HomeMy WebLinkAboutMFP24002985.pdfDEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Minor Franchise Permit: MFP24002985
IVR Number: 24002985
Permit Information
Permit Name: Puget Sound Energy - Electric
Address/Location:06/11/2024Application Date:2143701210Parcel Number: 520 SW SUNSET BLVD
Permit Type:06/26/2024Issue Date:Franchise
Permit Work Class:06/26/2025Expiration Date:Minor Utility
Job Number: 101174815Franchise Type:Electric
Description: Puget Sound Energy Electric CREW TO REPLACE DAMAGED POLES AT P03) 317764 165650 AND P02 (317748
165645). CREW TO REPLACE EXISTING OH WIRE BETWEEN P03 P02. CREW TO PARK AT P01 (317748 165632)
TO SWING EXISTING OH SERVICE WIRE. NO HS CUTS.
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031ApplicantX
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
Puget Sound Energy Inc 10885 NE 4th Street, PSE08-N08
Bellevue, WA 98009
B: (888) 225-5773Emergency
Contact
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 425.235.7736) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
DEPARTMENT OF PUBLIC WORKS
Page 1 of 3 | Published: 10/27/2021
Transportation Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN APPLICATION
Published: 10/27/2021
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL AT LEAST FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a traffic control
plan (TCP) and obtain city's approval of that plan when construction, repair, or maintenance work is to be conducted
within the city's right-of-way.
1. Fill out the Traffic Control Plan (TCP) Application form and prepare required submittal documents.
2. The following items are all required for submittal of the TCP Application:
☐Electronic Copy of the TCP Application
☐Electronic Copy of the TCP Layout, on 11” X 17” paper size format, which shall:
Include map(s) showing the location of the project and work area.
Be legible lettering and clear, contrasting, symbols of viewing or printing.
Must indicate street names, and north arrow and scale.
Types of plans required:
o Work hour plan – show all mobility impacts during construction hours.
o Non-work plan - show all mobility impacts after work hours when limited or no work is
happening in the right-of-way (ROW), if applicable.
o Changing construction phases – show construction sequence and each construction phase
change even if the traffic control is not modified, if applicable.
o Pedestrian access/detour plan, if applicable.
- Shall conform to the Washington State Traffic Control Flagger Certification handbook, by the
Evergreen Safety Council.
3. Submit Application via email to TCP@rentonwa.gov with the subject line “TCP Application – [Project Name].”
Project Name: Permit #:
Site Address:
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Construction Company:
Contact Name: Phone/Cell: _________________________
Business Address: City/State: Zip:
Description of Work:
Approval By: _________________________________________________ Date:____________________
Transportation Engineering
PLEASE SEE ATTACHED
POTELCO, INC
6905 S 228TH ST KENT, WA 98032
101174815
520 SW Sunset Blvd
Tony Contreras 206-637-3648
Monday Friday 9:00am 3:00pm
Scott Warlick CED 6/26/2024
MFP24002985
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 2 of 3 | Published: 10/27/2021
PERMIT HOLDER AGREES TO ALL THE FOLLOWING:
Must have approved Traffic Control Plan (TCP) prior to commencing the work.
Maintain existing pedestrian access. The work on pedestrian facilities, shall be limited to one corner at a time,
with the least possible inconvenience or delay to pedestrians.
WORK TIME begins when any street or travel lane is fully or partially closed. This includes set up within the
traveled way.
Comply with all traffic regulations of the City of Renton and the State of Washington.
Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for all street
and lane closures, and the plan shall be performed in compliance with the Manual on Uniform Traffic Control
Devices.
Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
Contractor or entity must call Renton School District (425-204-4455) or any public/private agency, including public
transit, to be affected by a temporary lane or road closure a minimum of five business days (excluding weekends
and holidays) prior to starting any work.
Contractor or entity must notify King County Metro in writing at construction.coord@kingcounty.gov a minimum
of five business days (excluding weekends and holidays) prior to starting any work impacting bus stops, a
temporary lane or road closure. Work requiring removing a bus shelter or sign requires notification in writing a
minimum of 30 business days (excluding weekends and holidays). Please call King County Metro at 206-477-1140
with any questions.
Any lane or street closures not in conformance with the approved traffic control plan and/or without notification
of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200 Signs or Flaggers at
thoroughfare work sites and R.C.W. 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments, including all
costs of defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved traffic control plans including claims arising from towing of private vehicles and
the acts of the Permit Holder’s agents and employees.
The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and in
such event shall indemnify and hold harmless the City for any such claims paid, including the City’s reasonable
attorney’s fees and litigation costs incurred resulting from such claim.
