HomeMy WebLinkAboutT-434302CO
i
C)
i
0
Lu
ABBREVIATIONS:
1 P
1 POLE (2P, 3P, 4P, ETC.)
A
AMPERE
AC
ABOVE COUNTER
ACLG
ABOVE CEILING
ADO
AUTOMATIC DOOR OPENER
AF
AMPFRAME
AFF
ABOVE FINISHED FLOOR
AFG
ABOVE FINISHED GRADE
AFI
ARC FAULT CIRCUIT INTERRUPTER
AHU
AIR HANDLING UNIT
AL
ALUMINUM
ALT
ALTERNATE
AMP
AMPERE
AMPL
AMPLIFIER
ANNUN
ANNUNCIATOR
APPROX
APPROXIMATELY
AQ-STAT
AQUASTAT
ARCH
ARCHITECT, ARCHITECTURAL
AS
AMP SWITCH
AT
AMP TRIP
ATS
AUTOMATIC TRANSFER SWITCH
AUTO
AUTOMATIC
AUX
AUXILIARY
AV
AUDIO VISUAL
AWG
AMERICAN WIRE GAUGE
BATT
BATTERY
BD
BOARD
BLDG
BUILDING
BMS
BUILDING MANAGEMENT SYSTEM
C
CONDUIT
CAB
CABINET
CAT
CATALOG
CATV
CABLE TELEVISION
CB
CIRCUIT BREAKER
CCTV
CLOSED CIRCUIT TELEVISION
CCT
CIRCUIT
CLG
CEILING
COMB
COMBINATION
CMPR
COMPRESSOR
CONN
CONNECTION
CONST
CONSTRUCTION
CONT
CONTINUATION OR CONTINUOUS
CONTR
CONTRACTOR
CONV
CONVECTOR
CP
CIRCULATING PUMP
CRT
CATHODE-RAY TUBE
CT
CURRENT TRANSFORMER
CTR
CENTER
CU
COPPER
DCP
DOMESTIC WATER CIRCULATING PUMP
DEPT
DEPARTMENT
DET
DETAIL
DIA
DIAMETER
DISC
DISCONNECT
DIST
DISTRIBUTION
DN
DOWN
DPR
DAMPER
DS
SAFETY DISCONNECT SWITCH
DT
DOUBLE THROW
DWG
DRAWING
EC
ELECTRICAL CONTRACTOR
ELEC
ELECTRIC, ELECTRICAL
ELEV
ELEVATOR
ELU
EMERGENCY LIGHTING UNIT
EM
EMERGENCY
EMS
ENERGY MANAGEMENT SYSTEM
EMT
ELECTRICAL METALLIC TUBING
EP
ELECTRIC PNEUMATIC
EQUIP
EQUIPMENT
EWC
ELECTRIC WATER COOLER
EXIST
EXISTING
EXH
EXHAUST
EXP
EXPLOSION PROOF
IC
INTERRUPTING CAPACITY
IG
ISOLATED GROUND
IMC
INTERMEDIATE METAL CONDUIT
INCAND
INCANDESCENT
IR
INFRARED
I/W
INTERLOCK WITH
J-BOX JUNCTION BOX
KV
KILOVOLT
KVA
KILOVOLT -AMPERE
KVAR
KILOVOLT -AMPERE REACTIVE
KW
KILOWATT
KWH
KILOWATT HOUR
LOC
LOCATE OR LOCATION
LT
LIGHT
LTG
LIGHTING
LTNG
LIGHTNING
LV
LOW VOLTAGE
MAX
MAG.S
M/C
MC
MCB
MCC
MDC
MDP
MFR
MFS
MH
MIC
MIN
MISC
MLO
MMS
MOA
MSP
MSBD
MT
MT.0
MTS
MTR
N.C.
NEC
NEMA
NFDS
NIC
NL
N.O.
