HomeMy WebLinkAboutSWP272332 CONCEPTUAL DRAINAGE REPORT
FOR
PARCEL A - WASHINGTON TECHNICAL CENTER
LOCATED AT
SOUTHWEST 7TH STREET NEAR POWELL AVENUE
RENTON, WASHINGTON
FOR
SGA CORPORATION
BY
JOHN E. ANDERSON, P.E. RLCFI�/F�
APR z 6 1997
BUSH, ROED & HITCHINGS, INC. CEVELC�,,y,t.r t
2009 MINOR AVENUE EAST c►T REN
yCF ..,,w"ING
TCN
SEATTLE, WA 98102
(206) 323-4144
BRH JOB NO. 97102.00
DATEt;'
APRIL 24, 1997
6878
STER�9
s`SI�NA1.
EXPIRES 12/1 -47
••uc.0 art 4mnrs � I
:o.�: •oenw.asoU '
BbIOK OtG Y!M
soar uu Nmm 4 Insn =1 - 59' I rnt m,s: 4..onan
R-369.1 4'
s,nmaat
29' 52- _
o.r.c s0we s 0a¢L,onl L=1 15.44'± ——————p
N 8- 4
/ `�' 23 0ax w oo0as I I I
/ I I
/ .0, 3:
/ ,y► " a rx I I i�
ti o
PROPOSED BlnIDiNG I
F.F.- 22.0 I o
/, t •ores K ae
r r IfN.i I M
/ n rniae e R a.to.s
/ Q /---�0--1 p • re v rr •nvo I s
to
00' w 505.27' —``————————
S.W. 7th ST-
T W N H 0 M E
t.
�' _`�' - 1:✓ E 70 �%'I � � 6 H / �� S _C ,-2� 22 � S -6 r
60 UNITS
-
�� /J
K q� b/IgS 7o36
o Cw�U,rf z� ss 2 ^ A
I
C 4 11-314 /� �114 3 e �)b,40-y N NITS I
C. NO
5 Ac.
r.[.B6 +yeas -A`CONS
� $
jp' RA/[RO•�O k 776 35-2_ c irr. _ EAS!•M�NT __ ���
— — - K.�a — • _ zis ei 13 12
_ r
.+/ I 4 1(�Ac its ��►
G OV�t LO �2
30-10
5 _
C A LI "j ;C E E 3R
Q
a t
6E0 A/ HORMEL 8 0. d
352lw�lwr> _ J - -��anvwv� _ ow G� b P A R K
CENTRAL
. 3 2 / �. S G A SITE h 7-18 Ac- PU6ET INC.
_fff7.ei
i as r 37-77 /.. 5AIA6 '�� 1�4Iw:
dv h1.254 �' i us T1251
- — --5 7- -
r 4, 94
333E LAS OF SIE TTLE TLAS OF SEATTLE
RIGHTED& PUBLISHED BY 336W
]len,, COPYRIGHTED & PUBLISHED BY
KROLL MA OMPANY, INC., SEATT KROLL MAP COMPANY, INC., SEATTLE
SCALE: ET SCALE t INCH 200 FEET
I„=zco�
c
TABLE OF CONTENTS
I. Project Overview
II. Preliminary Conditions Summary
III. Core and Special Requirements
IV. Detention Analysis
V. Water Quality Design
VI. Level I Analysis
C
1
I. PROJECT OVERVIEW
SGA is proposing to build a 34,585 square foot office/warehouse building on Parcel A of Washington
Technical Center. The total site is 2.88 acres in size. Railroad tracks are located on the northern and
eastern boundaries. The tracks are located within easements recorded with the plat. Southwest 7th
Street is the southern boundary of the site. Grades on the site vary from elevation 20 in the
northeastern corner to elevation 16 in the southwestern corner. The ground slopes within the
property are between 1 and 2 percent. Ground cover consists of blackberry bushes and grasses.
The proposed building would be dock high. Truck loading docks would be located on the north side
of the building. The building finish floor elevation would be approximately 2.5 feet above the
existing ground elevation. There will be approximately 1.3 acres of asphalt paving around the
building for vehicle parking lot and truck maneuvering areas. Storm water runoff from the asphalt
pavement will be conveyed to a combine wetpond/detention pond located at the southwest corner
of the site. The wetpond is over-sized so biofiltration swales are not required. Preliminary design
has included provisions for biofiltration swale, but landscape requirements may make grading of
swales impractical.
Construction of an office/warehouse building on this site is consistent with surrounding
developments. Utilities within Southwest 7th Street have been sized for this type of development.
There is adequate depth for gravity storm water and sanitary sewer connections. According to City
records, a 10 inch water main is stubbed to the southeast corner and a 12 inch water main is located
within Southwest 7th Street. Therefore, the development of this property does not present any
significant design problems.
c
H. PRELIMINARY CONDITIONS SUMMARY
The 2.88 acre site is covered with blackberry bushes and grasses. Existing ground slopes from west
to east at slopes between 1 and 2 percent. A 60 inch storm drainage pipe is located in Southwest 7th
Street. According to the City, storm water runoff from the developed site can be discharge to the
60 inch pipe. Storm water detention is required prior to discharge from the site. The detention pond
will be sized using the King County Design Manual Method as adopted by city of Renton. No offsite
areas contribute to the storm water flows. An existing CN value of 82 will be used to calculate the
pre-developed storm water peak flows.
