THIS SET OF APPROVED PLANS MUST BE ON THE JOB AT ALLTIMES DURING CONSTRUCTION. THIS BUILDING IS NOT TO BEOCCUPIED UNTIL AFTER FINAL INSPECTION BY THE RENTONBUILDING DIVISION AND RECEIPT OF CERTIFICATE OFOCCUPANCY.APPROVAL SHALL NOT BE CONSTRUED AS THE AUTHORITY TOVIOLATE OR CANCEL ANY PROVISIONS OF CODES, ORDINANCES,OR OTHER REGULATIONS ENFORCED BY THIS CITY.DATE: 08/23/2021
Lateral Loading: Area, Height & Weight Data Page 1.1 of 1.3 MaxQuake © 1995-2021 Archforms Ltd.
Date:Firm:All Rights Reserved Lateral Load Analysis &
Job:By:Q21W.2 Construction Design Software
FLOOR PLAN AREAS & SHEAR WALL GRID SPACING TYPICAL DEAD LOADS Wind Area Calc
•Establish Grid Spacing and Floor Plan Configuration at Each Level• •Establish Dead Loads (lbs/sf)•See Page 1.2 &1.3
Left Right Roof: R Rb Interior Wall
Perim Overall Roofing 4 Gyp.Bd 6
Shear Wall Spacing R Rb 1or2 b Wall Width FL Wdth Sheathing 3 Framing 4
Back LF ft 60 Framing 3 Int. Finish
Roof 2 24.6 60 VT Rf Area Snow Other
2nd Fl/Rf 1 36.5 21.9 133 60 L-R 10 10
1st Fl 21.9 133 60 Zone E Ceiling:
Roof 2 3.6 Roof at 2nd Fl 540 Insulation Exterior Wall
2nd Fl/Rf 1 4.67 2.8 39.34 Typ OH Framing Ext Finish 4
1st Fl 2.8 39.34 L to R Zone G Gyp. Bd. Shear 1.5
Roof 2 6.8 2 2890 Other Framing 3
2nd Fl/Rf 1 20 6.0 40 Insulation 0.5
1st Fl 6.0 40 Zone B Oh Zn E Floor: 1or2 1b 2b Gyp. Bd. 3
Roof 2 4.7 60 48 Floor 4 Int .Finish
2nd Fl/Rf 1 12 3.6 54 48 Sub. Fl. 2 code additional
1st Fl 3.6 54 Zone D Oh Zn G Framing 3.5 12
Roof 2 389 98 Insul 0.5
2nd Fl/Rf 1 10 98 Topping
1st Fl Other
Roof 2 Zone A 10
2nd Fl/Rf 1 216 FLOOR HEIGHTS & WIND AREA
1st Fl 264 •Establish Floor to Floor and Roof Heights (ft)•
Roof 2 Zone C Roof Roof Floor
2nd Fl/Rf 1 443 Pitch Height Height
1st Fl 541 X/12
Front Irregular Plan or Zone Adj 5 8.5
Roof 2 Typical Overhang F to B Y
Rf Area R & Rb+OH /100 20.0 1.5 3.7 5.1 9.3 5 4
Overall Depth ft a= Zone B Zone D Rf 2 Area + OH 3,963
2nd Fl / Roof 1 2nd Fl Framing Ht.
Rf Area R & Rb+OH/100 Floor 2 Area 3,430 1st Fl Top Plate Ht.
Floor 2 & 2b Area /100 17.6 1.5 2.9 4.7 7.7 Floor 2b Area Total Ht.
Perimeter Wall LF 266 1st Fl Framing Ht.
Overall Depth ft a= Zone B Zone D Bsmt or Crawl Ht.
1st Floor Zone A Zone C Total Ht.
Floor 1 & 1b Area /100 18 1.5 2.9 4.7 7.7 Floor 1 Area 3,430 Wind Ht.@Ridge
Perimeter Wall LF Floor 1b Area Wind Ht.@Gable Ridge F to B L to R
Overall Depth ft a= Zone A Zone C Wl1 Perimeter LF 266 Mean Roof Ht.Runs? Y
Hips?Y Y
MAY 12 2021
SINGH RESIDENCE
Hz Rf Area
Hz Wl Area
5 6
424
22
1
2
1
2
2
5
FloorRoof
Area+OH Area / 100
.8.
GPM/BM
API License Expires
1-Jan-22
26.25
Oh Zn G
72
25.25
73.17
73.17
6
73.17 Dpth of Roof 1st Fl
72
396264
78.514 40 22.66121.17
216 2
1
48
ASCE7 a = less of 10%of least horiz dim or 40%of ht but not less than 4%of least horiz dim (min 3 ft) Sec 6.2 Low-rise Building: ht < 60 ft. Rf ht < least horiz dim.
Vt Rf Area
F-B
Rf 1 Rb Area + OH
Rf 1 R Area + OH
Wl 2 Perimeter LF
Rf 2b Area + OH
IF L Plan w/ both Legs >
15%of Plan or Vert SW offset.Y?
48
Oh Zn E
324
277
1
10
Zone G
2,744
29.50
1
11
9686
Zone E
2
1
2
R
2
73.17
Dpth of Roof 2nd Fl
6
606
78.51121.17 4 40 22.66
R
H
F
G
E 1 1
R
11
R R
2
2
D
A
1
R
1
R
2
1
B
C
1
2
1
2
1
R
R
2
R
1
R
2 2
1
1
R R
2
R
2
R
1
2
R
1 2 3 4 7
2 18.6711.33
Wind Load Areas - Front to Back Page 1.2 of 1.3 MaxQuake Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Horizontal Line Name Bay Lgth 1 24 2 2 3 4 4 11.33 5 18.67 6 7 .8. Vert Roof Areas
Sum lgth to line or mid line 12.0 24.0 25.0 26.0 28.0 30.0 35.7 41.3 50.7 60.0
2nd Roof Lgth of line to mid line 12.0 12.0 1.0 1.0 2.0 2.0 5.7 5.7 9.3 9.3
2a Lgth >12.0 12.0
2a Lgth < 60.0 2.7 9.3
2a Lgth 12.0 12.0
Int Lgth 9.6 12.0 2.0 4.0 11.3 6.7
Rake Lgth 20.4 20.4 1.7 18.7
Rise at > 8.5 5.0 3.5
Rise at < 0.7 2.8 5.0
R2 Area 60 Hip/Gable B1 Area 30 30 30
277 Hip/Gable D1 Area 138 87 17 34 96 43
204 Slope Zone B2 Area 9 102 102
306 Slope Zone D2 Area 102 17 34 96 57
Sum lgth to line or mid line 12.0 24.0 25.0 26.0 28.0 30.0 35.7 41.3 50.7 60.0
1st Roof Lgth of line to mid line 12.0 12.0 1.0 1.0 2.0 2.0 5.7 5.7 9.3 9.3
2a Lgth >12.0 12.0
2a Lgth < 60.0 2.7 9.3
2a Lgth 12.0 12.0
Int Lgth 20.4 12.0 2.0 4.0 11.3 6.7
Rake Lgth 9.6 9.6 2.9 9.6
Rise at > 4.0 5.0
R1 Area Rise at < 5.0
60 Hip/Gable B1 Area 30 30 30
163 Hip/Gable D1 Area 71 58 8 16 45 36 Horiz Rf & Wl Areas
96 Slope Zone B2 Area 4 48 48
144 Slope Zone D2 Area 48 8 16 45 27
W2 Area 216 Wl Zone A Area 108 108
324 Wl Zone C Area 108 18 36 102 60
W1 Area 264 Wl Zone A Area 132 132
396 Wl Zone C Area 132 22 44 125 73
Base Wl Area 48 Wl Zone A Area 24 24
72 Wl Zone C Area 24 4 8 23 13
Vertical Lift 686 Zone E & F Area 439 247
R2 Area 2744 Zone G & H Area 1317 146 293 466 522
48 Oh Zone E Area 24 24
72 Oh Zone G Area 24 4 8 23 13
R1 Area Zone E Area
Zone G Area
48 Oh Zone E Area 24 24 Zone F assumed to Equal Zone E
72 Oh Zone G Area 24 4 8 23 13 Zone H assumed to Equal Zone G
© 1995-2021
E G
GG
G
G
E E
Ridge
Ri
d
g
e
2a
2a
L/2
OhE OhG OhE
Transverse Case A Wind
Longitudinal Case B Wind
OhE OhEOhG
Hip
A A
B
C
D B21 1122
Transverse Case A Wind
Ridge
2a
A AC
2aLongitudinal Case A Wind
B1D1
E
Wind Load Areas - Left to Right Page 1.3 of 1.3 MaxQuake Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Horizontal Line Name Bay Lgth A 36.5 B 4.67 C 20 D 12 E F G H Vert Roof Areas
Sum lgth to line or mid line 18.3 36.5 38.8 41.2 51.2 61.2 67.2 73.2
2nd Roof Lgth of line to mid line 18.3 18.3 2.3 2.3 10.0 10.0 6.0 6.0
2a Lgth >12.0 12.0
2a Lgth < 73.2 6.0 6.0
2a Lgth 12.0 12.0
Int Lgth 16.2 24.5 4.7 20.0
Rake Lgth 20.4 20.4 8.4 12.0
Rise at > 8.5 5.0 3.5
Rise at < 3.5 5.0
R2 Area 60 Hip/Gable B1 Area 30 30 30
389 Hip/Gable D1 Area 194 194 40 155
204 Slope Zone B2 Area 9 102 102
418 Slope Zone D2 Area 208 40 170
Sum lgth to line or mid line 18.3 36.5 38.8 41.2 51.2 61.2 67.2 73.2
1st Roof Lgth of line to mid line 18.3 18.3 2.3 2.3 10.0 10.0 6.0 6.0
2a Lgth >12.0 12.0
2a Lgth < 73.2 6.0 6.0
2a Lgth 12.0 12.0
Int Lgth 27.0 24.5 4.7 20.0
Rake Lgth 9.6 9.6 9.6 9.6
Rise at > 4.0 5.0
R1 Area Rise at < 5.0
60 Hip/Gable B1 Area 30 30 30
10 216 Hip/Gable D1 Area 97 108 19 80 10 10 Horiz Rf & Wl Areas
96 Slope Zone B2 Area 4 48 48
197 Slope Zone D2 Area 98 19 80
W2 Area 216 Wl Zone A Area 108 108
443 Wl Zone C Area 221 42 180
W1 Area 264 Wl Zone A Area 132 132
541 Wl Zone C Area 270 51 220
Base Wl Area 48 Wl Zone A Area 24 24
98 Wl Zone C Area 49 9 40
Vertical Lift 540 Zone E & F Area 360 180
R2 Area 2890 Zone G & H Area 1830 280 600 180
48 Oh Zone E Area 24 24
98 Oh Zone G Area 49 9 40
R1 Area Zone E Area
Zone G Area
48 Oh Zone E Area 24 24 Zone F assumed to Equal Zone E
98 Oh Zone G Area 49 9 40 Zone H assumed to Equal Zone G
© 1995-2021
EE G
GG
G
G
E E
Ridge
Ri
d
g
e
2a
a
L/2
OhE OhG OhE
Transverse Case A Wind
Longitudinal Case B Wind
OhE OhEOhG
Hip
A A
B
C
D B21 1122
Transverse Case A Wind
Ridge
2a
A AC
2aLongitudinal Case B Wind
B1D1
Lateral Load Analysis: Seismic & Wind Loads Page 2.0 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
SEISMIC LOADS Sec.12.7.2 ASCE 7-16 BUILDING CODE 19 CBC X 18 IBC ASCE/SEI 7-16
•Establish Dead Loads•2nd Floor 1st Floor Base Level WFCM & SDPWS -15
Item DL(psf) Area (sf) DL(lbs) Area(sf) DL(lbs) Area(sf) DL(lbs)•Vertical Distribution of Shear to Various Levels•Sec. 12.8.3 ASCE7
Roof R 10 3,963 39,629 Fx= V (Wtx)(Htx)^k/Sum(Wti)(Hti)^k Ht from plate to foundation Eh= pQe Eq.(12.4.3)
Roof Rb k=1 Eq.(12.8-12) ASCE7 Wt x Ht x^k (Wt)(Ht)^k Fx p F to B p L to R
Ceiling 5 3,430 17,151 3,430 17,151 Roof 2 71,162 22 1,565,568 15,576 1.00 1.00
Ext Wall 12 2,397 28,765 2,930 35,157 266 3,196 ####2nd Fl/Rf 1 117,716 13 1,530,305 15,225 1.00 1.00
Int Wall 10 3,430 34,302 3,430 34,302 1st Floor 89,379 2 178,757 1,778 1.30 1.30
F 1 or 2 10 3,430 34,302 3,430 34,302 Sum 278,256 22 3,274,630 32,579 p Sec 12.3.4 ASCE7
Fl 1b or 2b WIND LOADS
Sum 2nd 154,149 Sum 1st 120,912 Base 3,196 •Adjusted Wind Zone Pressures•Eq. 28.5-1 ASCE7 Ps= ⅄KztIP s30 =
Sum 2nd,1st & Base 278,256 Wind Loads per Simple Diaphragm Lowrise Envelope Fig. 28.5-1 ASCE 7 Roof 2 Ø Roof 1 Ø
•Distribute Weights to Various Levels•Roof 2 2nd Fl 1st Fl Base Fl Wt Procedure for MWFRS per ASCE7-16 Tbl. 28.4-1 Longitudinal (Case B) Transvers (Case A)
Tributary Weight Line Rf 1 Line Line Line Sum HZ Zone A 16.0 -16.0 16.0
Wt Roof 2nd (R+Rb)39,629 39,629 Wind Speed 110 Fig.1609.3 IBC / Fig.26.5 ASCE7 Zone B 16.0 16.0 16.0
Wt Ceil 2nd 17,151 17,151 Risk Cat.II Tbl.1604.5 IBC/Tbl.1.5-1 ASCE Zone C 16.0 -16.0 16.0
1/2Wt Ext Wl 2 14,382 14,382 28,765 Exposure=B Zone D 16.0 16.0 16.0
Wt Int Wl 2 34,302 34,302 Ht. Coef ⅄1.00 Tbl.28.5-1 ASCE/IBC1609.1.1.1VT Zone E -16.0 -16.0 -16.0