NPF
NTS
OH
OL
PA
PB
PE
PED
PF
PH
PIV
PNL
PP
PR
PRI
PROJ
PRV
PT
PVC
PWR
QUAN
MAXIMUM
MAGNETIC STARTER
MOMENTARY CONTACT
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION CENTER
MAIN DISTRIBUTION PANEL
MANUFACTURER
MAIN FUSED DISCONNECT SW
MANHOLE
MICROPHONE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MANUAL MOTOR STARTER
MULTIOUTLET ASSEMBLY
MOTOR STARTER PANELBOARD
MAIN SWITCHBOARD
MOUNT
EMPTY CONDUIT
MANUAL TRANSFER SWITCH
MOTOR, MOTORIZED
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NON -FUSED SAFETY DISCONNECT SWITCH
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NORMAL POWER FACTOR
NOT TO SCALE
OVERHEAD
OVERLOADS
PUBLIC ADDRESS
PULL BOX OR PUSHBUTTON
PNEUMATIC ELECTRIC
PEDESTAL
POWER FACTOR
PHASE
POST INDICATING VALVE
PANEL
POWER POLE
PAIR
PRIMARY
PROJECTION
POWER ROOF VENTILATOR
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE (CONDUIT)
POWER
QUANTITY
RCPT
RECEPTACLE
FA
FIRE ALARM
REQD
REQUIRED
FABP
FIRE ALARM BOOSTER POWER
RM
ROOM
FACP
FIRE ALARM CONTROL PANEL
RSC
RIGID STEEL CONDUIT
FCU
FAN COIL UNIT
RTU
ROOF TOP UNIT
FIXT
FIXTURE
FLR
FLOOR
SC
SURFACE CONDUIT
FLUOR
FLUORESCENT
SEC
SECONDARY
FU
FUSE
SHT
SHEET
FUDS
FUSED SAFETY DISCONNECT SWITCH
SIM
SIMILAR
S/N
SOLID NEUTRAL
GA
GAUGE
SPEC
SPECIFICATION
GAL
GALLON
SPKR
SPEAKER
GALV
GALVANIZED
SP
SPARE
GC
GENERAL CONTRACTOR
SR
SURFACE RACEWAY
GEN
GENERATOR
SS
STAINLESS STEEL
G,GFI
GROUND FAULT CIRCUIT INTERRUPTER
SSW
SELECTOR SWITCH
GFP
GROUND FAULT PROTECTOR
S/S
STOP/START PUSHBUTTONS
GND
GROUND
STA
STATION
GRS
GALVANIZED RIGID STEEL (CONDUIT)
STD
STANDARD
GYP BD
GYPSUM BOARD
SURF
SURFACE MOUNTED
SW
SWITCH
HOA
HANDS -OFF -AUTOMATIC SWITCH
SWBD
SWITCHBOARD
HORIZ
HORIZONTAL
SYM
SYMMETRICAL
HP
HORSEPOWER
SYS
SYSTEM
HPF
HIGH POWER FACTOR
HT
HEIGHT
TEL
TELEPHONE
HTG
HEATING
TEL/DATA
TELEPHONE/DATA
HTR
HEATER
TERM
TERMINAL
HV
HIGH VOLTAGE
TL
TWIST LOCK
HVAC
HEATING, VENTILATING AND AIR
TR
TAMPER RESISTANT
CONDITIONING
T-STAT
THERMOSTAT
TTC
TELEPHONE TERMINAL CABINET
TV
TELEVISION
TVTC
TELEVISION TERMINAL CABINET
TYP
TYPICAL
UC
UNDER COUNTER
UE
UNDERGROUND ELECTRICAL
UG
UNDERGROUND
UH
UNIT HEATER
UNO
UNLESS NOTED OTHERWISE
UT
UNDERGROUND TELEPHONE
UTIL
UTILITY
UV
ULTRAVIOLET
V
VOLT
VA
VOLT-AMPERES
VDT
VIDEO DISPLAY TERMINAL
VERT
VERTICAL
VFD
VARIABLE FREQUENCY DRIVE
VOL
VOLUME
W
WATT
W/
WITH
WG
WIRE GUARD
WH
WATER HEATER
W/O
WITHOUT
WP
WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
z ANGLE
@ AT
♦ DELTA
FEET
INCHES
# NUMBER
0 PHASE
C CENTER LINE
P PLATE
BID SET
BP
4/10/25
PERMIT COMMENTS
BP
4/14/25
ADDENDUM 1
BP
4/17/25
ADDENDUM 2
BP
5/1/25
PERMIT COMMENTS
BP
5/21/25
■ ■ .