In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder will pay for
legal counsel chosen by the City to defend against same.
Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic or
pedestrian safety or travel.
All permit conditions shall be met.
NOTES:
Total road closure lasting more than twenty-four (24) hours is subject to the approval by the City Council.
Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by a traffic control plan layout or reference to WSDOT.
Approved Temporary Traffic Control Plan must be at the work site during work hours.
Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded to safely redirect pedestrians around a work zone.
Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or slippery
road conditions during work and non-work hours.
Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a company
logo or any legally acceptable sign showing the company name, address, and telephone number at a conspicuous
place on the vehicle or equipment.
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 3 of 3 | Published: 10/27/2021
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
seventy-two (72) hours in advance of effective date and time.
The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop (3555
NE 2nd Street).
I certify that the information on this application and within the submittal documents are accurate to the best of my
knowledge and I acknowledge all the requirements on this application.
Applicant’s Signature Date
Applicant’s Name (Print)
CORRIE RYDBERG
#520P01P02P03STEVENS AVE SW BUSSTOPBUSSTOPSW SUNSE
T
B
LVDSW SUNSET BLVDSW SUNSET BLVDSTE
V
E
N
S
A
V
E
S
W SW 3RD PL111111111010
LIND
AVE
SW11112020131112111112111111111211111111121111111113111111111111
ARRW-BRDR11-2STREETCLOSEDW20-1ROAD
WORK
AHEA
D
RIGHT L
A
N
E
CLOS
E
D
AHEA
D W20-5RW4-2R35
0
'
≥350'≥350
'≥W20-1ROADWORKAHEAD350'≥W20-1ROADWORKAHEAD10
0
'
≥
W20-1
ROADWORKAHEAD100'≥W20-1ROADWORKAHEAD100'≥
100'≥
W20-
3
ROADCLOSEDAHEADLOCALACCESSONLYSTREET CLOSEDTOTHRU TRAFFICR5-133R11-4S/WCLOSEDR9-9DETOURM4-9BMOVE BUS STOP 75' WEST.KING COUNTY METRO WILL BECONTACTED AT 206-477-1150 FIVE DAYSIN ADVANCE OF SCHEDULED DATE.RESIDENT(S) WILL BE INFORMED OFTEMPORARY DRIVEWAY CLOSUREADA COMPLIANTCURB RAMPCUSTOMER OUTREACH TO INFORMRESIDENTS OF ROAD CLOSUREPRIOR TO WORK START.CREW TO FACILITATE EMERGENCYVEHICLES ACCESS WHEN NEEDED.1818NSIGN SPACINGMPH60/6545/5535/403025"X"1000'500'350'200'100'CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040Project Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVFlaviana Nunes425-424-7386flaviana.rodriguesnunes@pse.com1 OF 3520 SW Sunset Blvd, Renton0 51495504906/05/2024LEGEND28" TRAFFIC CONESIGN LOCATIONTRAFFIC FLOWWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYCHEVRONARROW BOARDPOLEMINIMUM TAPER LENGTH=L (FT.)LANEWIDTH101112207075802510511512530150165180352052252454027029532045475495540POSTED SPEED (MPH)505005506005555060566060-66072065--78070--840TEMPORARY TRAFFIC CONTROL PLANPuget Sound EnergyTraffic Control Supervisor:Flaviana R. NunesCard No. 013414Card Exp. 11/2026flaviana.rodriguesnunes@pse.com(425)424-7386Notes:1. All signs and spacing to conform to theMUTCD and City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated,if indicated use ADA compliant channelization.3. Channelizing devices are 28" traffic cones.Use traffic drums (barrels) with steady burningType C lights on all State State Routes and Hwys.4. Sign size can be a minimum of 36" x 36" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 10' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place during approved work hours asper jurisdictional requirements. (Generally between 9a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3p.m. on arterials. If night time work is approved,signaling and flagges shall conform to WAC296-155-305. Night time work to take place between_____________and ______________.)8. All Flagger and Downstream tapers shall be 50'-100'.X'X'PLACE W20-1 SIGNS ON ALLADJACENT STREETS WITHIN FEET OF WORK AREAROADWORKAHEADW20-1 ROADWORKAHEADW20-11050MFP24002985
