LEGEND:
WDF
CLF
0
FOUND MONUMENT AS NOTED
FOUND CORNER MONUMENT AS NOTED
PROPERTY LINE
PROPERTY CORNER
ROAD SIGNAGE
POWER JUNCTION BOX, SIZE VARIES
CABLE JUNCTION BOX, SIZE VARIES
TELEPHONE JUNCTION BOX, SIZE VARIES
LIGHT POLE WITH ARM
WATER METER
WATER VALVE
FIRE HYDRANT
STORM DRAIN CATCH BASIN
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
TELEPHONE MANHOLE
WOOD FENCE
CHAINLINK FENCE
DECIDUOUS TREE
EVERGREEN TREE
SANITARY SEWER LINE
STORM LINE
P UNDERGROUND POWER
- W UNDERGROUND WA TER
UNDERGROUND GAS
UNDERGROUND TELEPHONE
UNDERGROUND CABLE
EDGE OF PA VEMEN T
FENCE
CONCRETE
ROOF AND FOOTING DRAIN NOTE:
ALL ROOF DOWNSPOUTS AND FOOTING DRAINS WILL BE CONNECTED TO CATCH
BASIN 1 VIA THE PROPOSED STORM STUB SHOWN ON THE PLANS.
EXISTING SANITARY SEWER SERVICE NOTE:
CONDITION OF EXISTING STUB AND SIDE SEWER LATERAL TO BE EVALUATED
PRIOR TO CONSTRUCTION AND IF DETERMINED TO BE DEFICIENT WILL REQUIRE
REPLACEMENT BACK TO THE MAN.
WATER MAIN CONSTRUCTION NOTES:
1. EXISTING WATER SERVICES ALONG WELLS AVENUE S BETWEEN S 2ND STREET
AND THE PROJECT SITE SERVED BY THE EXISTING 6" WATER MAIN WILL BE
TRANSFERRED TO THE NEW 12" WATER MAIN UPON COMPLETION. THE NEW
12" WATER MAIN MUST BE INSTALLED, TESTED, AND ACCEPTED PRIOR TO
TRANSFER OF SERVICES.
2. CITY CREWS WILL COMPLETE THE TRANSFER OF SERVICES INCLUDING
INSTALLATION OF NEW SERVICE LINES, METER SETTER/BOXES, AND
RESTORATION OF STREET CROSSINGS ASSOCIATED WITH THE NEW SERVICE
LINES. CONTRACTOR IS RESPONSIBLE FOR STREET RESTORATION ASSOCIATED
WITH THE WATER MAIN CONSTRUCTION.
J. SERVICES WILL BE TRANSFERRED FOR THE FOLLOWING PARCELS: 7231501090
(126 WELLS AVE S), 7231502020 (123 WELLS AVE S), 0007200085 (122
WELLS AVE S), 0007200091 (118 WELLS AVE S).
4. CITY CREWS WILL ABANDON THE EXISTING 6" WATER MAIN FOLLOWING THE
TRANSFER OF SERVICES TO THE NEW 12" WATER MAIN.
5. ALL FITTINGS AND VALVES WITH MECHANICAL JOINT (MJ) END(S) SHALL HAVE
A WEDGE -TYPE RETAINER GLAND EQUAL TO MEGALUG SERIES 1100.
6. CONCRETE THRUST BLOCKS REQUIRED ON ALL FITTINGS PER COR STANDARD
PLANS 330.2 AND 330.3.
7 CONTRACTOR TO POTHOLE ALL UTILITY CROSSINGS TO IDENTIFY CONFLICTS
WITH NEW WATER MAIN PRIOR TO CONSTRUCTION. CONTRACTOR TO PROMPTLY
NOTIFY CITY OF ANY CONFLICTS.