ELECTRICAL GENERAL NOTES:
GENERAL:
1. COORDINATE ELECTRICAL WORK WITH MECHANICAL,
ARCHITECTURAL, STRUCTURAL, CIVIL AND LANDSCAPE
WORK SHOWN ON OTHER CONTRACT DOCUMENTS.
PROVIDE ADDITIONAL OFFSETS FOR COORDINATED
INSTALLATION WHERE REQUIRED.
2. FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT
LOCATIONS ALONG WITH CONNECTION REQUIREMENTS
AND CONTROL WIRING PRIOR TO ROUGH -IN.
3. CONTRACTOR IS RESPONSIBLE FOR PROVIDE ALL LINE
VOLTAGE CIRCUITING AND CONNECTIONS TO
MECHANICAL EQUIPMENT, PACKAGED UNITS, CONTROL
PANELS, MOTOR STARTERS, MOTOR CONTROLLERS,
VARIABLE FREQUENCY DRIVES AND SIMILAR EQUIPMENT.
COORDINATE ADDITIONAL REQUIREMENTS WITH
CONTROLS CONTRACTOR.
4. COORDINATE EQUIPMENT CONNECTIONS WITH
MANUFACTURERS' CERTIFIED DRAWINGS.
5. COORDINATE ELECTRICAL, COMMUNICATIONS, AND
ELECTRONIC SAFETY AND SECURITY WORK PRIOR TO
INSTALLATION. EQUIPMENT ACCESS TAKES PRECEDENCE
OVER CONDUIT FOR AVAILABLE SPACE.
6. WHERE USED, THE TERM "PROVIDE" SHALL MEAN
"FURNISH AND INSTALL".
7. PROVIDE CONDUCTORS OPERATING AT 50 VOLTS OR
GREATER IN RACEWAY. PROVIDE METAL RACEWAY
WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB.
PROVIDE PVC RACEWAY BELOW THE FLOOR SLAB AND
UNDERGROUND RACEWAY OUTSIDE THE STRUCTURE.
8. CONDUIT AND WIRE IS NOT PERMITTED TO BE INSTALLED
BELOW FLOOR SLAB UNLESS INDICATED ON PLAN BY
DASHED CONDUIT.
9. LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY.
REMOVE DIRT, DEBRIS, EMPTY CARTONS, TOOLS,
CONDUIT AND WIRE SCRAPS AND MISCELLANEOUS
SPARE EQUIPMENT AND MATERIALS USED IN THIS
DIVISION OF THE WORK DURING CONSTRUCTION.
COMPONENTS SHALL BE FREE OF DUST, GRIT AND
FOREIGN MATERIALS AND LEFT AS NEW BEFORE FINAL
ACCEPTANCE OF WORK.
10. PERFORM WORK TO COMPLY WITH THE STANDARD
PRACTICES FOR GOOD WORKMANSHIP PUBLISHED BY
NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION
(NECA). COMPLY WITH THE LATEST ENFORCED EDITION
OF THE NATIONAL ELECTRICAL CODE (NEC), LOCAL
CODES, AMENDMENTS, AND ORDINANCES.
11. PERFORM ELECTRICAL WORK UNDER THE SUPERVISION
OF A LICENSED MASTER ELECTRICIAN. PROCURE
PERMITS AND LICENSES AND PAY FEES ASSOCIATED
WITH THIS WORK.
12. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING ALL
DOCUMENTATION REQUIRED TO CITY OF RENTON FOR
PERMITTING. COORDINATE WITH ENGINEER FOR ANY
ADDITIONAL DOCUMENTATION.
13. PROVIDE NEW, COMMERCIAL GRADE MATERIALS
FURNISHED FOR THIS PROJECT THAT ARE FREE OF
DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY UNO.
14. CONTRACTOR IS RESPONSIBLE FOR WIRING ELECTRICAL
ITEMS SHOWN ON DRAWINGS.
15. PROVIDE 4" MINIMUM CONCRETE BASES (HOUSEKEEPING
PADS) UNDER FLOOR MOUNTED ELECTRICAL
EQUIPMENT. THIS INCLUDES, BUT IS NOT LIMITED TO
SWITCHBOARDS, GENERATORS, TRANSFORMERS, AND
MOTOR CONTROL CENTERS. COMPLY WITH
REQUIREMENTS FOR EQUIPMENT BASES AND
FOUNDATIONS SPECIFIED IN DIVISION 03.
