Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutzW-4305setLi) Ln
O O
C't) Co
~ N
N
n
V
L�
0
W
1
NOTES:
I�
1 I I LJ
JON�S
CD
/ - IQ
EXISTING SIDE SEE
WER RE P PR/ I 10' DRIVEWAY ESMT I 1 20' INGRESS, E SS & UTILITIES
SON �N �30 TO BE CAPPED AND PROPOSED PROPERTY REG No 4731181 ESM'T PER (R2)
PE�O SOS �21016 / l ABANDONED ---- ------------- LINE (TYP) - - � /
------------------ --- -------------
PPN SSMH / /
RIM EL=204.09 06 \ 212� ti /218
8"CONC(E)IE=196.59 -25.00 dN.
8"CONC(N)IE=196.29 0� )
55CO7
/ .)4. _ j _) 18LF 6" PVC 6 /E 210.38
z / - -3SCO 5 90.1489 6" IE 209.59
/ PROPOSED FINISH 6, lE 6 1 _
I LU I ( / GRADE CONTOUR (TYP) 6" If- 206.91
SSCo 6
d
EX/STING WATER METER I I I .; I 2 » ° °' d °. ° ° 4LF 6 PVC 3 0� 0 P� F
TO BE REMOVED I I I PAD 6 IF 09.16 I Q . a . ° 90.0575 PAD I P\ PNSIRoEN
SAL VAGED BY CITY (TYP) � 216.0 . ' ° ° l 217.0 / �N \0L� G N0'
° » d .a ° °
I I 13LF 6 PVC : I ° N N N
I I / 00.1415 ° /GSN\NGS\�\SP
° d °
° - : ° »
EX/STING GROUND 6" IF 211.00 a I° , ° ° d 6 /E 210.61
��RSO ��E 1016� I . ll /
CONTOUR (TYP) '° ° ` ° ° 1 f 44.84, 13.27' RT �
0 SSCO 5A
6 /E 206.9 2" BLOWOFF ASSEUBL Y /
FQ 6" lE 206.91 ,o PER CORD STD. PLAN 340.1 I {'
CUT AND CAP EXISTING I WITH CONC. BLOCKING
WATER SERVICE AT MAIN / I \ 8LF 6" PVC I I \ 0' 50NG ON
PER CURRENT PUBLIC / I 00.2812 >f44.83, 5.96' RT I I G J �0 g
WORKS SPEC/F/CA TONS / \ ° d SSCO 5 I o 0 ON ON 23
Lq d ° 91LF 6 PVC ° ° I ° m ° 6 /E 206.91 CAP (M✓� I N �N, I \N� 0 G N�G�2� 0�
s'N' H `t 0 0.0296 ° WITH CONC BLOCKING
I ( J ON 3�
r IM EL=205.23 O / Q ° 6 /E 206.91 I SE QN
8"CONC(E,S)IE=198.43 °' » a I` d
8"coNc(w)IE-198.23 I \ 1 DOMESTIC WATER METER ° : ° ° , o' ..�. TRACT C I L-- P
NEW 8" IE 198.43 I WITH PR PROVIDED FOR a ° 10 O (ACCESS & UTILITIES)
I I 1 \ EACH LOT (TYP) \ ES 15
a p 40' PUBLIC STORM J0N �O�E N l
4f95.91, 5.33' RT \ ° '\ \ l 88LF 6" PVC a a a DRA/NGE & 4 \ P �3 R� P
" I ° PAD 0 0.032.3 UTILITIES EASEMENT \ PPN Q P g8 1
CONNECT TO EXISTING 8 MAIN I I I \ 216.0 \ N PIPE CROSS/RZ�� ORN
I -REDUCER (FL) 6If- 209.93 SEE UTILITY CROSSING
GE\ )
Q P
FINAL CONNECTION TO EX. I I I I ° I I 6" CLEANOUT 2LF 6" p BLE, SHEET C5.21. i
8 WATER MAIN TO BE
DONE BY CITY FORCES PER / I I i 169LF 8" PVC 6" If 20L I l 1.4J50 SSCO 4
