MCKEE ENTERPRISES BROTHERTON CADILLAC FIRELINE DCDA BYPASS DCVA
Backflow Assembly Test Report Made By Mako Assist on: 05/24/2024 at 12:52 PM SITE Water Authority: Contact Name: Service Address: RENTON WATER CODY @ MCKEE ENTERPRISES 215 SW 12th St Renton, WA 98057 United States ASSEMBLY Type: Size: Manufacturer: Model: Serial Number: Geo Tag: Meter Reading Before: Meter Reading After: DCDA-I 6 INCH wilkins 350astda 35792 47.4687998662186 -122.22034365177528 .10cf .10cfTEST GAUGE Name: Serial Number: Calibration Date: MAKO MK5 2AC19070168 2024-01-30 TEST RESULTS Test Procedure Followed: Line Pressure (LP) (PSID): Bypass Check Valve 1 (BPCV 1) (PSID): Bypass Check Valve 2 (BPCV 2) (PSID): Check Valve 1 (CV 1) (PSID): Check Valve 2 (CV 2) (PSID): USC Manual 10/ABPA 76.0 1.8 1.9 2.5 3.4 BPCV 1 Held Tight?: BPCV 2 Held Tight?: CV 1 Held Tight?: CV 2 Held Tight?: YES YES YES YES COMMENTS JOB- BROTHERTON CADILLAC METER- # 95357723 LOCATION- SW CORNER OF LOT INSIDE VAULT NEXT TO POST INDICATOR. PASS CERTIFIED BY: Name: Certificate #: Company: Phone: Email: Travis Grant B5889 Grant Utilities Inc. 4254492072 travisgrant@me.com