE EXISTING ROCKERY TO PREPARE
TRENCH SUBGRADE AND SIDEWALLS.
CONTRACTOR SHALL ROUTE ANY SURFACE
WATER FROM EXISTING BUILDINGS TO CB #7.
EXISTING WATER SHALL BE ABANDONED IN PLACE
AND PROPOSED WATER SHALL BE ONLINE AND
OPERATIONAL BEFORE STORM STRUCTURE IS
INSTALLED. BYPASS PUMP EXISTING STORM AS
REQUIRED.
CONNECT EX PIPE TO NEW CATCH BASIN WITH
FABRICATED SAND COLLAR OF SAME MATERIAL
AS THE CONNECTING PIPE.
PROVIDE MINIMUM 1-FOOT DITCH FREEBOARD
ABOVE BIRDCAGE INLET.
PRESERVE AND PROTECT TREE.
1
2
3
4
5
6
NOTES:
1. CATCH BASIN TYPE 1 PER COR STD PLAN 200.00
2. CATCH BASIN TYPE 2 PER COR STD PLAN 201.00
3. CATCH BASIN INSTALLATION PER COR STD PLAN
202.00
4. PIPE ZONE BEDDING AND COMPACTION PER COR STD
PLAN 220.10
5. TYPICAL TRENCH AND BACKFILL PER COR STD PLAN
220.20
6. EXISTING STORM PIPES SHALL BE REMOVED WHEN
LOCATED WITHIN 30 INCHES OF NEW STORM
FACILITIES.
7. EXISTING STORM PIPES SHALL BE CAPPED WHERE
SHOWN AND PLUGGED AND ABANDONED IN PLACE
PER WSDOT STD SPEC 7-08.3(4) WHEN LOCATED
FARTHER THAN 30 INCHES FROM NEW STORM
FACILITIES.
8. EXISTING STORM STRUCTURES IDENTIFIED FOR
REMOVAL SHALL BE REMOVED AND THE AREA
RESTORED AS SHOWN ON THE RESTORATION
SHEETS.
9. PIPE SLOPE SHOWN IN PROFILE VIEW IS CALCULATED
FROM C/L OF STRUCTURE TO C/L OF STRUCTURE.
7
8
9
BIRD CAGE OVERFLOW STRUCTURE
PER COR STD PLAN 234.20
STA 41+78CB #7
TYPE 1 W/ GRATE
STA 40+59
18" SD
PP
REMOVE
EX CB
CB #9
TYPE 1 W/ GRATE
STA 40+12.5
REMOVE EX CB
18" SD
PP
18" SD
PP
BRONSON WAY NECB #8
TYPE 1 W/ GRATE
STA 40+44
2
1
314+0015+0050+004 0 +0 0
41+00
4
2
+
0
0
43+00
300+00
5
LIMITS OF
CONSTRUCTION
4
6
9
EX GRADE AT
C/L OF PIPE
ALIGNMENT BIRD CAGEOVERFLOWSTRUCTURERIM 163.016 LF - 18" SD PP
S=8.3%CB #9RIM EL 157.45IE 153.2 - 18" IN (E)IE 154.4 - 18" OUT (W)CB #8RIM EL 158.1731 LF
18" SD PP CB #7RIM EL 159.25IE 155.7 - 18" IN (E)IE 155.7 - 18" OUT (W)IE 160.5 - 18" OUT (W)EX 18"
OUTFALL
IE 151.4
1 1 9 L F - 1 8 " S D PP
S =4 .0 %EX 6" W, IE 154.15ESTIMATED8" W, IE 155.08FINAL
GRADE
EX IE 152.7 - 18" OUT (W)IE 152.6 - 18" IN (E)165
160
155
150
145
40+00 41+00 42+00
165
160
155
150
145
140 140
170
160
170
160EX SS, IE 146.46PROVIDE 6" MIN
CLEARANCE W/
ETHAFOAM PAD
1.9%67
8
DATE:
DRAWING NO:
SHEET:
DESIGNED:
DRAWN:
CHECKED:
APPROVED:
SURVEYED:FILENAME: S:\Cad\Renton\22-10795 Windsor Hills\Design\dwgs\P22-10795_SD-22.dwgCITY OF
RENTON
Planning/Building/Public Works Dept.