6 /E 209.13
COR STD PLAN 300. 4 I I ; ` 00.0420 6" lE 204.34 e 6" lE 212. 00 _ 6" lE 209.13 /
CB, TYPE I I \ ' 2 4 ' -
RIM EL=200.31 ° \ 24 26LF 6" PVC
12"DI(W)IE=198.84 I 2 00.1400
\�
ooze / I °O ' ' : ° ° 23 ° SSCO 3
°HP ° " o2LF 6" PVC 18 14 6 /E 209.75
SD _
006000 6" lE 209.75
-w w ,'I \ » l �,� 13 ° �. 20LF 6" PVC
N r] co 28LF 6 PVC `� ° d ° 0 0.1470 ptitio SS A /s ue- SS SS `�' 0 0(0314 / s �°°'. a SDe6 G
J - - \` 6» lE 206.81
N 31 S T S T \ [ OADW11771F 8" DI / " 6 /E 206.81
_ 6LF 8" 9LF 6 PVC
-----�,-J--- ---1 (PUBLIC - 6 E o 3�7� » 5 90.IJ78
r'H-SFr ` i N N N N N 12 ° 23LF 6 DI
PAD
" 7.0
Lc �r c 6 /E 120J 46 2>
- - - 214 N
\ / - - SSMH
° . °� • q tr I 6 3.23, 6.35RT STA. 6f76.11, 7' L
W /
1Of00.00, PARK A l/E N = - z ® a \ �`E�¢ 07 5LF 8-D1 10' CAP (UJ) TYPE 1-48" %
_
5f00.00, ROAD A N ° \ �� \ \ _ WITH CONC BLOCKING RIM 215.65 (
206 I 8 If OUT 205.52' �W)
w 25.00 'IN 6" 1E 205. 49
Q
I \ \ TRACT B I I 10' ACCESS
CONNECT TO EX SSUH I 6f70.65, 6.33 RT EASEMENT
8" 1E 198.43 J w' - / I I \ (ACCESS & UTILITl�S) 6" If-204.22 \
POL YP/G STA T/ON I
, 0f50.00, ROAD B =
\ 6f 46.61, ROAD A
FIRE HYDRANT WITH SHEAR
BLOCKING PER DETAILS 310.1
& 310.2 ON SHEET C5.32 &
C5.33
REN �2 5
G\�� 33�210
PQN
N
SCALE: 1" = 20'
0 10 20 40
SEWER LEGEND
SEE WER P/P
co
SEWER STRUCTURE
SEWER SER146F
� SEWER P/PE FLOW ARROW
- - SEWER EASEMENT
EX/STING SEWER PIPE
WA TER LEGEND
WATER MAIN
)7d IN[
WATER F/TT/NG
0
FIRE HYDRANT
WATER METER
❑o
BLOW -OFF ASSEMBL Y
101
POL YP/G STATION
Q
PRESSURE REDUCING VALA Vf
- -
WATER EASEMENT
EX/STING WA TER PIPE
SURFACE LEGEND
EX GROUND CONTOUR MA✓R
EX GROUND CONTOUR M/NR
210 FINISH GRADE CONTOUR MA✓R
212 FINISH GRADE CONTOUR M/NR
CAUT/ON.- UTILITY CONFLICTS
LOCATIONS OF UT/L/T/ES AS SHOWN ON THESE PLANS ARE BASED ON UNVERIFIED PUBLIC
INFORMATION AND SHALL BE FIELD Vf-R/F/ED BY THE CONTRACTOR.
PR/OR TO CONSTRUCT/ON, CONTRACTOR SHALL CONTACT ALL UTILITY COMPAN/ES, AND CALL
UTILITY LOCATE 0 811.
PR/OR TO CONSTRUCT/ON, CONTRACTOR SHALL POTHOLE EXISTING UT/L/TIES, CONTACTING THE
SURVEYOR OF RECORD TO SURI/EY THE HORIZONTAL AND VfRT/CAL LOCATIONS AND VERIFY
THE LOCATION, DIXNS/ON, AND DEPTH OF ALL EXISTING UTILITIES ON THE PROJECT S/TE.