16. COORDINATE ATTACHMENTS TO STRUCTURE TO VERIFY
THAT ATTACHMENT POINTS ON EQUIPMENT AND
STRUCTURE CAN ACCEPT SEISMIC, WEIGHT, AND OTHER
LOADS IMPOSED.
17. MAINTAIN INDICATED FIRE AND SMOKE RATING OF
WALLS, PARTITIONS, CEILINGS, AND FLOORS AT
ELECTRICAL PENETRATIONS. SEAL PENETRATIONS WITH
FIRESTOP MATERIAL. PROVIDE MATERIAL IN
ACCORDANCE WITH ASTM E 814 AND UL 1479 3M OR
APPROVED. COMPLY WITH REQUIREMENTS SPECIFIED IN
DIVISION 07.
18. PROVIDE FIREBLOCKING AND DRAFT STOPPING AT
ELECTRICAL PENETRATIONS IN COMBUSTIBLE
CONCEALED SPACES PER THE INTERNATIONAL BUILDING
CODE.
19. REFER TO TYPICAL DETAILS PROVIDED IN THIS DRAWING
SET FOR EQUIPMENT INSTALLATION. CONTRACTOR IS
RESPONSIBLE FOR CONFORMANCE WITH DETAILS.
20. LOCATIONS AND SIZES OF FLOOR, WALL, AND ROOF
OPENINGS SHALL BE COORDINATED WITH OTHER
TRADES INVOLVED. INCLUDE IN THE COST OF
ELECTRICAL WORK, CUTTING, CORING, PATCHING AND
PAINTING OF EXISTING WALLS, CEILINGS, FLOORS AND
ROOFS AS REQUIRED TO ACCOMMODATE WORK AS
INDICATED IN THE ELECTRICAL CONTRACT DOCUMENTS,
UNLESS SPECIFICALLY SHOWN ON ARCHITECTURAL
DRAWINGS.
SURVEYED:
DESIGNED:
N S
DRAWN:
NS
CHECKED:
BP
APPROVED:
BP
SCALE:
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
21. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
SAFEKEEPING OF THEIR OWN PROPERTY ON THE JOB
SITE. OWNER ASSUMES NO RESPONSIBILITY FOR
PROTECTION OF PROPERTIES AGAINST FIRE, THEFT AND
ENVIRONMENTAL CONDITIONS.
22. CLEAN THE JOB SITE DAILY AND REMOVE FROM THE
PREMISES ANY DIRT AND DEBRIS CAUSE BY THE
PERFORMANCE OF THE WORK INCLUDED IN THIS
CONTRACT. BEFORE SUBSTANTIAL COMPLETION, CLEAN
EQUIPMENT, FIXTURES, EXPOSED CONDUIT AND SIMILAR
ITEMS.
23. PROVIDE EQUIPMENT THAT FITS INTO THE SPACE
ALLOTTED AND ALLOWS ADEQUATE ACCEPTABLE
CLEARANCE FOR INSTALLATION, REPLACEMENT, ENTRY,
SERVICING AND MAINTENANCE. COORDINATE WITH
OTHER TRADES TO ENSURE NO CONFLICT WITH
REQUIRED CLEARANCES.
24. BUILDING SPACE IS LIMITED. STRONG ATTENTION TO
DETAIL AND CARE MUST BE TAKEN WHEN DEVELOPING
SHOP DRAWING SO ROUTING IS COORDINATED WITH
OTHER DISCIPLINES.
25. MATERIALS WITHIN PLENUMS SHALL BE
NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
INDEX OF NOT MORE THAN 25 AND A SMOKE -DEVELOPED
INDEX OF NOT MORE THAN 50 WHEN TESTED IN
ACCORDANCE WITH ASTM E 84 OR UL 723.
EXISTING ELECTRICAL:
1. WORK SHALL BE PERFORMED IN A CLEAN AND
WORKMANLIKE MANNER. CARE SHALL BE EXERCISED TO
MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TO
OTHER AREAS OF THE BUILDING WHICH ARE TO REMAIN
IN OPERATION. ISOLATE WORK AREAS BY MEANS OF
TEMPORARY PARTITIONS AND/OR TARPS TO KEEP DUST
AND DIRT WITHIN THE CONSTRUCTION AREA.
2. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE
REUSED IN NEW SYSTEMS, EXCEPT WHERE INDICATED
AS BEING RELOCATED.
3. WHERE INDICATED, CONDUIT OR PORTIONS OF CONDUIT
SHALL BE REUSED. REFER TO DRAWING PLANS FOR
POINTS OF CONNECTIONS.
4. PROVIDE TEMPORARY SUPPORT OF EXISTING
ELECTRICAL SYSTEMS WHERE REQUIRED BY
DEMOLITION OR ALTERATION OF EXISTING STRUCTURE
DURING CONSTRUCTION. COORDINATE WITH GENERAL
CONTRACTOR AND PROVIDE ALL NECESSARY CONDUIT
AND EQUIPMENT SUPPORTS AND HANGERS TO MAINTAIN
INTEGRITY, SAFETY AND PROPER OPERATION OF
EXISTING ELECTRICAL SYSTEMS FOR THE DURATION OF
THE WORK.
DEMOLITION:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
COORDINATE DEMOLITION/INSTALLATION OF ELECTRICAL
SYSTEMS AND THOSE REQUIRING ELECTRICAL
CONNECTIONS TO MAINTAIN NEC REQUIRED
CLEARANCES, INCLUDED BY NOT LIMITED TO AREAS
ABOVE ACCESSIBLE CEILINGS.
2. COORDINATE WITH OTHER TRADES FOR PROPER
DEMOLITION OF EQUIPMENT. CONSULT THE DRAWINGS
OF OTHER TRADES OR CRAFTS TO AVOID CONFLICTS
WITH EQUIPMENT, ETC. RESOLVE CONFLICTS PRIOR TO
ROUGH -IN AND AT NO ADDITIONAL COST TO THE OWNER.
3. TAKE CAUTION IN DEMOLITION OF ELECTRICAL
EQUIPMENT.
4. CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF
ALL CONDUIT AND EQUIPMENT INDICATED ON DRAWINGS
INCLUDING ALL ASSOCIATED HANGERS, WIREMOLD,
WIRING, DEVICES, CONTROLS, AND APPURTENANCES
ASSOCIATED WITH EACH PIECE OF EQUIPMENT.
5. EXISTING CONTROL PATHWAYS MAY BE RE -USED.
COORDINATE CONTROLS DEMO WORK PRIOR TO
DEMOLITION.
6. WHERE EXISTING ITEMS PENETRATE A WALL OR ROOF,
CONTRACTOR SHALL PROVIDE INFILL AT (E)
PENETRATIONS THROUGH WALL/ROOF WITH LIKE
MATERIALS. PATCH & REPAIR TO MATCH SURROUNDING
SURFACES INCLUDING PAINT.
7. CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT OF
EXISTING ELECTRICAL EQUIPMENT WHERE REQUIRED BY
DEMOLITION OR ALTERATION OF EXISTING STRUCTURE
DURING CONSTRUCTION. COORDINATE WITH GC AND
PROVIDE NECESSARY SUPPORTS AND HANGERS TO
MAINTAIN INTEGRITY, SAFETY AND PROPER OPERATION
OF EXISTING ELECTRICAL SYSTEMS.
8. THE OWNER HAS THE RIGHT TO RETAIN OWNERSHIP OF
ANY MATERIALS BEING REMOVED. DELIVER ITEMS TO
THE OWNER'S REPRESENTATIVE AS INDICATED IN THE
CONTRACT DOCUMENTS. NOTIFY OWNER IN WRITING AT
LEAST 7 DAYS IN ADVANCE OF DEMOLITION.
CITY OF
,1N C.
wasgr
RENTON
oraAi, Planning/Building/Public Works Dept.
�� I�1 �,�
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
EDEVELOPMENT ENGINEERING
HBray 06/13/2025 %jl
RSD TRANSPORTATION EXPANSION
ELECTRICAL ABBREVIATIONS
AND NOTES
DATE:
05/21/25
FIELDBOOK:
PAGE:
DRAWING NO:
EOO2
SHEET: OF:
25 OF 30
0
T
T
C)
C)
m
N
,
u
0)
C)
C)
C)
C)
i
Nt
N
Ir
'i1
co
C)
C)
C)
i
N
Q
J
T-434302