III. CORE AND SPECIAL REQUIREMENTS
CORE REQUIREMENT#1:
Storm water will be discharged to the existing 60 inch storm drainage pipe located in Southwest 7th
Street. The pipe design included this property in the tributary area. This is the City's recommended
storm drainage connection. Therefore Core Requirement #1 is met.
CORE REQUIREMENT#2
The railroad tracks and Southwest 7th Street grades prevent offsite storm water from entering the
site. Therefore, no upstream basin analysis is required for this property.
Storm water discharged from the site will be conveyed by 60 inch storm pipe in Southwest 7th Street.
The 60 inch pipe flows west to Naches Avenue. The storm water then flows north in Naches where
it is discharged into a regional storm water mitigation area. The existing conveyance system was
design to convey storm water discharged from site. Original sizing for the pipe used the Rational
Method of analysis. Current design standards use the hydrograph method that lowers peak rate
discharge from that calculated by the Rational Method. Therefore, the downstream system has
adequate capacity for the proposed development.
CORE REQUIREMENT#3
Peak rate control will be provided for the storm water runoff. A storm water detention system will
be located in the southwest corner of the site. Developed storm water peak rate discharges from
the site will be limited to the 2 year, 10 year and 100 year pre-developed values. Storm water
detention facility calculations are included in the report. ! V� , �,� ?'�6
The City allows over-sizing the wetpond igation of the biofiltration swale requirements. The
wetpond required size must be increased bZ30 ercent to eliminate the biofiltration swale. Wetpond
sizing for this project will use this pro ' n to mitigate the biofiltration requirements. Wetpond
sizing calculations are included in the report.
CORE REQUIREMENT#4
Detailed pipe sizing calculation will be provided for the final design. The pipes will be sized
according to City Standards.
CORE REQUIREMENT#5
A detailed erosion/sedimentation control plan will be prepared for the site grading. The plan will
meet all City Standards.
SPECIAL REQUIREMENTS SECTION 1.3
The only Special Requirement that applies to this project is 1.3.5. A wetpond is required because the
development will have 1.3 acres of imperious surface area subject to vehicular use. A wetpond will
be constructed in the storm water detention pond area.
IV. DETENTION ANALYSIS
KING COUNTY, WASHINGTON, SURFACE WATER DESIGN MANUAL
FIGURE 3.SIA HYDROLOGIC SOIL GROUP OF THE SOILS IN KING COUNTY
HYDROLOGIC HYDROLOGIC
SOIL GROUP GROUP' SOIL GROUP GROUP'
Alderwood C Orcas Peat D
Arents.Alderwood Material C Oridia D
Arents,.Everett Material B Ovall C
Beausite C PBchuck C
Bellingham D Puget D
Briscot D Puyallup B
Buckley D Ragnar B
Coastal Beaches Variable Renton D
Eadmont Sat Loam D Riverwash Variable
Edgewick C Salal C
Everett A Sammamish D
Indianola A Seattle D
1Qtsap C Shacar D
luaus C Si Sat C
Mixed Alluvial Land Variable - Snohomish D
Newton A Sultan C
Newberg B Tukwila D
Nooksack C Urban Vartabl
Normal Sandy Loam D Woodinville D
HYDROLOGIC SOIL GROUP CLASSIFICATIONS
A (Low runoff potentia). Sods having high infiltration rates, even when thoroughly wetted,and consisting
chiefly-of deep,well-to-excessively drained sands or gravels. These sods have a high rate of water
transmission.
B. (Moderately low runoff potential). Sods having moderate infiltration rates when thoroughly wetted,and
consisting chiefly of moderately fine to moderately coarse textures. These sods have a moderate rate of
water transmission.
C. (Moderately high runoff potential). Sods having slow infiltration rates when thoroughly wetted, and
consisting chiefly of sods with a layer that impedes downward movement of water,or sods with moderately
fine to fine textures. These sods have a slow rate of water transmission.
D. (High runoff potential). Sods having very slow infiltration rates when thoroughly wetted and consisting
chiefly of day sods with a high swelling potential, sods with a permanent high water table, sods with a
hardpan or day layer at or near the surface,and shallow soils over nearly Impervious material. These sods
have a very stow rate of water transmission.
• From SCS,TR-55, Second Edition,June 1986. Exhibit A-1. Revisions made from SCS, Sol Interpretation
Record. Form 05,September 1988.
3.5.2-2 I/90
'ICING COUNTY, WASHINGTON, SURFACE WATER DESIGN MANUAL
TABLE 3.52B SCS WESTERN WASHINGTON RUNOFF CURVE NUMBERS
SCS WESTERN WASHINGTON RUNOFF CURVE NUMBERS (Published by SCS in 1982)
Runoff curve numbers for selected agricultural, suburban and urban land use for Type 1A
rainfall distribution. 24-hour storm du ratiort.
CURVE NUMBERS BY
HYDROLOGIC SOIL GROUP
LAND USE DESCRIPTION A B C D
Cultivated is xl(1): winter condition 861, 91 94 95
Mountain open areas: low growing brush and grasslands 74 82 89 92
Meadow or pasture: 65 78 85 89
Wood or forest land: undisturbed 42 64 76 81
Wood or forest land: young second growth or brush 55 72 81 86
Orchard: with cover crop 81 88 92 94
Open spaces, lawns, parks, golf courses, cemeteries,
landscaping.
good condition: grass cover on 75%
or more of the area 68 80 86 90
fair condition: grass cover on 50% -
to 75% of the area 77 85 90 92
Gravel roads and parking lots 76 85 89 91
Dirt roads and parking lots 72 82 87 89 l
Impervious surfaces, pavement, roofs, etc. 98 98 98 98
Open water bodies: lakes, wetlands, ponds, etc. 100 100 100 100
Single Family Residential (2)
Dwelling Unit/Gross Acre % Impervious (3)
1.0 DU/GA 15 Separate curve number
1.5 DU/GA 20 shall be selected
2.0 DU/GA 25 for pervious and
2.5 DU/GA 30 Impervious portion
3.0 DU/GA 34 of the site or basin
3.5 DU/GA 38
4.0 DU/GA 42
4.5 DU/GA 46
5.0 DU/GA 48 _
5.5 DU/GA 50
6.0 DU/GA 52
6.5 DU/GA 54
7.0 DU/GA 56
Planned unit developments, % Impervious
condominiums, apartments, must be computed
commercial business and
Industrial areas.