WORK
A
R
E
A
DETOURM9-4RDET
O
U
R
M4-9LProject Address:PagePSEPUGETSOUNDENERGYDesigner:Job #REVFlaviana Nunes425-424-7386flaviana.rodriguesnunes@pse.com2 OF 3520 SW Sunset Blvd, Renton0 51495504906/05/2024TEMPORARY TRAFFIC CONTROL PLANDETOUR MAP FOR CLOSURE ON STEVENS AVE SWPuget Sound EnergyTraffic Control Supervisor:Flaviana R. NunesCard No. 013414Card Exp. 11/2026flaviana.rodriguesnunes@pse.com(425)424-7386NMFP24002985
#520
P01
P02
P03
STEVENS AVE SW18
18
BUS
STOP
BUS
STOP
SW SUN
S
E
T
B
L
V
D
SW SUNSET BLVD STEVENS AVE SWSW
3
R
D
P
L
11
11 STEVENS AVE SW11
11
101013 11 12 11111211111111121111111113111111111111RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE FROMTOTOW AWAY AREAPHONE 684-5444NAME OF FIRM XXX-XXX-XXXXNO PARKINGPLACE SIGNS BOTH
SIDES OF WORK AREA
STOP
STOP
STOP W20-1ROADWORKAHEADW20-4ONE LANEROADAHEAD100'≥100'≥100'≥W20-7AW20-
1ROADWORKAHEAD BEPREPAREDTOSTOPW3-4
100'≥
100'≥
100'≥W20-7AW20-1RO
A
D
W
O
R
K
AH
E
A
D W20-4ON
E
L
A
N
E
RO
A
D
AH
E
A
D100'≥100'≥100'≥W20-7AW20-1ROADWORKAHEADBEPREPAREDTOSTOPW3-4350'≥
350'≥
350'≥
W20-7A
W20-1ROADWORKAHEAD BEPREPAREDTOSTOPW3-4
350'≥350'≥350'≥W20-7AN
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Project Address:
Page
PSE PUGET
SOUND
ENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
3 OF 3520 SW Sunset Blvd, Renton
0
514955049
06/05/2024
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flagges shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
FLAGGER
STOP
POLE
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Flaviana R. Nunes
Card No. 013414
Card Exp. 11/2026
flaviana.rodriguesnunes@pse.com
(425)424-7386X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-11050
MFP24002985
357
380
400
440
361
523
520
524
371
532
438
525
SW SUNS
E
T
B
L
V
DSTEVENS AVE SWSW SUNSET BLVD
STEVENS AVE SWDWY #6 CUBEAR
17
65'
EOP
100'
ROW
317724-165626
317747-165598
317748-165632
317748-165645
50 KVA 120/240V (B)
317764-165650
37.5 kVA 120/240V (B)
T92644 (25T)
317736-165648
317735-165648#2 ACSRCREW TO SWING
OH SVC WIRE TO
NEW METER
LOCATION
604
510
TREE REMOVAL
REQUIRED
317766-165637
15 kVA 120/240V (B)EAR17DEEP SET POLE
SITE PLAN
POWER GENERAL NOTES - RESIDENTIAL PROJECT
N
Vicinity Map
47.4782, -122.2247
Owner / Developer Contact Info
officeATTN:
DOUGLAS DO
520 SW SUNSET BLVD
RENTON, WA 98057
ALLYSSA MONTAGUE 425-309-2407
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
EAR-17
11/23
187.00 128.00 205.00
0.00 1.89 0.00
187.00 129.89 205.00
Service
OH Misc
Xfmr Transfer
Pole & Wire Removal
Superior
ORDER#NOTIF#
PWR
PROJECT PHASE
593258515514962230
593258514
583076923
108156349
CABLE TV
PHONE
GAS
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
10.
7.
6.
5.
4.
3.
2.
1.All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Inclement weather conditions may cause delays in construction times and dates.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
8.
9.
SCALE: 1" = 50'101174815THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
101174815514955049
CIRCUIT FEET ADDED: 0'
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
1580 SQ. FT.
200 AMPS
ELECTRIC
12.9 KW
80A
2.8 %
3.0 %
00 1"2"
00 50'100'
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
T. CONTRERAS 206-637-3648 5/3/24
H. DAY 253-243-5816 5/3/24
H. DAY 253-243-5816 5/3/24
NOT REQUIRED RENTON
DOUGLAS DO
OH L/E, OH SEC WRECKOUT, B/O POLE, POLE REPLACE & MOD SERVICE
520 SW SUNSET BLVD, RENTON, WA, 98057
N/A N/A
N/A 101174815
AS SHOWN 1 OF 1
KING N/A N/A CSPSKEPM
SW 18-23N-05E N/A N/A
2305E071 2305E076 2305E071 EAR-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:TONY CONTRERAS
206-637-3648
TONY.CONTRERAS@PSE.COM
JOB SITE
JOB SITE
SITE SPECIFIC NOTES
AT P01: 317748-165632
-EXISTING 40' FOREIGN OWNED SERVICE POLE TO REMAIN.
