HomeMy WebLinkAboutMCKEE ENTERPRISES BROTHERTON CADILLAC DOMESTIC RPBABackflow Assembly Test Report
Made By Mako Assist on: 05/24/2024 at 12:21 PM
SITE
Water Authority:
Contact Name:
Service Address:
RENTON WATER
CODY @ MCKEE ENTERPRISES
215 SW 12th St
Renton, WA 98057
United States
ASSEMBLY
Type:
Size:
Manufacturer:
Model:
Serial Number:
Geo Tag:
RP
2 INCH
wilkins
975xl2
4977179
47.46908712215382
-122.22041885544125
TEST GAUGE
Name:
Serial Number:
Calibration Date:
MAKO MK5
2AC19070168
2024-01-30
TEST RESULTS
Test Procedure Followed:
Relief Valve Opening Point (RV) (PSID):
Check Valve 1 (CV 1) (PSID):
Line Pressure (LP) (PSID):
USC Manual 10/ABPA
2.9
7.8
74.0
RV Fully Opened?:
CV 1 Held Tight?:
CV 2 Held Tight?:
YES
YES
YES
COMMENTS
JOB- BROTHERTON CADILLAC
METER #
96056940
LOCATION- SW CORNER OF BLDG INSIDE INSULATED
ENCLOSURE.
PASS
CERTIFIED BY:
Name:
Certificate #:
Company:
Phone:
Email:
Travis Grant
B5889
Grant Utilities Inc.
4254492072
travisgrant@me.com