HomeMy WebLinkAboutAPPROVED_2024-04-29 SSK-25 - Light Pole Spread Footing SEATTLE | KIRKLAND | MOUNT VERNON | WHIDBEY ISLAND | FEDERAL WAY | SPOKANE STRUCTURAL CALCULATIONS FOR SOLERA APARTMENTS LIGHT POLE FOUNDATIONS RENTON, WA April 29, 2024 ITEM PAGE Foundation and Anchorage Design ................................................................. Page 1 to 14 04/29/202
4
DEVELOPMENT ENGINEERING
Michael Sippo 05/03/2024
No Exceptions Taken
3" CLRCONC SIDE WALK
WHERE OCCURS
2" CLR(10) #6 EA WAY
TOP/BTM
5'-6" SQ3'-0"26" EMBED MIN5 1 2" THREAD EXPOSURE
ABOVE SIDEWALK
LIGHT POLE
(4) 1 14" F1554 GALV ANCHOR BOLTS
W/ (2) 1 12" THICK BOLT CIRCLES
AS SHOWN IN COR STD. PLAN 117.1A
BALANCE PER 2/SSK25
AT INTERFERING PIPE LOCATIONS
NOTE: ALL OTHER REQUIREMENTS FOR THIS LIGHT
POLE SHALL CONFORM WITH CITY OF RENTON
STANDARD PLAN 117.1A. THE FOOTING DEPICTED IN
THE SKETCH MAY ONLY BE USED WITH APPROVAL
FROM THE CITY OF RENTON
5" CLRLIGHT POLE SPREAD FOOTING DETAIL
SCALE 3/4" = 1'-0"
1
SSK25
9706 4Th Ave NE
Suite 300
Seattle, WA 98115
P: 206.523.0024
F: 206.523.1012Formerly DCG/Watershed www.facetnw.comFormerly DCG/Watershed4/29/2024
1/14
Facet - Page 1 of 14
9" MIN 4" MIN3'-0" MAX6" MINPIPES TO CLEAR
SLEEVES BY 1"
ALL AROUND
TYP
2
1
2'-0" MIN9" MIN1'-6" MIN
CONDUIT
PIPE IN
SLEEVE
PLAN
SECTION ELEVATION
FORM VERTICAL
CHASES WITH
CURVED SHEET METAL
REINF
PER PLAN
NO PIPES ARE
TO BE WITHIN
4" OF REBAR
DROP FTG WHERE
PIPES ARE LESS
THAN 2'-6"
FROM BOTTOM
OF FTG
CONC FILL TO BE PLACED
BEFORE FTG IS POURED
MAKE SAME WIDTH AT FTG
AND FULL WIDTH OF PIPE TRENCH
NO EXCAVATION FOR
PIPE TRENCH PARALLEL
TO FTG BELOW THIS LINE
NOTE: CONDUITS TO BE PLACED SO
AS NOT TO CROSS OTHER CONDUITS
WHEN TURNED UP INTO STUD WALLS
PIPE
PIPE THRU FTG CONFLICT DETAIL
SCALE 1/2" = 1'-0"
1
SSK25
9706 4Th Ave NE
Suite 300
Seattle, WA 98115
P: 206.523.0024
F: 206.523.1012Formerly DCG/Watershed www.facetnw.comFormerly DCG/Watershed4/29/2024
2/14
Facet - Page 2 of 14
3" CLRCONC SIDE WALK
WHERE OCCURS
26" EMBED MIN5 12" THREAD EXPOSURE
ABOVE SIDEWALK
LIGHT POLE
(4) 1 14" F1554 GALV ANCHOR BOLTS
W/ (2) 1 1 2" THICK BOLT CIRCLES
AS SHOWN IN COR STD. PLAN 117.1A
NOTE: ALL OTHER REQUIREMENTS FOR THIS LIGHT
POLE SHALL CONFORM WITH CITY OF RENTON
STANDARD PLAN 117.1A. THE FOOTING DEPICTED IN
THE SKETCH MAY ONLY BE USED WITH APPROVAL
FROM THE CITY OF RENTON
5" CLR3'-0" ROUND
1 12" CLR
(8) #5V BARS EVENLY SPACED
W/ #4 HOOPS AT 12" O.C.2" CLR5'-0"TYPICAL LIGHT POST POLE FOOTING
SCALE 1/2" = 1'-0"
3
SSK25
9706 4Th Ave NE
Suite 300
Seattle, WA 98115
P: 206.523.0024
F: 206.523.1012Formerly DCG/Watershed www.facetnw.comFormerly DCG/Watershed4/29/2024
3/14
Facet - Page 3 of 14
General Footing
LIC# : KW-06012482, Build:20.23.08.01 FACET (c) ENERCALC INC 1983-2023
DESCRIPTION:Light Post Spread Footing
Project File: Solera Light Pole FDN.ec6
Code References
Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16
Load Combinations Used : IBC 2021
General Information
Material Properties Soil Design Values
2.50
Analysis Settings
250.0
ksi No
ksfAllowable Soil Bearing =
=
3.0
60.0
3,122.0
145.0
=0.30Flexure=0.90
Shear =
ValuesM
0.00180
Soil Passive Resistance (for Sliding)
1.0 =
Increases based on footing plan dimension
Add Pedestal Wt for Soil Pressure No:
Use Pedestal wt for stability, mom & shear No:
Allowable pressure increase per foot of depth
=ksfwhen max. length or width is greater than
=ft
:
=
Add Ftg Wt for Soil Pressure Yes
Yes:Use ftg wt for stability, moments & shears
when footing base is below ft
pcf Increase Bearing By Footing Weight
=pcf
Min. Overturning Safety Factor
=
: 1
Increases based on footing Depth0.750
=
Soil/Concrete Friction Coeff.
Ec : Concrete Elastic Modulus
=
=Footing base depth below soil surface ft
=Allow press. increase per foot of depth ksf
=
: 11.0Min. Sliding Safety Factor =
=
Concrete Density
=
Min Allow % Temp Reinf.
ksif'c : Concrete 28 day strength
fy : Rebar Yield ksi
Min Steel % Bending Reinf.
Soil Density =110.0 pcf
#
Dimensions
Width parallel to X-X Axis 5.50 ft
Length parallel to Z-Z Axis
=
5.50 ft
=Pedestal dimensions...px : parallel to X-X Axis inpz : parallel to Z-Z Axis inHeight==
in
Footing Thickness
=
36.0 in=
Rebar Centerline to Edge of Concrete...=inat Bottom of footing 3.0
Reinforcing
#
Bars parallel to X-X Axis
Reinforcing Bar Size
=
6Number of Bars =10.0
Bars parallel to Z-Z Axis
Reinforcing Bar Size =6Number of Bars =10.0
Bandwidth Distribution Check (ACI 15.4.4.2)
Direction Requiring Closer Separation
n/a
# Bars required within zone n/a
# Bars required on each side of zone n/a
Applied Loads
0.20
D Lr
ksf
L S
P : Column LoadOB : Overburden =k
W E
M-zz
V-x
=
=0.010 k0.5850 0.3610
V-z k0.780 0.3610
18.135
M-xx =
0.360 k-ft=
k-ft
12.996
24.180 12.996
H
=
4/14
Facet - Page 4 of 14
General Footing
LIC# : KW-06012482, Build:20.23.08.01 FACET (c) ENERCALC INC 1983-2023
DESCRIPTION:Light Post Spread Footing
Project File: Solera Light Pole FDN.ec6
PASS 6.736 Sliding - X-X 0.3570 k 2.405 k +0.60D+0.60W
PASS 5.138 Sliding - Z-Z 0.4680 k 2.405 k +0.60D+0.60W
DESIGN SUMMARY Design OK
Governing Load CombinationMin. Ratio Item Applied Capacity
PASS 0.5020 Soil Bearing 1.255 ksf 2.50 ksf +0.60D+0.60W about X-X axis
PASS 1.385 Overturning - X-X 15.912 k-ft 22.042 k-ft +0.60D+0.60W
PASS 1.811 Overturning - Z-Z 12.168 k-ft 22.042 k-ft +0.60D+0.60W
PASS n/a Uplift 0.0 k 0.0 k No Uplift
PASS 0.01902 Z Flexure (+X)2.206 k-ft/ft 115.976 k-ft/ft +0.90D+W
PASS 0.01497 Z Flexure (-X)1.736 k-ft/ft 115.976 k-ft/ft +1.20D+W
PASS 0.02880 X Flexure (+Z)3.341 k-ft/ft 115.976 k-ft/ft +0.90D+W
PASS 0.01690 X Flexure (-Z)1.960 k-ft/ft 115.976 k-ft/ft +1.20D+W
PASS n/a 1-way Shear (+X)0.0 psi 82.158 psi n/a
PASS 0.0 1-way Shear (-X)0.0 psi 0.0 psi n/a
PASS n/a 1-way Shear (+Z)0.0 psi 82.158 psi n/a
PASS n/a 1-way Shear (-Z)0.0 psi 82.158 psi n/a
PASS n/a 2-way Punching 0.6865 psi 82.158 psi +0.90D+W
Top reinforcing mat required (see 'Bending' tab).