IN ADD/T/ON, CONTRACTOR SHALL POTHOLE LOCATIONS OF NEW UTILITY CROSSINGS TO
Vf-RIFY NO CONFL/CTS EXIST.
IF CONFL/CTS EXIST, THE CONTRACTOR SHALL CONSUL T CORE DES/GN, INC. TO RESOL Vf
CONFLICTS PR/OR TO PROCEEDING WITH CONSTRUCTION.
ALL PIPES WITH LESS THAN ONE AND A HALF FEET (1.5) OF VERTICAL SEPARATION SHALL
HAVE- ETHAFOAM, OR APPROVED EQUIVALENT, PLACED BETWEEN THE PIPES TO MAINTAIN
SEPARA T/ON.
w 61662J, 6.34 RT \
1. MIN/MUM OF 18-INCH VERTICAL SEPARATION BETWEEN SEWER, I z \ \ \ FIRE HYDRANT ASSEMBLY 10' PUBLIC STORM
WATER AND STORM LINES WHERE MIN/MUM SEPARATION /S 6f52.61, 6.33 RT DRAINAGE &
\ » 1-8 x6 TEE (M✓xFL)
NOT FEAS/BLE, NON -POTABLE WATER PIPE SHALL BE RIM-203.84 I Q C 1-81x4 TEE (MJXFL) 017LWS EASEMENT
PRESSURE RATED PIPE (PVC C900, D1,, OR EQUAL) I N I \ \ 1-4" GATE VAL Vf- (FLXUJ) 1N6 GATE VAL l/E (M✓xFL) PROJECT NO. 20081 K
W \ \\ W/ CONC BLOCK/NG W7H CONC BLOCK/NG
2C . ALL ONSTRUCT/ON SHALL BE /N ACCORDANCE WITH THE CITY I o I \
OF RENTON STANDARD SPEC/F/CA TONS I I
3. CONTRACTOR SHALL FIELD VERIFY ALL CONNECTIONS TO I z I \ \
EXISTING PIPES FOR PROPER RTT/NGS AND DEPTH. I \ 3g &
4. ALL WATER F/TT/NGS AND VALVES WITH MECHANICAL JOINT I� 25' I 25' I II vo NERD j0 3250�
(M✓) ENDS SHALL HA VE A WEDGE- TYPE RETAINER GLAND
EQUAL TO MEGALUG SERIES 1100. I Q I\ I GPRO
5. SEE SHEET CA01 FOR U17LITY CROSSING TABLE. ER 50 I fD-z \ \ I P? P PR \
25.00 ---- -- / X X -
M PN <Of
I'
P IX I
I < \NID 3251
I
oHP OHP 80�G \A���10
I I I PPN
NO.
N
O
N
u
\ ti�;PoF�wAsyMpd CIVIL ENGINEERING
\ ,2j TRACiA" - �;�P� y�'• -4 LANDSCAPE ARCHITECTURE
2 (TREE RETENTION)
PLANNING
TRACT D o • G41843���� DESIGN SURVEYING
(FUTURE F`�SIBNAL ENVl
CONVEYANCE) 12100 NE 195th St, Suite 300 Bothell, Washington 98011 425.885.7877 V
-21 / 04/02/25
X X X
\ _ IN COMPLIANCE WITH CITY OF RENTON STANDARDS O
�\ DEVELOPMENT ENGINEERING t^
�'-�- vJ 7_ELE
VEN 48 HHuynh 04/17/2025
ApN 33421032 Z
WASTEWATER UTILITY WATER UTILITY r
S 430501 W 430501 jstowell 03/04/2025 ABDOUL GAFOUR 03/06/2025 W
SURVEYED: SCALE: DATE:
JONES RENTON SHORT PLA T
VERTICAL: NAVD 1988 � CITY 0 F �u
OTHERS HORIZONTAL- NAD 1983/1991
DESIGNED: O
FLAWO BA/NOTT/ 3102PARKA VEN, RENTON, WA 98056 FIELDBOOK:
RENTON PAGE
DRAWN: I;R
O
CHUCK FEML/NG ONE INCH DATUM DRAWING NO:
CHECKED:
AT FULL SCALE Planning/Building/Public Works Dept. SEWER &WATER PLAN C5, 01 \l
U/CHAEL MOODY IF NOT ONE INCH
REVISION BY DATE AP P R APPROVED: SCALE ACCORDINGLY SHEET: OF:
M/CHAEL MOODY 18 34
0
N
O
O
N
WE
L0
co
I
N
nV
I\
O
O
O
WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CITY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR
AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ON -SITE.
