HomeMy WebLinkAbout12Y a Gam' CITY OF RENTON FIRE PREVENTION BUREAU MEMORANDUM BATE: December 22, 2000 TO: Lesley Nishihira, Planner FROM: .Jim Gray, Assistant Fire Marshal f SUBJECT: Fry Electronics Store, N 8u' 8s G den Av N Fire Department Comments: 1. The preliminary fire now is 6000 GPM, one hydrant is required within 150 feet of the stricture and five additional hydrants are required within 300 feet of the structure. 2_ A fire mitigation fee of $78,624.00 is required based on $.52 per square foot of the building square footage_ 3_ separate plans and permit are required for the installation of fire alarm and sprinkler systems. 4_ Fire Department access roadways are required to within 150 feet of all portions of the building exterior_ Roadways are a minimum 20'in width with a turning radius of 45 foot outside and 25 foot inside. 5. Provide a list of the flammable, combustible liquids and any hazardous chemical to be used or stored on site_ Please feel free to contact me if you have any questions. _ i 1