HomeMy WebLinkAboutT-434307SIZE CHART
POLE HT.
A
B
25'
72"
24"
SACK EXPOSED PORTION OF POLE
BASE WITH MATCHING GROUT TO
FILL VOIDS AND COVER FORM MARKS
COPPER EQUIPMENT GROUND CONDI
ATTACH TO INTERNAL LUG WELDED II`
OF POLE GROUNDED CONDUCTOR SH
SAME SIZE AND TYPE AS SUPPLY CON
2" SECURITY CE
(B)
DIAMETER OF POLE BASE SIZED AT
THE DIAMETER OF POLE BASE
CANOPY PLUS 2" ABOVE BEVEL.
TYPICAL POLE BASE DETAIL
SCALE: NONE
TYPICAL LIGHT AND POLES AS SPECIFIED
POLE GROUND LUG. TERMINATE EQUIPMENT
GROUNDING CONDUCTOR AND FIXTURE GROUND.
TERMINATE CONDUITS AT BASE OF HAND HOLE
ANCHOR BOLTS, NUTS, AND LEVELING NUTS BY
POLE MANUFACTURER. COORDINATE SIZE AND
SPACING WITH SUPPLIER.
BEVEL 2" AT 45 DEGREES
(2) #4 TIES AT 2" O.C. AT TOP
GRADE
GROUNDING ELECTRODE CONDUCTOR IN 1/2"C,
IRREVERSIBLE CONNECTION AT POLE GROUND LUG,
EXOTHERMIC WELD AT GROUND ROD. SEAL BELOW GRADE.
INSTALL 1/2" X 10'-0" COPPER GROUND ROD
REINFORCING RODS 4#4 VERTICAL WITH
2" MINIMUM COVER & #4 TIES AT 16" O.C.
THROUGH DEPTH OF BASE.
INSTALL ANCHOR BOLTS AS
RECOMMENDED BY POLE MANUFACTURER
CONDUIT(S)-REFER TO PLANS. FOR DIRECT
BURIED CABLE APPLICATIONS PROVIDE 90' DOWN
SWEEP WITH BUSHED ENDS AND SEALED.
CONCRETE POLE BASE
RECORD DRAWINGS
w
w NO. REVISION
FINISHED GRADE
BURIED IDENTIFICATION TAPE
UNDISTURBED EARTH
BACKFILL - PLACE AND COMPACT IN 8"
LAYERS
SAND
N]nTF.q-
1. CONDUIT SHALL HAVE A MINIMUM OF 36" OF COVER.
2. PROVIDE A MINIMUM OF 12" HORIZONTAL SEPARATION BETWEEN CONDUIT AND OTHER UTILITIES.
3. CONDUIT SHALL BE 4" SCHEDULE 40, LION.
4. COORDINATE WITH UTILITY COMPANIES FOR ALL REQUIREMENTS.
5. CONFORM TO ALL REQUIREMENTS INDICATED IN CIVIL DRAWINGS AND SPECIFICATIONS.
6. REFER TO SHEET E102 AND COMMUNICATION FLOOR PLANS FOR QUANTITY OF CONDUITS.
7. COORDINATE ROUTING WITH PLUMBING AND STRUCTURAL ELEMENTS. ROUTE CONDUITS BELOW FOOTINGS OR PROVIDE SLEEVES IN
FOOTINGS PER STRUCTURAL DETAILS.
TYPICAL DUCT BANK DETAIL
SCALE: NONE
nnizinin izninomini cr!E NOTES AND LANDSCAPING
NAL REQUIREMENTS.
