HomeMy WebLinkAboutMFP24002301.pdfDEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Major Franchise Permit: MFP24002301
IVR Number: 24002301
Permit Information
Permit Name: Puget Sound Energy - Electric
Address/Location:05/02/2024Application Date:3342101040Parcel Number: 1017 N 30TH ST
Permit Type:05/15/2024Issue Date:Franchise
Permit Work Class:05/15/2025Expiration Date:Major Utility
Job Number: 101164576Franchise Type:Electric
Description: Puget Sound Energy Electric P03_319026 166349_1706 NE 24TH ST_3343903637_25. P04_318997
166482_2324 ABERDEEN AVE NE_3343901527_25. P05_319014 166482_2332 ABERDEEN AVE
NE_3343901526_25. P06_319015 166532_2317 CAMAS AVE NE_345700250_25. P07_318992 166601_2416 NE
23RD ST_646300090_25. P08_318991 166586_2412 NE 23RD ST_646300080_25. P10_318766 166409_1900
NE 16TH ST_3343902642_25. P11_318708 166387_1402 KENNEWICK AVE NE_1839500070_10. P11A_318717
166387_1402 KENNEWICK AVE NE_1839500070_10. P12_318707 166396_1401 LINCOLN AVE
NE_1839500075_10
POTELCO CREW TO REPLACE B/O POLE @P01 (319230 166141), P03 (319026 166349), P04 (318997 166482),
P05 (319014 166482), P06 (319015 166532), P07 (318992 166601), P08 (318991 166586), P10 (318766 166409),
P11 (318708 166387), P11A(318717 166387), P12 (318707 166396)
UPGRADE EXISTING SIDEWALK GUY @ P06. UPGRADE EXISTING DOWN GUY @ P07, P09, P10, P11A. REMOVE
NEUTRAL BETWEEN P05 & P5A. REMOVE SECONDARY BETWEEN P10 TO P10A
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031ApplicantX
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
Puget Sound Energy Inc 10885 NE 4th Street, PSE08-N08
Bellevue, WA 98009
B: (888) 225-5773Emergency
Contact
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 425.235.7736) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
Page 1 of 2THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
DEPARTMENT OF PUBLIC WORKS
Page 1 of 3 | Published: 10/27/2021
Transportation Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN APPLICATION
Published: 10/27/2021
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL AT LEAST FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a traffic control
plan (TCP) and obtain city's approval of that plan when construction, repair, or maintenance work is to be conducted
within the city's right-of-way.
1. Fill out the Traffic Control Plan (TCP) Application form and prepare required submittal documents.
2. The following items are all required for submittal of the TCP Application:
☐Electronic Copy of the TCP Application
☐Electronic Copy of the TCP Layout, on 11” X 17” paper size format, which shall:
Include map(s) showing the location of the project and work area.
Be legible lettering and clear, contrasting, symbols of viewing or printing.
Must indicate street names, and north arrow and scale.
Types of plans required:
o Work hour plan – show all mobility impacts during construction hours.
o Non-work plan - show all mobility impacts after work hours when limited or no work is
happening in the right-of-way (ROW), if applicable.
o Changing construction phases – show construction sequence and each construction phase
change even if the traffic control is not modified, if applicable.
o Pedestrian access/detour plan, if applicable.
- Shall conform to the Washington State Traffic Control Flagger Certification handbook, by the
Evergreen Safety Council.
3. Submit Application via email to TCP@rentonwa.gov with the subject line “TCP Application – [Project Name].”
Project Name: Permit #:
Site Address:
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Construction Company:
Contact Name: Phone/Cell: _________________________
Business Address: City/State: Zip:
Description of Work:
Approval By: _________________________________________________ Date:____________________
Transportation Engineering
PLEASE SEE ATTACHED
POTELCO, INC
6905 S 228TH ST KENT, WA 98032
101164576
1017 N 30TH ST(
Echo Good 253-325-1522
MFP24002301
Monday - Friday 8:00AM - 3:00PM
Scott Warlick CED 5/9/2024
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 2 of 3 | Published: 10/27/2021
PERMIT HOLDER AGREES TO ALL THE FOLLOWING:
Must have approved Traffic Control Plan (TCP) prior to commencing the work.
Maintain existing pedestrian access. The work on pedestrian facilities, shall be limited to one corner at a time,
with the least possible inconvenience or delay to pedestrians.
WORK TIME begins when any street or travel lane is fully or partially closed. This includes set up within the
traveled way.
Comply with all traffic regulations of the City of Renton and the State of Washington.
Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for all street
and lane closures, and the plan shall be performed in compliance with the Manual on Uniform Traffic Control
Devices.
Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
Contractor or entity must call Renton School District (425-204-4455) or any public/private agency, including public
transit, to be affected by a temporary lane or road closure a minimum of five business days (excluding weekends
and holidays) prior to starting any work.
Contractor or entity must notify King County Metro in writing at construction.coord@kingcounty.gov a minimum
of five business days (excluding weekends and holidays) prior to starting any work impacting bus stops, a
temporary lane or road closure. Work requiring removing a bus shelter or sign requires notification in writing a
minimum of 30 business days (excluding weekends and holidays). Please call King County Metro at 206-477-1140
with any questions.
Any lane or street closures not in conformance with the approved traffic control plan and/or without notification
of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200 Signs or Flaggers at
thoroughfare work sites and R.C.W. 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments, including all
costs of defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved traffic control plans including claims arising from towing of private vehicles and
the acts of the Permit Holder’s agents and employees.
The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and in
such event shall indemnify and hold harmless the City for any such claims paid, including the City’s reasonable
attorney’s fees and litigation costs incurred resulting from such claim.
In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder will pay for
legal counsel chosen by the City to defend against same.
Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic or
pedestrian safety or travel.
All permit conditions shall be met.
NOTES:
Total road closure lasting more than twenty-four (24) hours is subject to the approval by the City Council.
Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by a traffic control plan layout or reference to WSDOT.
Approved Temporary Traffic Control Plan must be at the work site during work hours.
Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded to safely redirect pedestrians around a work zone.
Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or slippery
road conditions during work and non-work hours.
Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a company
logo or any legally acceptable sign showing the company name, address, and telephone number at a conspicuous
place on the vehicle or equipment.
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 3 of 3 | Published: 10/27/2021
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
seventy-two (72) hours in advance of effective date and time.
The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop (3555
NE 2nd Street).
I certify that the information on this application and within the submittal documents are accurate to the best of my
knowledge and I acknowledge all the requirements on this application.
Applicant’s Signature Date
Applicant’s Name (Print)
CORRIE RYDBERG
1017 N 30th St Renton WA 98056 USAP0111111111N 30TH STN 30TH STSTOPSTOP
PARK AVE N
BURNETT AVE N
W20-1ROAD
WORK
AHEAD W20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7A0'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com1 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-7316MFP24002301
P03
1706 NE 24th St
Renton
WA 98056
USA
15 151313
1010NE 24TH ST
NE 23RD STJONES AVE NESTOP
FLAGGER
W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROAD
WORKAHEAD W20-1STOP
FLAGGERW20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1W20-7A
W20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1
14 14
STOP
FLAGGER
FROMTOTOW AWAY AREAPHONE 684-5444NAME OF FIRM XXX-XXX-XXXXNO PARKINGPLACE SIGNS BOTHSIDES OF WORK AREASTOP
FLAGGER
0'60'30'
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Jaber Tofan
206-406-8460
Jaber.tofan@pse.com
2 OF 111017 N 30TH ST Renton WA 98056
0
11925049
03/05/2024
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Jaber Tofan
Card No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-7316
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours
as per jurisdictional requirements. (Generally
between 9 a.m. and 4 p.m. on non-arterials and
from 9 a.m. to 3 p.m. on arterials. If night time
work is approved, Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MFP24002301
P04
2332 Aberdeen Ave NE
Renton
WA 98056
USA
P05
2324 Aberdeen Ave NE
Renton
WA 98056
USA
P5A
10 101212 121210 10
ALL-WAY
STOP1212
10 10
FROM TO
TOW AWAY AREA
PHONE 684-5444
NAME OF FIRM XXX-XXX-XXXX
NO PARKING
STOP
W20-1ROAD
WORK
AHEAD W20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7ANE 24TH ST
NE 24TH ST
MONTEREY AVE NEBLAINE AVE NENE 24TH PL
ABERDEEN AVE NEABERDEEN AVE NEFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PARKW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7ASTOPW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7AW20-1
ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥
W20-7A
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Jaber Tofan
206-406-8460
Jaber.tofan@pse.com
3 OF 111017 N 30TH ST Renton WA 98056
0
11925049
03/05/2024
0'60'30'
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Jaber Tofan
Card No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-7316
