HomeMy WebLinkAboutS-3971087' 1 NOT TO SCALE MANHOLE FRAME AND COVER SEE STD. PLAN 401 ADJUSTMENT RINGS (2" MIN.) SEE NOTE 6 MORTAR JOINT(S) (3/8" MIN.) SEE NOTE 5 CONE (ECCENTRIC) RUBBER GASKETED JOINTS IN ACCORDANCE WITH ASTM C-443 STEPS - POLYPROPYLENE STEPS SHALL BE INCLUDED CONCRETE RISER BY PIPE INC., OR APPROVED EQUAL. LADDER -POLYPROPYLENE SHALL BE ATTACHED TO MANHOLE MAX. PIPE SIZE - 'E' CONCRETE SHELF PRECAST BASE SECTION OR CAST IN SHELF. 'A' 11 'B' 'C' 'D' 'E' 48" MH 48" 6" MIN. 5"MIN 24" MIN. 21" I.D. 54" MH 54" 8" MIN. 5.5" MIN. 24" MIN. 24" I.D. 60" MH 60" 8" MIN. 6" MIN. 42" MIN. 30" I.D. NOTES: 1. STEPS TO BE POLYPROPYLENE SAFETY STEPS. 2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED. 3. CASTING SHALL BE PER STD. PLAN 401. 4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE. 5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, BRICKS AND CASTING SHALL BE GROUTED. 6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED WITH A COMBINATION OF ADJUSTMENT RINGS, BRICKS AND MORTAR ONLY. BRICKS SHALL BE STAGGERED TO CREATE A RUNNING BOND OR 1/2 BOND. THE USE OF SHIMS IS PROHIBITED. ,7, SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING, COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC-AROSHIELD OR APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE. 8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE WITH ASTM C-443. 9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE. 10. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR-N-SEAL BOOTS OR APPROVED EQUAL. 11. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM OF 12" ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE. IN PAVED AREAS, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. vti�Y pi STD. PLAN - 400.1 PUBLIC WORKS STANDARD SANITARY MANHOLE DEPARTMENT SEPTEMBER 2011 W (SEE NOTE 7) LIMITS OF PIPE ZONE _TD,1 BEDDING MATERIAL FOR SANITARY SEWER PIPE O.D. OF PIPE (SEE NOTE 5) FOUNDATION LEVEL 6" BEDDING FOR SANITARY SEWER PIPE NOTES; 1. PROVIDE UNIFORM SUPPORT UNDER BARREL. 2. HAND TAMP UNDER HAUNCHES. 3. COMPACT BEDDING MATERIAL TO 95% MAX. DENSITY EXCEPT DIRECTLY OVER PIPE. HAND TAMP ONLY. 4. PIPE INSTALLATION SHALL BE PER SECTION 7-08 OF THE STANDARD SPECIFICATIONS. 5. PIPE ZONE MATERIAL SHALL BE PER SECTION 9-03.12(3)' OF THE STANDARD SPECIFICATIONS OR PEA GRAVEL. 6. PIPE MUST BE ANCHORED IN SUCH A MANNER AS TO ENSURE FLOW LINE IS MAINTAINED. 7. TRENCH WIDTH SHALL BE PER SF-C-I[ION 2-09.4 OF THE STANDARD SPECIFICATIONS. Cj STD. PLAN - 405 • PUBLIC WORKS PIPE BEDDING AP OVER: DEPARTMENT FOR SANITARY SEWERS V o Call 2 Working Days Before You Dig 811 Utilities Underground Location Center (ID,MT,ND,OR,WA) a BOLTHOLES - 3 PLCS EQUALLY SPACED 120° APART ON 23 1/16' (586mm) DIA B.C. (SEE DETAIL) RENTON SEWER MROE IN USA COVER & FRAME PLAN VIEW 25' DIA, E635mm] 1" 3/4' �25mm] E19mm] 1 8 3/4' 2 1/2" E222mm] E64mm] TYP COVER SECTION VIEW 26 112' DIA _ E673mm] 25 1/4' DIA E641mm7, 1 1/16' 1/4' (6mm) DIA NEOPRENE GASKET E27mm] } 6' E152mm] - I � 5/8' -3 3/8" DIA CL OPEN E16mm] COVER BOTTOM VIEW (3) BLT SOC, (ALLEN HEAD) 5/8'-11 X 1.5 SS RUBBER WASHER EON BOLTING DETAIL 1/4'11- 1 16mm] ~ [27mm] 1 13mm] ER3mm] GASKET GROOVE DETAIL Lbb/MMJ NOTES: FRAME SECTION VIEW 1. ALL COVERS SHALL BE LOCKING LID PER EAST JORDAN IRON WORKS INC. No. 3717C1 OR EQUAL. 