LUMINAIRE SCHEDULE
CONSTRUCTION
LIGHT SOURCE
ELECTRICAL
PRODUCT
TYPE
DESCRIPTION
LENS/LOUVER
MOUNTING
LAMP
LUMENS DOWN
LUMENS UP
CCT
CRI
BALLAST/DRIVER
VOLTAGE
WATTS
EMERGENCY COMPONENT
MANUFACTURER
MODEL
NOTE
S1
POLE LIGHT
--
POLE
LED
13538 Im
0 Im
4000 K
80
REMOTE LED DRIVER, 0-10V
277 V
116
--
KIM LIGHTING
1 SA-WP9SA2-81 L-450-4K8-4W-SQ-UNV-BLT-SCH-S
POLE: 22.5' HIGH 8.5" SQUARE ALUMINUM POLE.
STANDARD CAP, CAST ALUMINUM SMOOTH ROUND
BASE.
S2
12' LIGHT COLUMN
--
BOLLARD
LED
10216 Im
0 Im
4000 K
80
REMOTE LED DRIVER, 0-10V
277 V
106
--
SELUX
MTRCL-12-4-4B30-40-BL-277-MS
ORIENT MOTION SENSOR PER DRAWINGS. INCLUDE
PHOTOCELL.
ELECTRICAL SITE PLAN
SCALER "=20'
i
!•
a
— — — — RIDGE
SERVICE BUILDING
ELECTRICAL ROOM
BID SET
BP
4/ 10/25
SURVEYED:
i
PERMIT COMMENTS
BP
4/14/25
DESIGNED:
2
ADDENDUM 1
BP
4/17/25
NS
s
ADDENDUM 2
BP
5/1/25
DRAWN:
NS
4
PERMIT COMMENTS
BP
5/21/25
CHECKEDBP
NO.
REVISION
BY
DATE
APPR
APPROVED:
BP
WAC 51-50-0429 EV CHARGING
INFRASTRUCTURE
OCCUPANCY TYPE
GROUP B
# OF STAFF PARKING STALLS
45
# OF ACCESSIBLE PARKING STALLS
1
EV CHARGING STATIONS (10%)
5
EV-READY PARKING SPACES (10%)
5
EV-CAPABLE PARKING SPACES (10%)
5
# OF EV CHARGING STATIONS
6
# OF EV-READY PARKING SPACES
6
# OF EV-CAPABLE PARKING SPACES
5
# OF ACCESSIBLE EV CHARGING PARKING SPACES
1
NOTES:
PROVISIONS SHALL APPLY ONLY TO DESIGNATED EMPLOYEE PARKING SPACES
1) FOR GROUPS
A, E, AND M OCCUPANCIES.
A MINIMUM 40-AMPERE DEDICATED 208/240V BRANCH CIRCUIT SHALL BE
2) INSTALLED FOR EACH
EV READY PARKING SPACE AND EV CHARGING STATION.
BRANCH CIRCUITS SHALL TERMINATE IN A JUNCTION BOX FOR EV READY PARKING
3) SPACES OR AT EV CHARGING STATIONS.
RACEWAY CAPABLE OF ACCOMODATING A 40-AMPERE DEDICATED 208/240V
4) BRANCH CIRCUIT SHALL TERMINATE IN A JUNCTION BOX FOR EACH EV-CAPABLE
PARKING SPACE.
4
p
\ o
�V \
O ��-- 1L1X --- --
O I 1L10 - — — — — — IT!
1L12
EL 1H1
p V - XFMR 1 L8X
_ 1L8
_I-Z----- 1L9
—1 . P_ p —
AL
Illlillllllllllllllll {IIIIIIIJ III I I IIIIIIIIIIIII Q II �
/ — all
dh
� ENLARGED SERVICE BUILDING ELECTRICAL ROOM
SCALE:
E301 I SCALE:1/8" = 1'-0"
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
CITY OF
,1N C. A�,
wasgr x o VR
RENTON
Planning/Building/Public Works Dept.
GENERAL NOTES:
T
T
1. BRANCH CIRCUITING INDICATED ON PLANS AND
C)
SCHEDULES IS BASED UPON EXISTING PLANS AND
C)
SITE OBSERVATION, CONTRACTOR TO FIELD VERIFY.
(v
2. EQUIPMENT SHOWN IN DIAGRAMMATIC. COORDINATE
U
EQUIPMENT LOCATION WITH ARCHITECTURAL,
STRUCTURAL, CIVIL, AND LANDSCAPING PRIOR TO
INSTALLATION.
3. PROVIDE RIGID STEEL SWEEPS FOR ALL
UNDERGROUND CONDUITS.
