HomeMy WebLinkAboutR-3693222I. MAY24, 2011 REMSEO BID ISSUE
rn
c0
M
O
W
H
GROUND ROD AND WIRE INSTALLATIONS
FOR MANHOLES AND HANDHOLES
ROUTE GROUND WIRE
INTO MANHOLE NEXT
TO DUCT(S) OR #6 AWG SOLID COPPER
THROUGH A HOLE INSULATED GROUND WIRE
DRILLED IN MANHOLE
LEAVE SLACK COILED IN
MANHOLE TO EXTEND 6'
ABOVE LID
#6 AWG SOLID COPPER Imo'
GROUND WIRE BONDED
TO GROUND ROD WITH
PANDUIT GCE250-1/0
CRIMP COMPRESSION F:r
CONNECTOR. A ;
DUCT(S)
'GROUND
F L
�ROUIvD ROD �.:.;� --_ _ .: T•.=::
GROUNDING
FOR MANHOLES
NOT TO SCALE
PANDUIT PARTS UST
PANDUIT PART #
DESCRIPTION
GCE250-1/0
GROUND "E" STYLE CONNECTOR
5/8" GROUND ROD TO #6 SOLID
(REQUIRED AT INSTALLATION OF MANHOLE/SPLICE BOX)
GC£1/0-1/0
GROUND "E" STYLE CONNECTOR
#6 SOLID WIRE TO #6 SOLID HARE
(USED WHEN CONNECTING SPLICE CASE OR FILTER/ARRESTOR TO
PREINSTALLED GROUND WIRE)
CO-92OG-250
jDIE FOR 250 CONNECTORS
CO-92OG--1/0
IDIE FOR 1/0 CONNECTORS
CT-2931
IPORTABLE COMPRESSION TOOL
1.05"
fl
2.66"
GCE250-1 /0
CONNECTOR DETAIL
NOT TO SCALE
0.66'I 1---- 0,94"
I T
1.=
1.72"
GCE1/0-1/0
CONNECTOR DETAIL
NOT TO SCALE
#6 AWG SOLID COPPER
INSULATED GROUND WIRE
LEAVE SLACK COILED IN
HANDHOLE TO EXTEND 6'
ABOVE GRADE
6"
#6 AWG SOLID COPPER
GROUND WIRE BONDED
TO GROUND ROD WITH
PANDUIT GCE250-1/0
CRIMP COMPRESSION
CONNECTOR.
12"
EXISTING GRADE
HANDHOLE
DUCT(S)
BOTTOM OF
TRENCH
ROUTE WIRE INTO HANDHOLE NEXT TO
DUCT(S) OR THROUGH A HOLE
DRILLED IN SPLICE BOX
5/8"x8' GROUND ROD
WITHIN 12" OF SPLICE BOX
AND 6" BELOW TOP OF BOX
GROUNDING FOR
HANDHOLES
NOT TO SCALE
GROUNDING FOR MANHOLES AND HANDHOLES;
THE GROUND ROD FOR A MANHOLE OR HANDHOLE
SHOULD BE DRIVEN INTO NON --DISTURBED DIRT AS
NEAR TO THE STRUCTURE AS POSSIBLE.
UNDISTURBED DIRT HAS GREATER CONDUCTIVITY THAN
COMPACTED FILL DIRT. IF UNABLE TO INSTALL THE
ROD INTO UNDISTURBED DIRT NEAR THE STRUCTURE,
DRIVE THE ROD DEEPER BELOW THE STRUCTURE IF
POSSIBLE. THE TOP OF THE ROD SHOULD BE AT
LEAST AS DEEP AS THE SHOULDER OF THE MANHOLE
OR AT LEAST SIX INCHES BELOW THE TOP OF, THE
HANDHOLE.
THE GROUND WIRE WILL BE BONDED TO THE ROD
WITH THE PROPER PANDUIT CRIMP CONNECTOR AND
ROUTED INTO THE MANHOLE/HANDHOLE EITHER
THROUGH ONE OF THE CABLE ENTRANCES OR A
HOLE DRILLED INTO THE UPPER PART OF THE
STRUCTURE.
+ THERE SHALL BE ENOUGH SLACK WIRE LEFT IN THE
STRUCTURE TO EASILY REACH SIX FEET ABOVE THE
MANHOLE LID OR SIX FEET ABOVE THE FINISH GRADE
OVER THE HANDHOLE. THIS WILL EASE THE
INSTALLATION OF FUTURE SPLICE CASES OR
FILTER/ARRESTORS. COIL THE SLACK WIRE NEATLY
AND USE PLASTIC TIES TO SECURE IT OUT OF THE
WAY.
R-3693222
1 SuarJRFACE Unurf UNFS, AS SHOWN HEREON,
WEAEOOF,? ACccmweTO AVAAABLE
AECOR9lNrOPMATI0.Y FROM THEAEFEAENEEO
COMPANIESAHO PUBUCAGERCIK AND :NEW
LOCATIONSAPE AMOxIMATE CNLY. ACTVAL
LOCATIONS MUST RE DETERMINED IN THE FIN.
SIENA EN'DL'MING CROUP ASSUMES NO
R ESPONUBILDT toh DAMAGESIN"'
ROW AT A
AMULT DP U1a90 OM1EEE0 OR MMCCUAATELY
SHOWN.
2 RIFERTO PLANSTInfO L&q WASHINGTON
TAmMA02 UGHTGUIDE SYSTEM, 3ELLERAIETO
TAODMA02 SHEETS WK-IU33125•A34
PROkCrd2R04A5 9UILTo2(24r86, eY RUOA
COMM UNIC.TIONS SEAVICES.
3. RMILTO PUNSTULED SFRANDER BOULEVARD
FPIEEHNON, STRANDER BOULEVARDPLAN-PHASE
x, BY eorEETABAM,
Call before you dig.
Washington Utilities
Coordinating Council
1-900-424-5555
AT&T PROPRIETARY
[Internal Use Only)
Not for disclosure outside the AT&T
Companies, except underwritten
agreement.
Z011 AT&T Intellectual Property, All
Rights Reserved _-
AT&T PROPRICTARY This information
consututes confiidentialtmde secrets and
o0rnN eTCW0T f4iHottal information owned
by AT&T and is shared for critical
Infrastructure Protection purposes Only. it is
exempt from disclosure under the freeaoro
of Information Act 45 U.S.C. 552y,
Exemptions (bl(3)&(4), and Its disclosure is
Prohibited underthe Tfade Secrets Act
Ila U.S.0 19o5I, the Critical Infrastructure
InfOrmadon Act of 2002, 6 U.S.0 133, and
any State or local law requiring disclosure of
Informatlon or records. This information
must not be copied or dlstrihCted to others
not agreed upon by AT&T, but In all events
do not copy or distribute to such others
Without notification pursuant to Executive
Order 12600,
PREPARED FOR RECORD
OUTstDE PtANi ENGINEER OAT-
at&t
EA
vna.w"e.e:ro r.EEr.:::I:
SPECIFICATION,
PROJECT NUMBER:
OWNERSHIP-
LINE CODE:
CABLE CLLI:
SCALE: AS NOTED
BELLEVUE TO TACOMA 02
UGHTGUIDE SYSTEM
TYPICAL MANHOLE
GROUNDING DETAILS
8OF14