Loading...
HomeMy WebLinkAboutMCKEE ENTERPRISES BROTHERTON CADILLAC IRRIGATION DCVABackflow Assembly Test Report Made By Mako Assist on: 05/24/2024 at 12:01 PM SITE Water Authority: Contact Name: Service Address: RENTON WATER CODY @ MCKEE ENTERPRISES 215 SW 12th St Renton, WA 98057 United States ASSEMBLY Type: Size: Manufacturer: Model: Serial Number: Geo Tag: DC 1 INCH wilkins 350 B007187 47.4694818353558 -122.2204237049593 TEST GAUGE Name: Serial Number: Calibration Date: MAKO MK5 2AC19070168 2024-01-30 TEST RESULTS Test Procedure Followed: Line Pressure (LP) (PSID): Check Valve 1 (CV 1) (PSID): Check Valve 2 (CV 2) (PSID): USC Manual 10/ABPA 75.0 2.4 2.4 CV 1 Held Tight?: CV 2 Held Tight?: YES YES COMMENTS JOB- BROTHERTON CADILLAC METER # 95184950 LOCATION- FRONT OF SHOW ROOM OUT AT STREET. PASS CERTIFIED BY: Name: Certificate #: Company: Phone: Email: Travis Grant B5889 Grant Utilities Inc. 4254492072 travisgrant@me.com