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours
as per jurisdictional requirements. (Generally
between 9 a.m. and 4 p.m. on non-arterials and
from 9 a.m. to 3 p.m. on arterials. If night time
work is approved, Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MFP24002301
P04
2332 Aberdeen Ave NE
Renton
WA 98056
USA
P05
2324 Aberdeen Ave NE
Renton
WA 98056
USA
P5A
10 101212 121210 10
ALL-WAY
STOP
10 10
W20-1ROAD
WORK
AHEAD W20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7ANE 24TH ST
NE 24TH ST
MONTEREY AVE NEBLAINE AVE NENE 24TH PL
ABERDEEN AVE NEABERDEEN AVE NESTOP
STOP
STOP
W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7ASTOP
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Jaber Tofan
206-406-8460
Jaber.tofan@pse.com
4 OF 111017 N 30TH ST Renton WA 98056
0
11925049
03/05/2024
0'60'30'
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Jaber Tofan
Card No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-7316
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours
as per jurisdictional requirements. (Generally
between 9 a.m. and 4 p.m. on non-arterials and
from 9 a.m. to 3 p.m. on arterials. If night time
work is approved, Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MFP24002301
2317 Camas Ave NE Renton WA 98056 USAP06BLAINE AVE NE
W20-1ROAD
WORK
AHEAD
BE
PREPARED
TO
STOP W3-4100'≥100'≥100'≥W20-7ADAYTON AV NE
1212DAYTON AV NE12121414CAMAS AV NE14141414NE 24TH STNE 24TH ST1414CAMAS AV NEW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4X'≥X'≥X'≥W20-7AW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7A
W20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7AW20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7A
STO
PSTOP
DAYTON AV NESTOP
STO
P
Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com5 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
P072416 NE 23rd St Renton WA 98056 USAP081717
NE 24TH STNE 24TH ST1414NE 23RD PLNE 23RD STNE 23RD STDAYTON AV NE1212 121212121414NE 24TH STEDMONDS AV NE
EDMONDS AV NE
DAYTON AV NE
1313
W20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7A
W20-1ROAD
WORK
AHEAD W20-4ONE LANE
ROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥W20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7A100'≥STO
PSTOP STOPSTOP
1010Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com6 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
2416 NE 23rd St Renton WA 98056 USAP081717
NE 24TH STNE 24TH ST1414NE 23RD PLNE 23RD STNE 23RD STDAYTON AV NE1212
121212121414NE 24TH STEDMONDS AV NE
EDMONDS AV NE
DAYTON AV NE
1313
W20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥W20-1ROAD
WORK
AHEAD W20-4ONE LANEROAD
AHEAD100'≥100'≥W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥W20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥W20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4100'≥100'≥100'≥W20-7A100'≥STOP
1010STO
P
100'≥W20-7AProject Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com7 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
1900 NE 16th St Renton WA 98056 USAP101111
STO
PSTOP
100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥W20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥W20-1ROAD
WORK
AHEAD W20-4ONE LANEROADAHEAD100'≥100'≥W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥15151515FROM TO
TOW AWAY AREA
PHONE 684-5444
NAME OF FIRM XXX-XXX-XXXX
NO PARKING
12121313NE 16TH STNE 16TH STNE 16TH STLINCOLN AVE NE
STOP
W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AKENNEWICK AVE NE
KENNEWICK AVE NE
MONTEREY AVE NE
MONTEREY AVE NE MONTEREY AVE NEProject Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com8 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
P111402 Kennewick Ave NE Renton WA 98056 USA1401 Lincoln Ave NE Renton WA 98056 USAP12111116161010 1010STOP
STO
P
LINCOLN AVE NE
KENNEWICK AVE NE
KENNEWICK AVE NE KENNEWICK AVE NE
NE 14TH STNE 14TH STNE 14TH STMONTEREY AVE NE
MONTEREY AVE NE1313
1313W20-1ROAD
WORK
AHEAD W20-4ONE LANEROAD
AHEAD100'≥100'≥100'≥W20-7AW20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7A
Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com9 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
P111402 Kennewick Ave NE Renton WA 98056 USA1401 Lincoln Ave NE Renton WA 98056 USAP12111116161010 1010STOP
STOP
LINCOLN AVE NE
KENNEWICK AVE NE
KENNEWICK AVE NE
NE 14TH STNE 14TH STNE 14TH STMONTEREY AVE NE MONTEREY AVE NE1313
1313W20-1ROAD
WORK
AHEAD W20-4ONE LANEROAD
AHEAD100'≥100'≥100'≥W20-7AW20-1
ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥
W20-7A
STOP
STOP
Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVJaber Tofan206-406-8460Jaber.tofan@pse.com10 OF 111017 N 30TH ST Renton WA 980560 11925049 03/05/2024Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hoursas per jurisdictional requirements. (Generallybetween 9 a.m. and 4 p.m. on non-arterials andfrom 9 a.m. to 3 p.m. on arterials. If night timework is approved, Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYWORK AREACHEVRONARROW BOARDFLAGGERUNIFORMEDPOLICE OFFICERPOLICESTOPPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Jaber TofanCard No. ES2 000434Card Exp. 02/18/2028Jaber.Tofan@pse.com(425)424-73160'60'30'NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040MFP24002301
N
Vicinity Map
N.T.S.