Wt Floor 2 (2+2b)34,302 34,302 Topo Kzt 1.00 Eq.(26.8-1) & Fig.26.8-1 ASCE7 Zone G -16.0 -16.0 -16.0
Wt Roof 1st (R+Rb) Zone E oh -19.4 -16.0 -16.0
Wt Ceil 1 17,151 17,151 Topo Type: Flat Zone G oh -16.0 -16.0 -16.0
1/2 Wt Ext Wl 1 17,578 17,578 Load 35,157 Features:Escarpment Hill / Ridge Ht Distance Bldg Ht
Wt Int Wl 1 34,302 transfers 34,302 H= ft z= ft L= ft x=ft
Wt Floor 1 (1+1b)34,302 directly 34,302
1/2Wt Ext Wl Base 3,196 to Slab 3,196 •Total Wind Load In Each Direction At Each Level (lbs)•
Wt Ceil Base Trib Area F to B Trib Area L to R Wind Load
Line Sum 71,162 117,716 89,379 W=278,256 Horizontal B,A area D,C area Sum PsA B,A area D,C area Sum PsA F to B L to R
•Determine Base Shear•Roof 2 60 277 5,386 60 389 7,177
Default Site Class Y Roof 1 10 154 9,706 1,908
Site Class=D 1.359 Fig.1613.2.1(1,3-8) 0.2 Sec.2nd Floor 216 324 8,640 216 443 -10,536 9,600 1,324
Risk Cat =II 0.465 Fig.1613.2.1(2,3-8) 1.0 Sec.1st Floor 264 396 10,560 264 541 12,878 6,240 7,610
Resp Mod R=6.5 16 Fig.22-(14-17) ASCE7 Vert Uplift E,F,Eoh G,H,Goh Sum PsA E,F,Eoh G,H,Goh Sum PsA F to B L to R
Site Coef Fa=1.20 D Sec.1613.3.5 IBC Roof 2 734 2,816 -56,965 588 2,989 -57,225 56,965 57,225
Site Coef Fv=1.04 0.167 Eq.(12.8-2) ASCE7 Roof 1 48 72 -2,082 48 98 -2,341 2,082 2,341
Import Ie=1.000 8.992 for T < = TL Eq.(12.8-3)
Sms=FaSs=1.631 NA for T > TL Eq.(12.8-4)GOVERNING LATERAL LOADS
Sm1=FyS1=0.481 0.010 Eq.(12.8-5) ASCE7 •Maximum Total Load In Each Direction At Each Level (lbs)•Wind %of Seismic
Sds=2/3Sms=1.087 NA for S1 => 0.6g Eq.(12.8-6) Front to Back Left to Right F to B L to R
Sd1=2/3Sm1=0.321 46,542 Eq(12.8-1) ASCE7 Roof 2 15,576 Seismic 15,576 Seismic 62%12%
P limit Cu=1.400 2nd Fl / Roof 1 15,225 Seismic 15,225 Seismic 63%9%
Ta=Cth^n 0.232 1st Floor 6,240 Wind 7,610 Wind 270%329%
(ASD) Comb 5. ASCE7 12.4.132,579Tbl.12.8-1 ASCE7
Eq.(12.8-7) ASCE7
S.Coef Cs=Sds/(R/I) =
Cs not >Sd1 /T(R/I) =
Cs not>Sd1 TL/(R/I) T^2 =
Cs not < 0.01 =
Cs not<0.5 S1/(R/I) =
V (SD)= CsW =
V=(SD)*0.7=V(ASD) =
Tbl.11.5-1 ASCE7
Eq.(16-36) IBC
Eq. (16-37) IBC
Eq.(16-38) IBC
Tbl. 1613.2.3(1) IBC
Eq.(16-39) IBC
Tbl. 1613.2.3(2) IBC
Mapped %g: Ss=
Mapped %g: S1=
Mapped Period TL=
Seismic Design Cat.=
Sec 26.7.3 ASCE7/IBC 1609.4.3
Tbl. 20.3-1 ASCE7
Tbl.1604.5 IBC
Tbl.12.2-1 A-15 ASCE
2.4.1.7 0.6D+0.6W
Calculation Method per 12.8 ASCE7 & Sec.1613.2.5.2 IBCSec 11-4.2 ASCE7
HZ X
L
Z
H
Shear Wall Segments Data: Lines 1-8 Page 3.1 of 3.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis & Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
Segment (Seg) names a-g appear to show possible quadrants (q). Remove Segs not used. Move and add 1,2...to denote multiple (m) seg's in a quadrant, ie., b2.
Seg Variables; Lg: Seg lgth. Ht: Seg hght (from pg 1). X: Wl Opening. B: Bearing Wall? - B=yes. E: Ext./Int. Wall? - E or I. S: Stacked Seg above, same row, q-m & ≤ Lg.
2nd Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E
a 17 9 B E a 11 9 N I a 15 9 N I a1 4.3 9 B E
1,2,3..b 4.1 9 B E a2 7.8 9 B E
Wall c 21 9 B E c 8 9 B E b 4 9 B E b 4.3 9 N E a3 10 9 B E
Lines d 3.5 9 B E b 4.7 9 B E
Run
From
Front
to sum38.00 Syst sum 25.56 Syst sum Syst sum3.56 Syst sum 19.27 Syst sum27.07 Syst sum Syst sum Syst
Back Ht/Lg>2.0<3.5:adj V atb Ht/Lg>2.0<3.5:adj V atb Ht/Lg>2.0<3.5:adj V atb Ht/Lg>2.0<3.5:adj V ata1
38 ext Seg Lg adj to 2Lg^2/ht 16 ext load trans to adj Ln Seg Lg adj to 2Lg^2/ht 4 ext Seg Lg adj to 2Lg^2/ht 4 ext Seg Lg adj to 2Lg^2/ht 27 ext
1st Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S
a 19 10 B E S a 17 10 N I S a 15 10 N I S a1 9.5 10 B E S
b 21 10 B E b 3.5 10 B E b 4.6 10 N E a2 5.5 10 B E
c 2.5 4 B E c 2.5 5 B E b 3.8 10 B E
d 26 10 B E d 2.5 5 B E
sum66.53 Syst sum 19.50 Syst sum 5.00 Syst sum2.45 Syst sum 19.33 Syst sum17.81 Syst sum Syst sum Syst
Ht/Lg>2.0<3.5:adj V atb Ht/Lg>2.0<3.5:adj V atb Ht/Lg>2.0<3.5:adj V atb
Seg Lg adj to 2Lg^2/ht Seg Lg adj to 2Lg^2/ht Seg Lg adj to 2Lg^2/ht
67 ext 3 ext 5 ext 4 ext 5 ext 19 ext
Base Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S
a 37 1 N E S a a a 37 1 N E
b 4.7 1 N E b b b 4.7 1 N E
c 20 1 N E c c c 20 1 B E
d 12 1 N E d d d 12 1 B E
sum73.17 Syst sum Syst sum Syst sum32.00 Syst sum Syst sum41.17 Syst sum Syst sum Syst
73 ext load trans to adj Ln load trans to adj Ln 32 ext load trans to adj Ln 41 ext
"= max X ht / Wall ht"
WS WS
WS
Lines Run
Front - Back
WS
WS
WS WS WS WSWS
WS WS WS
WS
Shear Wall Segments Data: Lines A-H Page 3.2 of 3.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis & Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Line A Line B Line C Line D Line E Line F Line G Line H
Segment (Seg) names 1-7 appear to show possible quadrants (q). Remove Segs not used. Move and add a,b...to denote multiple (m) seg's in a quadrant, ie., 2b.
Seg Variables; Lg: Seg lgth. Ht: Seg hght (from pg 1). X: Wl Opening. B: Bearing Wall? - B=yes. E: Ext. /Int. Wall? - E or I. S: Stacked Seg above, same row, q-m & ≤ Lg.
2nd Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E q-m Lg Ht X B E
1 20 9 B E 1 11 9 N I 1a 3 9 B E
A,B,C..1b 3 9 B E
Wall
Lines 4 4 9 B E 4a 3 9 B E
Run 5 4.3 9 B E 4b 3 9 B E 5a 3 9 B E
From 5b 3.8 9 B E
Side
to sum27.22 Syst sum 4.00 Syst sum15.76 Syst sum4.00 Syst sum Syst sum Syst sum Syst sum Syst
Side Ht/Lg>2.0<3.5:adj V at4 Ht/Lg>2.0<3.5:adj V at4a Ht/Lg>2.0<3.5:adj V at5a Ht/Lg>2.0<3.5:adj V at1a
Seg Lg adj to 2Lg^2/ht 28 ext Seg Lg adj to 2Lg^2/ht 6 ext Seg Lg adj to 2Lg^2/ht 7 ext Seg Lg adj to 2Lg^2/ht 6 ext load trans to adj Ln
1st Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S
1a 4.5 10 B E 1 12 10 B I 1a 13 10 B I 1 6.5 10 N E
1b 4.3 10 B E 1b 7 10 B I 2 6.5 10 N E
1c 4.1 10 B E
4a 3 10 B E S
5 6.3 10 B E S 4b 3 10 B E S 5a 4 10 B E S
5b 4 10 B E S
sum17.49 Syst sum 15.93 Syst sum26.40 Syst sum Syst sum 13.00 Syst sum Syst sum Syst sum Syst
Ht/Lg>2.0<3.5:adj V at1a Ht/Lg>2.0<3.5:adj V at4a Ht/Lg>2.0<3.5:adj V at5a
Seg Lg adj to 2Lg^2/ht Seg Lg adj to 2Lg^2/ht Seg Lg adj to 2Lg^2/ht load trans to adj Ln
19 ext 6 ext 8 ext 13 ext
Base Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables Seg Wall Variables
level q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S q-m Lg Ht X B E S
1 24 1 N E 1 1 1 1 24 1 N E S
2 2 2 2 1 N E
3 3 3 4 1 N E
4 11 1 N E
5 19 1 N E
sum24.00 Syst sum Syst sum30.00 Syst sum Syst sum ### Syst sum Syst sum Syst sum Syst
24 ext load trans to adj Ln 30 ext load trans to adj Ln 30 ext
"= max X ht / Wall ht"
WS
WS WS
WS WS WS
WS
WSWS
WS WS
Lines Run
Left - Right
Diaphragm Flexibility: Length/Width Ratio & Drift Limits Page 4.0 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
DIAPHRAGM DIVISIONS AND LENGTH / WIDTH RATIOS UNBLOCKED DIAPHRAGM LIMITATIONSASCE7 Sec 12.3.1 & Sec1613.6.1 STORY DRIFT
+ + + + +Actual Limit
Roof 2 Line Eq. 23-2 12.12-1
grid 24 2 4 11.33 18.67 Drift Limit =0.02 ht.
# # # ## # # ## # # ## # # ## # # #5 5536.5 #
#
#
#
1.37 #
#
#
#
41.17 d >2/3 w?0.58 <2.16
4.67 #
#
#
#
#
#
#
#
4.67# # # ## # # #220#
#
#
#
#
#
#
#
32 0.66 <2.16
12 #
#
#
#
#
#
#
#
12+ + + ++ + + ++ + + +
4 Walls?Unblock Blocked Ratio>4:1 Blk Cant d >2/3 w?diaph 4 30 6 4 2 30 18.67 2 0.49 0.95 0.59<<<Rf1 / Fl 2 Line 2.16 2.16 2.16 Act Drift < Limit
grid 24 2 4 11.33 18.67 Drift Limit =0.02 ht.
# # # ## # # ## # # ## # # ## # # #5 59Adjust36.5 #
#
#
#
2.44 #
#
#
#
73.17 Unblock 0.85 <2.4
Interior 4.67 #
#
#
#
#
#
#
#
#
#
#
#
36.67
Shear 20 #
#
#
#
#
#
#
#
32
Walls 12 #
#
#
#
#
#
#
#
12# # # ## # # ## # # #3and 0.85 <2.4
Block
Ratios 4 Walls?Unblock Blocked Ratio>4:1 Blk Cant d >2/3 w?diaph 4 30 6 4 3 30 18.67 2 0.52 1.00 1.00<<<1st Fl Line 2.4 2.4 2.4 Act Drift < Limit
grid 24 2 4 11.33 18.67 Drift Limit =0.02 ht.
# # # ## # # ## # # ## # # #4 5936.5 #
#
#
#
1.37 #
#
#
#
#
#
#
#
41.17 Unblock 0.07 <0.24
4.67 #
#
#
#
#
#
#
#
#
#
#
#
4.67# # # ## # # #2 5920#
#
#
#
1.07 #
#
#
#
32 Unblock 0.07 <0.24
12 #
#
#
#
#
#
#
#
12# # # ## # # ## # # #3 0.07 <0.24
4 Walls?Unblock Blocked Ratio>4:1 Blk Cant d >2/3 w?diaph 4 30 6 4 4 30 18.67 2 0.06 1.00 1.00<>>0.24 0.24 0.24
# # # # #
If Gap? Check Load Dist btwn Jogs in Bldg - Cantilever wings out from Bldg Shear Lines.Actual= Drift Limit=Act Drift < Limit
5 6Unblocked
D
G
H
E
F
.8.
2 3
2 3 4 6
.8.
B
1 2 3 7 .8.
A
4
5 6 71
A
B
Blocked?
5 7
4
H
C
D
E
B
F
G
A
C
H
F
G
G
H
F
A
F
G
H
D
C
E
B
C
E
F
G
H
D
Actual= Drift
Limit=
A
B
C
E
1
B
C
D
.8. 7612453
A
l/w Ratios <Tbl.2305.2.3,Cantilever d< 25' & 2/3 w, Topping<1-1/2" and Wl Drift <Tbl.12.12-1
Limitations: MaxTopping 1-1/2",Max Blocked Ratio 4.0, Unblocked 3.0, all Cantilevers Blocked
Shear Wall/Collector Line Perimeter of Cantilevered Diaphragm Edge
1 2
2
Unblocked
3 4
5
7 .8. Actual= Drift
Limit=
6 7 .8.
