SUBJECT: REVIEW OF SUBMITTALS FOR TALBOT HELL WATER MAIN
REPLACEMENT PROJECT, PHASE 1
Mr. Buno:
We have received on May 21, 2004 your submittals dated May 21, 2004 for the materials to be
used on the City's stormwater and water main improvements portion of the above project. Our
review comments are:
DESCRIPTION
Specifications
STATUS
No.
1
Class 52, Ductile Iron Pipe
7-11.3(6) &
Approved
by Pacific States
9-30.1
2
Northtown Company
7-11.3(6) & 9-
Approved
30.1
3
Tyler DI Fittings (Mechanical
7-11.3(6)
Approved with conditions
Joint and Flanged Fittings only)
All DI pipes and fittings shall be
polywrapped with 8 mil. Polyethylene
plastic per AWWA C105
4
ROMAC tapping sleeve FTS 420
9-30.3(8)
Approved with conditions
with fusion epoxy coating 8-12
Tapping sleeve must have fusion epoxy -
mil
coat inside and outside.
Wet -tap must be done by City -approved
Wet -tap contractors.
5
Mueller Super Centurion Fire
9-30.5
Approved with conditions
Hydrant
Install per Renton Standard Details
shown on Standard Detail BR41. 5"
Storz adaptors are required.
6
Mueller Gate Valves -Resilient
9.30.3(1)
Approved with conditions
Seated (6", 8")
Use MJ x MJ, MJxFL, FLxFL valves
only
Install per Renton Standard Details
shown on Standard Detail BR46.
7
Olympic Foundry, Inc.
9.30.3(1)
Approved with conditions
Valve Box
Install per Renton Standard Detail
BR46.
8
Carsonite Utility Marker
9.30.3(5)
Approved with conditions
Valve Marker Posts
Install per Renton Standard Detail
BR46
HAFile Sys\WTR - Drinking Water Utility\WTR-27 - Water Project Files\WTR-27-3142 Talbot Hill Phase IWONTRACTOR
CORRESPONDENCE\Submittal Review.doc\r
F
June 1, 2004
Page 2
9
Harrington Permanent Hydrant
7-14.3,
Approved with conditions
Storz Adapter
9.30.5
Install per Renton Standard Detail
BR24
10
Crispin UL Series 1" Air&
9.30.3(7)
Approved with conditions
Vacuum Release Valve Assembly
Install per Renton Standard Detail
BR50
11
4"-ROMAC Coupling Style 501
Approved with conditions
Only use for connection between pipe
with dissimilar materials or different
Outside Diameters (OD's) - Use DI
(MJ) long body solid sleeves for all
other connections between similar pipe
materials and OD's.
12
Cerro Copper Water Tube,
7-15.3,
Approved with conditions
Type K
9.30.6
Install per Renton Standard Detail
BR41
13
Mueller Service Brass Fittings and
7-15.3,
Approved with conditions
Water Meter Setter
9-30.6
Install per Renton Standard Detail
BR41.
End connection types must conform to
Renton Standard Details for water
service installation, and for meter setter
ends.
14
Fogtite No. 2 Meter Box
7-11.3(6),
Approved with conditions
9-30.3(7)
Install per Renton Standard Detail
BR50
15
Mid -States Plastics, Inc. MSP
7-15.3
NOT Approved. l Z.q-1e,
Ductile Iron Covers
Revise and install per Renton Standard
Detail BR41 to equal MSCBC-i5R1!R
w/ reader lid and 1 5/8" drilled hole for
touchread pit lid.
16
Mid -States Plastics, Inc. MSP
7-15.3
NOT Approved.
Plastic Water Meter Box
Revise and install per Renton Standard
Detail BR41 toequal 44SBtTr-7M.
MSC,C,C.-132y -R
We have not received submittals on 6" and 8" Long Body type solid sleeve, and sources for
materials for select backfill, rocks for base and top course.