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND C
104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS
PER ANSI/AWWA C110/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS.
S. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS
AND 48 INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60 INCHES.
ANY DEVIATIONS MUST BE APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFLICTS OCCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST
METHOD (MDD) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MDD.
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS
AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO
CONCRETE BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIOR TO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE
SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY INSTALL AND REMOVE PLUGS
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT/ BLOCKING FORTESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITYTESTING.
S. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP DURING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, FLUSHED,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR.
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING
DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TO THE EXISTING WATER SYSTEM. THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
PUBLIC WORKS WATER PLAN GENERAL NOTES STD. PLAN - 300.0
DEPARTMENT MARCH 2O10
0.7" 4"
BLUE REFLECTIVE PAVEMENT MARKER,
STIMSONITE MODEL C88 OR EQUAL,
PLACED 4" FROM ROADWAY
CENTERLINE AS INDICATED BELOW
/IARKER
T
I I I
TWO LANE ROAD OFFSET MARKER
AARKER
FOUR LANE ROAD OFFSET MARKER
} PUBLIC WORKS
DEPARTMENT
MARKER
i
d t
I -
ON SIDE STREETS WHERE THE HYDRANT IS
WITHIN 20' OF A MAJOR STREET, THE MARKER
SHALL BE INSTALLED ON THAT MAJOR STREET
/IARKER
FIVE LANE ROAD OFFSET MARKER
FIRE HYDRANT ASSEMBLY
PAVEMENT MARKER
STD. PLAN - 310.3
METERED BACKFLOW ASSEMBLY
(TO BE OBTAINED FROM CITY)
(1) 2%' CONTROL VALVE
(1) CONSTRUCTION METER
(1) RPBA
METER SUPPORT (BY CONTRACTOR)
NSF 61 SUPPLY HOSE
HYDRANT ON EXISTING WATER MAIN
TEMPORARY BLOW -OFF ASSEMBLY
(1) 2" GALVANIZED PIPE
(1) 2" 90° BEND
(1) 2" GATE VALVE
NEW DI WATER MAIN POLYPIG
TEMPORARY BLOCKING
POLYPIG STATION
(1) VERTICAL CROSS (MJxFL), SIZE TO MATCH WATER MAIN
(1) BLIND FLANGE WITH 2" TAP ON TOP OF CROSS
1 TEMPORARY BLOW -OFF ASSEMBLY
(1) BLIND FLANGE ON BOTTOM OF CROSS
(1) PLUG (MJ) ON END OF CROSS WITH TEMPORARY THRUST BLOCKING
NOTES:
1. THE BACKFLOW PREVENTION ASSEMBLY AND SUPPLY HOSE MUST BE DISCONNECTED DURING HYDROSTATIC PRESSURE TESTING OF THE
NEW WATER MAIN.
2. POLYPIG AND ALL DEBRIS SHALL BE REMOVED FROM SUMP OF VERTICAL CROSS VIA SANITARY METHOD PRIOR TO DISINFECTION OF NEW
WATER MAIN.
3. UPON REMOVAL OF POLYPIG, REMOVE TEMPORARY BLOW -OFF ASSEMBLY AND INSTALL 2" PLUG.
4. THE NEW WATER MAIN SHALL BE CONNECTED TO THE EXISTING SYSTEM ONLY AFTER NEW WATER MAIN IS POLYPIGGED, DISINFECTED
AND SATISFACTORY BACTERIOLOGICAL SAMPLE RESULTS ARE OBTAINED.
5. THE INTERIORS OF ALL PIPES AND FITTINGS TO BE USED IN FINAL CONNECTION MUST BE SWABBED OR SPRAYED WITH A 5-6% AVAILABLE
CHLORINE SOLUTION.