5 6
3 41
D
E
Load Distribution to Segments: RM & OTM Pg 5.1 of 5.4 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Lateral Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
Force Seis %= Wind %= W/ft=if "w",- snow Vadj= V= SumV=
Distrib trib fl A/Sum flA trib wl A/Sum wlA Sum lev. w*trib area SumV from adj Ln Ln%*Vmax SorW Vadj+Vabv+V
2nd %S 25 %W 19 %S 27 %W 21 %S 7 %W 6 %S 11 %W 16 %S 18 %W 25 %S 12 %W 13 %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Seismic a 1-2 288 16 15.56 a 2 ft 120 2.8 18.98 a 2 ft 120 5.2 20.08 a1 5-6 248 0.9 2.629
15,576 b 1-2 288 0.9 6.386 a2 5-6 248 2.9 4.941
c 1-2 288 24 19.22 c 1-2 288 3.5 13.68 b 2 ft 138 0.4 19.01 b 2 ft 138 0.5 5.541 a3 5-6 248 5.1 6.562
p =d 1-2 288 0.7 4.654 b 5-6 248 1 2.947
Level V >
35%Base
Shear
p =b b 0.72 0.36 b b
1.00 2nd Level V 3.86 2nd Level V 4.14 2nd Level V 1.08 a 2nd Level V 1.75 2nd Level V 2.85 2nd Level V 1.9 2nd Level V 2nd Level V
Regular s 38 Sum V 3.86 s Sum V 4.85 s Sum V s Sum V 2.11 s Sum V 2.85 s 27 Sum V 1.9 Sum V Sum V
1st %S 25 %W 20 %S 27 %W 22 %S 7 %W 5 %S 11 %W 13 %S 18 %W 25 %S 12 %W 16 %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Seismic a 2 ft 423 30 43.75 a 2 ft 250 14 75.34 a 2 ft 250 11 64.12 a1 2 ft 879 15 15.64
15,225 b 2 ft 135 12 24.51 b 2 ft 288 0.7 38.26 b 2 ft 288 1.2 12.32 a2 2 ft 879 5.1 11.58
c 2 ft 366 0.4 4.565 c 2-4 105 0.1 2.628 b 2 ft 383 1 5.92
p =d 2 ft 135 17 29.87 d 2-4 105 0.1 2.628
Level V >
35%Base
Shear
p =67 Vadj line 2 19 Vadj line 7
1.00 b V above 3.86 b V above 4.85 V above V above 2.11 b V above 2.85 b V above 1.9 V above V above
1st Level V 3.78 1st Level V 4.05 a 1st Level V 1.05 a 1st Level V 1.71 1st Level V 2.78 a 1st Level V 1.85 1st Level V 1st Level V
Regular s Sum V 7.64 s Sum V 8.9 s Sum V 1.05 s Sum V 3.83 s Sum V 5.63 s Sum V 3.75 Sum V Sum V
Base %S 25 %W 20 %S 27 %W 22 %S 7 %W 5 %S 11 %W 13 %S 18 %W 25 %S 12 %W 16 %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Wind a 2 ft 445 113 47.97 a 2 ft 1780 454 5.978
6,240 b 2 ft 157 0.7 0.667 b 2 ft 405 1.7 0.765
c 2 ft 22 1.7 2.857 c 3-4 32 2.4 11.21
p =d 2 ft 157 4.3 1.714 d 3-4 32 0.9 6.729
Level V <
35%Base
Shear
p =73 Vadj line 2 2.23 13.9 41 2.715 Vadj line 7
1.30 V above 7.64 V above 8.9 V above 1.05 V above 3.83 V above 5.63 V above 3.75 V above V above
1.25 1.35 0.31 0.8 1.56 0.97
Regular w Sum V 11.1 w Sum V w Sum V w Sum V 18.5 w Sum V w Sum V 7.44 Sum V Sum V
Vadj line 7Vadj line6 or 8Vadj line5 or 7
Base Level V Base Level V Base Level V
Vadj line6 or 8
Vadj line6 or 8
Vadj line2 or 4
Vadj line2 or 4
Vadj line3 or 5
Vadj line3 or 5
Vadj line4 or 6
Vadj line4 or 6
Vadj line5 or 7
Vadj line5 or 7
Lines Run
Front - Back
Base Level V Base Level V
OTM= if St'k Vnet*ht
Vadj line 2 Vadj line4 or 6Vadj line3 or 5Vadj line2 or 4Vadj line1 or 3
Vadj line1 or 3
Vadj line1 or 3
Base Level V Base Level V Base Level V
if "s" pQe - 0.2 Sds D
if "w" 0.6D
RM= W / ft* Lg^2 / 2k SumV*Ht*Lg/∑Lg
Load Distribution to Segments: RM & OTM Pg 5.2 of 5.4 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Lateral Line A Line B Line C Line D Line E Line F Line G Line H
Force Seis %= Wind %= W/ft=if "w",-snow Vadj= V= SumV=
Distrib trib fl A/Sum flA trib wl A/Sum wlA Sum lev. w*trib area SumV from adj Ln Ln%*Vmax SorW Vadj+Vabv+V
2nd %S 30 %W 25 %S 35 %W 33 %S 13 %W 35 %S 15 %W 17 %S 7 %W -10 %S %W %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Seismic 1 A-B 382 28 30.12 1 2 ft 120 2.5 12.52 1a 2 ft 138 0.2 15.14
15,576 1b 2 ft 138 0.2 15.14
p =4 A-B 382 1.2 5.492 4a B-C 143 0.2 24.53
Level V > 5 A-B 382 1.4 6.436 4b B-C 143 0.2 24.53 5a B-C 143 0.2 2.384
35%Base 5b B-C 143 0.4 3.886
Shear
p =b b 1.03
1.00 2nd Level V 4.67 a 2nd Level V 5.45 2nd Level V 2.09 a 2nd Level V 2.34 2nd Level V 1.03 2nd Level V 2nd Level V 2nd Level V
Regular s 28 Sum V 4.67 s Sum V 5.45 s Sum V 2.09 w 6 Sum V 3.37 s Sum V Sum V Sum V Sum V
1st %S 30 %W 22 %S 35 %W 25 %S 13 %W 15 %S 15 %W 25 %S 7 %W 13 %S %W %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Seismic 1a A-B 776 3 21.41 1 A-C 409 12 83.45 1a C-D 370 12 30.75 1 2 ft 135 1.1 22.65
15,225 1b A-B 776 2.8 19.82 1b C-D 370 3.5 16.56 2 2 ft 135 1.1 22.65
1c A-B 776 2.5 17.77
p =4a B-C 441 0.8 83.7
Level V > 5 A-B 776 5.9 30.67 4b B-C 441 0.8 83.7 5a C-D 406 1.2 12.59
35%Base 5b C-D 406 1.2 14.68
Shear
p =19 Vadj line B 2.12 13 3.53 Vadj line G
1.00 b V above 4.67 b V above 5.45 b V above 2.09 V above 3.37 b V above V above V above V above
a 1st Level V 4.57 1st Level V 5.33 1st Level V 2.04 1st Level V 2.28 a 1st Level V 1 1st Level V 1st Level V 1st Level V
Regular s Sum V 9.24 s Sum V 10.8 s Sum V 6.24 s Sum V s Sum V 4.53 Sum V Sum V Sum V
Base %S 30 %W 25 %S 35 %W 28 %S 13 %W 17 %S 15 %W 22 %S 6 %W 8 %S %W %S %W %S %W
Level Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM Seg tA W/ft RM OTM
Wind 1 2 ft 2349 259 11.41 1 2 ft 157 17 25.87
7,610 2 2 ft 157 0.1 0.381
3 2 ft 22 0.1 0.826
p =4 2 ft 22 0.8 7.405
Level V < 5 2 ft 834 56 11.6
35%Base
Shear
p =24 Vadj line B 1.47 12.1 30 1.04 Vadj line G
1.30 V above 9.24 V above 10.8 V above 6.24 V above V above 4.53 V above V above V above
1.9 2.14 1.28 1.66 0.62
Regular w Sum V 12.6 w Sum V w Sum V 19.6 w Sum V w Sum V 6.19 Sum V Sum V Sum V
Vadj line GVadj lineE or GVadj lineB or D Vadj lineC or E Vadj lineD or F Vadj lineF or H
Lines Run
Left - Right
Vadj line B
Base Level V Base Level V Base Level V
if "s" pQe - 0.2 Sds D
if "w" 0.6D
RM= W / ft* Lg^2 / 2k
Base Level V Base Level V Base Level V Base Level V
OTM= if St'k Vnet*ht
SumV*Ht*Lg/∑Lg
Base Level V
Vadj lineF or H
Vadj lineF or H
Vadj lineA or C
Vadj lineA or C
Vadj lineB or D
Vadj lineB or D
Vadj lineC or E
Vadj lineC or E
Vadj lineD or F
Vadj lineD or F
Vadj lineE or G
Vadj lineE or G
Vadj lineA or C
Seismic Load Distribution to Grid Lines Pg 5.3 of 5.4 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
Front - Back Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing
2nd Level wt/ft % % % % % % % %
Roof 2 10
1/2 Ext Wl 2 12
Ceil 2 5
1st Level wt/ft 25 27 7 11 18 12
1/2 Ext Wl 2 12
Int Wl 2 10
Floor 2 10
Roof 1 10
1/2 Ext Wl 1 12
Ceil 1 5
Base Level wt/ft 25 27 7 11 18 12
1/2 Ext Wl 1 12
Int Wl 1 10
Floor 1 10
1/2 Ext Wl B 12
Ceil B
Load per Line 25 27 7 11 18 12
A Line B Line C Line D Line E Line F Line G Line H
Left - Right Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing
1st Level wt/ft % % % % % % % %
Roof 2 10
1/2 Ext Wl 2 12
Ceil 2 5
1st Level wt/ft 30 35 13 15 7
1/2 Ext Wl 2 12
Int Wl 2 10
Floor 2 10
Roof 1 10
1/2 Ext Wl 1 12
Ceil 1 5
Base Level wt/ft 30 35 13 15 7
1/2 Ext Wl 1 12
Int Wl 1 10
Floor 1 10
1/2 Ext Wl B 12
Ceil B
Load per Line 30 35 13 15 6
2nd Level Roof =1st Roof & 2nd Level Floor=1st Level Floor =Total Bldg Weight =
Total %
100.0
100.0
100.0
100.0
Total %
100.0
Component Wt.
4,665
4,665
7,686
11,097
1,496
9,257
4,240
3,843
17,339
4,240
272
1,496
2,332
4,665
4,680
7,686
5,182
14,381
Component Wt.
4,66517,561
17,561
Component Wt.
5,118
1,224
2,332
8,674
1,224
Component Wt.Component Wt.
3,727
Sceismic
2,640
Sceismic
58,442
44,573
19,984
6,543
8,780
264
1,463
3,239
4,139
264
8,780
Component Wt.
24 2
1,543
6,000
216
732
2,124
1,401
1,463
1,463 2,927
480
2,927
1,463
12,117
2,160
1,463
2,640
7,350
2,160
2,927
2,927
2,640
2,640
6,000
1,596
71,162
15,120
480
2,802
472
2,596
1,401
11,726
8,673
2,802
48
42,692
7,997
17,561
17,561
1,454
2,124
2,802
2,802
54,174
8,778
10,950
70,710
21,900
Component Wt.
2,596
8,778
21,900
117,716 278,256
100.0
89,379
19,800
3,000
8,974
11,412
2,160
Component Wt.
21,497
Component Wt.
3,600
15,480
3,564
1,800
648
3,600
Component Wt.
5,182
3,843
942
28,637
7,686
7,686
Component Wt.
BUILDING DEAD LOADS
6,543
24,560
7,182
10,950
7,114
3,600
2,916
3,564
2,160
4 11.3 18.7
36.5 4.67 20 12
Component Wt.
7,997
1,463
732
2,491
216
Component Wt.
35,308
7,182
21,900
21,900 6,000
2,916
3,600
6,800
Component Wt.
3,589
6,000
3,000
11,960
1,800
9,396
Wind Force Distribution to Grid Lines Pg 5.4 of 5.4 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
Front - Back Ln Spacing Ln Spacing Ln Spacing Ln Spacing 12.8.4.1 ASCE7 Horizontal Distribution of Seismic & Wind Forces for Flexible Diaphragms
2nd Level Wind Ps Force =% % % % % % %
% Wind P s 19 21 6 16 25 13
1st Level Wind P s Force =% % % % % % %
% Wind P s 20 22 5 13 25 16
Base Level Wind Ps Force =% % % % % % %
% Wind P s 20 22 5 13 25 16
A Line B Line C Line D Line E Line F Line G Line H
Left - Right Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing Ln Spacing
2nd Level Wind Ps Force =% % % % % % %
% Wind P s 25 33 35 17 -10
1st Level Wind P s Force =% % % % % % %
% Wind P s 22 25 15 25 13
Base Level Wind Ps Force =% % % % % % %
% Wind P s 25 28 17 22 8
16.0 34
Zone Area
16.0
Zone Area
87
P s
17
16.054
16.0
16.0
16.054 9
Wind
Wind
6,240
78
16.0
9,706
9,600
30
3,605
16.0
16.0
16.0
54
3,840
16.066
66
2,496
54
16.0
P s
320
Zone Area
78 16.0
208
13 16.0
416
16.0
9 16.0
11
P sZone Area
66 16.0
P s
30 16.0
194
Zone Area
40 16.0
110 -16.0
54
21
299
16.0
949
-16.021
54 -16.0
-16.0
-16.0
1,908
1,324
110 -16.0
Zone Area P s
16.026
3,796
159 16.0
584
78 16.0
7,610
486
30 16.0
P sZone Area
75
135 16.0
P s
16.0
22
Zone Area P s
2,347
Ps
62
Zone Area P s
2,080
100.00
100.00
Total %
100.00
Total %
90 -16.0
130 16.0
320
Zone Area P s
16.0
1,813
Zone Area Ps
1,178
Zone Area Ps
155 16.0
-16.090
1,045
Zone Area
96 16.0
51
51
P s
16.0
640
16.0
110 16.0
30 16.0
16.0
Zone Area
66 16.0
100.00
Total %
Zone Area Ps
Zone Area
54
16.0
P s
Zone Area
1,248
Zone Area
30
43
2,506
Zone Area P s
54
10 16.0
Zone Area Ps
78 16.0
346
-384
Zone Area Ps
54
Zone Area
-16.0
P s
-16.0
Zone AreaZone Area P s Ps
2,987
43 16.0
1,942
Zone Area
16.0
Zone Area P s
Ps
Zone Area
P s
Zone Area Ps
Ps
P sZone Area
P sZone Area
Zone AreaPs P sPsZone AreaPs Total %
4,426
1,728
2,592
Zone Area Ps Total %P s
2,592
960
1,728
Zone Area
2,112
5,114
3,168
2,496
3,744
960
6,217
-1,728
-3,540
4,327
100.00
Total %
2,112
-1,728
-3,540
154
2,496
24
1/2 Wl 1 zn C P s
1/2 Wl 1&B A P s
1/2 Wl 1&B C P s
Roof zone B P s
Roof zone D P s
1/2 Wl 2 zn A P s
1/2 Wl 2 zn C P s
1/2 Wl 2 zn A P s
1/2 Wl 2 zn C P s
Roof 1 zone B P s
Roof 1 zone D P s
1/2 Wl 1 zn A P s
Roof zone B P s
Roof zone D P s
1/2 Wl 2 zn A P s
1/2 Wl 2 zn C P s
1/2 Wl 1&B A P s
1/2 Wl 1&B C P s
1/2 Wl 2 zn A P s
1/2 Wl 2 zn C P s
Roof 1 zone B P s
Roof 1 zone D P s
1/2 Wl 1 zn A P s
1/2 Wl 1 zn C P s
2 4 11.3
36.5 4.67 20 12
74 16.0
416
18 16.0
26 16.0
18
832
Zone Area
16.0
16.0
16.0
30
66
37 16.0
Zone Area P s
78
54 16.0
30
16.0
16.0
Segment Construction: w/ Hold-Downs Page 6.1 of 6.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis & Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Front Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
to Uplift = Overturning Moment (OTM) - Resisting Moment (RM) / Segment Length (Seg Lg).