-2- Dy
Sincerely,\/
l
Rick Moreno, Project Manager Abdoul Gafour
Water Utility Water Utility Engineering Supervisor
rmoreno@ci.renton.wa.us agafour@ci.renton.wa.us
Phone: 425-430-7208 Phone: 425-430-7210
Zs q `a9 - 15 33
131x Z4N
"5277
6PLASTIC METERAL TO MID -STATES PLASTIC.
I CF SERIES MSBCFWITH 1.75" THICK DUCTILE
IRON DIAMOND PLATE COVER } WOW EQUAL TO MID -STATES
PLASTICS, INC. MSCBC R WITH READER LID AND 1-5/8"
DRILLED HOLE FOR CHREAD PIT LID (SEE -A)
13Z�-_fit
9" MIN
12" MAX
FINISH GRADE
..
z ¢ a
36" MIN COVER
0
N o v
NEW DUCTILE
IRON
WATERMAIN
I
Z
IN UNIMPROVED RIGHT OF
Z
J
WAY INSTALL METER BOX AT
PROPERTY LINE WITH 12"
w .
LONG COPPER TAILPIECE.
w .
a
a I
SIDEWALK
a.
a
TOUCHREAD WATER
METER TO BE
SUPPLIED BY THE
CITY
CITY
PIPING
—� 12
TYPE "K" SOFT
COPPER TUBING
PRIVATE
PIPING
IF SERVICE LINE TO HOUSE IS L3/4" OR 1"
TO BE INSTALLED IN THE FUTURE GALVANIZED
INSTALL FORD C14-33 OR 44 FIDT PLUG
x COMPRESSION COUPLING
zxa
0o
N 0 V
/ L LOOP DOWN TO CENTERLINE J3- Zit 7 Q - Z A
OF WATER MAIN TO
PROVIDE SLACK IN COPPER
COPPERSETTER FOR 5/8"x3/4" METER: FORD
SERVICE LINE TO METER.
VBH72-15W-44-33G, OR McDONALD BRASS: 21-215WCQ033, OR
ELLER: B-142 3/4 WITH ANGLE BALL VALVE ON INLET AND
SINGLE CH LVE ON OUTLET
CORPORATION STOP. FORD TAPERED THREAD
COPPERSETTER FOR 1" METER: FORD VBH72-15W-44-4_ 4G. OR
(CC). PACK JOINT
McDONALD BRASS: 21-415WCQQ44, OR MUELLER: 1427- L3- 24 }C , ZA
(3/4" F1000-3-G) OR AY MCDONALD 4701Q
BOTH INLET AND OUTLET WITH PACK JOINT WITH GRIP
(1" F1000-4-G) OR AY MCDONALD 4701Q
PADLOCK WINGS ON INLET ANGLE BALL VALVE AND SINGLE CHECK
VALVE ON OUTLET. ALL PACK -JOINT FITTINGS SHALL BE WITH
GRIPPER.
NOTE:
ALL METER BOXES INSTALLED WITHIN CONCRETE OR PAVED DRIVEWAYS SHALL BE
CAST-IRON EQUAL TO OLYMPIC FOUNDARY. EXPANSION JOINTS MUSH BE INSTALLED ON
BOTH SIDES OF METER BOX.
A— A DRILL 1-5/8" DIA. HOLE FOR AMR
(AUTOMATIC METER READ) TOUCHREAD DEVICE
L 2-1/2" MIN. FROM NEAREST
r — AND FRONT EDGE OF PIT LID
I
TYPICAL NOTE:
RIB I
l THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM
UNDERNEATH ERIB SPACING ALLOWS TO TIGHTEN AGAINST THEOPENSIDE OF MOR THE
NUT THAN
() 1 + " 1' % -t� `S ONE RIB.