(1) For a more detailed description of agricultural land use curve numbers refer to National Engineering
Handbook, Section 4, Hydrology, Chapter 9,August 1972.
(2) Assumes roof and driveway runoff Is directed into street/storm system.
(3) The remaining pervious areas (Iawn) are considered to be in good condition for these curve numbers.
3.5.2-3 V90
FAM
pill
MR
PRO
NOR
�' . �, „'.fir_■■� � -- , ►�- r -�
w
Come e .
A :
awl
I -- ;
min
WA �
�� , ��:�ir-� ,sue► �l/R1��\�� o t
mama
E '-r
yea= 1l��w� �1i���i'�� , `� 1.: .•�
rim,
� , ti. M►
• WAR►.R;
i/����� ��,��t � ter►
AWW
A PWAI
MCA
ow
�,�l� � sue►_ wR/.��, � ��
31
mb
orw
MRAlJNW
FA
, � . .
WM
Flop
son
ma
r
t 4/24/97 Bush, Roed & Hitchings, Inc . page 1
SGA CORP SITE IN RENTON
JOHN E . ANDERSON, P.E.
BASIN SUMMARY
BASIN ID: B1 NAME: 2 YEAR EXISTING
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE . . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 2 . 00 inches AREA. . : 2 . 88 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 18 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 .20 AREA. . : 0 . 00 Acres
CN. . . . . 98 . 00
PEAK RATE : 0 .29 cfs VOL: 0 . 16 Ac-ft TIME: 480 min
BASIN ID: B2 NAME: 10 YEAR EXISTING
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE. . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 2 . 90 inches AREA. . : 2 . 88 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 18 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 .20 AREA. . : 0 . 00 Acres
CN. . . . . 98 . 00
PEAK RATE : 0 . 72 cfs VOL: 0 .31 Ac-ft TIME : 480 min
BASIN ID: B3 NAME: 100 YEAR EXISTING
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE. . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 3 . 90 inches AREA. . : 2 . 88 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 .00
TIME OF CONC. . . . . : 18 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 .20 AREA. . : 0 .00 Acres
CN. . . . . 98 . 00
PEAK RATE: 1 .27 cfs VOL: 0 . 51 Ac-ft TIME: 480 min
Z 4/24/97 Bush, Roed & Hitchings, Inc . page 2
SGA CORP SITE IN RENTON
JOHN E . ANDERSON, P .E .
---------------------------------------------------------------------
---------------------------------------------------------------------
BASIN SUMMARY
BASIN ID: B4 NAME : 2 YEAR DEVELOPED
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE . . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 2 . 00 inches AREA. . : 0 . 60 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 12 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 .20 AREA. . : 2 . 28 Acres
CN. . . . . 98 . 00
PEAK RATE : 1 . 07 cfs VOL: 0 . 37 Ac-ft TIME : 480 min
BASIN ID: B5 NAME : 10 YEAR DEVELOPED
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE . . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 2 . 90 inches AREA. . : 0 . 60 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 12 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 . 20 AREA. . : 2 . 28 Acres
CN. . . . . 98 . 00
PEAK RATE : 1 . 66 cfs VOL : 0 . 57 Ac-ft TIME : 480 min
BASIN ID: B6 NAME: 100 YEAR DEVELOPED
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE . . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 3 . 90 inches AREA. . : 0 . 60 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 12 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 . 20 AREA. . : 2 . 28 Acres
CN. . . . . 98 . 00
PEAK RATE : 2 . 32 cfs VOL: 0 . 80 Ac-ft TIME: 480 min
4/24/97 Bush, Roed & Hitchings, Inc . page 4
SGA CORP SITE IN RENTON
JOHN E . ANDERSON, P.E .
---------------------------------------------------------------------
---------------------------------------------------------------------
HYDROGRAPH SUMMARY
PEAK TIME VOLUME
HYD RUNOFF OF OF Contrib
NUM RATE PEAK HYDRO Area
cfs min. cf-AcFt Acres
---------------------------------------------
---------------------------------------------
1 0 . 287 480 6782 cf 2 . 88 L �� ExisT
2 0 . 717 480 13598 cf 2 . 88 ko
3 1 . 272 480 22140 cf 2 . 88 too `(L ExksT
4 1 . 073 480 16098 cf 2 . 88 z Y;z bEv
5 1 . 659 480 24920 cf 2 . 88 (, -�2 mj
6 2 . 322 480 34948 cf 2 . 88 too YQ clev
7 0 .269 480 3955 cf 2 . 88
11 0 . 296 550 16098 cf 2 . 88 z Ye. Qaus�
12 0 . 722 520 24920 cf 2 . 88 o qR e-LiaPSt
13 0 . 998 520 34948 cf 2 . 88 \oo1{Cz ?-GLG-4%Sr-
t 4/24/97 Bush, Roed & Hitchings, Inc . page 5
SGA CORP SITE IN RENTON
JOHN E. ANDERSON, P.E.