Back Maximum required Hold Down (HD Type) selected from Hold-down and Wall Strap Schedule on Page 11.
2nd HD HD HD HD HD HD HD HD
Level Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type
a NA a 1,455 D H2 a 983 D H1a a1 402 D H1a
b 1,332 D H2 a2 260 D H1a
c NA c 1,269 D H2 b 4,648 D H8 b 1,165 D H1b a3 138 D NA
d 1,137 D H1b b 409 D H1a
V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
WlD WlD WlD WlD WlD WlD WlD WlD
Roof Uplift from Side to Side Winds resisted by Left and Right Ext. Walls Uplift (plf) Rf 2 @ Ext Wl Uplift Detail @ Rf 2 & Ext Wl D V
1st Fl HD Fl HD Fl HD Fl HD Fl HD Fl HD HD HD
Level Seg Uplift R Type Seg Uplift C Type Seg Uplift R Type Seg Uplift R Type Seg Uplift R Type Seg Uplift R Type Seg Uplift Type Seg Uplift Type
a 725 D H1a a 3,619 D H4 a 3,524 D H4 a1 49 D NA
b 598 D H1a b 10,739 D H14 b 2,425 D H2 a2 1,180 D H1b
c 1,651 D H2 c 1,001 D H1b b 1,304 D H2
d 477 D H1a d 1,001 D H1b
V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
WlD WlD WlD WlD WlD WlD WlD WlD
Roof Uplift from Side to Side Winds resisted by Left and Right Ext. Walls Uplift (plf) Rf 1 @ Ext Wl Uplift Detail @ Rf 1 & Ext Wl NA
Straps/Hold-Downs must run continuous down through the Wall below to the Foundation. If no Wall below; tie to Beams, sized for Hold-Down Point Loads.
Base HD HD HD HD HD HD HD HD
Level Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type
a NA a NA
Wind b 3 D NA b NA
Controls c 59 D NA c 438 D H1a
Use V d NA d 487 D H1a
140%
Over
Seismic
Values V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
per NDS WlD WlD WlD WlD WlD WlD WlD WlD
Tbl. 4.2B Shear per Linear Foot (V (plf)) = Sum of Shear at that Line & Level (Sum V) / Linear Feet of Shear Wall at that Line & Level (Sum Seg Lgth)
Maximum required Shear Wall Construction or Shear Frame for Wall Type Symbol is selected from Shear Wall Schedule on Page 11.
6
102 190
6
6 2
210
70
6
456
22
57
Lines Run
Front - Back
4
210
594
210 1,562
6
148
44 6
152
6 2
578
291
6
181
6
Segment Construction: w/ Hold-Downs Page 6.2 of 6.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Side Line A Line B Line C Line D Line E Line F Line G Line H
to Uplift = Overturning Moment (OTM) - Resisting Moment (RM) / Segment Length (Seg Lg).
Side Maximum required Hold Down (HD Type) selected from Hold-down and Wall Strap Schedule on Page 11.
2nd HD HD HD HD HD HD HD HD
Level Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type
1 121 D NA 1 951 D H1a 1a 4,969 D H8
1b 4,969 D H8
4 1,081 D H1b 4a 8,094 D H14
5 1,170 D H1b 4b 8,094 D H14 5a 713 D H1a
5b 910 D H1a
V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
WlD WlD WlD WlD WlD WlD WlD WlD
Roof Uplift from Front to Back Winds resisted by Front and Back Ext. Walls Uplift(plf) Rf 2 @ Ext Wl Uplift Detail @ Rf 2 & Ext Wl D W
1st Fl HD Fl HD Fl HD HD Fl HD HD HD HD
Level Seg Uplift R Type Seg Uplift R Type Seg Uplift R Type Seg Uplift Type Seg Uplift R Type Seg Uplift Type Seg Uplift Type Seg Uplift Type
1a 4,089 D H5 1 5,804 D H11 1a 1,445 D H2 1 3,317 D H4
1b 3,935 D H5 1b 1,870 D H2 2 3,317 D H4
1c 3,726 D H4
4a 27,646 D H19
5 3,906 D H5 4b 27,646 D H19 5a 2,836 D H4
5b 3,358 D H4
V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
WlD WlD WlD WlD WlD WlD WlD WlD
Roof Uplift from Front to Back Winds resisted by Front and Back Ext. Walls Uplift(plf) Rf 1 @ Ext Wl Uplift Detail @ Rf 1 & Ext Wl NA
Straps/Hold-Downs must run continuous down through the Wall below to the Foundation. If no Wall below; tie to Beams, sized for Hold-Down Point Loads.
Base HD HD HD HD HD HD HD HD
Level Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type Seg Uplift Type
1 NA 1 357 D H1a
Wind 2 131 D NA
Controls 3 180 D NA
Use V 4 579 D H1a
140%5 NA
Over
Seismic
Values V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf) V (plf)
per NDS WlD WlD Wl∆WlD WlD WlD WlD WlD
Tbl. 4.2B Shear per Linear Foot (V (plf)) = Sum of Shear at that Line & Level (Sum V) / Linear Feet of Shear Wall at that Line & Level (Sum Seg Lgth)
Maximum required Shear Wall Construction or Shear Frame for Wall Type Symbol is selected from Shear Wall Schedule on Page 11.
6 22 6
172 1321,363
22
841
Lines Run
Left - Right
348
254
3 2 6
206
3
261
4 33 4
525 654
237677
Diaphragm & Collector/Tie: Construction Page 8.1 of 8.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Front Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line .8.
to Seg C/T Load (back) - max. load on the Collector /Tie between this and Seg above. C/T Type - min. adequate Collector/Tie. Seg beg - feet Seg begins front of Quad Line.
Back front - C/T load at front of the front most Seg. Shear - the average Diaphragm Shear along the Line. IF "Gap" correct Line C/T discontinuity. Diph V. per ASCE7 12.10.1.1
2nd C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
Roof Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg
a a a a1
b 1920 ∆ C2 a2 253 ∆ C1 4
c 1499 ∆ C1 c 2198 ∆ C2 b 270 ∆ C1 b 1964 ∆ C2 a3 709 ∆ C1 12
d 3572 ∆ C3 b 1316 ∆ C1
front 149 NA front 144 NA front front 241 ∆ C1 front 6 NA front 0 NA front front
Shear(plf)14 Shear(plf)17 Shear(plf) Shear(plf)7 Shear(plf)18 Shear(plf)12 Shear(plf) Shear(plf)
Rf Diaph D R6 Rf Diaph D R6 Rf Diaph Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph Rf Diaph
1 Rf C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
2 Fl Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg
a a a a1
b 1152 ∆ C1 b 807 ∆ C1 b 3523 ∆ C3 a2 1634 ∆ C1 10
c 6885 ∆ C6 c 250 ∆ C1 b 2580 ∆ C2
d 1729 ∆ C1 d 260 ∆ C1
front 619 ∆ C1 front 1518 ∆ C1 front 58 NA front 734 ∆ C1 front 4 NA front 35 NA front front
Shear(plf)44 Shear(plf)51 Shear(plf)6 Shear(plf)22 Shear(plf)58 Shear(plf)39 Shear(plf) Shear(plf)
Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph Rf Diaph
Fl Diaph D F6 Fl Diaph D F6 Fl Diaph D F6 Fl Diaph D F6 Fl Diaph D F6 Fl Diaph D F6 Fl Diaph Fl Diaph
1st C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
Floor Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg Seg back Type beg
a a
Wind b 3767 ∆ C4 b 4475 ∆ C4
Control c 4249 ∆ C4 c 3340 ∆ C3
Use V d 6312 ∆ C6 d 6588 ∆ C6
140%
Over
Sched
Values front front front front front front 0 NA front front
per Sec Shear(plf)49 Shear(plf) Shear(plf) Shear(plf)81 Shear(plf) Shear(plf)58 Shear(plf) Shear(plf)
2306.3.2 Fl Diaph D F6 Fl Diaph Fl Diaph Fl Diaph D F6 Fl Diaph Fl Diaph D F6 Fl Diaph Fl Diaph
Lines Run
Front - Back
If Rf or Fl Diaph return "block?", load values are higher than the diaphragm capacity. Change to blocked diaphragm or fastener Option (pg 10) or add Shear Wall (pg 3or4)
Diaphragm & Collector/Tie: Construction Page 8.2 of 8.2 MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
Side Line A Line B Line C Line D Line E Line F Line G Line H
to Seg C/T Load (left) - max. load on the Collector /Tie between this and Seg to left. C/T Type - min. adequate Collector/Tie. Seg beg - feet Seg begins right of Quad Line.
Side right - C/T load at right of the right most Seg. Shear - the average Diaphragm Shear along Line. If "Gap" correct Line C/T discontinuity. Diph. V per ASCE7 12.10.1.1
2nd C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
Roof Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg
1 1 1a
1b 2438 ∆C2 3
4 2958 ∆C3 4a 697 ∆C1
5 3356 ∆C3 4b 3321 ∆C3 3 5a 1297 ∆C1
5b 1394 ∆C1 3
right 194 NA right 558 ∆C1 right 105 NA right 689 ∆C1 right right right right
Shear(plf)20 Shear(plf)23 Shear(plf)9 Shear(plf)29 Shear(plf)Shear(plf)Shear(plf)Shear(plf)
Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph Rf Diaph Rf Diaph Rf Diaph
1 Rf C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
2 Fl Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg
1a 1 1a 1
1b 883 ∆C1 5 1b 2502 ∆C2 13 2 1850 ∆C2
1c 1733 ∆C1 9
4a 7408 ∆C6
5 2537 ∆C2 4b 7867 ∆C6 3 5a 3850 ∆C4
5b 3681 ∆C3 4
right 545 ∆C1 right 1824 ∆C2 right 470 ∆C1 right right 32 NA right right right
Shear(plf)65 Shear(plf)76 Shear(plf)44 Shear(plf)Shear(plf)64 Shear(plf)Shear(plf)Shear(plf)
Rf Diaph D R6 Rf Diaph D R6 Rf Diaph D R6 Rf Diaph Rf Diaph D R6 Rf Diaph Rf Diaph Rf Diaph
Fl Diaph D F6 Fl Diaph D F6 Fl Diaph D F6 Fl Diaph Fl Diaph D F6 Fl Diaph Fl Diaph Fl Diaph
1st C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg C/T Load C/T Seg
Floor Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg Seg left Type beg
1 1
Wind 2 3364 ∆C3
Control 3 3644 ∆C3
Use V 4 3149 ∆C3
140%5 3067 ∆C3
Over
Sched
Values right 486 ∆C1 right right right right right right right
per Sec Shear(plf)68 Shear(plf)Shear(plf)105 Shear(plf)Shear(plf)66 Shear(plf)Shear(plf)Shear(plf)
2306.3.2 Fl Diaph D F6 Fl Diaph Fl Diaph D F6 Fl Diaph Fl Diaph D F6 Fl Diaph Fl Diaph Fl Diaph
If Rf or Fl Diaph return "block?", load values are higher than the diaphragm capacity. Change to blocked diaphragm or fastener Option (pg 10) or add Shear Wall (pg 3or4)
Lines Run
Left - Right
Shear Wall and Hold Down Schedules Schd W MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
SHEAR WALL OPTIONS:Place an "X" in the appropriate shaded block. Select only one option under each heading (except System when using frames)
Special Zone Hardware Mfg.Wall Framing Material Shear Wall System Ply/PB Wall Sheathing Fasteners
No X Simpson Doug Fir or So.Pine X WS-All Plywd or PB X 15/32" CC or CD Ply X 8d
Los Angeles Area USP X Hem Fir (s.grav.<.49)WS-Gyp,Stuc or Ply 15/32" Struc I Ply 10d
3-1/2" Metal Studs Wall Frame Units on Shd X 3/8"or1/2" CD Ply o/GB 14ga Staple
Other (Apx.W)Other (See Apx. W)Stud Spacing 1/2"Ext M,S/M-2 Prtcl Bd 1"Screw in SteelTo Customize, Overwrite Sched. on Apx. W below 16 in. o.c.Other Sheathing/Fastener Combo (See Apx. W)
WIND AND EARTHQUAKE DATA 18 IBC SHEAR WALL SCHEDULEWINDSCEISMICReisk Category II Hem-Fir Framing: values reduced to 82% of DF/SP
Risk Category II S Design Cat D Seis. Site Class D Wall Construction Footing Rf. Block
Basic Wind Speed 110 Ss Acc. %g 1.36 S. Res Coef. Cs 0.17 Wall Wind Seismic Edge AnchorSill to Framing Top Plate
Wind Exposure B S1 Acc. %g 0.465 Resp Mod Factor R 6.5 Type Shear Shear Nail Bolts Nail Lag Clips
Wind Horiz. (psf)16 Res Coef Sd1 0.32 Base V Symbol Capacity Capacity 8d 5/8"x12 16d 1/2"A35
Wind Vert. (psf)-16 Res Coef Sds 1.09 System:Light Frame SW (plf) (plf)GF:738 GF:100 GF:392 GF:470
ASCE7-16 Ch. 28 Part 2:Calculation Method per 12.8 ASCE7 & Sec.1613.2.5.2 IBC APA Tbl.1 Note 1,2 Note 3 Note 6 Note 7 Note 6,8 Note 9,10
construct wall as spec'd per symbol or any belowWALL HOLD-DOWN & STRAP SCHEDULE
Hem-Fir Framing: values reduced to 82% of DF/SP
Hold-Down Max. Min. Wall Foundation Bolt D 6 298 213 1/2"Ply 6"40"oc 6"oc 22"oc 24"oc
Symbol Uplift Post Fl to Fl Anchor Type Bolt 2,4,5 D 4 436 312 1/2"Ply 4"27"oc 4"oc 15"oc 16"oc
lbs.Size Strap Straps HD Dia.2,4,5 D 3 563 402 1/2"Ply 3"21"oc 11"oc 12"oc
Note 3,4 Note 2 Note 2,4 Note 2 2,4,5 D 2 735 525 1/2"Ply 2"16"oc 9"oc 10"oc
NA up to 246 use the hold-down across or below req'd type 2,4,5 D 44 872 623 ea side 1/2"Ply 4"14"oc 7"oc 8"oc
D H1a 984 2x CS20-18"LSTHD8 2,4,5 D 33 1,125 804 ea side 1/2"Ply 3"10"oc 6"oc 6"oc
D H1b 1,230 2x CS16-26"STHD10 LTT20B 1/2"2,4,5 D 22 1,469 1,050 ea side 1/2"Ply 2"8"oc 4"oc 4"oc
D H2 2,460 2-2x MST 48"STHD14 HDU2 5/8"?