STD. PLAN - 300.7
+ PUBLIC WORKS APPROVED:
DEPARTMENT POLYPIGGING NEW WATER MAINS
6/28/202,:
mamn vaseuma DATE
Public Works Atlminls"ator
FINISHED GRADE 9" TO 12"
o ,
24" TO 30"
22 Y/2° i
MAIN
LOOP DOWN TO CENTERLINE OF WATER MAIN
TO PROVIDE SLACK IN SERVICE LINE TO METER
MATERIALS
z
J
IN UNIMPROVED ROW,
w
INSTALL METER BOX
p
AT PROPERTY LINE WITH
a
1"COPPER TAILPIECE
SIDEWALK
i
1
z
J
w CITY PRIVATE
a
0
a PIPING PIPING
12"
21" TO 30"
1" BALL CORPORATION STOP WITH BALL VALVE, AWWA TAPERED THREAD (CC) INLET, QUICK JOINT OUTLET,
OA
CORPORATION STOP
FORD FB1000-4-Q-NL OR A.Y. MCDONALD 74701BQ
OB
TUBING
1" TYPE "K" SOFT COPPER TUBING
1" SETTER, QUICK JOINT INLET AND OUTLET, PADLOCK WINGS ON INLET ANGLE BALL VALVE, SINGLE CHECK
(C
METER SETTER
VALVE ON OUTLET, FORD VBH74-15W-44-44-Q-NL, A.Y. MCDONALD 721-415WCQQ 44, OR MUELLER
B-24701-6AN, INSTALL CENTERED AND SQUARED IN METER BOX, PROVIDE ADAPTERS FOR 5/8"0/4" METERS
OD
WATER METER
AMI WATER METER WITH RADIO AND BATTERY UNIT, TO BE PROVIDED BY THE CITY
OE
METER BOX
METER BOX, ARMORCAST A6001946PCX18, WITH METER BOX LID, ARMORCAST A6001969RCI-H7, TO READ
"RENTON WATER"
OF
COUPLER AND PLUG
COUPLER (PACK JOINT x PACK JOINT), FORD C4#-4#-Q-NL, WITH 1" GALVANIZED PLUG IF SERVICE LINE TO
PROPERTY IS TO BE INSTALLED IN THE FUTURE
�G
GRAVEL
1 Y/4" WASHED GRAVEL
PUBLIC WORKS 1" WATER SERVICE
l8/2023 DEPARTMENT
DATE
NO.
STD. PLAN - 320.1
DATE
NOTES:
1. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF SAFETY YELLOW DTM ACRYLIC GLOSS OR ENAMEL PAINT.
2. PUMPER NOZZLE TO FACE ROADWAY OR AS DIRECTED BY RRFA.
3. A MINIMUM 3' RADIUS UNOBSTRUCTED WORKING AREA SHALL BE PROVIDED AROUND THE OUTSIDE OF THE HYDRANT.
COMPRESSION TYPE HYDRANT (SEE APPROVED MATERIALS LIST) WITH 6" MJ INLET WITH LUGS, 5 %4" MVO,
O
HYDRANT
1 Y4" PENTAGON OPERATING NUT, TWO (2) 2 %" NST HOSE NOZZLES, AND 4.875" SST PUMPER NOZZLE
EQUIPPED WITH 5" STORZ ADAPTER AND 1/8" STAINLESS STEEL CABLE, WITH EXTENSION IF NECESSARY.