2. USE FRAME AND COVER FOR STORM (SPECIFY "DRAIN" ON COVER), SANITARY (SPECIFY "SEWER"), OR WATER (SPECIFY "WATER"). `�Y o STD. PLAN - 401 PUBLIC WORKS MANHOLE FRAME AND COVER DEPARTMENT DECEMBER 2008 ALL 90' TURNS SHALL BE ACCOMPLISHED BY MEANS OF A WYE WITH CLEANOUT AND 45' BEND. TWO 45' BENDS SHALL NOT BE 4" BEND AS REQUIRED (NO MORE ACCEPTABLE (SEE NOTE 11) THAN 45° BEND). EVERY 2ND 4" CLEANOUT WYE WITH - - CHANGE IN DIRECTION OR GRADE 45` BEND AND PLUG. WILL REQUIRE A SURFACE (SEE NOTE 11)j CLEANOUT WYE. (SEE NOTE 11) I w z J w z J w z J HOUSE Y H a HOUSE Y H a Tj_OSl > H a HOUSE 0 a 0 a 0 a y 3 -0" MIN. 4" SEWER PIPE SURFACE CLEANOUT 4" SURFACE n / CLEAN OUT (TYPICAL) 4" SEWER PIPE, SEE NOTES 2 6"x 6"x6" WYE (SEE STD PLAN - 407) L WYE 4" TEST TEE WITH r AND 3. MINIMUM LINE SIZE FOR I 4" WYE WITH PLUG FACE UP OTHER THAN SINGLE FAMILY IS 6" (TYPICAL) I PROPERTY LINE CLEAN OUT PROPERTY LINE - - 3' MIN. - - 6"x 4" REDUCER c� z z z (TYPICAL) MAIN SEWER LINE ?`; x, - NOTES: z IF THE BUILDING SEWER SERVES ANY FIXTURE HAVING 1. Prior to installation of a sanitary sewer connection, a side -sewer .z < FLOOD LEVEL RIMS LOCATED BELOW THE ELEVATION permit must be purchased from the City of Renton Public Works 'a I� o OF THE NEXT UPSTREAM MANHOLE COVER OF THE Department. � PUBLIC SEWER SYSTEM, A BACKFLOW PREVENTION 'io z DEVICE SUCH AS CLEAN CHECK EXTENDABLE BACKWATER VALVE OR APPROVED EQUAL SHALL BE 2 Types pipe and fittings that can be used for sanitary sewers iD INSTALLED. shall bee approved by the Department of Public Works. Rubber or m neoprene gaskets as specified by the manufacturer, shall be 0 o' 4" FLEXIBLE COUPLING (FERNCO OR EQUAL) used on joints. z 3. A minimum grade of 2% (1/4" per 'foot)"must be maintained m SURFACE CLEANOUT 4"x 4"x4" WYE with 4" pipe. In the event a 2% grade cannot be maintained, the owner must sign a City of Renton grade release form and then 4" PIPING can install 6" pipe at a grado xifl PLAN BUILDING DRAIN FOR 4. For Inspection of side sewer, call 24 hours in advance. The LOW ELEVATION HOUSE inspection phone number is on the side sewer permit. Site must be ready for inspection and representative on site when inspector arrives at appointed time. Side '3e'v_ier and stub shall be tested per City specifications. Make the connection at the 5'-0" house. Do not backfill the ditch until approval is given by the MAIN TO PROPERTY LINE 5'-0" PROPERTY LINE FROM THE HOUSE BUILDING DRAIN inspector. Final approval will be granted after the existing septic SIDE SEWER BUILDING SEWER 2'-6" tank has been pumped out and filled with sand. 3'-0"MIN. O 3' 0" I 5. Install side sewer with 2 minimum cover. 18" cover is allowed at the house if outlet is shallow. ( \\\ \ ( 6 If side sewer stub is not available. The owner shall be ut rn m ou ( 1 111 1 1 p N �lA responsible for its installation per standard drawing 406.1. All `lo m m mZ0 m a> rn A A O C c N z D ' x A x work within street right-of-way shall be done by a licensed and m mom m o o z m m '� z �' c Z O U l Z C D m o p A -,� X D o f +1 - Om bonded contractor. o0o min -om .m x- Z IO'tm Ox O m m o ro c m m D? o z o o m m rn c m = A m 7. All work shall be accomplished in accordance with the Washington o o N il m _c, m o c z n j m D