Loading...
HomeMy WebLinkAboutMCKEE ENTERPRISES BROTHERTON CADILLAC DOMESTIC RPBABackflow Assembly Test Report Made By Mako Assist on: 05/24/2024 at 12:21 PM SITE Water Authority: Contact Name: Service Address: RENTON WATER CODY @ MCKEE ENTERPRISES 215 SW 12th St Renton, WA 98057 United States ASSEMBLY Type: Size: Manufacturer: Model: Serial Number: Geo Tag: RP 2 INCH wilkins 975xl2 4977179 47.46908712215382 -122.22041885544125 TEST GAUGE Name: Serial Number: Calibration Date: MAKO MK5 2AC19070168 2024-01-30 TEST RESULTS Test Procedure Followed: Relief Valve Opening Point (RV) (PSID): Check Valve 1 (CV 1) (PSID): Line Pressure (LP) (PSID): USC Manual 10/ABPA 2.9 7.8 74.0 RV Fully Opened?: CV 1 Held Tight?: CV 2 Held Tight?: YES YES YES COMMENTS JOB- BROTHERTON CADILLAC METER # 96056940 LOCATION- SW CORNER OF BLDG INSIDE INSULATED ENCLOSURE. PASS CERTIFIED BY: Name: Certificate #: Company: Phone: Email: Travis Grant B5889 Grant Utilities Inc. 4254492072 travisgrant@me.com