STAGE STORAGE TABLE
CUSTOM STORAGE ID No. 1
Description: DETENTION POND
STAGE <----STORAGE----> STAGE <----STORAGE----> STAGE <----STO
(ft) ---cf--- --Ac-Ft- (ft) ---cf--- --Ac-Ft- (ft) ---cf---
12 .00 0 .0000 0 . 0000 13 . 10 3532 0 . 0811 14 . 20 750
12 . 10 321 . 10 0 . 0074 13 . 20 3853 0 . 0885 14 .30 804
12 .20 642 .20 0 . 0147 13 .30 4174 0 . 0958 14 .40 858
12 . 30 963 .30 0 . 0221 13 .40 4495 0 . 1032 14 .50 912
12 .40 1284 0 . 0295 13 . 50 4817 0 . 1106 14 . 60 966
12 .50 1606 0 . 0369 13 . 60 5138 0 . 1179 14 . 70 1020
12 . 60 1927 0 . 0442 13 . 70 5459 0 . 1253 14 . 80 1074
12 . 70 2248 0 .0516 13 . 80 5780 0 . 1327 14 .90 1128
12 .80 2569 0 . 0590 13 . 90 6101 0 .1401 15 .00 1182
12 .90 2890 0 . 0663 14 . 00 6422 0 .1474 15 . 10 1236
13 .00 3211 0 . 0737 14 . 10 6963 0 . 1598 15 .20 1290
P•2EA5 c�� C-orJTOURS �z , 14 �' 1�
t 4/24/97 Bush, Roed & Hitchings, Inc . page 6
SGA CORP SITE IN RENTON
JOHN E. ANDERSON, P.E.
-------------------------=-------------------------------------------
---------------------------------------------------------------------
DISCHARGE STRUCTURE LIST
MULTIPLE ORIFICE ID No. 1
Description: FROP-T
Outlet Elev: 12 .00
Elev: 12 . 00 ft Orifice Diameter: 3 .2500 in.
Elev: 13 .25 ft Orifice 2 Diameter: 4 . 7500 in.
4/24/97 Bush, Roed & Hitchings, Inc . page 7
SGA CORP SITE IN RENTON
JOHN E. ANDERSON, P.E.
LEVEL POOL TABLE SUMMARY
MATCH INFLOW ST DI <-PEAK-> STORAGE
<--------DESCRIPTION---------> (cfs) (cfs) id id <-STAGE> id VOL (cf)
2 YEAR . . . . . . . . . . . . . . . . . . . . . . . 0 .29 1 . 07 1 1 13 . 07 11 34
10 YEAR . . . . . . . . . . . . . . . . . . . . . . 0 . 72 1 . 66 1 1 13 . 60 12 51
100 YEAR . . . . . . . . . . . . . . . . . . . . . 1 .27 2 . 32 1 1 14 . 14 13 71
MvJS Env o
DC-TE�.1T�b►J
t L_� ► �L.E v 1 Z � F3 0-�dw. '�T�s r�1Tl 6�..
3 Wf'TPON P 3
E Lev 'So-vow'
TtrE bES'�.►JTi oN �o�o N�•5 Mcrn� Tt+A�ty TNr�T �EQu�¢�
s
V. WATER QUALITY DESIGN
s 4/24/97 Bush, Roed & Hitchings, Inc . page 3
SGA CORP SITE IN RENTON
JOHN E. ANDERSON, P.E.
---------------------------------------------------------------------
---------------------------------------------------------------------
BASIN SUMMARY
BASIN ID: B7 NAME : WATER QUALITY STORM
SBUH METHODOLOGY
TOTAL AREA. . . . . . . : 2 . 88 Acres BASEFLOWS : 0 . 00 cfs
RAINFALL TYPE. . . . : USER1 PERVIOUS AREA
PRECIPITATION. . . . : 0 .67 inches AREA. . : 0 . 60 Acres
TIME INTERVAL. . . . : 10 . 00 min CN. . . . : 82 . 00
TIME OF CONC. . . . . : 12 . 00 min IMPERVIOUS AREA
ABSTRACTION COEFF: 0 .20 AREA. . : 2 . 28 Acres
CN. . . . . 98 .00
PEAK RATE : 0 .27 cfs VOL: 0 . 09 Ac-ft TIME: 480 min
\�4 t✓TPCkJtp S 1-.F.C-
ELCV PRErk L N VOLUrAE CLFr>
8.00 1089.00 0.00 0.00 0.00
10.00 1548.00 2.00 2623.58 2623.58
12.00 2057.00 2.00 3592.96 6216.54 4—
EOM. (=>aPop
T�-E. �E Z�u t R-E.t� �ETPo►.�D
�✓OI.U►vtE = O ,bc,� AG_ F-� = 3, c� SS GF
ToA�,
MUS-r 1►�GR.�P�SE g`{ p., �S �1t`Tt'o►.tD �o L u M�
M t r`I t NA
Vot_ur-AE FR.a\/ t7_,) = (o� Zt � LF > IRcQvIR
o h•�[o* SG✓ C �� ��. �- r�-�-c r s eft�.+ �� y { o
��o r�-,►El U�l�w..- .cam - r.��e..�,p �j rL �y e� l-S tv /
Z,
T�- ui,-t-ol .fed
r�d,
J.3p.$ gsg-l (o.ol) x2,D
4t
Z l l 33 fill- 2 0 5 7 E+Z
V���P6 ftI 6 - S(Z
VI. LEVEL I ANALYSIS
Storm water will be discharged from the detention pond at the pre-developed peak flow rates to a
60 inch pipe located within Southwest 7th Street. From the connection point the storm water will
be tight lined approximately 1,100 feet west to Naches Avenue. Storm water is then tight lined north
approximately 650 feet in the Naches Avenue storm pipe. From the Naches storm system the storm
water is discharged into an open conveyance ditch that flows west into a regional detention basin.