Owner / Developer Contact Info
officeATTN:
PSE
-
-
KELLY ULICNY 425-429-0949
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
PHONE
CABLE TV
11925049 101164576
N/A 593254043
N/A 594157207
N/A 583075036
N/A N/A
N/A 108150582
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
OH Misc Expense
UG Misc Expense
OH Xfmr Expense
UG Xfmr Expense
Removal
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
E. GOOD 253-325-1522 2/26/24
M. WU 858-282-8818 2/26/24
...
M. WU 858-282-8818 2/26/24
N/A RENTON
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
1017 N 30TH ST, RENTON, WA 98056
ASPLUNDH CONSTRUCTION
N/A N/A
N/A 101164576
AS NOTED 1 OF 5
KING N/A N/A QCSOKE
SEE LIST N/A N/A
SEE LIST SEE LIST SEE LIST HIG-15
LUMEN
.
.
COMCAST
.
.
RENTON SCHOOL DIST
.
.
.
.
.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:ECHO GOOD
253-325-1522
ECHO.GOOD@PSE.COM
...
...
...101164576No
No
No
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
General
- Return removed materials to the local storeroom or PSE storeroom.
OVERHEAD CONSTRUCTION
Poles & Structures
- Poles are to be installed or relocated as staked. Unless otherwise noted, all pole location measurements
are from the roadside face of the pole.
- All new poles set shall be the class indicated on the sketch, or better. Do not set a lower class pole than
specified.
- Install ground plate assembly on all new poles. Install Switch Ground Assembly per standard specification
6014.1000 at new gang operated switch locations.
- Install grid numbers on all new and existing poles as shown on sketch.
- Straighten existing poles as indicated or as necessary.
- Treat all field-drilled poles with copper napthenate wood preservative.
- Remove old poles after communication companies have transferred off and return to PSE storeroom. Fill
and crown pole holes and restore area similar to adjacent landscaping.
Conductors & Equipment
- Transfer all overhead and underground primary, secondary and service conductors and guys to new poles
set, unless otherwise indicated on this sketch.
- Transfer existing transformers to new poles unless otherwise indicated on this sketch.
- Use stirrups to connect all overhead and underground primary taps, and all transformers. Install at all sites
being worked within the scope of the project where they are currently missing.
- For 12kV construction, always install avian protection with 4/0 Cu covered jumpers and #4 SD
aluminum-covered tie-wire (MID 8454500), For 34 kV construction, use bare wire primary jumpers with
preformed helical grip ties.
- Apply avian protection devices when required per Standard 6015.2000.
- Apply grit inhibitor on all Ampact, stirrup, and dead-end connections.
- Connect primary taps and transformers to same phase as existing unless otherwise shown on the drawing.
- All neutral connections to be made with solid compression connectors. Connect all pole grounds to
common neutral.
- Use Load-interrupter cutouts (with arc shields) on all primary overhead and underground taps with fused
protection above 40T.
- Install Wildlife Protectors on all transformers.
UNDERGROUND CONSTRUCTION
Excavation
-Trenching outside of the Right-of-way shall be of sufficient depth to provide a minimum of 36” of cover for
primary conductors and 24” of cover for secondary conductors.
-Road crossings and all trenches within the Right-of-way shall be of sufficient depth to provide a minimum
of 36” of cover for all conductors or as required by the permitting Agency.
-All conductors/conduits shall have a minimum of 3” of bed and 3” of clean sand cover.
-No rocks larger than 6” shall be included in backfill.
-Backfill in road crossings and within the Right-of-way shall be compacted to 95% density or as required
by the permitting Agency.
-Restore all excavated areas to original condition.
LEGEND
CONDUIT RISER
OVERHEAD TRANSFORMER
JUNCTION VAULT/JUNCTION BOX
NEW CONDUCTOR AND OR TRENCH LINE
DISCONNECT - FUSED
PULL VAULT OR SPLICE VAULT
EXISTING POLE
DOWN GUY
DISCONNECT - UNFUSED
NEW POLE
PADMOUNT TRANSFORMER
SECONDARY HANDHOLE
EXISTING CONDUCTOR TO BE REMOVED
OR ABANDONED
STREET LIGHT
TOTAL UNDERGROUND TRANSFORMER
ENERGY CUSTOMER DEMAND POINT
OR
OR
OR
OVERHEAD JUMPER CONNECTION
SITE 4-6
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit Field Face
Quadrant
Climbing
SpaceRoad Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
NOT TO SCALE
UTILITY POLE EROSION CONTROL DETAIL
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
Not to scale Drainage ditches or Dry vegetated sites
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
N 30TH ST
405SITE 1BURNETT AVE NSITE 2
PVT RD
NE 24TH ST
EDMONDS AVE NESITE 3
NE 23RD PL
SITE 7
NE 16TH ST
NE 14TH ST
SITE 8
NE 27TH PL
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
U-MAPS
2305E017
2305E018
2305E020
2405E127
OH CKT MAPS
2305E040
2405E136
UG CKT MAPS
2305E017
2305E018
2305E020
2405E127
1/4 SECTIONS
SW32-T24N-R05E
DLC05-T23N-R05E
SITE 9
HIGH AVE NE
N/A 108154302UG SVC Removal
714-713-3033 4/8/24
MFP24002301
This permit is for Major construction work in the ROW and will be billed at an additional
$158/HR for inspections. After hours and weekend work will be billed at $175/HR
RESTORATION PER CITY OF RENTON STANDARDS
ABCABCN#2ACSR
N 28TH PL
PVT ROAD
#4CUANA(ACCESS)
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
E. GOOD 253-325-1522 2/26/24
M. WU 858-282-8818 2/26/24
...