D H4 3,743 2-2x MST 60"HDU4 5/8"1
D H5 4,629 2-2x MST 72"HDU5 5/8"2
D H8 5,715 4x4 CMST12+78"HDU8 7/8"3
D H11 7,556 4x6 CMST12+178"HDU11 1"4
D H14 11,788 4x8 2- CMST12+60"HDU14 1"5
D H19 15,875 6x6 HD19 1-1/4"6
?Add inches to Fl to Fl Tie Strap for gap across Joist 7
1 8
2 9
10
3
4
14
32,579
X
Rased Floor
Wall
Sheathing
Material
Straps and HD's as Mfg. by Simpson Strong-Tie Co. Cat C-2015
Nail Straps w/10d or SDS 1/4" Scw at HD (min.pen.1-3/4") Anchors into 8" Stem wall
and Mfg. Data for Nailing, Bolt and Embedment Requirements
If No Cont. Rim Joist Add Lgth Of Gap.10d at CS, 16d: CMST & MST
Straps and Hold-Downs must run continuous to Walls below;
if no Wall below, tie to Beams, sized for Hold-Down Point Loads
Sheathing: 15/32" (4 ply min) CD, CC Plyor OSB with all edges blocked
Framing: 2x HF typ @ 16"oc.for 3/8" up to 24"oc.for 1/2", 3x req'd if 10d w/ +1-5/8" penetration, 2" or 3"oc
Typical Fasteners: 8d Common or Galv. Box nails (no sinkers), nail field @12"
3x (or 2x w/ dbl AB) at plate and 3x panel edges at walls w/ Shear > 300 lbs.
Offset panel edges on opposite sides of wall and stagger plate splices
Anchor Bolts spaced per Schd w/ 3"x3"x0.229" Plate Washers req'd at Mud Sill
Stagger 16d nails in 2x, lags at 3x plates when no sheathing continuity to Rim Joist
Pre-drill 3/8" hole for Lag. Provide Washer. Adjust lgth for 2" penetration into Joist.
Clips: Plate to Blocks only req'd if no shear sheathing continuity from Wall to Blocks
Anchors and Clips as Mfg. by Simpson Strong-Tie Co. Cat C-2015
Stucco Lath Nails min. : galv. 11ga. x1-1/2" long w/ 7/16" dia head furred out 1/4".
Diaphragm, Collector, Uplift & Tie-Down Schedules Schd Y MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis &
Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Construction Design Software
DIAPHRAGM OPTIONS: COLLECTOR / TIE & DIAPHRAGM SCHEDULERf/Fl Framing Mat.Rf/Fl Diaphragm Fasteners Collector Sizing determined per 12.12.1.1 ASCE7
X DF or So. Pine Roof: 1/2" CDX or OSB 8d Com Only C/T Max.Collector/Tie Tie Tie Rod
Hem Fir Floor: 3/4" CDX or OSB X 8d@Rf, 10@Fl Type Force Cont. Joist or Strap Washer
Other T&G Glue & Nail 10d Com Only Symbol (lbs) Solid Blocking or Cont.Dia.Dia.HD
To Customize, Overwrite Schedule or See Apx. D 14 ga Staple less of C&T parallel to grain:425 Joist 20ksi 625
Change Hardware on Wall Schedule (Shd W) Tab Other Note 1,2,6 Note 2,3,4 Note 4 Note 5 Note 7
Use Collector/Tie as spec'd per symbol or any belowNA240Note: 20%reduction due to L shaped plan or SW vetical offset ROOF UPLIFT CONNECTOR SCHEDULE D C1 1,784 2x4 MSTI26
Hem-Fir Framing: values reduced to 82% of DF/SP D C2 2,800 2x6 MST48 5/8"1.43 HTT4
Wall Uplift Stud to Plate Plate to Rafter Stud to Rafter D C3 3,696 2x8 MST60 5/8"1.88 HTT5
Type (plf)at 16" oc at 24"oc at 16"at 16" oc D C4 4,640 2x10 MST72 7/8"2.36 HDU8
50 D C5 5,680 2x12 2-MST37 7/8"2.89 HDU8
D T 82 Ply Nailing or H!H1 D C6 8,320 2-2x10 2-MST60 1"4.24 HDU11
D U 164 A35 H1 H1 H2A D C7 8,520 2-2x10 HST5 1"4.34 HDU11
D V 234 SSP H2.5A H2.5A H10S ?D W 357 SSP H8 H8 H10S 1
D X 517 DSP MTS12 MTS12 MTS12 2
D Y 832 TSP HTS20 HTS20 HTS20 3
D Z 1,517 FTA7 FTA7 FTA7 4
?5
1 Anchors and Clips as Mfg. by Simpson Strong-Tie Co. Cat C-2015 6
Rod Strength Options:7
Standard Strength X 8 ALLTHREAD ROD CAPACITY High Strength Roof Shear Diaphragm Edge Floor Shear Diaph.
Combo Std & High Diaphragm Load Material Nail Diaphragm Load Material
Standard Strength Rod High Strength Rod Anchor Bearing Plate NDS 14.2/2.0 (plf)Note 1,2,4 Note 3 Symbol (plf)Note 1,2,4
Size Dia.lbs.Anchor Bolt Size Dia.lbs.Bolt Type Plate Size lbs.8d Nail b=blocked 10d Nail b=blocked
2500 psi Conc.2500 psi Conc.D R6 170 1/2" Ply 6"D F6 215 3/4" Ply
4 1/2" 4,271 4h 1/2" 7,753 SB1x30"A 2" x 2" x 3/16"2,500 D R6b 270 1/2" Ply 6"D F6b 320 3/4" Ply
5 5/8"6,673 5h 5/8"11,620 See Det B 3" x 3-1/4" x 3/8"6,090 D R4b 360 1/2" Ply 4"D F4b 425 3/4" Ply
6 3/4"9,609 6h 3/4"17,083 See Det C 6" x 3-1/4" x 5/8"12,180 D R3b 530 1/2" Ply 2-1/2"D F3b 640 3/4" Ply
7 7/8"13,079 7h 7/8"22,750 See Det D 9" x 3-1/4" x 7/8"18,280 D R2b 600 1/2" Ply 2"D F2b 730 3/4" Ply
8 1"17,082 8h 1"29,732 See Det E Custom 24,000 ? ?
9 1-1/8"21,620 9h 1-1/8"36,188 See Det ? 1
1 1-1/4"26,691 1h 1-1/4"49,809 See Det 2
? ? 3
4
" in 3000 psi
5/8" SSTB16
7/8" SSTB28
SB 7/8"x24
SB 1"x30
Provide End Wall Post at ea. TD: 2-2x min at 4-5, 4x min at 6-7 and 6x min at 8-1 Rod Size
Nut Capacity(1/3 Fu) for ea. Rod Diameter Exceeds Schedule Rod Capacity (2/3 fy)
Floor 3/4 CD-AC Ply/OSB, Roof 1/2 CD Ply/OSB (Block All Edges at b suffix Diaph)
Framing: 2x typ, 3x req'd if 10d pen more than1-5/8", or nails spaced less than 3"oc
Typ. Fasteners: 8d Com. @ Roof,10d Com. @ Floor (no sinkers) field 12"@Rf,10"@Fl
Continuous Rim Rafter/Joist Recommended at Perimeter of all Diaphragms
ASTM A36 Standard Strength Steel
See Det
See Det
Between Blocks or breaks in Rafters/Joists provide straps to maintain Tie continuity
A properly sized continuous Rafter or Joist can act as both Collector and Tie
Provide Cont. Rim Joist/Rafter or Solid Blocking at all Shear Wall Grid Lines
ASTM A193 B7 High Strength Steel Plate Area x 625 psi = Capacity
ASTM A36 Std Strength Steel
Overstrength Factor for Seismic Included in base shear per 12.4.3.1 &12.10.2.1 ASCE7
HD at Rod to Shear Wall and/or Rft/Jst. Mfg. by Simpson Strong-Tie Cat C-2015
Connect Continuous Collector/Tie to shear wall as required by Shear Wall Schedule
Provide Washer w/ Dia. (inches) at end of blocked Rft/Jst bays, Mal. iron or 1/4" St.
Run All-thread Rod thru Rft/Jst, lgth=Load/Shear(plf), secure ends w/ Washer or HD
Unblocked
Blocked
Blocked
Blocked
Blocked
Wind Pressure for Exterior Components & Cladding Schd Z MaxQuake © 1995-2021 Archforms Ltd.
Date:MAY 12 2021 Firm:API All Rights Reserved Lateral Load Analysis & Job:SINGH RESIDENCE By:GPM/BM Q21W.2 Overturning Calculation Template
Wind Pressure for GCp
Section 1609.6.3
Horiz P 16.0
GCp P
(psf)
-3.6 -58Uplift-3.4 -54
or -3.2 -51
Out--3.0 -48
Force -2.8 -45
-2.6 -42
-2.4 -38
-2.2 -35
-2.0 -32
-1.8 -29
-1.6 -26
-1.4 -22
-1.2 -19
-1.0 -16
-0.8 -13
-0.6 -10
-0.4 -6
-0.2 -3
0.0 0
Down 0.2 3
Load 0.4 6
or 0.6 10
In-0.8 13
Force 1.0 16
1.2 19
1.4 22
1.6 26
Note:
1. Values are for
enclosed Buildings.
2. Graphs from ASCE7-10
Fig.30.4-1 thru 2C & 4
for GCp. See ASCE 7
Ch 30 for other Config.