The tight line system and detention basin were sized using the Rational Design Method . Current
City design standards for peak rate control are more restrictive than used to size the existing system.
Therefore development of this site will not adversely impact the existing storm system.
4 cry F.
REPORT City of Renton
& Department of Planning/Building/Public Works A- 7�
DECISION ENVIRONMENTAL REVIEW&
ADMINISTRATIVE LAND USE ACTION
DECISION DATE: May 27, 1997
Project Name: SW 7th Street Office/Warehouse
Applicant: David Kehle
Owner. L-O Renton II, Inc.
File Number. LUA-97-057,SA,ECF
Project Manager.' Mark R. Pywell, AICP
Project Description: The applicant seeks approval to construct a 34,585 s.f. office/warehouse
building for speculative uses.
Project Location: SW 7th Street, East of Powell Ave. SW
Exist. Bldg. Area SF: N/A Proposed New Bldg. Area SF 34,585 sf
Site Area: 125,628 sf Total Building Area SF: 34,585 sf
17
COf
IN
/ iZ A5 MIN0 T0N Ti[ CNN CALt
,..'. ' IM I` PRO.IFCT aW: IM _ •� r \.,
Im
OFFICE tND � OFFICE- /yam
. q F 1 F •nr t
...F..! .�.
CO
\11 EAR G.. .N
E C N N i I� oHs INDUSTRI9 c �•$^.
1
NS
i� � PARK N N.
HBORH D].1AF
1 �OPT�S4 E A- y1200
2
Project Location Map SITEERC.DOC
City of Renton PB/PW Department Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICE/WAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 2 of]3
PART ONE: PROJECT DESCRIPTION/BACKGROUND
The applicant seeks approval to construct a 34,585 square foot building that will house a
combination of warehouse and office space. The office space will support the warehouse use.
PART TWO: ENVIRONMENTAL REVIEW
In compliance with RCW 43.21C.240, the following project environmental review addresses only
those project impacts that are not adequately addressed under existing development standards
and environmental regulations.
A. Environmental Impacts
The Proposal was circulated and reviewed by various City Departments and Divisions to
determine whether the applicant has adequately identified and addressed environmental
impacts anticipated to occur in conjunction with the proposed development. Staff reviewers
have identified that the proposal is likely to have the following probable impacts:
(1) Earth
Impacts: The applicant will be grading the site in order to construct the proposed building.
Approximately 2,500 cubic yards of fill will need to be imported in order to raise the building
floor elevation to the required height. This amount of fill will require approximately 125
round-trip truck trips. As this is an industrial area this volume of traffic should not impact the
adjacent roads. The applicant will need to provide temporary erosion control measures to
ensure that dust and erosion do not become a problem during the construction phase of the
project. Plan Review staff note that the applicant will need to install and maintain the
temporary erosion control measures to the satisfaction of the Development Services
representatives.
After the construction phase of the project, the portions of the site that are not used for the
building and paved areas will be landscaped in accordance with the Code-requirements for
this area.
The Green River Valley area is an area that prior to development provided a significant
amount of wildlife habitat. In response to the loss of habitat area the City adopted an
ordinance that requires a minimum of 2% of a site be reserved for wildlife habitat area. This
area is in addition to other landscape requirements. Although the detention pond provides
the area that is required, the plans submitted are not detailed enough to demonstrate that
the plant materials will provide the habitat that is required. The applicant will need to
provide a plan that demonstrates that the habitat area is provided and the landscape
materials that will be used to create suitable habitat.
Mitigation Measures: The applicant shall install and maintain Temporary Erosion Control
Measures to the satisfaction of the representative of the Development Services Division for
the duration of the project.
The applicant will need to provide a wildlife life habitat plan that demonstrates that the area
reserved is equal to or greater than 2% of the site and identifies the plant materials that will
be used in this area to the satisfaction of the Development Services Division prior to the
issuance of building permits.
SITEERC.DOC
City of Renton Pl"WDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICEIWAREHOUSE L UA-97-07,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 3 of 13
Policy Nexus: Mining, Excavation, and Grading Ordinance, Environmental Ordinance
(SEPA)
(2) Air
Impacts: As noted in the Earth Section above, one source of potential air quality impacts
during the construction phase of the project will be from fugitive dust. The applicant will
need to provide temporary erosion control measures that will include sprinkling the site in
order to prevent fugitive dust. The applicant will also need to provide measure to prevent
erosion caused by storm water runoff during the construction phase of the project.
Adverse air quality impacts during the operation phase of the building would include vehicle
exhaust and exhaust from the building heating source. Existing state and federal standards
regulate these potential impacts. Properly operating equipment will keep these potential
impacts to levels below that allowed by the state and federal requirements.
Mitigation Measures: No further mitigation required.
Policy Nexus: N/A
(3) Water
Impacts: Storm water normally collects pollutants from paved surfaces that motorized
vehicles travel on. In this case that would include the parking areas and interior roadways.
The applicant has designed a storm water quality system that will treat the water on-site
prior to releasing into the off-site system.