E NOTES
E NOTES
NOTES:
1. COORDINATE WITH LANDSCAPE ARCHITECT/DRAWINGS FOR ADDITIONAL DETAILS.
2. GATE HARDWARE AND ACCESS CONTROLS SHALL UTILIZE THE FOLLOWING DISTRICT STANDARD PRODUCTS:
2.1. COMPATIBLE ELECTRIC STRIKE 9600-630 H.E.S.
2.2. SEE SPECIFICATIONS FOR CARD READER AND ADDITIONAL ACCESS CONTROL REQUIREMENTS.
3. HARDWARE SHALL BE MOUNTED AT ADA HEIGHT 42" AFG UNLESS NOTED OTHERWISE.
4. PROVIDE NEMA 3R LOCKABLE WEATHERPROOF ENCLOSURE SIMILAR TO EXISTING PHOTO FOR CABLE ROUTING.
5. PROVIDE BACK BOX AND CARD READER MOUNTED ON BACK SIDE OF WEATHERPROOF CABLE ENCLOSURE.
6. PROVIDE ALL CONDUIT STRAPS/SUPPORTS REQUIRED TO SECURELY MOUNT CARD READER/CABLE ENCLOSURE TO GATE.
7. PROVIDE ADDITIONAL HARDWARE AND ACCESS CONTROL COMPONENTS AS NEEDED TO ACCOMMODATE DISTRICT
STANDARDS AND ACCESS CONTROLS SHOWN ON LANDSCAPE DRAWINGS AND INSTALL A COMPLETE AND FULLY
FUNCTIONAL SYSTEM COMPATIBLE WITH CARD READER AND SPECIFIED LOCK CORES. SUBMIT ALL COMPONENTS FOR
APPROVAL.
8. ALL HARDWARE AND ACCESS CONTROL COMPONENTS SHALL BE RATED FOR EXTERIOR USE.
9. SEE SPECIFICATIONS FOR ACCESS CONTROL REQUIREMENTS.
GATE WITH PANIC HARDWARE DETAIL
SCALE:1/2" = V-0"
BP 11 1 /3/251 1 SURVEYED:
DESIGNED:
NS
DRAWN:
NS
CHECKED:
BP
BY DATE AP P R APPROVED:
BP
NOTES 1,2
SCALE:
CITY OF
ONE INCH DATUM RENTON
AT FULL SCALE Planning/Building/Public Works Dept.
IF NOT ONE INCH
SCALE ACCORDINGLY
NOTES:
1. ROUTE NEW ACCESS CONTROL CONDUIT FROM CABLE JUNCTION BOX TO NEW
GATE HARDWARE. SEE SHEET E3.01 FOR PATHWAY ROUTING. ROUTE CABLING
THROUGH NEW AND EXISTING PATHWAYS TO ACCESS CONTROL HEAD END IN MDF
ROOM AND INTEGRATE NEW CONTROLS AND PROVIDE RE -PROGRAMMING OF
EXISTING ACCESS CONTROL SYSTEM FOR A COMPLETE AND OPERABLE SYSTEM.
PROVIDE CONDUIT ROUTING PLAN TO OWNER, ENGINEER, CIVIL, AND LANDSCAPE
FOR APPROVAL PRIOR TO INSTALLATION.
2. PROVIDE ALL CONDUIT STRAPS/SUPPORTS REQUIRED TO SECURELY MOUNT CARD
READER/CABLE ENCLOSURE TO GATE.
3. SEE SPECIFICATIONS FOR ACCESS CONTROL REQUIREMENTS.
EXISTING GATE HARDWARE
SCALE: NONE
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
RSD TRANSPORTATION EXPANSION
ELECTRICAL DETAILS
DATE:
11/03/25
FIELDBOOK:
PAGE:
E901
SHEET: OF:
30 OF 30
O
T
T
'�
Y J
N
WA
0
0
N
rr
n
co
0
0
N
Q
J
RECORD DRAWING: THIS RECORD DRAWING HAS BEEN PREPARED BY METRIX ENGINEERS BASED ON AS -BUILT INFORMATION SUBMITTED, IN PART OR IN FULL, BY OTHERS. WHILE THIS INFORMATION IS BELIEVED TO BE RELIABLE, THE ARCHITECT AND ENGINEER HAVE NOT
VERIFIED THE ACCURACY AND/OR COMPLETENESS OF THE INFORMATION PROVIDED AND THUS SHALL NOT BE RESPONSIBLE FOR ITS ACCURACY, NOR FOR THE ERRORS OR OMISSIONS WHICH MAY HAVE BEEN INCORPORATED INTO THE RECORD DOCUMENT AS A RESULT.
T-434307