SCALE:
COR PROJECT NO:
NO.REVISION BY DATE
APPR OF:
BHC Consultants, LLC
1601 Fifth Avenue, Suite 500
Seattle, Washington 98101
206.505.3400
206.505.3406 (fax)
www.bhcconsultants.com
45243STATE O F WASHIN
G
T
ONR
E
GI S T E R E DP
ROF
ESSIONAL E N G IN E ER REBL DAY
O
C
HI
LTREEECCAO V E WINDSOR HILLS
UTILITY IMPROVEMENTS PROJECT
MARCH 2024
1-800-424-5555 or 811
UNDERGROUND SERVICE
Call 48 Hours
Before You Dig
03/08/2024
ISSUED FOR BID MTM 03-2024 RLO STORMWATER DETAILS SD-22
69 85
B. Ochiltree, P.E.
A. Cariaso
R. Dorn, P.E.
B. Ochiltree, P.E.
AS SHOWN
27-04186
DEBRIS CAGE NOTES:
1. MAINTAIN 45 DEGREE ANGLE ON
VERTICAL BARS AND 7" OC MAX
SPACING OF BARS AROUND
LOWER STEEL BAND.
2. METAL PARTS MUST BE
CORROSION RESISTANT.
QUARRY SPALL DITCH
2
SD-20SCALE: 1" = 1'-0"
DETAIL
QUARRY SPALLS,
16-INCH DEPTH,
WSDOT 8-15.3(6)
1
2
1'-5"MIN WIDTH 5'-4"1
2.5 MAX
1
2
1
2.5 MAX
1
1
1
1
BIRD CAGE OVERFLOW STRUCTURE
1
SD-21NTS
DETAIL
PLAN
SECTION A-A
6" THICK GRAVEL BACKFILL
FOR PIPE ZONE BEDDING
DEBRIS CAGE, SEE DETAIL 3
4 - 1" DIA WEEP HOLES
48" DIA TYPE 2
CATCH BASIN BASE
3'-0"1'-6"TYPQUARRY SPALLS PER
WSDOT 8-15.3(6)
18" PP OUTLET PIPE
FLOW
FLOW
FLOW
AA
9'-0"
4 - 1" DIA WEEP HOLES
1' - 0" MINFREEBOARDPROVIDE MAINTENANCE ACCESS BY
WELDING 4 CROSSBARS TO 4 VERTICAL
BARS AS SHOWN. HING UPPER ENDS
WITH FLANGES/BOLTS AND PROVIDE
LOCKING MECHANISM (PADLOCK) ON
LOWER END. LOCATE STEPS DIRECTLY
BELOW.
3/4" DIAMETER SMOOTH
BARS, EQUALLY SPACED
(4" OC MAX)
4 HOOK CLAMPS EVENLY
PLACED, SEE BELOW
UPPER STEEL BAND
3/4" X 4" WIDE
48" DIAMETER TYPE 2
CATCH BASIN
3/4" DIAMETER SMOOTH ROUND
BARS WELDED EQUALLY SPACED.
BARS SHALL BE WELDED TO UPPER
AND LOWER BANDS (22 BARS
EVENLY SPACED).