8. CONTRACTOR TO POTHOLE EXISTING SIDE SEWERS CROSSING NEW WATER
MAIN PRIOR TO BEGINNING CONSTRUCTION OF WATER MAIN. DEPTH AND
ELEVATION AT THE TOP OF SIDE SEWER AND AVAILABLE CLEARANCE TO NEW
WATER MAIN SHALL BE PROVIDED TO CITY. IF AVAILABLE CLEARANCE IS LESS
THAN 18 INCHES BUT GREATER THAN 6 INCHES, WATER MAIN SHALL BE
INSTALLED WITH CDF PIPE ENCASEMENT EXTENDING 10' ON BOTH SIDES OF
CROSSING. IF AVAILABLE CLEARANCE TO NEW WATER MAIN IS LESS THAN 6
INCHES, SIDE SEWER SHALL BE REPLACED TO PROVIDE 18 INCHES OF
CLEARANCE FROM NEW WATER MAIN IN ACCORDANCE WITH CITY OF RENTON
STANDARD PLAN 406.1 IF SIDE SEWER REPLACEMENT IS REQUIRED,
CONTRACTOR SHALL SUBMIT A DESIGN OF THE NEW SIDE SEWER TO THE CITY
FOR APPROVAL PRIOR TO CONSTRUCTION.
9. WITH 90' BEND EXISTING 6" LINE WILL BE DECOMMISSIONED. THRUST BLOCK
WILL LIKELY EXTEND INTO SIDEWALK AREA AND MAY REQUIRE REMOVAL OF
CURB/GUTTER/SIDEWALK FOR INSTALLATION. PROVIDE APPLICABLE NOTES
AND DETAILS ON HOW THIS AREA WILL BE CONSTRUCTED.
AS -BUILT
"l CERTIFY THAT THE INFORMATION SHOWN HEREON WHICH WAS
AS -BUILT BY D.R. STRONG, AND MAY INCLUDE LOCATIONS,
ELEVATIONS, DEPTHS, PIPE SIZES, AND AS -BUILT COMMENTS,
ACCURATELY REFLECTS EXIS77NG FIELD COND177ONS AS DETERMINED BY
ME OR UNDER MY DIRECT SUPERVISION ON THIS DATE: 912412025.
IN
Call 2 Working Days Before You Dig
811
Utilities Underground Location Center
(ID,MT,ND,OR,WA)
1r
►5
N W 1/4 SECTION 17, TOWNSHIP 23 N, RANGE 5 W,
BA SSA NO MUL fl ML y
I ':�'I
NEW 4" DDCV FIRE
SPRINKLER ASSEMBLY W
STANDPIPE OUTS/DE
CONNEC77ON PER STD.
COR PLAN 370.3
NEW 1.5" WATER SERVICE AND PLANTER (SEE DETAIL SHEET C13)
WA7ER METER W DCVi4 LIMITS OF HALF
BEHIND METER PER STREET GRIND AND
COR STD. DTL. 320.2 & 340.8 I OVERLAY (TYP.)
(SEE DETAIL SHEET C11) 11 LF 120 DI
I
' o I►
N8824 50 W 120.09'
A
---- - ---- --
CB 1, TYPE 1----- _---------�-
PROPOSED STA. 2+70.67, 19.05' L
p UNCOVERED MUL TI-FAMIL Y RIM 39.67
STRUCTURE 8" /E OUT 37.48 (E)
�O� _ -j BALCONY (TYP.) CB 3, TYPE 1
LOWER FF = 40.00' STA. 10+05.04, 0.00' R
"� , RIM 4a28
58 LF 6" PVC SEWER 6" /E /N 36.75 (W) 10+
STUB 0 2.00X MIN. SLOPE A 1
q� 3 /E OUT 39.82 (E)
GRADE COVERED R/ WAY a 3" IE OUT 39.76 (E)
2 PROPOSED YARD DRAIN *1/CH WILL
_ CONNECT TO 7HE EXIS77NG SEWER MAIN ° a
LOW POINT EL. 0 RIM = 39.75 ° .