AT P02: 317748-165645 (REPLACE)
-TOP EXISTING POLE 2017 35' CL-2 POLE AT COMMS LEVEL
-REMOVE ALL PSE EQUIPMENT
-INSTALL (1) 50' CL-3 DISTRIBUTION POLE W/ GROUNDS AS STAKED (DEEP SET) 6010.1000 (PD503)
-INSTALL 1Ø SINGLE PHASE DEADEND FRAMING PER STD 6031.1040 (DE2115)
-INSTALL (1) STIRRUP & HOT CLAMP, TAP B PHASE (MID: 2254000 & 2153100)
-INSTALL (1) 50KVA 120/240V OH XFMR W/LB C/O (FUSE @ 15T) 6025.1000 (TRFRXF)
-INSTALL (2) 4" RIGID CLEVIS, NEUTRAL IN COMMON POSITION PER STD 6015.1000 (INDNRC)
-TRANSFER EXISTING SERVICES TO NEW OH TRF
-INSTALL GRID NUMBER
-POLE STUB TO BE REMOVED ONCE COMMS ARE TRANSFERRED
AT P03: 317764-165650 (REPLACE)
-TOP EXISTING B/O POLE 1987 40' CL-3 POLE AT COMMS LEVEL
-REMOVE ALL PSE EQUIPMENT
-INSTALL (1) 45' CL-3 DISTRIBUTION POLE W/ GROUNDS AS STAKED 6010.1000 (PD453)
-INSTALL 1Ø SINGLE PHASE DOUBLE DEADEND FRAMING PER STD 6031.1043 (DDE2115)
-TRANSFER (1) 12KV 200 AMP OH/UG TERMINATION AND OH FUSE TO NEW POLE
-INSTALL (1) STIRRUP & HOT CLAMP, TAP B PHASE (MID: 2254000 & 2153100)
-TRANSFER EXISTING 37.5KVA 120/240V XFMR TO NEW POLE
-INSTALL (2) 4" RIGID CLEVIS, NEUTRAL IN COMMON POSITION PER STD 6015.1000 (INDNRC)
-TRANSFER (4) 3" SECONDARY RISERS ON NEW STANDOFF BRACKETS TO NEW POLE
-TRANSFER (1) 2" PRIMARY RISER ON NEW STANDOFF BRACKETS TO NEW POLE
-TRANSFER EXISTING SERVICES TO NEW OH TRF
-INSTALL GRID NUMBER
-POLE STUB TO BE REMOVED ONCE COMMS ARE TRANSFERRED
M01 AT "520": NEW METER BASE
-INSTALL 200A METER
M02 AT "520": EXISTING METER BASE
-REMOVE EXISTING METER
SITE SPECIFIC NOTES
-SEE SITE PLAN AND TABLES FOR NEW INSTALLS AND REMOVALS
3-13
2X3-3
2-129
3-10
WIRE STRINGING
PRIMARY & SECONDARY
Location
Usage Wire Size & Type
Quantity
of wires
Length
(per wire)TotalFromTo
P03 P02 PRI #2 ACSR 1 160'
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
Wk
Loc
Pole Data Pole
TEL TV FIBER TRAN RMVD ID NUMBER
Grid #Length Class Year TOPPED RMVD
P02 317764-165650 35'2 2017
P03 317748-165645 40'3 1987
POLE TABLE (NEW)
Work
Location
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P02 317764-165650 45'CL-3
P03 317748-165645 45'CL-3
SECONDARY CABLE REMOVAL TABLE
Work
Location Wire Size Quantity
Length
(per
conductor)
Remarks
From To
P03 P02 1/0 OH TPX 1 160'
MAST HEIGHT BELOW 26"
METER SURFACE MOUNTED, U-BOLTS SECURE MAST
SERVICE BRACKET
WEATHERHEAD
FLASHING
18" MIN
18" MIN
24" MAX *FLASHING IN COURSES
OF SHINGLES
MINIMUM 2" x 6" INSTALLED
SOLIDLY BETWEEN RAFTERS
OR STUDS WITH HOLE
BORED FOR SNUG FIT
2" x 6" INSTALLED
SOLIDLY BETWEEN
RAFTERS AND AGAINST
ROOF SHEATHING
RIGID STEEL
CONDUIT
STRUCTURAL
FRAMING
AND FINISH
MATERIALS
STUD
GROUND
* ADDITIONAL SUPPORT GUYS REQUIRED FOR ATTACHMENTS GREATER
THAN 24" ABOVE ROOFLINE OR IF SERVICE LINE EXCEEDS 100' IN LENGTH
MAST HEIGHT BELOW 26"
METER SURFACE MOUNTED, GALVANIZED LAG BOLTS SECURE MAST
SERVICE BRACKET