3/4" & 1" WATER SERVICE
ADOPTED
v CITY OF RENTON
` + STANDARD PLANS
IST DATE: 04/04
DWG. NAME: BR41 SP PAGE: B106
Punch list for water main replacement -Talbot Hill W.T.R-27-3142
09/13/04 inspector -Ron McPhee (206) 999-1831
Meter boxes
Broken lids
1819 Davis ave so
1517 Morris ave so
1609 Morris ave so
1719 Morris ave so
610 S 15th
Drill hole for touch reads
628 S 15th
617 S15th
Install touch reads
617 S15th
1519 Talbot rd so
Fire Hydrants
1814 Davis ave so -install storz
All hydrants need blue reflectors installed in road
1814 Davis av so -need to dress gravel shoulder to drain into C.B
1608 Davis av so -need to expose hydrant foot valve and inline valve also clean ditch at
the end of the culvert also replace beauty bark around hydrant and meter box
631 s 15thst expose two-inch valve box
Talbot rd so STA 42+90 remove three valve boxes-STA 43+79 raise and center three
valve boxes in asphalt-STA44+13 eight -inch wet tap install valve nut extension
613s16thst-expose foot valve
Replace fog line—sl5thst at Smithers ave so and on Talbot rd so at Sol6thst
Asphalt
Seal all seams with AR4000
1523 Talbot road so install berm and repair grass
Fix low spot (bump) in transition at crossing of sI5thst at Morris ave so (most
western crossing)
S 15thst at Morris av so (most eastern intersection) replace asphalt in abandoned valve
box
ag- 6LAt1+5 ate, req)141r�
�' ✓ 11
�- 17— Oct
µ, Rom,
ram. t (l3 Sj l6 �4 s
Or tr e0 t a c-erJQ
j Ron McPhee - Talbot Hill. DOC Pagel
CITY OF RENTON
MAINTENANCE ADMINISTRATION SECTION
"WALK-THRU" INSPECTION PUNCH LIST"
DATE: 9/22/2004
TO: Kayren Kittrick
FROM: Bill Wressell
PROJECT NAME: Talbot Hill Water Main Replacement Phase I
INSPECTOR: Ron McPhee
Bill Wressell
1. 3 water valves low on S 18'b and Morris Av S
2. Asphalt bad on S 18' and Morris Av S
3. Asphalt bad on S 19`h and Morris Av S
4. Asphalt bad on S 17' and Morns Av S
5. Seal patches on Talbot Rd S
6. Seal patches on S 16`h St
7. Seal patch at 1632 Morris Av S
8. Seal across from 1523 Moms Av S
9. Seal Smithers Av S at S 15' St
10. Seal patch at 711 S 151' St
11. Seal patches at Shattuck Av S and S 19" St
JASTREET\PMS\WALKTHRU\Talbot Hill.DOC t
7
Kathy Keolker-Wheeler, Mayor
September 22, 2004
Dan Buno
Buno Construction, LLC
20219 99th Avenue SE
Snohomish, WA 98296
SENT VIA FAX 425-489-1533
CITY OF RENTON
PlanningBuilding/PublicWorks Department
Gregg Zimmerman P.E., Administrator
SUBJECT: TALBOT HILL PROJECT- FINAL WALK THROUGH
Dear Dan:
On September 13, 2004, the City provided a detailed punch list of items that require your
attention in order to obtain the City's acceptance of the project.
The remaining items listed below must be completed in order to close out this project:
1. Seal all seams within project area with AR4000 (S. 16th Street, and various
locations as described in the original punch list);
2. Remove three (3) gate valve boxes in shoulder along Talbot Rd. S (adjacent to
chain link fence and roadway shoulder);
3. Repair or replace Storz Adapter on fire hydrant fronting 613 S. 16th Street; and
4. Provide As -Built data for alignment of main, location of all gate valves, tee's, fire
hydrants and tie-in connections.
Your immediate attention to these items is appreciated. Please call me at (425) 430-7208
to set a time to evaluate all requests for change orders you have.