°
a 6" PVC STORM STUB
°E�°
)OF LINE FOR OVERHANG N882452"W 120.10'
OVER DRIVEWAY ACCESS 15 LF TRENCH DRA/N TO
TO RESIDENCES COLLECT RUN-OFF FROM
UNCOVERED DRIVEWAY AREA
D.R. STRONG
CONSUL TING ENGINEERS
ENGINEERS PLANNERS SURVEYORS
620 - 7th AVENUE KIRKLAND, WA 98033
O 425 827 3063 F 425 827 2423
BE PROVIDED1 AT THIS CB TO EXIS77NG 6" PVC SANITARY SEWER
(SEE DETAIL SHEET C10)
STUB; CONTRACTOR TO VERIFY /E OF
EXISTING STUB AND ENGINEER TO VERIFY
SLOPE WILL MEET MIN/MUM STANDARDS
SSCO TYR
INSTALL 1' SERVICE LINE WITH
SINGLE /" IRRIGA77ON METER AND
DCVA ASSEMBLY BEHIND METER
(COR STD PLAN 320.1 & 340.8)
2.5' x 3' WATER
EASEMENT
EX/S77NG 29 LF 6"
PVC SEWER STUB
ALL
ON SI TE 1-12 STA'GAVAL
AS-BUIL TS SHOWN I
ON
SHEET C7
EASEMENT
--32 LF 8" D.l. ,
0 1.03% (P3)
12' PROPOSED
SIDEWALK Wlq T
i
2.75' R. 0. W.
DEDICA TION -(/I
W1I11ifI11
\f
i
i
i
I I
I i �
I I
o I I
o
� I I
N I I
I I
I
R I I
f7.8'
W.M.
STA. 3+01.04' 5.5' R
1-12 x6 TEE FLxFL
1-6" GATE VALVE (FLxM✓)
1-12" GATE VAL VE ( M_I)J)
1-12" ADAPTER (FLxM✓) W/
CONCRETE THRUST BLOCKING
1-12" PIPE SPOOL
1-12" POLYP/G STATION PER STD.
PLAN NO 300.7 SHACKLE TEE,
VALVE TO DEAD MAN BLOCK
(SEE SHEET C12)
(INSTALL DEADMAN BLOCK TO
RESTRAINT VALVE AND 7EE)
STA. 3+01.06' 17.95' R
CUT /N CONNEC77ON BY CITY FORCES TO
USE CUT /N 7EE W/ TWO VALVES PER
COR STD. PLAN 300.2 (SEE SHEET C11).
1-6 x6" 7EE (FLxFL) W/
CONCRETE 7HRUST BLOCKING
2-6" GATE VALVES (FLxM✓)
3-6" D/ SPOOL (LF AS REQ.)
3-6" SOLID SLEEVE (M✓)
(INSTALL DEAD MAN BLOCK AND END CAP
RON EXIS77NG 6- WA7E
ESTRAIN NEW 90 BEND) R MAIN TO
i
12 LF 6" D/ CL. 52
W SOLID SLEEVE
_STA. 2+90.44; 5.5' R
1-6 x12 7EE M✓xFL W1 CONCRETE BLOCK/N
1-6" GATE VALVE (FLxM✓)
1-DDCV FIRE SPRINKLER ASS'Y PER COR STD.
0+ 9.04 PLAN 350.3 AND 370.3
(SEE DETAIL SHEET C13)
\W RV/ /N TO BE
CONNECTED TO NEW 12" WATER MAIN
\ CB Z TYPE 1
(SADDLE EXIS77NG STORM MAIN,
STA. 2+70.61, 13.41' R
RIM 39.77
8" IE /N 37.15 (W)
EX. 12" IE /N 36.27 (S)
EX. 12 /E OUT 36.27 (N)
STA. 2+78.91. 5.50' R
1-6 z12" 7EE (M✓xFL) W/
CONCRETE BLOCKING
1-6" GATE VALVE (FLxMJ)
1-FIRE HYDRANT ASS'Y
PER COR S7D. PLAN
3f0.1, =2 AND 310.3
(SEE DETAIL SHEET C12)
TO BE CONNECTED TO
NEW 12" WATER MAIN
70 BE CONNECTED TO
NEW 12" WA7ER MAIN
I
I I
I I
i I
I I
SAWCUT PER COR STD,
DTL. 110.1
(SEE DETAIL SHEET C8)
I
I I '
I I
I I
I I
I I
I I
o i i EX. 6" WATER MAIN TO
o i I BE ABANDONED /N
PLACE
I �
i I
' � I
� I ,
� I
i I
I I
I I
i I
� I
I I
I I
� I 7 LF 12" D/ CL. 52
I I
T. 0+56. 7' 5 5' R
1-12 45' BEND (M✓) W/ I I 1. 0+5 .18 1 ,
CONCRETE BLOCKING I 1-12" 45- BEND (M✓) W/
1 CONCRETE BLOCKING
:ONN C1TON TO X. 12" CATER MAIN BY
CITY FORCES PER COR S7D PLAN 300.4
1-12" SLEEVE (MJ) \I
1-D/ SPOOL (LF AS REQ)
INSTALL 12" POLYP/GG/NG STA77ON AT
END OF NEW 12" WATER MAIN PER COR LJ
S7D PLAN 300.7
REMOVE EX. 6" GATF VALVE AND
CAP M✓ EX. 6 WATER MA/N
BY
CITY FORCES)
3 X F/R HYDRANT
s
N
W
I NORTH
GRAPHIC SCALE
I`� ' 20' 40'