M. WU 858-282-8818 2/26/24
N/A RENTON
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
1017 N 30TH ST, RENTON, WA 98056
ASPLUNDH CONSTRUCTION
N/A N/A
N/A 101164576
AS NOTED 2 OF 5
KING N/A N/A QCSOKE
SEE LIST N/A N/A
SEE LIST SEE LIST SEE LIST HIG-15
LUMEN
.
.
COMCAST
.
.
RENTON SCHOOL DIST
.
.
.
.
.
...
...
...101164576 POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID # HEIGHT CLASS YEAR TOPPED RMVD
P01 319230-166141 40 3 1960
P02 319160-166101 40 4 1960
P03 319026-166349 30 1 1975
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P01 319230-166141 45 H1
P02 319160-166101 45 1
P03 319026-166349 35 3
SITE PLAN 1
1" = 50'
SITE PLAN 2
1" = 50'
SITE PLAN 3
1" = 50'
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P01
319230-166141
25kVA
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P01
319230-166141
25kVA
6211250
P02: 319160-166101 (Avg. Span = 172', Angle = 2°)
-EX 40' CL 4, 1960 POLE TO BE REPLACED
-INST 45' CL 1 (PD451) 6010.1000
-INST 1Ø PTP #4CU (TAN115) 6031.1010
-ROLL NEUT TO COMMON POSITION
-TRANSFER 1Ø #4CU PRI & NEUT (E/W)
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
P03: 319026-166349
-EX 30' CL 1, 1975 POLE TO BE REPLACED
-INST 35' CL 3 (PS353) 6010.1100
-TRANSFER OH TPX SEC
-TRANSFER OH TPX SVC
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
P01: 319230-166141 (Avg. Span = 151', Angle = 0°)
BRUSH REMOVAL REQ'D
-EX 40' CL 3, 1960 POLE TO BE REPLACED
-INST 45' CL H1 (PD45H1) 6010.1000
-DEEP SET +1' DUE TO CROSSWIND
-INST 3Ø PTP #2ACSR (TAN312) 6033.1010
-ROLL NEUT TO COMMON POSITION
-TRANSFER 3Ø #2ACSR PRI & NEUT (E/W)
-RM EX RUSTY 25kVA 120/240V XFMR & C/O
-INST 25kVA 120/240V XFMR (TRFNXF) 6025.1000; TAP CØ
-INST (2) RIGID CLEVIS (INDNRC) 6015.1000
-TRANSFER (6) OH TPX SVC'S
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
2-81
2-129
2-81
2-129 2-81
2-129
714-713-3033 4/8/24
MFP24002301
100T
X91025(N)
X91026(S)#4CU100T
T91027
AØADD500
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
E. GOOD 253-325-1522 2/26/24
M. WU 858-282-8818 2/26/24
...
M. WU 858-282-8818 2/26/24
N/A RENTON
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
1017 N 30TH ST, RENTON, WA 98056
ASPLUNDH CONSTRUCTION
N/A N/A
N/A 101164576
AS NOTED 3 OF 5
KING N/A N/A QCSOKE
SEE LIST N/A N/A
SEE LIST SEE LIST SEE LIST HIG-15
LUMEN
.
.
COMCAST
.
.
RENTON SCHOOL DIST
.
.
.
.
.
...
...