WEATHERHEAD
FLASHING
FRONT VIEW
GALVANIZED LAG-BOLT
INTO FRAMING MEMBER
HEAVY-WALL
STRUT-TYPE
CHANNEL HEAVY-WALL
STRUT-TYPE
CHANNEL
18" MIN
24" MAX *
SERVICE DROP
DETAIL
BLOCKING BETWEEN
MAST AND BUILDING
5/16" U-BOLTS
2" x 6" BACKING
SHIM METER
BASE/SOCKET
AND FASTEN WITH
SCREWS
FLUSH
METER
SOCKET
GROUND
RIGID STEEL
STRUCTURAL
FRAMING AND
FINISH MATERIALS
24" MAX *
SERVICE DROP
SERVICE BRACKET
FLASHING
MAST HEIGHT BELOW 26"
METER FLUSH MOUNTED
SERVICE DROP WEATHERHEAD
MINIMUM 2' x 6" BETWEEN
RAFTERS WITH HOLE
BORED FOR SNUG FIT
RIGID STEEL CONDUIT
UN-GUYED SERVICE MAST DETAIL
SCALE: NONE
Installed at site:
Grid Number:
kVA Rating:
TRANSFORMER INSTALLATION (OH)
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
Foreman to redline the following information
50kVA 120/240v
6211350
P02
317748-165645
UTILITY POLE EROSION CONTROL DETAIL
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
Not to scale Drainage ditches or Dry vegetated sites
SERVICE LINE
(UTILITY OWNED)
SERVICE MAST
CONNECTION POINT
24'
16-1/2'
12'13'
STATE HIGHWAYS STREETS, ALLEYS, COUNTY ROADS,
DRIVEWAYS, AND PARKING AREAS
RESIDENTIAL PROPERTY
OVERHEAD SERVICE CLEARANCE DETAIL
SCALE: NONE
TOP VIEW 18" MIN
3' MIN WORKING
SPACE
18" MIN
3' MIN 4' MIN
6' MAX
5' PREFERRED
6" MIN
6' MAX
3' MIN
3' MIN
Neare
s
t
S
i
d
e
W
a
l
l
or Ob
s
t
r
u
c
t
i
o
n
An
y
O
b
s
t
r
u
c
t
i
o
n
Ab
o
v
e
M
e
t
e
r
Me
t
e
r
E
n
c
l
o
s
u
r
e
Working SpaceMETER CLEARANCES
SCALE: NONE
CUSTOMER DEVELOPMENT NOTES:
A PRE CONSTRUCTION MEETING IS REQUIRED WITH YOUR PROJECT MANAGER PRIOR TO STARTING ANY SITE WORK.
CUSTOMER IS RESPONSIBLE FOR ALL TRENCHING, SELECT BACKFILL, COMPACTION & RESTORATION PER
PUGET SOUND ENERGY STANDARDS & LOCAL MUNICIPALITY.
CUSTOMER IS RESPONSIBLE FOR THE FOLLOWING:
JOB SITE READINESS.
-JOB SITE NEEDS TO BE 100% READY FOR INSPECTION 5 BUSINESS DAYS PRIOR TO
CONSTRUCTION DATE.
-ALL WORK IN RIGHT OF WAY MUST BE COORDINATED WITH PROJECT MANAGER AND LOCAL
MUNICIPALITY.
-ALL TRENCH, AND LOCAL ELECTRICAL MUNICIPALITIES AKA "L&I, CITY", INSPECTIONS MUST BE COMPLETED 5
BUSINESS DAYS PRIOR TO SCHEDULED CONSTRUCTION DATE.
-IF A SECOND INSPECTION IS REQUIRED, ADDITIONAL FEE'S WILL BE APPLIED.
-IF A PRE-CON IS REQUIRED BY THE CITY, COUNTY OR W.S. DOT A PSE PROJECT MANAGER WILL SET-UP AND
SCHEDULE A MEETING WITH THE MUNICIPALITY BEFORE ANY EXCAVATION OR INSTALLATION BEGINS.
3-11
New pole at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER TRANSFER
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P03
317764-165650
37.5kVA
2-129
Field Face
Quadrant
Road Face
Quadrant
Climbing
Space
5" Min
CLDirection of Vehicular TrafficC
LTOP VIEW
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit
CONDUIT RISER PLACEMENT DETAIL (P03)
SCALE: NONE
4'x4' Work Pit
T. Van Santford 253-318-6897 08/07/2024
RESTORATION PER CITY OF RENTON STANDARDS
MFP24002985