EXISTING
WATER MAIN
TESTING CONNECTION
POLYPIG STATION PER STD PLAN 300.7
(1) VERTICAL CROSS (MJxFL)
(1) BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG
(1) BLIND FLANGE ON BOTTOM
(1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY
WITH TEMPORARY THRUST BLOCKING
8'+
a a o
;7//// �� oOo NEW DI WATER MAIN
a
TEMPORARY BLOCKING
® CONNECTION TO EXISTING MAIN (BY CITY FORCES)
(1) TEE (FLxFL)
(2) DI SPOOLS
(2) LONG BODY DI SLEEVES (MJ) OR COUPLING ADAPTERS (ROMAC 501 OR EQUAL)
(3) GATE VALVES (FLxMJ)
(1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY
WITH CONCRETE THRUST BLOCKING PER STD PLAN 330.1
FINAL CONNECTION
UPON COMPLETION OF POLYPIGGING, HYDROSTATIC TESTING,
AND DISINFECTION, REMOVE TEMPORARY THRUST BLOCKING
AND TEMPORARY BLOW -OFF ASSEMBLIES
FINAL CONNECTION (BY CITY FORCES)
(2) DI SPOOLS
(1) LONG BODY DI SLEEVE (MJ)
1 NEW DI WATER MAIN
NOTES:
1. ALL CONNECTIONS TO EXISTING WATER MAINS WILL BE CONDUCTED BY CITY FORCES AS
SPECIFIED IN SECTION 5-14.2 OF THE CITY OF RENTON WATER UTILITY CONSTRUCTION
STANDARDS
2. LONG BODY DI SLEEVE FOR CONNECTION FROM DI TO DI PIPE AND FROM DI TO CI PIPE WITH
SAME OUTSIDE DIAMETER
3. COUPLING ADAPTORS FOR CONNECTION FROM DI TO CI PIPE WITH DIFFERENT O.D. AND
FROM DI TO AC OR TO STEEL PIPE
PUBLIC WORKS CONNECTION TO WATER MAIN
DEPARTMENT CUT -IN TEE AND THREE VALVES
VALVE BOX AND LID
SECTION A -A
C
8" TO 12"
MATERIALS
STD. PLAN - 300.3
6/28/2023
Macon Pastu[ha DATE
Publk Works Atlministnt«
VALVE OPERATING NUT EXTENSION
7 2" SQUARE
OPERATING NUT
MAIN 4%4' DIAMETER
Ys" MIN THICKNESS
1" DIAMETER STEEL,
LENGTH AS REQUIRED
MIN THICKNESS
7 2Y4' INSIDE MEASUREMENT
21/4" DEPTH
NOTES:
1. EXTENSIONS ARE REQUIRED WHEN VALVE NUT IS MORE THAN 3'
BELOW FINISHED GRADE. EXTENSIONS ARE TO BE A MINIMUM
OF V LONG. ONLY ONE EXTENSION TO BE USED PER VALVE.
2. ALL EXTENSIONS ARE TO BE MADE OF STEEL, SIZED AS NOTED,
WITH ANTICORROSION COATING CONFORMING TO AWWA C210
VALVE MARKER POST
/O
TWO-PIECE VALVE BOX WITH REGULAR
BASE SECTION TO FIT AND STANDARD 8"
34"
OA
VALVE BOX
TOP SECTION, OLYMPIC FOUNDRY INC
940 OR RICH #045 (NON -LOCKING)
3"
MIN
E
COVER TO MATCH VALVE BOX
B
O
VALVE BOX LID
MANUFACTURER, TO READ "WATER",
62"
WITH EARS IN DIRECTION OF WATER
>
\\
MAIN
\
�j
8" THICK HMA FOR VALVE IN PAVED
24'
\
OC
HMA COLLAR
AREA OR 3'x3'x6" CONCRETE PAD IN
'
UNPAVED AREA
1`
O
OPERATING
SEE DETAIL, THIS SHEET
NUT EXTENSION
WHITE MARKER POST WITH ANCHOR
E
O
MARKER POST
BARB AND BLUE LABEL TO READ
NOTES:
"WATER", CARSONITE UTILITY MARKER
CRM3 066-08 OR EQUAL
1. VALVE MARKER POST TO BE USED FOR ALL MAINLINE VALVES
OUTSIDE PAVED AREAS.
2. DISTANCE TO VALVE SHALL BE NEATLY STENCILED
ON THE POST
WITH 2" NUMERALS.
VALVE BOX, STD. PLAN - 330.7
PUBLIC WORKS APPROVED:
DEPARTMENT OPERATING NUT EXTENSION,( 6/28/2023
AND MARKER POST Martin Pa uda
pbrw•rka Aamim"mt« DATE
TOPOGRAPHY, BOUNDARY, AND UTILITIES STATEMENT
FURR ENGINEERING SERVICES PLLC. DOES NOT WARRANT THE TOPOGRAPHY,
BOUNDARY, AND/OR EXISTING UTILITIES SHOWN ON THESE PLANS. IT IS THE
CONTRACTORS' RESPONSIBILITY TO HAVE ALL EXISTING IMPROVEMENTS FIELD
VERIFIED PRIOR TO CONSTRUCTION. ANY SUBSURFACE EXPLORATION OF EXISTING
UNDERGROUND UTILITIES (POWER, WATER, SEWER, TELECOM, ETC.) SHALL BE
PERFORMED BY THE CONTRACTOR. DISCREPANCIES BETWEEN WHAT IS SHOWN ON THE
PLANS AND LOCATED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF
FURR ENGINEERING SERVICES PLLC. PRIOR TO CONSTRUCTION ACTIVITIES.
Know what's below.
Call before you dig.
NE 1 /4 OF THE SW 1 /4 OF SEC. 20, T. 23N., R. 05 E, W.M.
GRANT PLACE TOWNHOMES
IV V 1 GJ:
1.
FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF SAFETY YELLOW DTM ACRYLIC GLOSS OR ENAMEL PAINT.
2.
PUMPER NOZZLE TO FACE ROADWAY OR AS DIRECTED BY RRFA.
3.
A MINIMUM 3' RADIUS UNOBSTRUCTED
WORKING AREA SHALL BE PROVIDED AROUND THE OUTSIDE OF THE HYDRANT.
MATERIALS
COMPRESSION TYPE HYDRANT (SEE APPROVED MATERIALS LIST) WITH 6" MJ INLET WITH LUGS, 51/4" MVO,
OA
HYDRANT
1 Y4" PENTAGON OPERATING NUT, TWO (2) 2 Y2" NST HOSE NOZZLES, AND 4.875" SST PUMPER NOZZLE
EQUIPPED WITH S" STORZ ADAPTER AND 1/8" STAINLESS STEEL CABLE, WITH EXTENSION IF NECESSARY.
OB
TEE
MAIN LINE TEE WITH 6" FLANGE SIDE OUTLET
OC
VALVE
6" GATE VALVE (FLxMJ)
OD
VALVE BOX
VALVE BOX AND LID PER STD PLAN 330.7
OE
PIPE
CLASS 52 DI, LENGTH TO FIT
OF
JOINT RESTRAINT
MECHANICAL JOINT RESTRAINT WITH CONCRETE BLOCKING OR (2) 3/4" CORTEN STEEL TIE RODS
OG
GRAVEL
1 %4" WASHED DRAIN ROCK, MINIMUM 1' ABOVE BOOT FLANGE WITH 8-MIL POLYETHYLENE SHEETING
AROUND TOP AND SIDES OF GRAVEL
O
CONCRETE BLOCK
MINIMUM 16"x8"x4" CONCRETE BLOCKS UNDER FIRE HYDRANT AND GATE VALVE
OI
BLOCKING
CONCRETE BLOCKING PER STD PLAN 330.1
J0
SHEAR BLOCK
4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT, SEE STANDARD DETAIL 310.2
O
PAVEMENT MARKER
BLUE REFLECTIVE PAVEMENT MARKER PER STD PLAN 310.3
• STD. PLAN 310.1
t .} PUBLIC WORKS FIRE HYDRANT ASSEMBLY APPROVED:
DEPARTMENT
6/28/202L]36/28/2023
ryuhli<nWosks`Admimstrrtor DATE
PLAN
---
a
a
° L_-- _J H
� — J
A D
Pa d A<
%/ J da
/ G G A
PROFILE
MATERIALS
OA TEE MAIN LINE TEE WITH 4" SIDE OUTLET (MJxFL) WITH PLUG (MJ)
OB GATE VALVE 4" GATE VALVE WITH 2" SQUARE OPERATING NUT AND VALVE OPERATING NUT EXTENSION AS REQUIRED
PER STD PLAN 330.1
OC VALVE BOX AND LID VALVE BOX AND LID PER STD PLAN 330.8
OD FLANGE 4"x2" TAPPED FLANGE (FLxFIPT)
OE PIPE 2" BRASS OR BRONZE NIPPLE, LENGTH TO FIT
OF BEND 2" 90- BRASS BEND (FIPT x PACK JOINT), FORD C14-77-Q-NL OR EQUAL
OG ADAPTER 2"x2 Y2" BRASS ADAPTER (FIPTxMNST)
OH CAP 2 %i' CAP (FNST) WITH GASKET, NOT VENTED
OI METER BOX AND LID METER BOX, ARMORCAST A6001640PCX18, WITH METER BOX LID, ARMORCAST A6001947RCI-H7, TO READ
"RENTON WATER", EXPANSION JOINTS MUST BE INSTALLED 12" MINIMUM ON BOTH SIDES OF METER BOX
J0 BLOCKING CONCRETE BLOCKING PER STD PLAN 330.1
STD. PLAN - 340.1
• PUBLIC WORKS 2 BLOW -OFF ASSEMBLY APPROVED:
DEPARTMENT (PERMANENT) L_1vtjL 6/28/2023
o "w.`'+m„.k..— DATE
8/23/2024
4
PER CITY COMMENTS
3
PER CITY COMMENTS
2
PER CITY COMMENTS
1
PER CITY COMMENTS
►Na
ilk A ON N •►
MAIN
FINISHED GRADE 9" TO 12"
n
a a24" TO 90"
LOOP DOWN TO CENTERLINE OF WATER MAIN
TO PROVIDE SLACK IN SERVICE LINE TO METER
.I
Z
J
IN UNIMPROVED ROW,
w INSTALL. METER BOX
w CITY PRIVATE
a. AT PROPERTY LINE WITH
ap
1" COPPER TAILPIECE
a
PIPING PIPING
SIDEWALK
r,..
12"
TO 30„
nri
MATERIALS
CORPORATION STOP
1" BALL CORPORATION STOP WITH BALL VALVE, AWWATAPERED THREAD (CC) INLET, QUICK JOINT OUTLET,.
FORD FB1000-4-Q-NL OR A.Y. MCDONALD 74701BQ
TUBING
1" TYPE "K" SOFT COPPERTUBING
1" SETTER, QUICK JOINT INLET AND OUTLET, PADLOCK WINGS ON INLET ANGLE BALL VALVE, SINGLE CHECK
METER SETTER
VALVE ON OUTLET, FORD VBH74 15W-44-44-Q-NL, A.Y. MCDONALD 721-415WCQQ 44, OR MUELLER
B-24701-6AN, INSTALL CENTERED AND SQUARED IN METER BOX, PROVIDE ADAPTERS FOR 5/8"0/4" METERS
WATER METER
AMI WATER METER WITH RADIO AND BATTERY UNIT, TO BE PROVIDED BY THE CITY
METER BOX
METER BOX, ARMORCAST A6001946PCX18, WITH METER BOX LID, ARMORCAST A6001969RCI-H7, TO READ
LJ
"RENTON WATER"
'F
COUPLER AND PLUG
COUPLER (PACK JOINT x PACK JOINT), FORD C4#-4#-Q-NL, WITH 1" GALVANIZED PLUG IF SERVICE LINE TO
PROPERTY IS TO BE INSTALLED IN THE FUTURE
G
GRAVEL
1%4"WASHED GRAVEL
PUBLIC WORKS
DEPARTMENT
1" WATER SERVICE
STD. PLAN - 320.1
DATE
NOTES:=�
1.
AIR AND VACUUM RELEASE VALVE ASSEMBLY MUST BE INSTALLED AT THE HIGHEST POINT IN THE WATER MAIN. IF THE HIGH POINT FALLS
IN A LOCATION WHERE THE ASSEMBLY CANNOT BE INSTALLED, PROVIDE ADDITIONAL DEPTH OF MAIN TO CREATE THE HIGH POINT AT A
LOCATION WHERE THE ASSEMBLY CAN BE INSTALLED.
2.
LOCATE METER BOX OUTSIDE OF TRAFFIC AREAS, BEHIND THE CURB.
MATERIALS
O
CORPORATION STOP
1" BALLCORP WITH AWWA TAPERED (CC) INLETAND COPPER THREAD OUTLET, FORD FB600-4-NL OR EQUAL
OB
SWING JOINT
1" BRASS SWING JOINT
OC
PIPE
1" TYPE "K" SOFT COPPER TUBING
OD
COUPLING
1" STRAIGHT COUPLING (MIPT x PACK JOINT), FORD C84-44, MUELLER H15428, OR EQUAL
OE
GATE VALVE
1" BRONZE GATE VALVE, THREADED, RED -WHITE VALVE NO. 280, OHIO BRASS NO. 2500, OR EQUAL
OF
UNION
1" BRASS UNION
OG
PIPE
1" BRASS NIPPLE
OH
AIR &VACUUM
RELEASE VALVE
1" AIR AND VACUUM RELEASE VALVE ASSEMBLY, APCO NO. 143-C, VAL-MATIC NO. 201-C, OR CRISPIN UL10,
OR EQUAL
ASSEMBLY
OI
PIPE
1" GALVANIZED IRON NIPPLE
JC
BEND
1" 90a GALVANIZED IRON BEND
OK
UNION
1" GALVANIZED IRON UNION
OL
PIPE
1" GALVANIZED IRON PIPE, LENGTH TO FIT
(1) 2"X1" BELL REDUCER
OM
SWING JOINT
(2) 2" 90• STREET ELLS
ON
PIPE
2" GALVANIZED IRON PIPE, LENGTH TO FIT, FIELD LOCATE
OO
BEND
2" 180• RETURN BEND, OPEN PATTERN
OP
STRAINER
2" BEEHIVE STRAINER
®
METER BOX AND LID
METER BOX, ARMORCASTA6001946PCX18, WITH METER BOX LID, ARMORCAST A6001969RCI-H7, TO READ
"RENTON WATER"
OR
GRAVEL
1 V4" WASHED GRAVEL
STD. PLAN - 340.3
PUBLIC WORKS
1 AIR AND VACUUM RELEASE
APPROVED:
DEPARTMENT
VALVE ASSEMBLY
6/28/2023
Martin Pa.wtna DATE
wamw«waemmkmat«
SURVEYED:
DAF
08/26/24
DESIGNED:
DAF
DAF
07/29/24
DAF
05/21 /24
DRAWN:
TJW, FEM
DAF
04/04/24
CHECKED:
DAF
BY
DATE
APPR
APPROVED:
SCALE:
1 "=30'
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL• NAVD 1988
HORIZONTAL- NAD 1983/1991
DATU M
w
z
J
Qr
I rr
LL- W
I DIRECTION OF FLOW
3„
DX 0 (MIN.)
6" MIN.
6"MIN.(TYP.) UNION (TYP.)
PLAN
3"MAX.
z 00 z
-Q 0
PO r'i
6"MIN.
TO CITY
METER STACKED METER SECTION\_6" MIN. FREE
BOXES DRAINING GRAVEL
NOTES:
1. ALL DOUBLE CHECK VALVE ASSEMBLIES (DCVA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW PREVENTION
ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASHINGTON
DEPARTMENT OF HEALTH.
2_ THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
OF THE INSTALLATION OF THE DCVA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE
DCVA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN,
3. THE DCVA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST
REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., A.TTN: WATER
UTILITYCROSS—CONNECTION CONTROL SPECIALIST, FAX NO. 425-430-7241,.
4. DCVA AND METER BOX SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER.
° PUBLIC WORKS �'4" TO 2" DOUBLE CHECK VALVE STD. PLAN — 340.8
` DEPARTMENT ASSEMBLY FOR IRRIGATION OR
,TOE RESIDENTIAL FIRE SPRINKLER MARCH 2O10
CITY OF
vR
RENTON
Planning/Building/Public Works Dept.
URR
0
O
C„)
N
An
u
r-r �
Vt
N
Q
J
SERVICES, PLLC
4715142nd PI. SW #B,
Edmonds, WA 98026
ph 206.890.8291
W-429003 Uj
IN COMPLIANCE WITH CITY OF RENTON STANDARDS O
2
WATER UTILITY DEVELOPMENT ENGINEERING z
ABDOUL GAFOUR 09/13/2024 NJanders, 09/16/2024
O
I—
W
U
Q
DATE: J
GRANT PLACE TOWNHOMES 11/21/23
1600 GRANT AVE S RENTON, WA 98055 PAGE, OK: z
PARCEL 2023059052 PAGE:
DRAWING NO:
20069 im
WATER DETAILS SHEET: OF:
C6.2 28 V