1 INCH = 20 FT.
2 CITY COMMENTS 7.3.24 YLP 08.23.24 YLP SURVEYED: SCALE:
DJC VERTICAL: NAVD 1988
3 CITY COMMENTS 9.10.24 YLP 09.19.24 YAP DESIGNED: AS NOTED HORIZONTAL: NAD 1983/1991
4 STORM REVISION DUE TO DUCT BANK CONFLICT YLP 12.13.24 YLP YLP
5 UTILITY REVISION YLP 01.10.25 YLP DRAWN:
GLI3 ONE INCH DATUM
6 UTILITY REVISION YLP 01.24.25 YLP CHECKED: Y� .
AT FULL SCALE
IF NOT ONE INCH
APPROVED: SCALE ACCORDINGLY
N 0. REVISION BY DATE AP P R
YLP
A00%k
C TY OF
RENTON
P"R
Planning/Building/Public Works Dept.
i
DRIVEWAY GRADING DETAIL PER COR STD. DTL. 104.3
1' = 10"
UTILITY CROSSING TABLE
CROSSING NO.
E.G.
UTILITY
BOTTOM OF PIPE
TOP OF PIPE
CLEARANCE (FT)
0
39.92
12" SD
3718
1.51
12" WA
35.67
0
39.97
8" SD
37.27
2.95
8" WA
34.32
0
39.91
6" WA
35.86
1.57
8" SS
34.29
®
39.84
6" WA
35.79
1.54
"SS
34.25
0
39.49
12" SD
36.31
1.50
6" WA
34.81
UTILITY CROSSING NOTES:
1. ALL LOCATIONS OF POWER, GAS, AND OTHER DRY UTILITIES SHOWN IN
PROFILE ARE APPROXIMATE. 3' OF COVER FROM THE EXISTING GRADE
WAS ASSUMED FOR ALL OF THE EXISTING DRY UTILITIES. CONTRACTOR
TO POTHOLE ALL EXISTING UTILITIES TO CONFIRM THERE ARE NO
CONFLICTS. IF ANY CONFLICTS WITH THE PROPOSED WATER MAIN AND
STORM LINE ARE FOUND, EXISTING SERVICES WILL BE RELOCATED SO
AS TO PROVIDE THE MINIMUM 1. OF VERTICAL SEPARATION.
2. REQUIRED MINIMUM VERTICAL SEPARATION FOR ALL UTILITES CAN BE
FOUND BELOW.•
S-417601
W-417601
R-417605
UTILI TY CROSSING
ALLOWABLE CLEARANCE
UTILITY
VERTICAL CLEARANCE
NATURAL GAS
12 INCHES
ELECTRIC
12 INCHES
TELECOMMUNICATIONS
12 INCHES
FIBER OPTICS
12 INCHES
SANITARY SEWER
18 INCHES
STORM DRAINAGE
18 INCHES
RECLAIMED WATER
18 INCHES
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DATE:
BASSANO MULTI -FAMILY 11.20.20
UTILITY, ROAD, AND GRADING PLAN PAGE: OOK:
PAGE:
117 WELLS AVENUE S C5
RENTON, WASHINGTON 98057 SHEET: OF:
DRS PROJECT NO. 20070