Mitigation Measures: No further mitigation is required.
Policy Nexus: N/A
(4) Archeological
Impacts: There is a known archeological site on the property to the north of the subject
property. This site was reviewed as part of that project. The review concluded that only a
small portion of that property was an archeological site and that it did not reach the edge of
that property. The subject property is separated from the property to the north by a set of
railroad tracks. Further review of the reports filed on the known archeological site did not
reveal any indication that the site crossed over the railroad tracks and entered the subject
property. In accordance with State requirements, if the applicant finds any indications of
historic artifacts during the construction phase of the project, the project will need to be
stopped until further archeological investigation has concluded.
Mitigation Measures: No further mitigation is required.
Policy Nexus: N/A
SITEERC.DOC
City of Renton PIRPWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICF/WAREHOUSE L UA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 4 of 13
(5) Public Services
Impacts: The Fire Prevention Bureau note that the proposed project will have an adverse
impact on the City's ability to address fire prevention and emergency response unless the
Code-required improvements are installed. The City also applies a Fire Mitigation fee to
projects to address the need for improvements in the City's installation and equipment
needed to respond to the burden imposed by this project. A Fire Mitigation Fee of $0.52
per square foot of new construction ($0.52 X 34,585 sf= $17,984.20).
Mitigation Measures: The applicant shall submit a Fire Mitigation Fee of $0.52 per square
foot of new construction (estimated at$17,984.20) prior to the issuance of building permits.
Policy Nexus: Fire Mitigation Fee Resolution, Environmental Ordinance (SEPA)
(5) Transportation
Impacts: The proposed development of this vacant property will impact the City's existing
street system and transportation related improvements. In order to mitigate this impact the
City has established a Transportation Mitigation Fee of $75.00 per new trip generated. The
ITE Manual estimates that a project of this size will generate approximately 168.77 trips per
day. The mitigation fee is estimated to be $12,657.75.
A construction plan indicating haul route and hours, construction hours and a traffic control
plan shall be submitted for approval prior to any permit being issued. Haul hours shall be
restricted to 8:30 a.m. to 3:30 p.m. unless approved in advance by the Development
Services Division.
Construction hours shall be limited to between 7:00 a.m. and 7:00 p.m., Monday through
Friday, Saturdays as arranged but no hours in excess of the weekday hours, and no
Sunday construction.
Mitigation Measures: The applicant shall submit a Transportation Mitigation Fee of $75.00
per new trip generated (estimated at $12,657.75) prior to the issuance of building permits.
A construction plan indicating haul route and hours, construction hours and a traffic control
plan shall be submitted for approval prior to any permit being issued. Haul hours shall be
restricted to 8:30 a.m. to 3:30 p.m. unless approved in advance by the Development
Services Division.
Policy Nexus: Transportation Mitigation Fee Resolution, Environmental Review Ordinance
(SEPA)
SITEERC.DOC
City of Renton P/B/PWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICF/WAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 5 of 13
B. Recommendation
Based on analysis of probable impacts from the proposal, staff recommend that the
Responsible Officials make the following Environmental Determination:
DETERMINATION OF DETERMINATION OF
NON-SIGNIFICANCE NON- SIGNIFICANCE- MITIGATED.
Issue DNS with 14 day Appeal Period. X Issue DNS-M with 15 day Comment
and Appeal Period.
Issue DNS with 15 day Comment and Issue DNS-M with 15 day Comment
Appeal Period. Period followed by a 14 day Appeal
Period.
C. Mitigation Measures
1. The applicant shall install and maintain Temporary Erosion Control Measures to the
satisfaction of the representative of the Development Services Division for the duration of the
project.
2. The applicant will need to provide a wildlife life habitat plan that demonstrates that the area
reserved is equal to or greater than 2% of the site and identifies the plant materials that will be
used in this area to the satisfaction of the Development Services Division prior to the issuance of
building permits.
3. The applicant shall submit a Fire Mitigation Fee of $0.52 per square foot of new
construction (estimated at $17,984.20) prior to the issuance of building permits.
4. The applicant shall submit a Transportation Mitigation Fee of $75.00 per new trip generated
(estimated at $12,657.75) prior to the issuance of building permits.
5. A construction plan indicating haul route and hours, construction hours and a traffic control
plan shall be submitted for approval prior to any permit being issued. Haul hours shall be restricted
to 8:30 a.m. to 3:30 p.m. unless approved in advance by the Development Services Division.
SITEERCLOC
City of Renton PB/PWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICEIWAREHO USE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 6 of 13
Advisory Notes to Applicant:
The following notes are supplemental information provided in conjunction with the environmental
determination. Because these notes are provided as information only, they are not subject to the
appeal process for environmental determinations.
1. Garbage and recyclable deposit areas and collection points shall be easily and safely accessible to
hauling trucks.
Plan Review
WATER
1. The System Development Charge shall be at the current rate of$0.113 per square foot of the
gross site area. The fee has been partially paid previously leaving a balance of $4929.96 payable with the
issue of the construction permit.
2. A looped 10-inch water main is required around the building to meet fire flow requirements. The
stub crossing may be utilized towards this condition with all additional pipe and crossing at 10-inch
diameters.
SANITARY SEWER
1. The System Development Charge shall be at the current rate of $0.078 per square foot of the
gross site area. The fee was partially paid previously leaving a balance of$9,789.98 payable with the
issue of the construction permit.
SURFACE WATER
1. The System Development Charge shall be at the current rate of$0.129 per square foot of the
gross site area for a fee of$16,206.01 payable with the issue of the construction permit.