LOWER STEEL BAND 3/4" X 4" WIDE
FORMED TO FIT IN GROOVE OF CB
RISER
STANDARD GALVANIZED
STEPS OR LADDER
18"
16° TYP
PLAN
AA
SECTION A-A
DEBRIS CAGE DETAIL
3
SD-20SCALE: 1" = 1'-0"
DETAIL
SMOOTH
VERTICAL BARS
HOOK CLAMP
ANCHORED TO
CATCH BASIN RISER
CATCH BASIN
RISER
4 5 °
HOOK CLAMP
4
-SCALE: 1" = 1'-0"
DETAIL
1+002+003+004+005+006+007+008+009+0010+0011+0012+0013+0014+0015+0016+0017+0018+0019+0020+0021+0022+0030+0031+0032+0033+0034+0035+0036+0037+0038+0039+0040+0041+0042+0043+0044+0045+0046+0047+0050+0051+0052+0053+0054+0055+0056+0057+0088+0179+8080+0081+0082+0083+0084+0085+0086+0087+0088+0075+7659+5060+0061+0063+0064+0065+0066+0067+0068+0069+0070+0071+0072+0073+0074+0075+00C39C40C46C47 800+00801+00802+00803+00804+00805+00806+00700+00701+00702+00702+9062+00DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024RESTORATION KEY PLANR-170BVL/DVBDVBBVLEMS
1+002+003+004+005+006+007+0030+0031+0059+5060+0061+00803+00804+00805+00800+00701+00702+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024BRONSON WAY NERESTORATION PLAN STA 1+00 TO 7+0071BVL/DVBDVBBVLEMSR-2
7+008+009+0010+0011+0012+0013+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024BRONSON WAY NERESTORATION PLAN STA 7+00 TO 13+0072BVL/DVBDVBBVLEMSR-3
13+0014+0015+0016+0017+0018+0019+0050+0051+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024BRONSON WAY NERESTORATION PLAN STA 13+00 TO 19+5073BVL/DVBDVBBVLEMSR-4
20+0021+0022+0045+00
46+00
47+00
1+00
2+00 3+00 4+00 5+00 6+00
7+00
8+00
9+00
10+0
0
11+0
0
12+00
13+0
0
14+00
15+00
16+00 17+00 18+0019+0020+0021+0022+00
30+0
0 31+00 32+00 33+0034+00
35+00
36+00
37+0038+0
0
39+0
0
40+
0
0
41+0
0
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+0
0
52+0053+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+0083+0084+00
85+0086+00
87+00
88+0075+
76
59+5
0
60+00
61+0
0
63+0
0
64+0
0
65+0
0
66+0
0
67+00
68+00
69+00
70+00
71+00
72+0
0
73+00
74+00
75+00
C39
C40
C46C47
800+00
801+00
802+0
0
803+
0
0
804+00
805+00
806+0
0700+00701+
00 702+00702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024BRONSON WAY NERESTORATION PLAN STA 19+50 TO 22+5074BVL/DVBDVBBVLEMSR-5
39+0040+0041+0042+0043+0044+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024GRANDEY WAY NERESTORATION PLAN STA 38+00 TO 44+5075BVL/DVBDVBBVLEMSR-6
32+0033+0034+0035+0036+0037+0038+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024GRANDEY WAY NERESTORATION PLAN STA 31+50 TO 38+5076BVL/DVBDVBBVLEMSR-7
61+0063+0064+0065+0066+0067+0062+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024WINDSOR WAY NERESTORATION PLAN STA 61+00 TO 67+0077BVL/DVBDVBBVLEMSR-8
67+0068+0069+0070+0071+0072+001+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024WINDSOR WAY NERESTORATION PLAN STA 67+00 TO 72+5078BVL/DVBDVBBVLEMSR-9
88+0184+0085+0086+0087+0088+0073+0074+0075+00C471+00
2+00 3+00 4+00 5+00 6+00
7+00
8+00
9+00
10+0
0
11+
0
0
12+0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+
00
21+
00
22+
0030+00 31+00 32+0033+0034+0035+00
36+00