OB
TEE
MAIN LINE TEE WITH 6" FLANGE SIDE OUTLET
OC
VALVE
6" GATE VALVE (FLxMJ)
OD
VALVE BOX
VALVE BOX AND LID PER STD PLAN 330.7
OE
PIPE
CLASS 52 DI, LENGTH TO FIT
OF
JOINT RESTRAINT
MECHANICAL JOINT RESTRAINT WITH CONCRETE BLOCKING OR (2) 3/4" CORTEN STEEL TIE RODS
O
GRAVEL
1 X" WASHED DRAIN ROCK, MINIMUM 1' ABOVE BOOT FLANGE WITH 8-MIL POLYETHYLENE SHEETING
AROUND TOP AND SIDES OF GRAVEL
O
CONCRETE BLOCK
MINIMUM 16"x8"x4" CONCRETE BLOCKS UNDER FIRE HYDRANT AND GATE VALVE
O
BLOCKING
CONCRETE BLOCKING PER STD PLAN 330.1
O
SHEAR BLOCK
4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT, SEE STANDARD DETAIL 310.2
O
PAVEMENT MARKER
BLUE REFLECTIVE PAVEMENT MARKER PER STD PLAN 310.3
STD. PLAN - 310.1
,+ PUBLIC WORKS
APPROVED:
FIRE HYDRANT ASSEMBLY
�^
DEPARTMENT
6/28/202.,7
wtha DATE
Publlc Works Atlminiztra[ar
90° BEND 45° BEND
CAP / PLUG
TEE
22 %2° BEND
11 Y4° BEND
B
v E
MINIMUM BEARING AREA
AGAINST UNDISTURBED SOIL (SF)
PIPE
PR(PSI)RE
O
O
O
O
O
SIZE
4
200
2/(1)
1/(NONE)
1/(NONE)
NONE
NONE
300
3/(2)
2/(2)
2/(1)
1/(1)
NONE
6
200
4/(3)
3/(2)
3/(1)
1M)
1/(NONE)
300
6/(4)
4/(3)
3/(2)
2/(1)
1/(NONE)
8r
200
7/(5)
5/(3)
4/(3)
2/(2)
1/(1)
300
11/(8)
8/(5)
6/(4)
3/(2)
2/(1)
10"
200
11/(8)
8/(6)
6/(4)
3/(2)
2/(1)
275
16/(11)
11/(7)
9/(6)
5/(3)
3/(2)
12"
200
16/(11)
11/(8)
9/(6)
5/(3)
3/(2)
250
24/(16)
17/(11)
13/(9)
7/(5)
4/(3)
14"
200
22/(13)
16/(11)
12/(8)
6/(4)
3/(2)
250
33/(22)
23/(16)
18/(12)
9/(6)
5/(3)
16"
200
29/(19)
21/(14)
16/(11)
8/(6)
S/(3)
225
32/(21)
23/(16)
17/(12)
9/(6)
5/(3)
18"
200
36/(24)
26/(17)
20/(13)
10/(7)
5/(4)
20"
200
45/(29)
32/(21)
24/(16)
13/(8)
24"
200
64/(43)
46/(30)
35/(23)
18/(12)
* VALUES BASED ON SAFE BEARING LOAD OF 2,000/(3,000) PSF
SOIL TYPE
MUCK OR PEAT
SOFT CLAY
SAND
SAND AND GRAVEL
CEMENTED WITH CLAY
HARD SHALE
SAFE BEARING LOAD
0
1,000
2,000
3,000
4,000
10,000
NOTES:
1. MINIMUM BEARING AREA MUST BE ADJUSTED FOR PIPE SIZE, PRESSURE, AND SOIL CONDITIONS.
2. FITTINGS SHALL BE POLYWRAPPED PRIOR TO POURING CONCRETE BLOCKING.
3. CONCRETE BLOCKING SHALL BE CAST IN PLACE AND SHALL HAVE A MINIMUM OF 0.25 SF BEARING AREA AGAINST THE FITTING.
4. CONCRETE BLOCKING SHALL BEAR AGAINST FITTINGS ONLY AND SHALL BE CLEAR OF JOINTS TO PERMIT TAKING UP OR DISMANTLING
JOINT.
5. CONTRACTOR SHALL INSTALL BLOCKING ADEQUATE TO WITHSTAND FULL HYDROSTATIC TEST PRESSURE AS WELL AS TO CONTINUOUSLY
WITHSTAND OPERATING PRESSURE UNDER ALL CONDITIONS OF SERVICE.
6. ALL CONCRETE SHALL BE MECHANICALLY MIXED. JOB SITE MIXING, HAND -MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT
ALLOWED.