TRANSPORTATION
1. A Traffic Mitigation Fee of$75.00 per additional Average Daily Trip shall be assessed. In
accordance with the ITE manual, this use generates 168.77 trips per day for a fee of$12,657.75, payable
with the issue of the building permit.
PLAN REVIEW - GENERAL
1. All plans shall conform to the Renton Drafting Standards.
2. A construction permit is required. When plans are complete three copies of the drawings, two
copies of the drainage report, a construction estimate, application and appropriate fee shall be submitted
to the fourth floor counter. It is recommended to call 235-2631 to verify the fees as generated by the
permit system prior to issuing a check.
Fire Prevention Bureau
1. The preliminary fire flow required is 2,750 gpm. Three fire hydrants are required. One fire hydrant is
required within 150-feet of the proposed structure and two fire hydrants are required within 300-feet of the
structure. A looped water main is required to be installed around the building.
2. An approved sprinkler system is required to be installed throughout the structure.
3. An approved fire alarm system is required to be installed through-out the structure.
SITEERC.DOC
City of Renton PB/P W Department Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICF/WAREHOUSE LUA-97-057 SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 7 of 13
Additional Notes
Community Services Department
1. All landscaped areas outside of the property lines are to be maintained by the property
owner/applicant.
2. Recommend against using the species "platanus" along the road. The root system of this plant can
heave paved areas and the wood is brittle causing tree branches to break and fall.
Police Department
1. It is estimated that the proposed building will generate 17.88 calls for service annually.
2. This area of Renton has been reporting an increase in the number of commercial burglaries, auto thefts
and recoveries, and car prowling incidents. The applicant will need to install heavy duty locks, solid core
doors with peep-holes, and exterior lighting. An intrusion alarm system is recommended.
PART THREE: ADMINISTRATIVE LAND USE ACTION - REPORT & DECISION
This decision on the administrative land use action is made concurrently with the environmental
determination.
A. Type of Land Use Action
XX Site Plan Review Shoreline Substantial Development Permit
Conditional Use Binding Site Plan
Special Permit for Grade & Fill Administrative Code Determination
B. Exhibits
The following exhibits were entered into the record:
Exhibit No. 1: Yellow file containing: application, proof of posting and publication, environmental
review and other documentation pertinent to this request.
Exhibit No. 2: Drawing No. P-1, Site Plan (Received April 25, 1997).
Exhibit No. 3: Drawing No. PS-2, Building Floor Plan (Received April 25, 1997).
Exhibit No. 4: Drawing No. PS-3, Building Elevation (Received April 25, 1997).
Exhibit No. 5: Drawing No. L-1, Landscape Plan (Received April 25, 1997).
Exhibit No. 6: Drawing No. 1 of 1, Grading & Utility Plan
SITEERC.DOC
City of Renton P/BTWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICF.IWAREHOUSE L UA-97-057 SA ECF
REPORT AND DECISION OFMay 27,1997 Page 8 of 13
C. Consistency with Site Plan Criteria
In reviewing the proposal with respect to the site Plan Approval Criteria set forth in Section 4-31-
33(D) of the Site Plan Ordinance, the following issues have been identified by City Departmental
Reviewers and Divisional Reviewers:
1. GENERAL CRITERIA:
a. Conformance with the comprehensive plan, its elements and policies;
The proposed project is consistent with the Comprehensive Plan, its elements and policies. The
subject property is designated as Valley Planning Area. This designation allows for a variety of
office and industrial land uses. The proposed project will allow for a warehouse/manufacturing
operation with the supporting office space.
b. Conformance with existing land use regulations;
The subject property is zoned IM (Medium Industrial). This zoning designation supports the
Comprehensive Plan designation discussed above and allows for a variety of manufacturing and
warehouse uses. The proposed office space would be allowed as accessory to the
warehouse/manufacturing operation.
C. Mitigation of impacts to surrounding properties and uses;
The applicant has proposed to provide a landscape buffer around the perimeter of the project site
and adjacent to the building. This will soften the appearance of the industrial building. In addition
the elevations of the building demonstrates several techniques to soften the linear appearance of
the building. These include the treatment and location of the windows, the painted reveals, and the
painting scheme for the building.
d. Mitigation of impacts of the proposed site plan to the site;
The project site is fairly level and without any sensitive areas, such as wetlands, that need to be
addressed through the site plan. The location of the proposed building takes into account the size
and shape of the lot and the location of the adjacent streets and railroad tracks.
The applicant is proposing to provide a storm water system that addresses the need to improve the
quality of the storm water collected within the parking lot. The applicant needs to provide an area
for wildlife habitat that is equal to 2% of the site area. On this site that would equal 2,512 square
feet of area. The site plan notes that this is a requirement but does not demonstrate the location of
the area nor does it call out the plant materials that will be used in the area. City staff has
recommended a mitigation measure to address this issue.
e. Conservation of area-wide property values;
The development of this property will help to conserve the area-wide property values. The
development of the vacant parcel will raise the value of the property to a level equal to similarly
developed properties in the area.
sITEERCLOC
City of Renton PB/PWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICE/WAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 17,1997 Page 9 of 13
f. Safety and efficiency of vehicle and pedestrian circulation;
The applicant has developed a safe and efficient vehicle circulation system on the subject property
that connects into the adjacent roadway in two locations. These driveway were designed to comply
with City standards. The one area of concern for City staff is the movement of pedestrians from
the building to the sidewalk along the adjacent street. It is assumed that future employees could
use the bus or other commuter options that would require them to walk onto the subject property.