DATE: 5/16/2021 COMPANY:
VITRUVIUS BUILD: Base DESIGNED BY: Glen Merkel
CUSTOMER: MANJIT SINGH REVIEWED BY: Glen Merkel
PROJ. ADDRESS: 10628 SE 144TH STREETRENTON, WA 98059
PROJECT SUMMARY
Project Name: SINGH RESIDENCE
Governing Codes:Building Code: 2018 International Building CodeASCE: ASCE 7-16Steel: AISC 360-16Concrete: ACI 318-14Masonry: TMS 402/602-16
Page 1
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
Level: Roof
Module Location: HDR1 TYPModule Type: Roof Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 2
Member Dimensions: (1) 3.5 in. X 7.25 in. X 5.5 ft
Section Adequacy:8.94%
Controlling Factor: Bending Stress Y
Module Location: HDR2 TYPModule Type: Roof Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 1
Member Dimensions: (1) 5.5 in. X 9.25 in. X 8 ft
Section Adequacy:4.23%
Controlling Factor: Bending Stress Y
Module Location: HDR3 TYPModule Type: Roof Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 5.25 in. X 9.5 in. X 5.5 ft
Section Adequacy:21.4%
Controlling Factor: Shear Stress Y
Module Location: HDR4 MASTER BEDROOMModule Type: Roof Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 1
Member Dimensions: (1) 5.5 in. X 9.5 in. X 8.5 ft
Section Adequacy:22.89%
Controlling Factor: Bending Stress Y
Module Location: RB1 ROOF BEAMModule Type: Roof Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 5.25 in. X 9.5 in. X 10 ft
Section Adequacy:34.76%
Controlling Factor: Bending Stress Y
Module Location: RB2 ROOF BEAMModule Type: Roof Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 9.5 in. X 10 ft
Section Adequacy:44.98%
Controlling Factor: Bending Stress Y
Module Location: HDR8 FRONT ENTRYModule Type: Floor Beam
Material Type: Solid Sawn Douglas Fir-Larch No. 1
Member Dimensions: (1) 5.5 in. X 9.5 in. X 10 ft
Section Adequacy:28.53%
Controlling Factor: Bending Stress Y
Level: Main Floor
Module Location: TPY SECOND FJ1Module Type: Floor Joist
Material Type: I-Joists Roseburg RFPI 40
Member Dimensions: (1) 2.3125 in. X 11.875 in. X 19.5 ft
Section Adequacy:2.76%
Controlling Factor: Deflection
Module Location: TPY SECOND FJ2Module Type: Floor Joist
Material Type: I-Joists Roseburg RFPI 20
Member Dimensions: (1) 1.75 in. X 11.875 in. X 16 ft
Section Adequacy:30.53%
Controlling Factor: Deflection
Module Location: FB1 AT REAR PATIOModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 5.25 in. X 18 in. X 21.5 ft
Section Adequacy:13.83%
Controlling Factor: Bending Stress Y
Module Location: FB2 AT EATING AREAModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 10 ft
Section Adequacy:31.65%
Controlling Factor: Bearing Stress
Module Location: FB3 AT FRONT BALCONYModule Type: Floor Beam
Material Type: Structural Composite Lumber RedBuilt 2.0E Redlam LVL
Member Dimensions: (1) 1.75 in. X 11.875 in. X 12.33 ft
Section Adequacy:47.4%
Controlling Factor: Bending Stress Y
Module Location: FB4 BEAM AT LIVING RMModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 5.25 in. X 16 in. X 18.5 ft
Section Adequacy:25.69%
Controlling Factor: Deflection
Module Location: FB6 BEAM AT LIVING RMModule Type: Floor Beam
Page 2
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 18.5 ft
Section Adequacy:35.25%
Controlling Factor: Deflection
Module Location: FB5 NEAR STAIR AREAModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 7 in. X 11.875 in. X 13 ft
Section Adequacy:7.36%
Controlling Factor: Bending Stress Y
Module Location: FB7 BEAM AT DINING RMModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 11 ft
Section Adequacy:30.4%
Controlling Factor: Bending Stress Y
Module Location: FB8 AT ENTRY AREAModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 1.75 in. X 11.875 in. X 7 ft
Section Adequacy:42.03%
Controlling Factor: Shear Stress Y
Module Location: FB9 AT LIVING ROOMModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 9.5 in. X 6 ft
Section Adequacy:66.23%
Controlling Factor: Shear Stress Y
Module Location: FB10 AT KITCHENModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 18.67 ft
Section Adequacy:39.07%
Controlling Factor: Deflection
Module Location: FB11 AT KITCHEN_DINING
Module Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 9.5 in. X 6 ft
Section Adequacy:30.89%
Controlling Factor: Shear Stress Y
Module Location: FB12 OVER GARAGEModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 13.75 ft
Section Adequacy:41.44%
Controlling Factor: Deflection
Module Location: FB13 OVER GARAGEModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products LVL
2.0E Rigidlam
Member Dimensions: (1) 3.5 in. X 11.875 in. X 13.75 ft
Section Adequacy:53.21%
Controlling Factor: Deflection
Module Location: FB14 OVER GARAGE
Module Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 5.25 in. X 11.875 in. X 14.5 ft
Section Adequacy:1.72%
Controlling Factor: Deflection
Module Location: FB15 OVER GARAGEModule Type: Floor Beam
Material Type: Glulams Stress Class Rated 24F-1.8E 24F-V4 DF/DF
Member Dimensions: (1) 10.75 in. X 21 in. X 23.5 ft
Section Adequacy:4.15%
Controlling Factor: Bending Stress Y
Module Location: FB16 OVER GARAGEModule Type: Floor Beam
Material Type: Glulams Stress Class Rated 24F-1.8E 24F-V4 DF/DF
Member Dimensions: (1) 8.75 in. X 21 in. X 21 ft
Section Adequacy:5.72%
Controlling Factor: Bearing Stress
Module Location: HDR5 TYPModule Type: Floor Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 2
Member Dimensions: (1) 3.5 in. X 7.25 in. X 5 ft
Section Adequacy:26.12%
Controlling Factor: Shear Stress Y
Module Location: HDR6 LIVING ROOMModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 3.5 in. X 9.5 in. X 9 ft
Section Adequacy:19.05%
Controlling Factor: Bending Stress Y
Module Location: HDR7 AT LIVING RMModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 5.25 in. X 11.875 in. X 11.5 ft
Section Adequacy:36.81%
Controlling Factor: Shear Stress Y
Module Location: HDR9 GARAGE DOOR HEADER
Module Type: Floor Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 1
Member Dimensions: (1) 5.5 in. X 11.5 in. X 10 ft
Section Adequacy:10.67%
Controlling Factor: Bending Stress Y
Module Location: HDR10 GARAGE DOOR HDRModule Type: Floor Beam
Material Type: Solid Sawn Spruce-Pine-Fir No. 1
Member Dimensions: (1) 5.5 in. X 11.5 in. X 16.5 ft
Section Adequacy:43.95%
Controlling Factor: Bending Stress Y
Module Location: HDR11 GARAGEModule Type: Floor Beam
Material Type: Structural Composite Lumber Roseburg Forest Products 2.0E LVL
Rigidlam
Member Dimensions: (1) 5.25 in. X 9.5 in. X 6.5 ft
Section Adequacy:22.07%
Controlling Factor: Bending Stress Y
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: HDR1 TYP CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 2 (1) 3.5 X 7.25 DRY
HDR1 TYP DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 5.5 Member Slope: 0/12 Actual Length (ft): 5.5 Roof Pitch: 0/12
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
25.38 111.15 25.9 4.9 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 875 450 135 1150 425 1400 510
Adjusted Values 1138 540 135 1208 425 1400 510
CM 1111111
CT 1111111
Ci 1111111
CF 1.3 1.2 1 1.05 1 1 1
Bending Adjustment Factors Cfu = 1 Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 5.5 0 5.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (15.7%)
PASS (8.9%)
PASS (75.9%)
PASS (57.5%)
MAGNITUDE
130.8
1191.1
0.066 (=L/997)
180.7
STRENGTH
155.3
1308.1
0.275 (=L/240)
425.0
LOCATION (ft)
0
2.75
2.75
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A8380013750000000
B8380013750000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 500 500 0 5.5 Snow Y
Uniform (lbf/ft) 300 300 0 5.5 Dead Y
Self Weight (lbf/ft) 4.9 4.9 0 5.5 Dead Y
Page 3
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: HDR2 TYP CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 1 (1) 5.5 X 9.25 DRY
HDR2 TYP DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 8 Member Slope: 0/12 Actual Length (ft): 8 Roof Pitch: 0/12
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
50.88 362.75 128.25 9.81 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 900 450 125 625 425 1300 470
Adjusted Values 900 450 125 625 425 1300 470
CM 1111111
CT 1111111
Ci 1111111
CF 1111111
Bending Adjustment Factors Cfu = 1.05Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 80801.001.001.001.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (33.6%)
PASS (4.2%)
PASS (75.6%)
PASS (60.4%)
MAGNITUDE
95.5
991.2
0.098 (=L/983)
168.3
STRENGTH
143.8
1035.0
0.400 (=L/240)
425.0
LOCATION (ft)
0
4
4
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 1239 0 0 2000 0 0 0 0 0 0 0
B 1239 0 0 2000 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 500 500 0 8 Snow Y
Uniform (lbf/ft) 300 300 0 8 Dead Y
Self Weight (lbf/ft) 9.81 9.81 0 8 Dead Y
Page 4
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: HDR3 TYP CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 9.5 DRY
HDR3 TYP DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 5.5 Member Slope: 0/12 Actual Length (ft): 5.5 Roof Pitch: 0/12
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
49.88 375.1 114.56 13.16 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 5.5 0 5.5 0 1.00 1.00 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (21.4%)
PASS (47.8%)
PASS (83.1%)
PASS (36.8%)
MAGNITUDE
262.1
1917.6
0.046 (=L/1422)
474.3
STRENGTH
333.5
3670.6
0.275 (=L/240)
750.0
LOCATION (ft)
0
1.54
2.48
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 3188 0 0 5528 0 0 0 0 0 0 0
B13470024600000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 225 225 0 5.5 Snow Y
Uniform (lbf/ft) 75 75 0 5.5 Dead Y
Point (lbf) 6750 - 1.5 - Snow Y
Point (lbf) 4050 - 1.5 - Dead Y
Self Weight (lbf/ft) 13.16 13.16 0 5.5 Dead Y
Page 5
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: HDR4 MASTER BEDROOM CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 1 (1) 5.5 X 9.5 DRY
HDR4 MASTER BEDROOM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 8.5 Member Slope: 0/12 Actual Length (ft): 8.5 Roof Pitch: 0/12
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
52.25 392.96 131.71 10.08 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 900 450 125 625 425 1300 470
Adjusted Values 900 450 125 625 425 1300 470
CM 1111111
CT 1111111
Ci 1111111
CF 1111111
Bending Adjustment Factors Cfu = 1.05Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 8.5 0 8.5 0 1.00 1.00 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (24.3%)
PASS (22.9%)
PASS (78.1%)
PASS (53.7%)
MAGNITUDE
108.8
798.1
0.093 (=L/1093)
196.8
STRENGTH
143.8
1035.0
0.425 (=L/240)
425.0
LOCATION (ft)
8.5
5.95
4.51
8.5
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A5600012870000000
B 1288 0 0 2500 0 0 0 0 0 0 0
Reaction Location
A B
Page 6
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 225 225 0 8.5 Snow Y
Uniform (lbf/ft) 75 75 0 8.5 Dead Y
Point (lbf) 1875 - 7 - Snow Y
Point (lbf) 1125 - 7 - Dead Y
Self Weight (lbf/ft) 10.08 10.08 0 8.5 Dead Y
Page 7
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: RB1 ROOF BEAM CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 9.5 DRY
RB1 ROOF BEAM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 10 Member Slope: 0/12 Actual Length (ft): 10 Roof Pitch: 0/12
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
49.88 375.1 114.56 13.16 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 10 0 10 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (49.8%)
PASS (34.8%)
PASS (58.1%)
PASS (59.6%)
MAGNITUDE
167.4
2394.6
0.210 (=L/573)
302.9
STRENGTH
333.5
3670.6
0.500 (=L/240)
750.0
LOCATION (ft)
0
4
4.8
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 2061 0 0 3505 0 0 0 0 0 0 0
B12210023450000000
Reaction Location
A B
Page 8
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 500 500 0 4 Snow Y
Uniform (lbf/ft) 300 300 0 4 Dead Y
Uniform (lbf/ft) 225 225 4 10 Snow Y
Uniform (lbf/ft) 75 75 4 10 Dead Y
Point (lbf) 2500 - 4 - Snow Y
Point (lbf) 1500 - 4 - Dead Y
Self Weight (lbf/ft) 13.16 13.16 0 10 Dead Y
Page 9
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: RB2 ROOF BEAM CODE: 2018 International Building Code
MEMBER TYPE: ROOF BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 9.5 DRY
RB2 ROOF BEAM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 10 Member Slope: 0/12 Actual Length (ft): 10 Roof Pitch: 0/12
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
33.25 250.07 33.94 8.77 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 10 0 10 0 1.00 0.97 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (62.2%)
PASS (45.0%)
PASS (65.1%)
PASS (69.6%)
MAGNITUDE
126.0
2019.5
0.174 (=L/688)
228.1
STRENGTH
333.5
3670.6
0.500 (=L/240)
750.0
LOCATION (ft)
10
5
5.1
10
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A8880014060000000
B10750017190000000
Reaction Location
A B
Page 10
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 125 125 0 5 Snow Y
Uniform (lbf/ft) 75 75 0 5 Dead Y
Uniform (lbf/ft) 250 250 5 10 Snow Y
Uniform (lbf/ft) 150 150 5 10 Dead Y
Point (lbf) 1250 - 5 - Snow Y
Point (lbf) 750 - 5 - Dead Y
Self Weight (lbf/ft) 8.77 8.77 0 10 Dead Y
Page 11
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: TPY SECOND FJ1 CODE:2018 International Building Code
MEMBER TYPE: FLOOR JOIST NDS: 2018 NDSMATERIAL: I-Joists
Roseburg RFPI 40 (1) 11.875 0(in) O.C. DRY
TPY SECOND FJ1 DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 19.5 Member Slope: 0/12 Actual Length (ft): 19.5 O.C. Spacing(in): 16
End Rcap End Rcap End Rcap End Rcap Int Rcap Int Rcap Int Rcap Int Rcap
EI x10⁶ BSW Lams K x10⁶ Mcap Vcap 1.75 NS 3.5 NS 1.75 WS 3.5 WS 3.5 NS 5.25 NS 3.5 WS 5.25 WS
(lbf-in²) (lbf/ft) (lbf) (lbf-ft) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf)
366 0 1 6.18 4855 1550 1200 1550 1400 1550 2500 2660 2625 2870
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft)
119.50100
PASS-FAIL
Shear Force (lbf)
Bending Moment (lbf-ft)
Deflection (in)
Bearing Load (lbf)
PASS/FAIL
PASS (53.9%)
PASS (28.2%)
PASS (2.8%)
PASS (53.9%)
MAGNITUDE
715.0
3485.6
0.474 (=L/494)
715.0
STRENGTH
1550.0
4855.0
0.488 (=L/480)
1550.0
