HomeMy WebLinkAbout40.1 1`SY P CITY OF RENTON 'FIRE PREVENTION BUREAU ��`MEMORANDUM DATE: April 17, 2001 TO: Lesley Nishihira, Planner FVDM: Jim Gray, Assistant Fire Marshal sLBJECT: Fry Electronics, 900 Garden Av. MITIGATION ITEMSs 1. A fir tmitigation building of square 624.00 is footarequired based on $.52 per squ FIRE CODE REQUIREMENTS: 1. The preliminary fire now is 6000 GPM, one hydrant is required within 150 feet of the structure and five additional hydrants are required within 300 feet of the structure. 2. Separate plans and permits are required for the installation of the fire alarm and sprinkler systems. 3. Fire Department access roadways are required to within 150 feet of all portions of the building exterior. Roadways are a minimum 20 in width with a turning radius of 45 foot outside and 25 foot inside. 4. Provide a list of the flammable, combustible liquids and any hazardous chemical to be used or stored on site. Please feel free to contact me if you have any questions