37+0038+
0
0
39+
0
0
40+00
41+0
0
42+
0
0
43+0
0
44+00
45+00
46+00 47+00
50+0
0
51+0
0
52+00
53+00
54+00
55+0
0
56+0057+00
88+0
1
79+8
0
80+00
81+00
82+00
83+00
84+0085+0086+00
87+00
88+0075+7659+50
60+0
0
61+
00
63+00
64+0
0
65+
00
66+0
0
67+0068+00
69+00
70+00
71+0
0
72+00
73+00
74+00
75+00C39
C40
C46C47
800+00
801+00
802+
0
0
803+0
0
804+00
805+00
806+
0
0
700+
00 701+0
0 702+00702+90
62+
00
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024WINDSOR WAY NERESTORATION PLAN STA 72+50 TO 76+0079BVL/DVBDVBBVLEMSR-10
80+0081+0082+0083+0084+00 C46C47
1+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024WINDSOR PL NERESTORATION PLAN STA 80+50 TO 84+0080BVL/DVBDVBBVLEMSR-11
51+0052+0053+0054+0055+0056+0057+0079+8080+00C39C401+00
2+00 3+00 4+00 5+00
6+00
7+00
8+00
9+0
0
10+
0
0
11+00
12+
0
0
13+00
14+00
15+00
16+00
17+00 18+0019+0020+0
021+0
022+0
0
30+0
0 31+00
32+0033+00 34+00
35+00
36+00
37+00
38+0
0
39+00
40+0
0
41+
00
42+0
0
43+00
44+00
45+00
46+00 47+00
50+00
51+
00
52+00
53+00
54+00 55+00
56+0057+00
88+01 79+80
80+0
0
81+00
82+00
83+0084+00
85+0086+00
87+00
88+0075+7
6
59+5
0
60+00
61+0
0
63+00
64+
00
65+0
0
66+
0
0
67+00
68+00
69+00
70+0071+
0
0
72+0
0
73+0074+0075+00C39
C40
C46C47
800+00
801+00
802
+
0
0
803+
0
0
804+00
805+00
806+00700+0
0 701+00702+0
0
702+90
62+0
0
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024BRONSON PL NERESTORATION PLAN STA 51+00 TO 57+0081BVL/DVBDVBBVLEMSR-12
DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master Restoration4.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS03-08-2024DRIVEWAY DETAILS82BVL/DVBDVBBVLEMSR-13
03-08-2024DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master TCP.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMS’WINDSOR WAY NETRAFFIC CONTROL PLAN83TC-1BVL/DVBDVBBVLEMS
03-08-2024DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master TCP.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMSWINDSOR PL NE & BRONSON PL NETRAFFIC CONTROL PLAN84’TC-2BVL/DVBDVBBVLEMS
03-08-2024DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master TCP.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMSBRONSON WAY NETRAFFIC CONTROL PLAN85’TC-3BVL/DVBDVBBVLEMS
03-08-2024DATE:DRAWING NO:SHEET:DESIGNED:DRAWN:CHECKED:APPROVED:SURVEYED:FILENAME: T:\Active Projects\Windsor Hills Utility (Renton) 2022-070\Design\Deliverables\2024-03-01 100%, IFB Submittal - Working\CAD\Windsor Hills Master TCP.dwg
CITY OFRENTONPlanning/Building/Public Works Dept.SCALE:COR PROJECT NO:NO.REVISIONBYDATEAPPROF:WINDSOR HILLSUTILITY IMPROVEMENTS PROJECTMARCH 20241-800-424-5555 or 811UNDERGROUND SERVICECall 48 HoursBefore You DigTransportation Planning | Design | Traffic Impact & Operations11400 SE 8th Street, Suite 200, Bellevue, WA 98004 | Office (425) 889-6747Transportation Engineering NorthWestProject Contact: Brenda Velazquez LopezPhone: 206-773-5386TENWPROJECT #: 2022-070861:20ISSUED FOR BID03-2024EMSEMSGRANDEY WAY NETRAFFIC CONTROL PLAN86’TC-4BVL/DVBDVBBVLEMS