LOCATION (ft)
0
9.75
9.75
0
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A195520000000000
B195520000000000
Reaction Location WS-Web Stiffener Required NSR-No Stiffener Required
A
NSR
B
NSRLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft²) 40 40 0 19.5 Live Y
Uniform (lbf/ft²) 15 15 0 19.5 Dead Y
Page 12
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: TPY SECOND FJ2 CODE:2018 International Building Code
MEMBER TYPE: FLOOR JOIST NDS: 2018 NDSMATERIAL: I-Joists
Roseburg RFPI 20 (1) 11.875 0(in) O.C. DRY
TPY SECOND FJ2 DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 16 Member Slope: 0/12 Actual Length (ft): 16 O.C. Spacing(in): 16
End Rcap End Rcap End Rcap End Rcap Int Rcap Int Rcap Int Rcap Int Rcap
EI x10⁶ BSW Lams K x10⁶ Mcap Vcap 1.75 NS 3.5 NS 1.75 WS 3.5 WS 3.5 NS 5.25 NS 3.5 WS 5.25 WS
(lbf-in²) (lbf/ft) (lbf) (lbf-ft) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf) (lbf)
283 0 1 6.18 3640 1420 950 1420 1225 1420 1935 2135 2035 2435
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft)
1160100
PASS-FAIL
Shear Force (lbf)
Bending Moment (lbf-ft)
Deflection (in)
Bearing Load (lbf)
PASS/FAIL
PASS (58.7%)
PASS (35.5%)
PASS (30.5%)
PASS (58.7%)
MAGNITUDE
586.7
2346.7
0.278 (=L/691)
586.7
STRENGTH
1420.0
3640.0
0.400 (=L/480)
1420.0
LOCATION (ft)
0
8
8
16
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A160427000000000
B160427000000000
Reaction Location WS-Web Stiffener Required NSR-No Stiffener Required
A
NSR
B
NSRLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft²) 40 40 0 16 Live Y
Uniform (lbf/ft²) 15 15 0 16 Dead Y
Page 13
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB1 AT REAR PATIO CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 18 DRY
FB1 AT REAR PATIO DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 21.5 Member Slope: 0/12 Actual Length (ft): 21.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
94.5 2551.5 217.05 24.94 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 0.95Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 21.5 0 21.5 0 1.00 0.90 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (44.6%)
PASS (13.8%)
PASS (22.9%)
PASS (15.5%)
MAGNITUDE
184.9
2920.1
0.553 (=L/467)
633.8
STRENGTH
333.5
3388.8
0.717 (=L/360)
750.0
LOCATION (ft)
21.5
9.68
10.75
21.5
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 6133 1563 0 5154 0 0 0 0 0 0 0
B57501187058960000000
Reaction Location
A B
Page 14
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 225 225 0 8 Snow Y
Uniform (lbf/ft) 75 75 0 8 Live Y
Uniform (lbf/ft) 500 500 8 21.5 Snow Y
Uniform (lbf/ft) 300 300 0 21.5 Dead Y
Point (lbf) 2500 - 8 - Snow Y
Point (lbf) 1500 - 8 - Dead Y
Uniform (lbf/ft) 120 120 0 21.5 Dead Y
Uniform (lbf/ft) 100 100 0 21.5 Live Y
Uniform (lbf/ft) 38 38 0 21.5 Dead Y
Self Weight (lbf/ft) 24.94 24.94 0 21.5 Dead Y
Page 15
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB2 AT EATING AREA CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB2 AT EATING AREA DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 10 Member Slope: 0/12 Actual Length (ft): 10
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 10 0 10 0 1.00 0.95 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (32.0%)
PASS (35.8%)
PASS (54.8%)
PASS (31.6%)
MAGNITUDE
226.6
2290.3
0.226 (=L/531)
512.6
STRENGTH
333.5
3569.7
0.500 (=L/240)
750.0
LOCATION (ft)
0
5
5
0
LOAD COMBO
D+0.75L+0.75S
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 2905 2000 0 2500 0 0 0 0 0 0 0
B 2905 2000 0 2500 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 500 500 0 10 Snow Y
Uniform (lbf/ft) 570 570 0 10 Dead Y
Uniform (lbf/ft) 400 400 0 10 Live Y
Self Weight (lbf/ft) 10.97 10.97 0 10 Dead Y
Page 16
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB3 AT FRONT BALCONY CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
RedBuilt 2.0E Redlam LVL (1) 1.75 X 11.875 DRY
FB3 AT FRONT BALCONY DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 12.33 Member Slope: 0/12 Actual Length (ft): 12.33
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
20.78 244.21 5.3 5.48 1 7.35 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 2900 1660 285 2635 750 2000 1000
Adjusted Values 2900 1660 285 2635 750 2000 1000
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 12.33 0 12.33 0 1.00 0.43 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (57.0%)
PASS (47.4%)
PASS (52.4%)
PASS (63.0%)
MAGNITUDE
122.6
1527.4
0.293 (=L/504)
277.3
STRENGTH
285.0
2904.1
0.617 (=L/240)
750.0
LOCATION (ft)
0
6.17
6.17
0
LOAD COMBO
D+L
D+L
D+L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A774925000000000
B774925000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 150 150 0 12.33 Live Y
Uniform (lbf/ft) 120 120 0 12.33 Dead Y
Self Weight (lbf/ft) 5.48 5.48 0 12.33 Dead Y
Page 17
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB4 BEAM AT LIVING RM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 16 DRY
FB4 BEAM AT LIVING RM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 18.5 Member Slope: 0/12 Actual Length (ft): 18.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
84 1792 192.94 22.17 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 0.96Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 4 0 4 0 1.00 0.96 1.00 1.00
2 14.5 0 14.5 0 1.00 1.00 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (43.2%)
PASS (48.1%)
PASS (25.7%)
PASS (86.3%)
MAGNITUDE
189.4
1785.3
0.198 (=L/484)
103.0
STRENGTH
333.5
3439.1
0.267 (=L/360)
750.0
LOCATION (ft)
4.07
8.88
0
4
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A00000000000
B62301180067470000000
C 3096 -255 0 4478 0 0 0 0 0 0 0
Reaction Location
AB C
Page 18
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 175 175 0 18.5 Snow Y
Uniform (lbf/ft) 195 195 0 18.5 Dead Y
Self Weight (lbf/ft) 22.17 22.17 0 18.5 Dead Y
Page 19
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB6 BEAM AT LIVING RM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB6 BEAM AT LIVING RM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 18.5 Member Slope: 0/12 Actual Length (ft): 18.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 4 0 4 0 1.00 0.98 1.00 1.00
2 14.5 0 14.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (75.7%)
PASS (65.1%)
PASS (35.2%)
PASS (80.9%)
MAGNITUDE
70.5
1058.0
0.259 (=L/371)
153.0
STRENGTH
290.0
3031.0
0.400 (=L/240)
801.1
LOCATION (ft)
3.88
4.07
0
4
LOAD COMBO
D+L
D+L
D+L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A00000000000
B12931652000000000
C-39268000000000
Reaction Location
AB C
Page 20
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 40 40 0 18.5 Live Y
Uniform (lbf/ft) 15 15 0 18.5 Dead Y
Self Weight (lbf/ft) 10.97 10.97 0 18.5 Dead Y
LINKED LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Point (lbf) 773.6085 - 0 - Dead Y
Point (lbf) 924.7501 - 0 - Live Y
Page 21
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB5 NEAR STAIR AREA CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 7 X 11.875 DRY
FB5 NEAR STAIR AREA DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 13 Member Slope: 0/12 Actual Length (ft): 13
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
83.12 976.83 339.43 21.94 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 13 0 13 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (39.8%)
PASS (7.4%)
PASS (24.4%)
PASS (39.5%)
MAGNITUDE
200.7
3307.0
0.328 (=L/476)
454.1
STRENGTH
333.5
3569.7
0.433 (=L/360)
750.0
LOCATION (ft)
13
7.02
6.76
13
LOAD COMBO
D+0.75L+0.75S
D+S
S
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 3835 2340 0 3623 0 0 0 0 0 0 0
B 5075 2340 0 5727 0 0 0 0 0 0 0
Reaction Location
A B
Page 22
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 360 360 0 13 Live Y
Uniform (lbf/ft) 255 255 0 13 Dead Y
Point (lbf) 6350 - 7 - Snow Y
Point (lbf) 3510 - 7 - Dead Y
Uniform (lbf/ft) 500 500 7 13 Snow Y
Uniform (lbf/ft) 300 300 7 13 Dead Y
Self Weight (lbf/ft) 21.94 21.94 0 13 Dead Y
Page 23
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB7 BEAM AT DINING RM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB7 BEAM AT DINING RM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 11 Member Slope: 0/12 Actual Length (ft): 11
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 11 0 11 0 1.00 0.94 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (35.9%)
PASS (30.4%)
PASS (42.5%)
PASS (35.6%)
MAGNITUDE
213.7
2484.5
0.211 (=L/627)
483.3
STRENGTH
333.5
3569.7
0.367 (=L/360)
750.0
LOCATION (ft)
11
5.5
5.61
11
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A22950026250000000
B 2670 0 0 3250 0 0 0 0 0 0 0
Reaction Location
A B
Page 24
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 250 250 0 11 Snow Y
Uniform (lbf/ft) 270 270 0 11 Dead Y
Point (lbf) 1250 - 4.5 - Snow Y
Point (lbf) 750 - 4.5 - Dead Y
Point (lbf) 1875 - 8 - Snow Y
Point (lbf) 1125 - 8 - Dead Y
Self Weight (lbf/ft) 10.97 10.97 0 11 Dead Y
Page 25
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB8 AT ENTRY AREA CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 1.75 X 11.875 DRY
FB8 AT ENTRY AREA DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 7 Member Slope: 0/12 Actual Length (ft): 7
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
20.78 244.21 5.3 5.48 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 7 0 7 0 1.00 0.69 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (42.0%)
PASS (61.7%)
PASS (77.2%)
PASS (49.3%)
MAGNITUDE
168.1
1189.2
0.053 (=L/1582)
380.3
STRENGTH
290.0
3104.0
0.233 (=L/360)
750.0
LOCATION (ft)
0
3.5
3.5
0
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A6491680000000000
B6491680000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 480 480 0 7 Live Y
Uniform (lbf/ft) 180 180 0 7 Dead Y
Self Weight (lbf/ft) 5.48 5.48 0 7 Dead Y
Page 26
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB9 AT LIVING ROOM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 9.5 DRY
FB9 AT LIVING ROOM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 6 Member Slope: 0/12 Actual Length (ft): 6
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
33.25 250.07 33.94 8.77 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 6 0 6 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (66.2%)
PASS (77.5%)
PASS (84.0%)
PASS (76.4%)
MAGNITUDE
97.9
719.5
0.032 (=L/2257)
177.2
STRENGTH
290.0
3191.9
0.200 (=L/360)
750.0
LOCATION (ft)
0
2.82
2.94
0
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A4641707000000000
B4991469000000000
Reaction Location
A B
Page 27
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 440 440 0 6 Live Y
Uniform (lbf/ft) 165 165 0 6 Dead Y
Point (lbf) 267.9311 - 1.67 - Live Y
Point (lbf) -39.46927 - 1.67 - Dead Y
Self Weight (lbf/ft) 8.77 8.77 0 6 Dead Y
Page 28
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB10 AT KITCHEN CODE:2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB10 AT KITCHEN DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 18.67 Member Slope: 0/12 Actual Length (ft): 18.67
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 18.67 0 18.67 0 1.00 0.88 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (66.8%)
PASS (56.7%)
PASS (39.1%)
PASS (71.0%)
MAGNITUDE
96.2
1343.5
0.379 (=L/591)
217.5
STRENGTH
290.0
3104.1
0.622 (=L/360)
750.0
LOCATION (ft)
0
3.92
8.59
0
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A8111854000000000
B417834000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 54 54 0 18.67 Live Y
Uniform (lbf/ft) 20 20 0 18.67 Dead Y
Self Weight (lbf/ft) 10.97 10.97 0 18.67 Dead Y
Page 29
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LINKED LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Point (lbf) 649.1937 - 3.67 - Dead Y
Point (lbf) 1680 - 3.67 - Live Y
Page 30
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB11 AT KITCHEN_DINING CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 9.5 DRY
FB11 AT KITCHEN_DINING DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 6 Member Slope: 0/12 Actual Length (ft): 6
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
33.25 250.07 33.94 8.77 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 6 0 6 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (30.9%)
PASS (49.2%)
PASS (69.0%)
PASS (51.6%)
MAGNITUDE
200.4
1620.0
0.062 (=L/1161)
362.7
STRENGTH
290.0
3191.9
0.200 (=L/360)
750.0
LOCATION (ft)
6
3.96
3.12
6
LOAD COMBO
D+L
D+L
L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 1017 2538 0 0 0 0 0 0 0 0 0
B12873156000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 640 640 0 6 Live Y
Uniform (lbf/ft) 240 240 0 6 Dead Y
Self Weight (lbf/ft) 8.77 8.77 0 6 Dead Y
Page 31
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB12 OVER GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB12 OVER GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 13.75 Member Slope: 0/12 Actual Length (ft): 13.75
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 13.75 0 13.75 0 1.00 0.93 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (58.2%)
PASS (45.7%)
PASS (41.4%)
PASS (63.4%)
MAGNITUDE
121.3
1685.7
0.403 (=L/410)
274.4
STRENGTH
290.0
3104.1
0.688 (=L/240)
750.0
LOCATION (ft)
0
6.88
6.88
0
LOAD COMBO
D+L
D+L
D+L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A15741788000000000
B15741788000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 260 260 0 13.75 Live Y
Uniform (lbf/ft) 218 218 0 13.75 Dead Y
Self Weight (lbf/ft) 10.97 10.97 0 13.75 Dead Y
Page 32
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB13 OVER GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 11.875 DRY
FB13 OVER GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 13.75 Member Slope: 0/12 Actual Length (ft): 13.75
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
41.56 488.41 42.43 10.97 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 13.75 0 13.75 0 1.00 0.93 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (62.6%)
PASS (57.1%)
PASS (53.2%)
PASS (65.3%)
MAGNITUDE
108.5
1333.2
0.322 (=L/513)
260.5
STRENGTH
290.0
3104.1
0.688 (=L/240)
750.0
LOCATION (ft)