4. PROVIDE HANDHOLES AS REQUIRED FOR ALL POWER
AND LIGHTING CIRCUITS. SPLICE CONDUCTORS IN
HANDHOLES. REFER TO SCHEDULES ON SHEET E0.02
FOR ADDITIONAL INFORMATION.
5. PROVIDE ADDITIONAL PULL BOXES AS REQUIRED TO
0)
MINIMIZE TOTAL BEND RADIUS TO 270 DEGREES FOR
r'-
POWER CONDUCTORS AND 180 DEGREES FOR LOW
Q
VOLTAGE CABLING. SIZE PULL BOXES PER NEC.
O
C)
6. PROVIDE 1"C, 2#10, 1#10 EGC TO ALL NEW POLE
C)
LUMINAIRES.
N
Ir
FLAG NOTES:
a_
PROVIDE (1) 1-1/2"C, 2#1, 1#6 FROM EV
CHARGING VAULT TO EV CHARGING STATION.
2� PROVIDE (1) 1-1/2"C, 2#4, 1#10 FROM EV
CHARGING VAULT TO EV READY PARKING SPACE
HAND HOLE. PROVIDE STUB -UP AND CAP FOR
FUTURE EV CHARGING STATION.
PROVIDE (1) 1-1/2"C WITH PULL STRING TO EV
CAPABLE HANDHOLE. PROVIDE STUB -UP AND
CAP FOR FUTURE EV CHARGING STATION.
PROVIDE OLDCASTLE PRECAST 233-BL VAULT
WITH 23-2436P NON-SKID COVER FOR EV
CHARGING VAULT.
PROVIDE ROUGH -IN FOR A FUTURE POLE
MOUNTED SECURITY CAMERA. COORDINATE
MOUNTING HEIGHT WITH OWNER PRIOR TO
INSTALLATION. PROVIDE 1" CONDUIT FROM NEW
LIGHT POLE BASE TO EXISTING POLE BASE
DENOTED BY FLAG NOTE 7 AND INTERCEPT
EXISTING SECURITY CAMERA CONDUIT. PROVIDE
PULLSTRING IN NEW AND EXISTING CONDUIT
BACK TO MDF ROOM.
EXISTING LIGHT POLE.
77 EXISTING SECURITY CAMERA MOUNT ON LIGHT
POLE.
PROVIDE OFCI CARD READER AND CFCI
ELECTRIC LOCK MOUNTED ON GATE. SEE DETAIL
3/E9.01. PROVIDE CONDUIT TO EXISTING ACCESS
CONTROL GATE HARDWARE NEAR BUILDING.
PROVIDE AND ROUTE CABLING IN NEW AND
EXISTING CONDUIT BACK TO MDF ROOM.
INTEGRATE CARD READER AND ELECTRIC LOCK
INTO EXISTING BUILDING ACCESS CONTROL
SYSTEM. REFER TO PHOTOS ON SHEET E9.01
FOR ADDITIONAL INFORMATION.
CIRCUIT NEW LUMINAIRES TO EXISTING
LIGHTING CIRCUIT ON PANEL 1H1. INTERCEPT
AND EXTEND EXISTING CONDUIT AND
CIRCUITING FROM EXISTING LIGHT POLES TO
NEW POLE LOCATIONS.
10 PROVIDE (1) 3/4"C, 2#12, 1#12G FOR IRRIGATION
CONTROL CABINET CONNECTION.
11 LOCATE MOTION SENSOR/PHOTOCELL ON
SOUTH SIDE OF LUMINAIRE.
12 LOCATE MOTION SENSOR/PHOTOCELL ON
NORTH SIDE OF LUMINAIRE.
R_>
PROVIDE TRENCHING IN LANDSCAPING AREAS
AND BORING UNDER CONCRETE AND ROADWAYS
FOR LOW VOLTAGE PATHWAYS. REFER TO CIVIL
AND LANDSCAPING FOR ADDITIONAL
INFORMATION.
E�>
ROUTE CONDUIT FOR NEW ACCESS CONTROL
PATHWAY TO EXISTING ACCESS CONTROL
JUNCTION BOX ON EXISTING GATE. PROVIDE ALL
CONDUIT STRAPS/SUPPORTS FOR A SECURE
INSTALLATION. SEE PHOTOS ON E9.01 FOR
EXISTING GATE HARDWARE.
13>
ROUTE (1) 2"C FROM EV VAULT TO ELECTRICAL
ROOM FOR FUTURE DATA CABLING.
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
E
ELOPMENT ENGINEERING
HBray 06/13/2025
RSD TRANSPORTATION EXPANSION
ELECTRICAL SITE PLAN
DATE:
05/21/25
PAGE:
E301
SHEET: OF:
27 OF 30
T-434304
co
C)
C)
C)
N
Q
J