HomeMy WebLinkAboutT-434307SIZE
POLE HT.
A
B
8'-12'
36"
12"
13'-20'
42"
16'.
21'-30'
72"
24"
31'-40'
78"
30"
ROi
CAI
VEI
OW
irel
01
FILI
ANI
Wll
WE
SACK EXPOSED PORTION OF POLE
BASE WITH MATCHING GROUT TO
FILL VOIDS AND COVER FORM MARKS
COPPER EQUIPMENT GROUND CONDL
ATTACH TO INTERNAL LUG WELDED Il�
OF POLE GROUNDED CONDUCTOR SH
SAME SIZE AND TYPE AS SUPPLY CON
2" SECURITY Cf
(B)
DIAMETER OF POLE BASE SIZED AT
THE DIAMETER OF POLE BASE
CANOPY PLUS 2" ABOVE BEVEL.
TYPICAL POLE BASE DETAIL
SCALE:NONE
TYPICAL LIGHT AND POLES AS SPECIFIED
PROVIDE FLEXIBLE RACEWAY FROM
MOUNTING BRACKET TO RIGID CONDUIT
STUB UP ADJACENT HAND HOLE.
POLE GROUND LUG. TERMINATE EQUIPMENT
GROUNDING CONDUCTOR AND FIXTURE GROUND.
TERMINATE CONDUITS AT BASE OF HAND HOLE
ANCHOR BOLTS, NUTS, AND LEVELING NUTS BY
POLE MANUFACTURER. COORDINATE SIZE AND
SPACING WITH SUPPLIER.
BEVEL 2" AT 45 DEGREES
GRADE
GROUNDING ELECTRODE CONDUCTOR IN 1/2"C,
IRREVERSIBLE CONNECTION AT POLE GROUND LUG,
EXOTHERMIC WELD AT GROUND ROD. SEAL BELOW GRADE.
INSTALL 1/2" X 10'-0" COPPER GROUND ROD
REINFORCING RODS 4#4 VERTICAL WITH
2" MINIMUM COVER & #4 TIES AT 16" O.C.
THROUGH DEPTH OF BASE.
INSTALL ANCHOR BOLTS AS
RECOMMENDED BY POLE MANUFACTURER
CONDUIT(S)-REFER TO PLANS. FOR DIRECT
BURIED CABLE APPLICATIONS PROVIDE 90' DOWN
SWEEP WITH BUSHED ENDS AND SEALED.
CONCRETE POLE BASE
FINISHED GRADE
BURIED IDENTIFICATION TAPE
UNDISTURBED EARTH
BACKFILL - PLACE AND COMPACT IN 8"
LAYERS
SAND
NOTES:
1. CONDUIT SHALL HAVE A MINIMUM OF 36" OF COVER.
2. PROVIDE A MINIMUM OF 12" HORIZONTAL SEPARATION BETWEEN CONDUIT AND OTHER UTILITIES.
3. CONDUIT SHALL BE 4" SCHEDULE 40, UON.
4. COORDINATE WITH UTILITY COMPANIES FOR ALL REQUIREMENTS.
5. CONFORM TO ALL REQUIREMENTS INDICATED IN CIVIL DRAWINGS AND SPECIFICATIONS.
6. REFER TO SHEET E102 AND COMMUNICATION FLOOR PLANS FOR QUANTITY OF CONDUITS.
7. COORDINATE ROUTING WITH PLUMBING AND STRUCTURAL ELEMENTS. ROUTE CONDUITS BELOW FOOTINGS OR PROVIDE SLEEVES IN
FOOTINGS PER STRUCTURAL DETAILS.
TYPICAL DUCT BANK DETAIL
SCALE:NONE
"�E NOTES AND LANDSCAPING
NAL REQUIREMENTS.
E NOTES
NOTES 1,2
E NOTES
NOTES-
1 . COORDINATE WITH LANDSCAPE ARCHITECT/DRAWINGS FOR ADDITIONAL DETAILS.