m mrm ? O-1 Dm m () z � m Industrial Safety and Health Act. (WISHA) m D vmi�X m z co { Io m zo y o m , N = oc m 8. All trench restoration for side sewers in the public right-of-way m D > m o' _ z y o m z c, o m „ z shall conform to the most current trench restoration rn z m m o °' z requirements as in the Renton Standard Drawings. ,m minrnD o min =z o o rn o v, o 9. All building sewer and side sewers shall have bedding, in- rn �^ o y accordance with standard drawing 405. = Dm m m ur - z m o m 10. There shall be a minimum 10 foot horizontal sepa(q�ionnl 'between A o N m m sanitary side sewers and water services and a minimum 5 foot c A horizontal separation between sanitary side sewers and all other z o 00 utilities. 11. The cleanout at the Right -of- Way shall be installed per CALL FOR LOCATIONS BEFORE YOU DIG` Standard Plan 407. The cleanout of the building shall be 48HR LOCATORS 1-800-424-5555 installed to surface grade. All other cleanouts shall be installed to within 12" of the surface. O TYPICAL BUILDING SEWER STD. PLAN - 406.2 PUBLIC WORKS .• * FROM PROPERTY LINE TO "`•` DEPARTMENT BUILDING CONNECTION AUGUST 2013 RECESSED - f III 'C�SEWER LIFT POCKET 3/4" LETTERING "SEWER" (,U a (2) BOLT SOC. (ALLEN HEAD)5/8" - 11 X 1.5 STAINLESS E STEEL �C�I REF. PART #00981177 - 1-3/16" 8" CL/ 10-1/2" - ASPHA 5/F 1/4" 1 I 1 UL �1-1/8" 2-1/4" CAST IRON RING AND COVER 45- (1 /8) BEND Not to Scale FRAME III a I L IR (ABLE a PIPE MATERIAL AS SPECIFIED BY THE ENGINEER NOTES: 1. B" AND 6" CLEAN -OUT RINGS AND COVERS ON SEWER MAINS SHALL BE EAST JORDAN IRON WORKS, INC. No. 3698 (PRODUCT NO. 00369803) OR APPROVED EQUAL. CLEAN OUT SHALL BE A WATER TIGHT ASSEMBLY. 2. IN UNIMPROVED AREAS, POUR A 1'-0" THICK, 2'-0" SQUARE CONCRETE, CLASS 3000, PAD AROUND THE RING AND COVER. E I� �� APPROVED: STD. PLAN - 403.1 `R •�" PUBLIC WORKS 8 OR 6 CLEANOUT DEPARTMENT FOR SANITARY SEWER MAIN veawm u D R/W SURFACE CLEANOUT WITH CAST IRON RING AND COVER I (EAST JORDAN IRON WORKS PRODUCT N0. 00367502 OR APPROVED EQUAL, SPECIFY "SEWER" ON LID), (SEE STD. PLAN 403.1 FOR INSTALLATION) E°6 ________ --------- - - - - - - - - - - - - - - J T--------------T- I JM EAGLE L - - - J THREADED BEND AS 1 CLEAN -OUT EXISTING 6" SEWER STUB REQUIRED ADAPTER HUB (REMOVE TO R/W) A PLUG OR APPROVED EQUAL EXISTING SANITARY SEWER MAIN (REMOVE) ------------------- \---- I- - - - - - - - - - - /- - - - - - 6"X6"X6" WYE h SEWER MAIN SIZE X 6" TEE PROPOSED SEWER MAIN • PUBLIC WORKS 7 DEPARTMENT BEND AS REQUIRED-' (NOT TO EXCEED 45') 6" SEWER STUB TYPICAL SIDE SEWER CONNECTION FOR SEWER MAIN REPLACEMENT 6"x 4" REDUCER EXISTING 4" SIDE SEWER 1� i IT L H STD. PLAN - 407 D: 17 DOES N O T N C � U D E A S- B U LT N E O R M AT O N 0 FIRST SUBMITTAL ESM 08/30/171 SURVEYED: SCALE: NTS VERTICAL: NAVD 1988 HORIZONTAL: NAD 1983/1991 DATU M 1 SECOND SUBMITTAL ESM 11/15/17 DESIGNED P� 2 THIRD SUBMITTAL ESM 01/03/18 DRAWN: CL ONE INCH CHECKED:: AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY N 0. REVISION BY DATE AP P R APPROVED: 'f CITY OF RENTON • Planning/Building/Public Works Dept. IN COMPLIANCE WITH CITY OF RENTON STANDARDS EARLINGTON TOWNHOMES SANITARY SEWER DETAILS & NOTES UTILITY PERMIT # 01/03/18 FIELDBOOK: PAGE: DRAWING NO: SS-06 SHEET: OF: 38 55 0 0 0 U D J L'�•J 0 0 'A0 1 S-397108