7. IN MUCK OR PEAT, ALL THRUSTS SHALL BE RESTRAINED BY PILES OR TIE RODS TO SOLID FOUNDATION OR MUCK OR PEAT SHALL BE
REMOVED AND REPLACED WITH BALLAST OF SUFFICIENT STABILITY TO RESIST THRUST.
8. CONCRETE BLOCKING SHALL BE LEFT OPEN OR SHEETED FOR MINIMUM 24 HOURS.
STD. PLAN - 330.1
+ PUBLIC WORKS CONCRETE BLOCKING APPROVED:
�+ DEPARTMENT FOR HORIZONTAL FITTINGS 6/28/2(
maMn Pas[ucha DATE
Public Works Atlministratm
SURVEYED:
OTHERS
DESIGNED:
FLA WO SAINOTTI
DRAWN:
CHUCK FEMLING
CHECKED.
MICHAEL MOODY
REVISION BY DATE APPR APPROVED:
MICHAEL MOODY
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 19W
HORIZONTAL' HAD 1983/1991
DATUM
TESTING CONNECTION
POLYPIG STATION PER STD PLAN 300.7
VERTICAL CROSS (MJxFL)
(1) BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG
(1) BLIND FLANGE ON BOTTOM
(1) PLUG (MJ) WITH 2" TAP AND TEMPORARY BLOW -OFF ASSEMBLY
WITH TEMPORARY THRUST BLOCKING
101±
EXISTING WATER MAINF/////// ��o�o NEW DI WATER MAIN
- TEMPORARY BLOCKING
EXISTING TEE, CAP, PLUG,
OR DEAD END LINE,
DO NOT DISTURB BLOCKING
C)
co
N
C)(1)
0
N
U
FINAL CONNECTION
UPON COMPLETION OF POLYPIGGING, HYDROSTATIC TESTING,
AND DISINFECTION, REMOVE TEMPORARY THRUST BLOCKING
AND TEMPORARY BLOW -OFF ASSEMBLIES
FINAL CONNECTION BY CITY FORCES
(1) DI SPOOL
(1) LONG BODY DI SLEEVE (MJ)
oOoI [NEWDI WATER MAIN
NOTES:
1. ALL CONNECTIONS TO EXISTING WATER MAINS WILL BE CONDUCTED BY CITY FORCES AS
SPECIFIED IN SECTION 5-14.2 OF THE CITY OF RENTON WATER UTILITY CONSTRUCTION
STANDARDS
2. LONG BODY DI SLEEVE FOR CONNECTION FROM DI TO DI PIPE AND FROM DI TO Cl PIPE WITH
SAME OUTSIDE DIAMETER
3. LONG BARREL COUPLING FOR CONNECTION FROM DI TO Cl PIPE WITH DIFFERENT O.D. AND
FROM DI TO AC OR TO STEEL PIPE
STD. PLAN - 300.4
•I.-t PUBLIC WORKS CONNECTION TO WATER MAIN APPROVED:
�G DEPARTMENT EXISTING TEE OR END LINE CAP 6/28/2023
0
marcvastuma DATE
Publlc Works Atlminis[ra[or
PROJECT NO. 2008 1K
111010
o yfy p� CIVIL ENGINEERING
,�c,•��
LANDSCAPE ARCHITECTURE
PLANNING
• 41843 '� DESIGN SURVEYING
O GISTE9-'q
�`�SIQNAL
ENVti
12100 NE 195th St, Suite 300 Bothell, Washington 98011 425.885.7877
V
W-430503
CITY OF
RENTON
vAlliv
Planning/Building/Public Works Dept.
04/02/25
I\
IN COMPLIANCE WITH CITY OF RENTON STANDARDS O
Effluy:nlh
ENT ENGINEERING
04/17/2025
0
WATER UTILITY Aor, %7%
ABDOUL GAFOUR 03/06/2025
JONES RENTON SHORT PLA T W
3102 PARK AVE N, RENTON, WA 98056 FlELDBOOK:
PAGE. O DRAWING NO:
WA TER DETAILS C5, 32
SHEET: n� OF.
0
N
O
O
N
WE