2. GATE HARDWARE AND ACCESS CONTROLS SHALL UTILIZE THE FOLLOWING DISTRICT STANDARD PRODUCTS:
2.1. COMPATIBLE ELECTRIC STRIKE 9600-630 H.E.S.
2.2. SEE SPECIFICATIONS FOR CARD READER AND ADDITIONAL ACCESS CONTROL REQUIREMENTS.
3. HARDWARE SHALL BE MOUNTED AT ADA HEIGHT 42" AFG UNLESS NOTED OTHERWISE.
4. PROVIDE NEMA 3R LOCKABLE WEATHERPROOF ENCLOSURE SIMILAR TO EXISTING PHOTO FOR CABLE ROUTING.
5. PROVIDE BACK BOX AND CARD READER MOUNTED ON BACK SIDE OF WEATHERPROOF CABLE ENCLOSURE.
6. PROVIDE ALL CONDUIT STRAPS/SUPPORTS REQUIRED TO SECURELY MOUNT CARD READER/CABLE ENCLOSURE TO GATE.
7. PROVIDE ADDITIONAL HARDWARE AND ACCESS CONTROL COMPONENTS AS NEEDED TO ACCOMMODATE DISTRICT
STANDARDS AND ACCESS CONTROLS SHOWN ON LANDSCAPE DRAWINGS AND INSTALL A COMPLETE AND FULLY
FUNCTIONAL SYSTEM COMPATIBLE WITH CARD READER AND SPECIFIED LOCK CORES. SUBMIT ALL COMPONENTS FOR
APPROVAL.
8. ALL HARDWARE AND ACCESS CONTROL COMPONENTS SHALL BE RATED FOR EXTERIOR USE.
9. SEE SPECIFICATIONS FOR ACCESS CONTROL REQUIREMENTS.
BID SET
BP
4/10/25
PERMIT COMMENTS
BP
4/14/25
ADDENDUM 1
BP
4/17/25
ADDENDUM 2
BP
5/1/25
PERMIT COMMENTS
BP
5/21/25
REVISION
GATE WITH PANIC HARDWARE DETAIL
SCALE:1/2" = 1'-0"
SURVEYED:
DESIGNED:
NS
DRAWN:
NS
CHECKED:
BP
APPROVED:
BP
SCALE:
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
L4C.0,;_Y0
+0O ri ••
Planning/Building/Public Works Dept.
NOTES:
1. ROUTE NEW ACCESS CONTROL CONDUIT FROM CABLE JUNCTION BOX TO NEW
GATE HARDWARE. SEE SHEET E3.01 FOR PATHWAY ROUTING. ROUTE CABLING
THROUGH NEW AND EXISTING PATHWAYS TO ACCESS CONTROL HEAD END IN MDF
ROOM AND INTEGRATE NEW CONTROLS AND PROVIDE RE -PROGRAMMING OF
EXISTING ACCESS CONTROL SYSTEM FOR A COMPLETE AND OPERABLE SYSTEM.
PROVIDE CONDUIT ROUTING PLAN TO OWNER, ENGINEER, CIVIL, AND LANDSCAPE
FOR APPROVAL PRIOR TO INSTALLATION.
2. PROVIDE ALL CONDUIT STRAPS/SUPPORTS REQUIRED TO SECURELY MOUNT CARD
READER/CABLE ENCLOSURE TO GATE.
3. SEE SPECIFICATIONS FOR ACCESS CONTROL REQUIREMENTS.
EXISTING GATE HARDWARE
SCALE:NONE
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
EDEVELOPMENT ENGINEERING
HBray 06/13/2025
RSD TRANSPORTATION EXPANSION
ELECTRICAL DETAILS
DATE:
05/21/25
FIELDBOOK:
PAGE:
DRAWING NO:
E901
SHEET: OF:
30 OF 30
O
T
T
'C)
u J
N
C)
C)
C)
C)
N
rr
'i1
M
O
0
N
Q
J
T-434307