Hand check required for anchor pullout.
Detailed Results
Rotation Axis &ZeccXecc Actual Soil Bearing Stress @ Location Actual / Allow
Soil Bearing
(in)Gross Allowable Bottom, -Z Top, +Z Left, -X Right, +X RatioLoad Combination...
X-X, D Only 2.50 n/a0.4416 0.4416 n/a 0.1770.0n/a
X-X, +D+0.60W 2.50 n/a0.0 1.033 n/a 0.41314.294n/a
X-X, +D+0.70E 2.50 n/a0.08975 0.7935 n/a 0.3178.853n/a
X-X, +D+0.450W 2.50 n/a0.01554 0.8677 n/a 0.34710.720n/a
X-X, +D+0.5250E 2.50 n/a0.1777 0.7055 n/a 0.2826.640n/a
X-X, +0.60D+0.60W 2.50 n/a0.0 1.255 n/a 0.50223.823n/a
X-X, +0.60D+0.70E 2.50 n/a0.0 0.6351 n/a 0.25414.755n/a
Z-Z, D Only 2.50 0.4277n/a n/a 0.4555 0.182n/a0.3503
Z-Z, +D+0.60W 2.50 0.001596n/a n/a 0.8816 0.353n/a11.071
Z-Z, +D+0.70E 2.50 0.07583n/a n/a 0.8074 0.323n/a9.203
Z-Z, +D+0.450W 2.50 0.1081n/a n/a 0.7751 0.310n/a8.390
Z-Z, +D+0.5250E 2.50 0.1638n/a n/a 0.7194 0.288n/a6.990
Z-Z, +0.60D+0.60W 2.50 0.0n/a n/a 0.7828 0.313n/a18.217
Z-Z, +0.60D+0.70E 2.50 0.0n/a n/a 0.6475 0.259n/a15.105
Rotation Axis &
Overturning Stability
Load Combination...StatusOverturning Moment Resisting Moment Stability Ratio
X-X, D Only None 0.0 k-ft Infinity OK
X-X, +D+0.60W 15.912 k-ft 36.737 k-ft 2.309 OK
X-X, +D+0.70E 9.855 k-ft 36.737 k-ft 3.728 OK
X-X, +D+0.450W 11.934 k-ft 36.737 k-ft 3.078 OK
X-X, +D+0.5250E 7.391 k-ft 36.737 k-ft 4.970 OK
X-X, +0.60D+0.60W 15.912 k-ft 22.042 k-ft 1.385 OK
X-X, +0.60D+0.70E 9.855 k-ft 22.042 k-ft 2.237 OK
Z-Z, D Only 0.390 k-ft 36.737 k-ft 94.196 OK
Z-Z, +D+0.60W 12.324 k-ft 36.737 k-ft 2.981 OK
Z-Z, +D+0.70E 10.245 k-ft 36.737 k-ft 3.586 OK
Z-Z, +D+0.450W 9.341 k-ft 36.737 k-ft 3.933 OK
Z-Z, +D+0.5250E 7.781 k-ft 36.737 k-ft 4.721 OK
Z-Z, +0.60D+0.60W 12.168 k-ft 22.042 k-ft 1.811 OK
Z-Z, +0.60D+0.70E 10.089 k-ft 22.042 k-ft 2.185 OK
5/14
Facet - Page 5 of 14
General Footing
LIC# : KW-06012482, Build:20.23.08.01 FACET (c) ENERCALC INC 1983-2023
DESCRIPTION:Light Post Spread Footing
Project File: Solera Light Pole FDN.ec6
Force Application Axis
Sliding Stability All units k
Load Combination...StatusSliding Force Resisting Force Stability Ratio
X-X, D Only 0.010 k 4.008 k 400.763 OK
X-X, +D+0.60W 0.3610 k 4.008 k 11.101 OK
X-X, +D+0.70E 0.2627 k 4.008 k 15.256 OK
X-X, +D+0.450W 0.2733 k 4.008 k 14.667 OK
X-X, +D+0.5250E 0.1995 k 4.008 k 20.086 OK
X-X, +0.60D+0.60W 0.3570 k 2.405 k 6.736 OK
X-X, +0.60D+0.70E 0.2587 k 2.405 k 9.295 OK
Z-Z, D Only 0.0 k 4.008 k No Sliding OK
Z-Z, +D+0.60W 0.4680 k 4.008 k 8.563 OK
Z-Z, +D+0.70E 0.2527 k 4.008 k 15.859 OK
Z-Z, +D+0.450W 0.3510 k 4.008 k 11.418 OK
Z-Z, +D+0.5250E 0.1895 k 4.008 k 21.146 OK
Z-Z, +0.60D+0.60W 0.4680 k 2.405 k 5.138 OK
Z-Z, +0.60D+0.70E 0.2527 k 2.405 k 9.516 OK
Flexure Axis & Load Combination in^2 in^2 in^2 k-ft
As Req'd
Footing Flexure
Tension
k-ft
Actual As StatusMuSide
Surface
Gvrn. As Phi*Mn
X-X, +1.40D 0.0350 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.40D 0.0350 -Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D 0.030 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D 0.030 -Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+0.50W 1.235 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+0.50W 1.175 -Z Top 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+W 2.862 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+W 1.960 -Z Top 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+E 1.310 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +1.20D+E 1.250 -Z Top 0.7776 AsMin 0.80 115.976 OK
X-X, +0.90D+W 3.341 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +0.90D+W 1.480 -Z Top 0.7776 AsMin 0.80 115.976 OK
X-X, +0.90D+E 1.334 +Z Bottom 0.7776 AsMin 0.80 115.976 OK
X-X, +0.90D+E 1.226 -Z Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.40D 0.01463 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.40D 0.08463 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D 0.01254 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D 0.07254 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+0.50W 0.9165 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+0.50W 0.9765 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+W 1.736 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+W 1.965 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+E 1.292 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +1.20D+E 1.352 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +0.90D+W 1.474 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +0.90D+W 2.206 +X Bottom 0.7776 AsMin 0.80 115.976 OK
Z-Z, +0.90D+E 1.249 -X Top 0.7776 AsMin 0.80 115.976 OK
Z-Z, +0.90D+E 1.374 +X Bottom 0.7776 AsMin 0.80 115.976 OK
One Way Shear
Vu @ +XLoad Combination...Vu @ -X Vu @ -Z Vu @ +Z Vu:Max Vu / Phi*VnPhi Vn Status
+1.40D 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+1.20D 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+1.20D+0.50W 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+1.20D+W 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+1.20D+E 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+0.90D+W 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
+0.90D+E 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
Vu / Phi*Vn
Two-Way "Punching" Shear All units k
StatusVuPhi*VnLoad Combination...
+1.40D 0.05 164.32 0.000293 OKpsipsi+1.20D 0.04 164.32 0.000251 OKpsipsi
+1.20D+0.50W 0.04 164.32 0.000251 OKpsipsi
6/14
Facet - Page 6 of 14
General Footing
LIC# : KW-06012482, Build:20.23.08.01 FACET (c) ENERCALC INC 1983-2023
DESCRIPTION:Light Post Spread Footing
Project File: Solera Light Pole FDN.ec6
Vu / Phi*Vn
Two-Way "Punching" Shear All units k
StatusVuPhi*VnLoad Combination...
+1.20D+W 0.34 164.32 0.002061 OKpsipsi
+1.20D+E 0.04 164.32 0.000251 OKpsipsi
+0.90D+W 0.69 164.32 0.004178 OKpsipsi
+0.90D+E 0.05 164.32 0.000329 OKpsipsi
7/14
Facet - Page 7 of 14
Company:Date:4/24/2023
Engineer:Page:1/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
1.Project information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
Project description:
Location:
Fastening description:
2. Input Data &Anchor Parameters
General
Design method:ACI 318-14
Units: Imperial units
Anchor Information:
Anchor type: Cast-in-place
Material: F1554 Grade 36
Diameter (inch): 1.250
Effective Embedment depth,hef (inch): 8.000
Anchor category:-
Anchor ductility: Yes
hmin (inch): 10.00
Cmin (inch): 1.65
Smin (inch): 5.00
Base Material
Concrete: Normal-weight
Concrete thickness,h (inch): 36.00
State: Uncracked
Compressive strength, f’c (psi): 2500
Ψc,V:1.4
Reinforcement condition:B tension,B shear
Supplemental edge reinforcement: No
Reinforcement provided at corners: No
Ignore concrete breakout in tension: No
Ignore concrete breakout in shear: No
Ignore 6do requirement: Yes
Build-up grout pad: No
Base Plate
Length x Width x Thickness (inch): 14.50 x 14.50 x 0.25
Recommended AnchorAnchor Name: Heavy Hex Bolt - 1 1/4"Ø Heavy Hex Bolt, F1554 Gr. 36
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
8/14
Facet - Page 8 of 14
Company:Date:4/24/2023
Engineer:Page:1/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
1.Project information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
Project description:
Location:
Fastening description:
2. Input Data &Anchor Parameters
General
Design method:ACI 318-14
Units: Imperial units
Anchor Information:
Anchor type: Cast-in-place
Material: F1554 Grade 36
Diameter (inch): 1.250
Effective Embedment depth,hef (inch): 8.000
Anchor category:-
Anchor ductility: Yes
hmin (inch): 10.00
Cmin (inch): 1.65
Smin (inch): 5.00
Base Material
Concrete: Normal-weight
Concrete thickness,h (inch): 36.00
State: Uncracked
Compressive strength, f’c (psi): 2500
Ψc,V:1.4
Reinforcement condition:B tension,B shear
Supplemental edge reinforcement: No
Reinforcement provided at corners: No
Ignore concrete breakout in tension: No
Ignore concrete breakout in shear: No
Ignore 6do requirement: Yes
Build-up grout pad: No
Base Plate
Length x Width x Thickness (inch): 14.50 x 14.50 x 0.25
Recommended AnchorAnchor Name: Heavy Hex Bolt - 1 1/4"Ø Heavy Hex Bolt, F1554 Gr. 36
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
9/14
Facet - Page 9 of 14
Company:Date:4/24/2023
Engineer:Page:2/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
Load and GeometryLoad factor source: ACI 318 Section 5.3
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: Not applicable
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: Yes
Strength level loads:
Nua [lb]:0
Vuax [lb]:0
Vuay [lb]:-780
Mux [ft-lb]: 24180
Muy [ft-lb]:0
Muz [ft-lb]:0
<Figure 1>
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
10/14
Facet - Page 10 of 14
Company:Date:4/24/2023
Engineer:Page:3/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
<Figure 2>
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
11/14
Facet - Page 11 of 14
Company:Date:4/24/2023
Engineer:Page:4/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
3. Resulting Anchor Forces
Anchor Tension load,
Nua (lb)
Shear load x,
Vuax (lb)
Shear load y,
Vuay (lb)
Shear load combined,
√(Vuax)²+(Vuay)² (lb)
1 0.0 0.0 -195.0 195.0
2 13239.7 0.0 -195.0 195.0
3 13239.7 0.0 -195.0 195.0
4 0.0 0.0 -195.0 195.0
Sum 26479.4 0.0 -780.0 780.0
Maximum concrete compression strain (‰): 0.18
Maximum concrete compression stress (psi): 789
Resultant tension force (lb): 26479
Resultant compression force (lb): 26480
Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00
Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00
Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00
Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00
<Figure 3>
4. Steel Strength of Anchor in Tension (Sec. 17.4.1)
Nsa (lb)Nsa (lb)
56200 0.75 42150
5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2)
Nb = kc a f’chef1.5 (Eq. 17.4.2.2a)
kc a f’c (psi)hef (in)Nb (lb)
24.0 1.00 2500 6.667 20656
Ncbg =(ANc / ANco)ec,N ed,N c,N cp,NNb (Sec. 17.3.1 &Eq. 17.4.2.1b)
ANc (in2)ANco (in2)ca,min (in)ec,N ed,N c,N cp,N Nb (lb)Ncbg (lb)
610.00 400.00 10.00 1.000 1.000 1.25 1.000 20656 0.70 27563
6. Pullout Strength of Anchor in Tension (Sec. 17.4.3)
Npn =c,PNp =c,P8Abrgf’c (Sec. 17.3.1, Eq. 17.4.3.1 &17.4.3.4)
c,P Abrg (in2)f’c (psi)Npn (lb)
1.4 2.24 2500 0.70 43845
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
12/14
Facet - Page 12 of 14
Company:Date:4/24/2023
Engineer:Page:5/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
8. Steel Strength of Anchor in Shear (Sec. 17.5.1)
Vsa (lb)grout grout Vsa (lb)
33720 1.0 0.65 21918
9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.5.2)
Shear perpendicular to edge in y-direction:
Vby =min|7(le / da)0.2 da a f’cca11.5; 9 a f’cca11.5|(Eq. 17.5.2.2a &Eq. 17.5.2.2b)
le (in)da (in)a f’c (psi)ca1 (in)Vby (lb)
8.00 1.250 1.00 2500 20.50 41768
Vcbgy =(AVc / AVco)ec,V ed,V c,V h,VVby (Sec. 17.3.1 &Eq. 17.5.2.1b)
AVc (in2)AVco (in2)ec,V ed,V c,V h,V Vby (lb)Vcbgy (lb)
937.88 1891.13 1.000 0.798 1.400 1.000 41768 0.70 16190
Shear parallel to edge in x-direction:
Vby =min|7(le / da)0.2 da a f’cca11.5; 9 a f’cca11.5|(Eq. 17.5.2.2a &Eq. 17.5.2.2b)
le (in)da (in)a f’c (psi)ca1 (in)Vby (lb)
8.00 1.250 1.00 2500 10.00 14230
Vcbgx =(2)(AVc / AVco)ec,V ed,V c,V h,VVby (Sec. 17.3.1, 17.5.2.1(c)&Eq. 17.5.2.1b)
AVc (in2)AVco (in2)ec,V ed,V c,V h,V Vby (lb)Vcbgx (lb)
457.50 450.00 1.000 1.000 1.400 1.000 14230 0.70 28356
10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3)
Vcpg =kcpNcbg =kcp(ANc / ANco)ec,N ed,N c,N cp,NNb(Sec. 17.3.1 &Eq. 17.5.3.1b)
kcp ANc (in2)ANco (in2)ec,N ed,N c,N cp,N Nb (lb)Vcpg (lb)
2.0 930.25 400.00 1.000 1.000 1.250 1.000 20656 0.70 84066
11. Results
Interaction of Tensile and Shear Forces (Sec. 17.6)
Tension Factored Load,Nua (lb)Design Strength, øNn (lb)Ratio Status
Steel 13240 42150 0.31 Pass
Concrete breakout 26479 27563 0.96 Pass (Governs)
Pullout 13240 43845 0.30 Pass
Shear Factored Load,Vua (lb)Design Strength, øVn (lb)Ratio Status
Steel 195 21918 0.01 Pass
T Concrete breakout y- 780 16190 0.05 Pass (Governs)
|| Concrete breakout x- 390 28356 0.01 Pass (Governs)
Pryout 780 84066 0.01 Pass
Interaction check Nua/Nn Vua/Vn Combined Ratio Permissible Status
Sec. 17.6.1 0.96 0.00 96.1% 1.0 Pass
1 1/4"Ø Heavy Hex Bolt, F1554 Gr. 36 with hef = 8.000 inch meets the selected design criteria.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
13/14
Facet - Page 13 of 14
Company:Date:4/24/2023
Engineer:Page:6/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.2.2309.2
12. Warnings
-Minimum spacing and edge distance requirement of 6da per ACI 318 Sections 17.7.1 and 17.7.2 for torqued cast-in-place anchor is waived per
designer option.
-Designer must exercise own judgement to determine if this design is suitable.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
14/14
Facet - Page 14 of 14