HomeMy WebLinkAbout2024-10-10 Brotherton Lift Station Pump Test ReportBrotherton CadillacStormwater Lift Station Pump Test Report10/10/2024Stage Float DescriptionFloat ElevationDesign Flowrate* (CFS)Design Flowrate (GPM)Tested Flowrate** (CFS)Tested Flowrate (GPM)1 Lead Pump On Min Power 14.26 0.28 126 0.31 1402 Lead Pump On Max Power 15.76 0.39 175 0.47 2113Lag Pump On Min Power16.860.602690.64287* DESIGN FLOWRATES PER APPROVED TIRTIR Pg. 129TIR Pg. 135TIR Pg. 141** TESTED FLOWRATES AS REPORTED BY MCKEE ENTERPRISES/HD FOWLER
Note these flow rates were done 10/9/24.
Pump (1) with minimum power 140gpm.Pump (1) max power 211gpm.Pump (2) minimum power 140gpm.Pump (2) max power 211gpmIn lag function, with (1) pump max and (1) pump mini mum the station achieved 287gpm.