...101164576 POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID # HEIGHT CLASS YEAR TOPPED RMVD
P04 318997-166482 45 1 1947
P05 319014-166482 45 2 1958
P06 319015-166532 40 4 1960
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P04 318997-166482 45 3
P05 319014-166482 45 H2
P06 319015-166532 45 2
SITE PLAN 5
1" = 50'
P04: 318997-166482 (Avg. Span = 147', Angle = 1°)
TREE TRIMMING REQ'D
GRID # INCORRECT IN FIELD
-EX 45' CL 1, 1947 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø PTP #4CU (TAN115) 6031.1010
-TRANSFER 1Ø #4CU PRI & NEUT (N/S)
-RM EX RUSTY 25kVA 120/240V XFMR & C/O
-INST 25kVA 120/240V XFMR (TRFNXF) 6025.1000
-INST RIGID CLEVIS (INDNRC) 6015.1000
-TRANSFER OH TPX SEC
-TRANSFER (2) OH TPX SVC'S
-RM EX RISER
-INST 3" RISER (RIS3CSS) 6042.1000
-TRANSFER 350 UG TPX SVC (W); EXTEND AS REQ'D
-ACTUAL 350 UG TPX ADDED L=_________
-ACTUAL TRENCH L=_________
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P04
318997-166482
25kVA
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P04
318997-166482
25kVA
6211250
P05: 319014-166482 (Avg. Span = 230', Angle = 0°)
TREE TRIMMING REQ'D
-EX 45' CL 2, 1958 POLE TO BE REPLACED
-INST 45' CL H2 (PD45H2) 6010.1000
-DEEP SET +1' DUE TO CROSSWIND
-INST 3Ø PTP 1/0ACSR (TAN313) 6033.1012
-TRANSFER 3Ø 1/0ACSR PRI & NEUT (E/W)
-INST 1Ø TAP #4CU (LAT115) 6031.5100
-SUB L/I C/O (9999109) FOR LB C/O
-FUSE @ 100T (3412700); TAP CØ
-INST SW# X91025
-TRANSFER 1Ø #4CU PRI & NEUT (N)
-INST 1Ø TAP #4CU (LAT115) 6031.5100
-SUB L/I C/O (9999109) FOR LB C/O
-FUSE @ 100T (3412700); TAP AØ
-INST SW# X91026
-TRANSFER 1Ø #4CU PRI & NEUT (S)
-RM EX RISER
-RM IDLE 350 UG TPX SEC; ±35'
-CUT AT BASE OF POLE
-ACTUAL 350 UG TPX REMOVED L=_________ BATCH YEAR_________
-ACTUAL TRENCH L=_________
-RETIRE ON WO# 108154302
-INST (2) RIGID CLEVIS (INDNRC) 6015.1000
-TRANSFER OH TPX SEC
-TRANSFER OH TPX SVC
-TRANSFER TRAFFIC LIGHT OH TPX SVC
-TRANSFER ST LIGHT (SLAH5446)
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
P06: 319015-166532 (Avg. Span = 129', Angle = 0°)
-EX 40' CL 4, 1960 POLE TO BE REPLACED
-INST 45' CL 2 (PD452) 6010.1000
-INST 3Ø PTP 1/0ACSR (TAN313) 6033.1012
-TRANSFER 3Ø 1/0ACSR PRI & NEUT (E/W)
-RM EX 1Ø TERM & C/O
-INST 1Ø TERM & L/I C/O (TSU1L1) 6043.1000
-FUSE @ 100T (3412700); TAP AØ
-INST SW# T91027
-RM (2) EX RISERS
-INST 2" RISER (RIS2CSS) 6042.1000
-TRANSFER 1Ø 1/0AL UG PRI (E); EXTEND AS REQ'D
-ACTUAL 1Ø 1/0AL UG PRI ADDED L=_________ BATCH YEAR_________
-ACTUAL TRENCH L=_________
-RM EX RUSTY 37.5kVA 120/240V XFMR & C/O
-INST 37.5kVA 120/240V XFMR (TRFPXF) 6025.1000; TAP AØ
-TRANSFER OH TPX SVC
-INST 3" RISER (RIS3CSS) 6042.1000
-TRANSFER 350 UG TPX SEC (S); EXTEND AS REQ'D
-ACTUAL 350 UG TPX ADDED L=_________
-ACTUAL TRENCH L=_________
-TRANSFER ST LIGHT (SLAH5454) 2-302
-RM EX SIDEWALK GUY
-INST 3/8" SEC SIDEWALK GUY (GYD3PB) 6013.0180 TO EX ANC
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P06
319015-166532
37.5kVA
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P06
319015-166532
37.5kVA
6211300
SPAN NOTE:
P05 TO P5A
-RM (1) SPAN OF #4CU NEUTRAL (DOUBLE NEUT)
-SEE WIRE REMOVAL TABLE
2-81
2-57
2-45XX
2-24XX
2-129
SITE PLAN 4
1" = 50'
2-81
2-24XX
2-129
2-81
2-24C
2-24C
2-24XR
2-302
2-129
WIRE REMOVAL TABLE
Location
Pri Sec Wire Size & Type Quantity
Length
(ft per
conductor)RemarksFrom To
P05 P5A COMMON NEUT 1 225
Total Feet (COMMON NEUT) Removed 225
2-20A
714-713-3033 4/8/24
MFP24002301
(PRIVATE)ANA#6CU
#4ACSR
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
E. GOOD 253-325-1522 2/26/24
M. WU 858-282-8818 2/26/24
...
M. WU 858-282-8818 2/26/24
N/A RENTON
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
1017 N 30TH ST, RENTON, WA 98056
ASPLUNDH CONSTRUCTION
N/A N/A
N/A 101164576
AS NOTED 4 OF 5
KING N/A N/A QCSOKE
SEE LIST N/A N/A
SEE LIST SEE LIST SEE LIST HIG-15
LUMEN
.
.
COMCAST
.
.
RENTON SCHOOL DIST
.
.
.
.
.
...
...
...101164576New pole at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER TRANSFER
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P09
318823-166587
25kVA
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID # HEIGHT CLASS YEAR TOPPED RMVD
P07 318992-166601 40 4 1955
P08 318991-166586 40 5 1960
P09 318823-166587 40 3 1959
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P07 318992-166601 45 3
P08 318991-166586 45 3
P09 318823-166587 45 3
SITE PLAN 7
1" = 50'
SITE PLAN 6
1" = 50'
P07: 318992-166601
GRID # MISSING IN FIELD
-EX 40' CL 4, 1955 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø DE #4ACSR (DE2115) 6031.1040
-TRANSFER 1Ø #4ACSR PRI & NEUT (W)
-TRANSFER OH TPX SEC
-TRANSFER (3) OH TPX SVC
-RM EX DG
-INST 3/8" PRI & NEUT DG'S (GYD3SA)(GYD3SAN) 6013.0100 TO EX ANC
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
MAPS AND RECORDS NOTE (P07):
OH SVC TO 2309 EDMONDS AVE NE DOES NOT
EXIST IN FIELD
P08: 318991-166586 (Avg. Span = 148', Angle = 0°)
-EX 40' CL 5, 1960 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø PTP #4ACSR (TAN112) 6031.1010
-TRANSFER 1Ø #4ACSR PRI & NEUT (E/W)
-RM EX RUSTY 37.5kVA 120/240V XFMR & C/O
-INST 37.5kVA 120/240V XFMR (TRFPXF) 6025.1000
-INST RIGID CLEVIS (INDNRC) 6015.1000
-TRANSFER OH TPX SEC
-TRANSFER (4) OH TPX SVC
-TRANSFER ST LIGHT (SLAH5450)
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P08
318991-166586
37.5kVA
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P08
318991-166586
37.5kVA
6211300
P09: 318823-166587 (Avg. Span = 128', Angle = 0°)
-EX 40' CL 3, 1959 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø DBL DE #6U (DDE0115) 6031.1043
-ROLL NEUT TO COMMON POSITION
-TRANSFER 1Ø #6CU PRI & NEUT (E/W)
-TRANSFER 25kVA 120/240V XFMR
-TRANSFER OH TPX SEC
-TRANSFER (2) OH TPX SVC'S
-TRANSFER ST LIGHT (SLAH4963) 2-302
-RM EX DG
-INST 3/8" SEC DG (GYD3SA) 6013.0100 TO EX ANC
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
2-81
2-302
2-129
2-81
2-129
2-81
2-129
714-713-3033 4/8/24
MFP24002301
X91029
X91028
25kVA 120/240V
BBBBDESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
E. GOOD 253-325-1522 2/26/24
M. WU 858-282-8818 2/26/24
...
M. WU 858-282-8818 2/26/24
N/A RENTON
HIG-15 REPL 13 POLES
DISTRIBUTION POLE REPLACEMENT
1017 N 30TH ST, RENTON, WA 98056
ASPLUNDH CONSTRUCTION
N/A N/A
N/A 101164576
AS NOTED 5 OF 5
KING N/A N/A QCSOKE
SEE LIST N/A N/A
SEE LIST SEE LIST SEE LIST HIG-15
LUMEN
.
.
COMCAST
.
.
RENTON SCHOOL DIST
.
.
.
.
.
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)101164576SITE PLAN 8
1" = 50'
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID # HEIGHT CLASS YEAR TOPPED RMVD
P10 318766-166409 40 5 1955
P11 318708-166387 40 2 1960
P12 318707-166396 40 3 1962
P13 318922-166321 35 5 1956
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P10 318766-166409 45 3
P11 318708-166387 45 3
P12 318707-166396 45 3
P13 318922-166321 35 3
P10: 318766-166409 (Avg. Span = 144', Angle = 2°)
BRUSH REMOVAL REQ'D
-EX 40' CL 5, 1955 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø PTP #6CU (TAN115) 6031.1010
-ROLL NEUT TO COMMON POSITION
-TRANSFER 1Ø #6CU PRI & NEUT (E/W)
-INST 1Ø VERT TAP #6CU (LATV115) 6031.5100
-ROLL NEUT TO COMMON POSITION
-FUSE @ 40T (3412500)
-INST SW# X91028
-TRANSFER 1Ø #6CU PRI & NEUT (S)
-INST 25kVA 120/240V XFMR (TRFNXF) 6025.1000
-INST RIGID CLEVIS (INDNRC) 6015.100
-TRANSFER OH TPX SVC
-RM EX RISER
-INST 3" RISER (RIS3CSS) 6042.1000
-TRANSFER 4/0 UG TPX SVC (N); EXTEND AS REQ'D
-ACTUAL 4/0 UG TPX ADDED L=_________
-ACTUAL TRENCH L=_________
-TRANSFER ST LT (SLAH4973)
-INST 3/8" PRI & NEUT DG'S (GYD3SA)(GYD3SAN) 6013.0100 TO EX ANC
-INST AUX EYE (8845300)
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
WIRE REMOVAL TABLE
Location
Pri Sec Wire Size & Type Quantity
Length
(ft per
conductor)RemarksFrom To
P10 P10A X #6CU OWS 3 125
Total Feet (#6CU OWS) Removed 375
P11: 318708-166387 (Avg. Span = 129', Angle = 0°)
-EX 40' CL 2, 1960 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø PTP #4ACSR (TAN112) 6031.1010
-ROLL NEUT TO COMMON POSITION
-TRANSFER 1Ø #4ACSR PRI & NEUT (E/W)
-RM 1Ø SWITCH C/O
-INST 1Ø SLACK SPAN TAP #2ACSR (SSDF172) 6031.5010
-INST 1Ø L/B SWITCH C/O (DLS115L) 6022.1000
-FUSE @ 25T (3412400)
-TRANSFER 1Ø #2ACSR PRI & NEUT (N)
-TRANSFER OH TPX SEC
-TRANSFER ST LT (SLAH4978)
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
P11A: 318717-166387
-EX 40' CL UNK, YR UNK POLE TO REMAIN
-RM EX PRI & NEUT DE'S (S)
-INST 1Ø SLACK SPAN TAP #2ACSR (SSDF172) 6031.5010
-INST SNGL HELIX ANC (ANDH1) 6012.1000 (L= 10' S)
-INST 3/8" PRI & NEUT DG'S (GYD3SA)(GYD3SAN) 6013.0100 TO NEW ANC
P12: 318707-166396 (Avg. Span = 108', Angle = 0°)
BRUSH REMOVAL REQ'D
GRID # MISSING IN FIELD
-EX 40' CL 3, 1962 POLE TO BE REPLACED
-INST 45' CL 3 (PD453) 6010.1000
-INST 1Ø PTP #4ACSR (TAN112) 6031.1010
-ROLL NEUT TO COMMON POSITION
-TRANSFER 1Ø #4ACSR PRI & NEUT (E/W)
-RM EX DBL BUSHING 25kVA 120/240V XFMR & C/O
-INST 25kVA 120/240V XFMR (TRFNXF) 6025.1000
-TRANSFER OH TP SEC
-TRANSFER OH TPX SVC
-RM EX RISER
-INST 3" RISER (RIS3CSS) 6042.1000
-TRANSFER 4/0 UG TPX SVC (S); EXTEND AS REQ'D
-ACTUAL 4/0 UG TPX ADDED L=_________
-ACTUAL TRENCH L=_________
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P12
318707-166396
25kVA
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P12
318707-166396
25kVA
6211250
P13: 318922-166321
GRID # MISSING IN FIELD
-EX 35' CL 5, 1956 TO BE REPLACED
-INST 35' CL 3 (PS353) 6010.1100
-TRANSFER OH TPX SEC
-TRANSFER OH TPX SVC
-RM EX DG
-INST 3/8" SEC DG (GYD3SA) 6013.0100 TO EX ANC
-TOP POLE ABOVE COMM
-REMOVE POLE STUB AFTER COMM HAS TRANSFERRED
SITE PLAN 9
1" = 50'
CREW NOTE (P13):
ACCESS POLE FROM 2021 JONES AVE NE
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P10
318766-166409
25kVA
6211250
MAPS AND RECORDS NOTE (P10):
SVC TO 1900 NE 16TH ST IS OH IN THE FIELD
2-81
2-24C
2-24XX
2-302
2-129
2-81
2-24C
2-302
2-129
2-81
2-24XX
2-129
2-21
1-8E
2-20A
2-81
2-129
714-713-3033 4/8/24
MFP24002301