Pedestrian will need to walk through the parking area and interior roadways to access the City's
sidewalk via a driveway. City staff would recommend that the applicant provide either a painted
crosswalk or a different paving material in the area where pedestrians will need to walk through the
parking area. This could connect with a walkway that would extend through the landscape area
along the front property line and connect with the sidewalk along the street.
g. Provision of adequate light and air;
The building is well set back from the property lines and existing buildings on adjacent lots. This
should allow adequate room for natural sunlight to reach the windows of the building and allow for
the circulation of air around the building.
h. Mitigation of noise, odors and other harmful or unhealthy conditions;
The proposed project is being constructed as a speculative building. Once a tenant has been
selected improvements will need to be established based upon that use. Any tenant moving into
the building will need to comply with existing City standards and codes in regards to noise, odors
and the use of hazardous materials.
i. Availability of public services and facilities to accommodate the proposed use; and
City services and facilities already exist to serve this building. The applicant will need to provide
the connections to these public services.
I Prevention of neighborhood deterioration and blight.
The applicant is proposing to develop a vacant lot. The construction of the building and the
maintenance of the grounds will help to prevent neighborhood deterioration and blight.
XX Copies of all Review Comments are contained in the Official File.
Copies of all Review Comments are attached to this report
D. Findings, Conclusions & Decision
Having reviewed the written record in the matter, the City now enters the following:
1) Request., The Applicant has requested Environmental Review and Administrative Site
Plan Approval for warehouse/manufacturing building with supporting office space.
2) Environmental Review. The applicant's file containing the application, State
Environmental Policy Act (SEPA) documentation, the comments from various City departments, the
public notices requesting citizen comment, and other pertinent documents was entered as Exhibit
No. 1.
SITEERC.DOC
City of Renton PB/PW Department Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICEIWAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 10 of 13
3) Site Plan Review: The applicant's site plan application complies with the requirements
for information for site plan review. The applicant's site plan and other project drawings are
entered as Exhibits No. 2 thru 6.
4) Comprehensive Plan: The subject proposal is consistent with the Comprehensive
Plan designation of Valley Planning Area.
5) Zoning: The Site Plan as presented, complies with the zoning requirements and
development standards of the Medium Industrial (IM) Zoning designation.
E. Conclusions
1) The subject proposal complies with the policies and codes of the City of Renton.
2) The proposal complies with the Comprehensive Plan designation of Valley Planning Area;
and the Zoning designation of Medium Industrial (IM).
F. Decision
The Site Plan for SW 7th Office/Warehouse, File No. LUA-97-057, is approved subject to the
following conditions.
CONDITIONS:
1. The applicant shall submit a revised site plan that demonstrates a pedestrian walkway linking the
proposed building with the existing sidewalk. The pedestrian walkway may either be painted on the
pavement or provided as a different paving material. The revised site plan shall be submitted with the
application for building permits.
EFFECTIVE DATE OF DECISION ON LAND USE ACTION:
SITEERCLOC
City of Renton PWWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICFIWAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 17,1997 Page 11 of 13
SIGNATURES:
James C. Hanson, Zoning Administrator date
Michael D.Kattermann,Zoning Administrator date
SITEERC.DOC
City of Renton Pl"W Department Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 7TH OFFICEIWAREHO USE _ L UA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 12 of 13
TRANSMITTED this 2nd day of June, 1997 to the applicant and owner.'
David Kahle
David Kahle, Architect
12720 Gateway Drive, Suite 116
Seattle, WA 98168
L-O Renton ll, Inc.
One University Square
600 University Street, Suite 2820
Seattle, WA 98168
TRANSMITTED this 2nd day of June, 1997 to the parties of record:
TRANSMITTED this 2nd day of June, 1997 to the following:
Larry Meckling,Building Official
Bob Arthur,Land Use Inspector
Art Larson,Fire Marshal
Neil Watts,Public Works Division
Lawrence J.Warren,City Attorney
South County Journal
ADMINISTRATIVE LAND USE AND ENVIRONMENTAL (COMBINED COMMENT AND APPEAL
PERIOD
• Environmental Determination Comment Process Comments regarding the environmental
determination must be filed in writing on or before 5:00 PM June 17, 1997 (15 days from the date of
publication).
Any aggrieved person feeling that the environmental determination of the Environmental Review Committee is based
on erroneous procedure, errors of law or fact, error in judgment, or the discovery of new evidence that could not be
reasonably available at the time of the determination may submit written comments. After review of the comments, if
the Environmental Review Committee finds there is not sufficient evidence to amend its original determination, then
there will be no further extension of the appeal period. Any person wishing to take further action would need to file a
formal appeal within the original 15-day timeframe.
Written comments must be filed with:
Jana Huerter, Land Use Review Supervisor
City of Renton Development Services Division
200 Mill Avenue South
Renton, WA 98055
SITEERC.DOC
City of Renton PB/PWDepartment Administrative Site Plan Approval&Environmental Review Committee Staff Report
SW 77W OFFICE/WAREHOUSE LUA-97-057,SA,ECF
REPORT AND DECISION OFMay 27,1997 Page 13 of 13
• Environmental Determination and Land Use Decision Appeal Process Appeals of either the
environmental determination [RCW 43.21.0075(3), WAC 197-11-680] and/or the land use decision must be
filed in writing on or before 5:00 PM June 17, 1997 (15 days from the date of publication).
If no appeals are filed by this date, both actions will become final.
Appeals must be filed in writing together with the required $75.00 application fee with: