WETWELL EIGHT TERMINATION BOX
FLOATS AND LEVEL TRANSMITTER
TERMINATION BOX 1
PUMP NO. 1 TERMINATION
BOX
PROPOSED NAMEPLATE,
TYP.
TERMINATION BOX,
STAINLESS STEEL NEMA 4
ENCLOSURE, 12"H X 12"W X
8" D. PROVIDE MEANS FOR -
PAD LOCKING. SECURE TO
WALL WITH (4) STAINLESS
STEEL CMU ANCHORS.
NAMEPLATE SCHEDULE
TERMINATION
BOX TAG
NAMEPLATE SCHEDULE
NP1
TERMINATION BOX — WET WELL FLOATS AND LEVEL
TRANSMITTER
NP2
TERMINATION BOX — WET WELL LIGHT
NP3
TERMINATION BOX — PUMP NO. 1
NP4
TERMINATION BOX — PUMP NO. 2
NP5
TERMINATION BOX — PUMP NO. 3
NP6
TERMINATION BOX — PUMP NO. 4
PUMP NO. 4 TERMINATION
BOX
PUMP NO. 3 TERMINATION
BOX
PUMP NO. 2 TERMINATION
BOX
PROPOSED ELECTRICAL —/ "-r i "I!' "i'1fHiri'il'I!rlll�lll ���flf I Ill%i� Irlf r I i��fJ' �i nI I!���
BUILDING
1If
iI !III' jll�ili'�Ill(i (j'Ir i�''Ii,I Ill j1111
LEAVE MINIMAL SEPARATION BETWEEN EDGE OF BUILDING I�i II
AND TRENCHBOX COVER TO ALLOW PASSAGE OF ALL
TRENCH BOX CABLES. MAXIMUM SEPARATION OF 6".
TERMINATION BOX OBLIQUE DETAIL
CADWELD TYPE TA.
CADWELD CABLE TO
CABLE TEE CONNECTION.
#1/0 COPPER
CONDUCTOR
GROUND TEE DETAIL
NOT TO SCALE
Al CADWELO TYPE GR
NOT TO SCALE
CADWELD TYPE RR. CADWELD
END CABLE TO UPP�"
CC
#11/0 COPPER CADWELD CABLE TO GROUND
_ CONDUCTOR ROD CONNECTION.
5/8" X 8' COPPER GROUND
ROD.
r
REBAR
PROPOSED CABLE
TRENCH SYSTEM
#1/0 COPPER
CONDUCTOR
GROUND REBAR DETAIL
NOT TO SCALE
CADWELD TYPE XA.
-ED CABLE TO CABLE
i CONNECTION.
Y1/0 COPPER CONDUCTOR (TYPICAL)
GROUND TEE DETAIL GROUND CROSS DETAIL
73
NOT TO SCALE NOT TO SCALE
0
:� ...
�� 'r rAB" -
AS
FEDND:
CALL 48 HOURS
BEFORE YOU DIG
33301 9th Avenue South, Suite 300
N
1-800-424-5555
Federal Way, Washington 98003-2600
teoor7zososz�
A ee ro'scrno.
N0.
J
206 431-2300 Fax: 206 431-2250
I ) I )
A.A 211.pa9
BOX, TYP. ` NPi
18' TIP. I U K t U
NP3
S-2
PROPOSED ELECTRICAL
BUILDING
PROPOSED CABLE
TRENCH SYSTEM
INSTALL WET WELL AND INLET
MANHOLE LIGHT SWITCHES
INSIDE TERMINATION BOX
TO PANEL "L"
LN-P-51 (INP6
"MCC" -=TO 'MCC"
TERMINATION BOX ELEVATION DETAIL
NOT TO SCALE
PROPOSED CONCRETE
COVER.
PROPOSED CONCRETE GROUND ROD
PROTECTOR 13" DEPTH X 12" HEIGHT
WITH COVER. PIPE INC. #12R-12A &
12R-12T, OR EQUAL.
5/8"x8' LONG COPPER GROUND ROD.
GROUND ROD DETAIL
NO SCALE
"MCC
ELECTRICAL
BUILDING WALL
SHOWNfit Uii i V�
_ �`" RENTON
ublic Works Department
ved For �pn ru r
REVISION BY DATE APPR nor _ H neon P F —r
CABLE,
NECESSAR
TERL
TERMINATION BOX
ENCLOSURE
CABLE FR06
TRENCH SYSTLI
PROPOSED TERMINAL
BLOCK WITHIN
TERMINATION BOX
ENCLOSURE
FIELD WIRE
CONNECTIONS
CORD GRIP (CGB),
SIZE TO CABLE
DIAMETER
CABLE TRANSITION ,
DETAIL (TYPICAL) S-2
NOT TO SCALE
CAST -IN -PLACE CONCRETE HOUSEKEEPING PAD,
SEE DWG NO. PS-16 FOR LOCATION. ROUGHEN
FLOOR UNDER PAO PRIOR TD POURING PAD.
% PROVIDE 44 W1.4xW1.4 WWM AT TOP FACE WITH
1-1/2" CLEAR COVER
FY MIN. BEYOND EQUIPMENT BOLTS, TYP.
7/8" CHAMFER, ALL OUTER EDGES
#4 DOWEL, EACH CORNER AND IS'
O.C. 3" EMBEDMENT INTO FLOOR
CONCRETE FLOOR AND
REINFORCEMENT PER BUILDING
STRUCTURAL DRAWINGS.
TYPICAL EQUIPMENT PAD
NOT TO SCALE
r rass,dx"
ti s'
aw a
16727 � n_.
R4ra,exw9
R-3693112
SfCNSA� !2/t15/ri SfCA
�12/5�201i
STRANDER BOULEVARD EXTENSION,
PHASE 1, SEGMENT 2A
ELECTRICAL DETAILS - SHEET i PS-20
119°f231