13.75
6.88
6.88
0
LOAD COMBO
D+L
D+L
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1
1
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 1287 1719 0 820 0 0 0 0 0 0 0
B 1287 1719 0 820 0 0 0 0 0 0 0
Reaction Location
A B
Page 33
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 250 250 0 13.75 Live Y
Uniform (lbf/ft) 105 105 0 13.75 Dead Y
Point (lbf) 820 - 1 - Snow Y
Point (lbf) 490 - 1 - Dead Y
Point (lbf) 820 - 12.75 - Snow Y
Point (lbf) 490 - 12.75 - Dead Y
Self Weight (lbf/ft) 10.97 10.97 0 13.75 Dead Y
Page 34
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB14 OVER GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 11.875 DRY
FB14 OVER GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 14.5 Member Slope: 0/12 Actual Length (ft): 14.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
62.34 732.62 143.2 16.45 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 14.5 0 14.5 0 1.00 0.98 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (22.4%)
PASS (4.6%)
PASS (1.7%)
PASS (21.9%)
MAGNITUDE
258.9
3406.2
0.713 (=L/244)
585.7
STRENGTH
333.5
3569.7
0.725 (=L/240)
750.0
LOCATION (ft)
0
6.09
7.11
0
LOAD COMBO
D+0.75L+0.75S
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 5268 2889 0 4437 0 0 0 0 0 0 0
B47252492030960000000
Reaction Location
A B
Page 35
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 90 90 0 6 Dead Y
Uniform (lbf/ft) 150 150 0 6 Snow Y
Uniform (lbf/ft) 120 120 0 14.5 Dead Y
Point (lbf) 1875 - 6 - Live Y
Point (lbf) 1125 - 6 - Dead Y
Uniform (lbf/ft) 375 375 6 14.5 Snow Y
Uniform (lbf/ft) 225 225 6 14.5 Dead Y
Point (lbf) 2625 - 3 - Snow Y
Point (lbf) 1575 - 3 - Dead Y
Self Weight (lbf/ft) 16.45 16.45 0 14.5 Dead Y
LINKED LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Point (lbf) 1574.154 - 12 - Dead Y
Point (lbf) 1787.5 - 12 - Live Y
Point (lbf) 1287.257 - 2 - Dead Y
Point (lbf) 1718.734 - 2 - Live Y
Point (lbf) 819.9922 - 2 - Snow Y
Page 36
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB15 OVER GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Glulams
Stress Class Rated 24F-1.8E 24F-V4 DF/DF (1) 10.75 X 21 DRY
FB15 OVER GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 23.5 Member Slope: 0/12 Actual Length (ft): 23.5
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
225.75 8296.31 2174.02 51.49 1 0.5 1
STRENGTH PROPERTIES
Fbx+ Fbx- Fby Ft Fvx Fvy Fc Fc⊥ Ex Exmin Ey Eymin
(psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi)
Base Values 2400 1850 1450 1100 265 230 1650 650 1800000 950000 1600000 850000
Adjusted Values 2400 1850 1450 1100 265 230 1650 650 1800000 950000 1600000 850000
CM 111111111111
CT 111111111111
Bending Adjustment Factors Cvr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 23.5 0 23.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (54.6%)
PASS (4.2%)
PASS (35.2%)
PASS (16.1%)
MAGNITUDE
120.2
2296.9
0.761 (=L/371)
545.5
STRENGTH
265.0
2396.3
1.175 (=L/240)
650.0
LOCATION (ft)
0
9.16
11.28
0
LOAD COMBO
D+L
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 10372 7722 0 5812 0 0 0 0 0 0 0
B 6828 6662 0 3248 0 0 0 0 0 0 0
Reaction Location
A B
Page 37
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 175 175 0 9.25 Snow Y
Uniform (lbf/ft) 245 245 0 9.25 Dead Y
Uniform (lbf/ft) 400 400 0 23.5 Live Y
Uniform (lbf/ft) 150 150 0 23.5 Dead Y
Point (lbf) 1250 - 9.25 - Snow Y
Point (lbf) 750 - 9.25 - Dead Y
Point (lbf) 4724.581 - 9.25 - Dead Y
Point (lbf) 2492.203 - 9.25 - Live Y
Point (lbf) 3095.598 - 9.25 - Snow Y
Self Weight (lbf/ft) 51.49 51.49 0 23.5 Dead Y
LINKED LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Point (lbf) 4724.581 - 9.25 - Dead Y
Point (lbf) 2492.203 - 9.25 - Live Y
Point (lbf) 3095.598 - 9.25 - Snow Y
Page 38
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: FB16 OVER GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Glulams
Stress Class Rated 24F-1.8E 24F-V4 DF/DF (1) 8.75 X 21 DRY
FB16 OVER GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 21 Member Slope: 0/12 Actual Length (ft): 21
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
183.75 6752.81 1172.36 41.91 1 0.5 1
STRENGTH PROPERTIES
Fbx+ Fbx- Fby Ft Fvx Fvy Fc Fc⊥ Ex Exmin Ey Eymin
(psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi) (psi)
Base Values 2400 1850 1450 1100 265 230 1650 650 1800000 950000 1600000 850000
Adjusted Values 2400 1850 1450 1100 265 230 1650 650 1800000 950000 1600000 850000
CM 111111111111
CT 111111111111
Bending Adjustment Factors Cvr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 21 0 21 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (49.7%)
PASS (19.7%)
PASS (50.3%)
PASS (5.7%)
MAGNITUDE
153.2
1986.2
0.522 (=L/483)
612.8
STRENGTH
304.8
2473.9
1.050 (=L/240)
650.0
LOCATION (ft)
21
14.49
11.13
21
LOAD COMBO
D+0.75L+0.75S
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A71554383061490000000
B94375785066560000000
Reaction Location
A B
Page 39
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
LOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 50 50 0 21 Snow Y
Uniform (lbf/ft) 30 30 0 21 Dead Y
Uniform (lbf/ft) 375 375 14.5 21 Snow Y
Uniform (lbf/ft) 345 345 14.5 21 Dead Y
Point (lbf) 2625 - 2 - Snow Y
Point (lbf) 1575 - 2 - Dead Y
Point (lbf) 2625 - 12 - Snow Y
Point (lbf) 1575 - 12 - Dead Y
Self Weight (lbf/ft) 41.91 41.91 0 21 Dead Y
Page 40
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR5 TYP CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 2 (1) 3.5 X 7.25 DRY
HDR5 TYP DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 5 Member Slope: 0/12 Actual Length (ft): 5
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
25.38 111.15 25.9 4.9 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 875 450 135 1150 425 1400 510
Adjusted Values 1138 540 135 1208 425 1400 510
CM 1111111
CT 1111111
Ci 1111111
CF 1.3 1.2 1 1.05 1 1 1
Bending Adjustment Factors Cfu = 1 Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 50501.000.991.001.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (26.1%)
PASS (27.4%)
PASS (75.6%)
PASS (67.6%)
MAGNITUDE
99.7
825.4
0.061 (=L/984)
137.7
STRENGTH
135.0
1137.5
0.250 (=L/240)
425.0
LOCATION (ft)
0
2.5
2.5
0
LOAD COMBO
D+L
D+L
D+L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A6871000000000000
B6871000000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 400 400 0 5 Live Y
Uniform (lbf/ft) 270 270 0 5 Dead Y
Self Weight (lbf/ft) 4.9 4.9 0 5 Dead Y
Page 41
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR6 LIVING ROOM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 3.5 X 9.5 DRY
HDR6 LIVING ROOM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 9 Member Slope: 0/12 Actual Length (ft): 9
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
33.25 250.07 33.94 8.77 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 9 0 9 0 1.00 0.97 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (21.6%)
PASS (19.0%)
PASS (34.8%)
PASS (36.9%)
MAGNITUDE
261.4
2971.4
0.293 (=L/368)
473.0
STRENGTH
333.5
3670.6
0.450 (=L/240)
750.0
LOCATION (ft)
9
4.5
4.5
0
LOAD COMBO
D+0.75L+0.75S
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 2672 1800 0 2362 0 0 0 0 0 0 0
B 2672 1800 0 2362 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 400 400 0 9 Live Y
Uniform (lbf/ft) 300 300 0 9 Dead Y
Uniform (lbf/ft) 50 50 0 9 Snow Y
Uniform (lbf/ft) 475 475 0 9 Snow Y
Uniform (lbf/ft) 285 285 0 9 Dead Y
Self Weight (lbf/ft) 8.77 8.77 0 9 Dead Y
Page 42
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR7 AT LIVING RM CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 11.875 DRY
HDR7 AT LIVING RM DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 11.5 Member Slope: 0/12 Actual Length (ft): 11.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
62.34 732.62 143.2 16.45 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1 Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 11.5 0 11.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (36.8%)
PASS (43.6%)
PASS (48.3%)
PASS (44.7%)
MAGNITUDE
183.3
1749.9
0.297 (=L/464)
414.5
STRENGTH
290.0
3104.1
0.575 (=L/240)
750.0
LOCATION (ft)
0
5.17
5.64
0
LOAD COMBO
D+L
D+L
D+L
D+L
DURATION FACTOR CD
1
1
1
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A34924125010060000000
B 2648 3047 0 1006 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 480 480 0 11.5 Live Y
Uniform (lbf/ft) 405 405 0 11.5 Dead Y
Uniform (lbf/ft) 175 175 0 11.5 Snow Y
Self Weight (lbf/ft) 16.45 16.45 0 11.5 Dead Y
Page 43
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Roof LOADING: ASD
MEMBER NAME: HDR8 FRONT ENTRY CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Douglas Fir-Larch No. 1 (1) 5.5 X 9.5 DRY
HDR8 FRONT ENTRY DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 10 Member Slope: 0/12 Actual Length (ft): 10
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
52.25 392.96 131.71 11.92 1 0.5 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 1350 675 170 925 625 1600 580
Adjusted Values 1350 675 170 925 625 1600 580
CM 1111111
CT 1111111
Ci 1111111
CF 1111111
Bending Adjustment Factors Cfu = 1.05Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 10 0 10 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (55.1%)
PASS (28.5%)
PASS (67.8%)
PASS (74.6%)
MAGNITUDE
87.8
1109.5
0.107 (=L/1117)
158.9
STRENGTH
195.5
1552.5
0.333 (=L/360)
625.0
LOCATION (ft)
0
5
5
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A15600015000000000
B15600015000000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 300 300 0 10 Snow Y
Uniform (lbf/ft) 300 300 0 10 Dead Y
Self Weight (lbf/ft) 11.92 11.92 0 10 Dead Y
Page 44
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR9 GARAGE DOOR HEADER CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 1 (1) 5.5 X 11.5 DRY
HDR9 GARAGE DOOR HEADER DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 10 Member Slope: 0/12 Actual Length (ft): 10
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
63.25 697.07 159.44 12.2 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 900 450 125 625 425 1300 470
Adjusted Values 900 450 125 625 425 1300 470
CM 1111111
CT 1111111
Ci 1111111
CF 1111111
Bending Adjustment Factors Cfu = 1.05Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 10 0 10 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (38.4%)
PASS (10.7%)
PASS (72.1%)
PASS (54.3%)
MAGNITUDE
88.6
924.5
0.093 (=L/1289)
194.1
STRENGTH
143.8
1035.0
0.333 (=L/360)
425.0
LOCATION (ft)
0
5
5
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 1861 200 0 1875 0 0 0 0 0 0 0
B 1861 200 0 1875 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 40 40 0 10 Live Y
Uniform (lbf/ft) 360 360 0 10 Dead Y
Uniform (lbf/ft) 375 375 0 10 Snow Y
Self Weight (lbf/ft) 12.2 12.2 0 10 Dead Y
Page 45
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR10 GARAGE DOOR HDR CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Solid Sawn
Spruce-Pine-Fir No. 1 (1) 5.5 X 11.5 DRY
HDR10 GARAGE DOOR HDR DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 16.5 Member Slope: 0/12 Actual Length (ft): 16.5
Area Ix Iy BSW Lams G Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
63.25 697.07 159.44 12.2 1 0.42 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 900 450 125 625 425 1300 470
Adjusted Values 900 450 125 625 425 1300 470
CM 1111111
CT 1111111
Ci 1111111
CF 1111111
Bending Adjustment Factors Cfu = 1.05Cr = 1
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 16.5 0 16.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (76.6%)
PASS (44.0%)
PASS (66.5%)
PASS (82.6%)
MAGNITUDE
33.7
580.1
0.184 (=L/1076)
73.8
STRENGTH
143.8
1035.0
0.550 (=L/360)
425.0
LOCATION (ft)
0
8.25
8.25
0
LOAD COMBO
D+S
D+S
S
D+S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A596008250000000
B596008250000000
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 100 100 0 16.5 Snow Y
Uniform (lbf/ft) 60 60 0 16.5 Dead Y
Self Weight (lbf/ft) 12.2 12.2 0 16.5 Dead Y
Page 46
2018 International Building Code ASDPROJECT: SINGH RESIDENCE
PASS
DATE: 5/16/2021 COMPANY: --VITRUVIUS BUILD: Base DESIGNED BY: Glen MerkelCUSTOMER: MANJIT SINGH REVIEWED BY: Glen MerkelPROJ. ADDRESS: 10628 SE 144TH STREET PROJECT NAME: SINGH RESIDENCE
RENTON, WA 98059
LEVEL: Main Floor LOADING: ASD
MEMBER NAME: HDR11 GARAGE CODE: 2018 International Building Code
MEMBER TYPE: FLOOR BEAM NDS: 2018 NDSMATERIAL: Structural Composite Lumber
Roseburg Forest Products 2.0E Rigidlam LVL (1) 5.25 X 9.5 DRY
HDR11 GARAGE DIAGRAM
BEAM PROPERTIES
Start (ft): 0 End (ft): 6.5 Member Slope: 0/12 Actual Length (ft): 6.5
Area Ix Iy BSW Lams Cfn Kcr
(in²) (in⁴) (in⁴) (lbf/ft) Creep Factor
49.88 375.1 114.56 13.16 1 8 1
STRENGTH PROPERTIES
Fb (psi) Ft (psi) Fv (psi) Fc (psi) Fc⊥(psi) E (psi) x10³ Emin (psi) x10³
Base Values 3100 2100 290 3000 750 2000 1056.958
Adjusted Values 3100 2100 290 3000 750 2000 1057
CM 1111111
CT 1111111
Bending Adjustment Factors CV = 1.03Cr = 1 Volume factor Is applied on a load combination basis And Is Not reflected in the adjusted values
BEAM DATA
Unbraced Length (ft) Beam End
Span Length (ft) Top Bottom Elev. Diff (ft) CL(Top) CL(Bottom) CL(Left)CL(Right)
1 6.5 0 6.5 0 1.00 0.99 1.00 1.00
PASS-FAIL
Shear Stress Y (psi)
Bending Stress Y (psi)
Deflection (in)
Bearing Stress (psi)
PASS/FAIL
PASS (44.1%)
PASS (22.1%)
PASS (64.7%)
PASS (55.0%)
MAGNITUDE
186.6
2860.7
0.115 (=L/681)
337.6
STRENGTH
333.5
3670.6
0.325 (=L/240)
750.0
LOCATION (ft)
0
3.25
3.25
6.5
LOAD COMBO
D+0.75L+0.75S
D+0.75L+0.75S
D+L
D+0.75L+0.75S
DURATION FACTOR CD
1.15
1.15
1.15
REACTIONS Units for V: lbf Units for M: lbf-ft
DEAD LIVE LIVE ROOF SNOW WIND + WIND - SEISMIC + SEISMIC - ICE RAIN EARTHY axis
A 2677 1834 0 2868 0 0 0 0 0 0 0
B 2677 1834 0 2868 0 0 0 0 0 0 0
Reaction Location
A BLOAD LIST
Type Left Magnitude Right Magnitude Load Start (ft) Load End (ft) Load Type Direction
Uniform (lbf/ft) 200 200 0 6.5 Snow Y
Uniform (lbf/ft) 120 120 0 6.5 Live Y
Self Weight (lbf/ft) 13.16 13.16 0 6.5 Dead Y
Page 47
2018 International Building Code ASDPROJECT: SINGH RESIDENCE