Sincerely,
If
Rick Moreno
Project Manager
cc: Abdoul Gafour, Water Utility Supervisor
Ray Sled, Water Maintenance Supervisor
H:\File Sys\WTR - Drinking Water Utility\WTR-27 - Water Project Files\WTR-27-3142 Talbot Hill Phase I\CONTRACTOR
CORRESPONDENCE\punch I ist.doc\RLM\tb
1055 South Grady Way - Renton, Washington 98055 R E N T O N
0 This paper contains 50 % recycled material, 30% post consumer AHEAD OF THE CURVE
f
UM09V,IJ_1_1'�a Complete Site Development Contracts -Commercial -Residential
RECEDED
NOTICE TO OWNER SEP' 0 2004
IMPORTANT: READ BOTH SIDES OF THIS NOTICE CAREFULLY CITYtrT�tI�,SRs T, N
PROTECT YOURSELF FROM PAYING TWICE
TO: City of Renton CETY OF REN T ON
DATE: September 7, 2004
FP C!.f= 4
RE: Talbot Hill Water Main Replacement — Phase 1C
Redmond, WA C!7" ;.,L:_, . ,
FROM: LAKERIDGE PAVING CO., LLC
At the request of: Buno Construction LLC
THIS IS NOT A LIEN: This notice is sent to you to tell you who is providing professional services,
materials, or equipment for the improvement of your property and to advise you of the rights of these
persons and your responsibilities. Also take note that laborers on your project may claim a lien without
sending you a notice.
OWNER/OCCUPIER OF EXISTING RESIDENTIAL PROPERTY
Under Washington law, those who famish labor, professional services, labor or equipment for the repair,
remodel, or alteration of your owner -occupied principal residence and who are not paid, have a right to
enforce their claim for payment against your property. This claim is known as a construction lien.
The law limits the amount that a lien claimant can claim against your property. Claims may only be made
against that portion of the contract price you have not paid to your prime contractor as of the time this
notice was given to you or three days after this notice was mailed to you. Review the back of this notice for
more information and ways to avoid lien claims.
COMMERCIAL AND/OR NEW RESIDENTIAL PROPERTY
We have or will be providing professional services, materials or equipment for the improvement of your
commercial or new residential project. In the event you or your contractor fail to pay us, we may file a lien
against your property. A lien may be claimed for all professional services, materials or equipment furnished
after a date that is sixty days before this notice was mailed to you, unless the improvement to your property
is the construction of a new single-family residence, than ten days before this notice was mailed to you.
Sender: LAKERIDGE PAVING CO., LLC
Address: PO Box 5430 — Kent, WA 98064
Telephone: (253) 631-8290
Brief description of professional services, materials, or equipment provided or to be provided:
ASPHALT PAVING.
�1
**IMPORTANT INFORMATION ON REVERSE SIDE** CC,
P.O. Box 5430, Kent, Washington 98064-5430 Phone: (253) 631-8290 Fax: (253) 630-9709
Bellevue Phone: (425) 453-0073 Tacoma Phone: (253) 535-6305
Contractor's License # LAKERPC050JM
P� m
CPS- Keay-oy-c3j
/�ivu,"I -IPA
IMPORTANT INFORMATION FOR YOUR PROTECTION
This notice is sent to inform you that we have or will provide professional services,
materials or equipment for the improvement of your property. We expect to be paid by
the person who ordered our services, but if we are not paid, we have the right to enforce
our claim by filling a construction lien against your property.
LEARN more about the lien laws and the meaning of this notice by discussing them
with your contractor, suppliers, Department of Labor and Industries, the firm sending you
this notice, your lender, or your attorney.
COMMON METHODS TO AVOID CONSTRUCTION LIENS There are
several methods available to protect your property form construction liens. The following
are two of the more commonly used methods.
DUAL PAYCHECKS (Joint checks): When paying your contractor for
service or materials, you may make checks payable jointly to the contractor and
the firms furnishing you this notice.
LIEN RELEASES: You may require your contractor to provide lien releases
signed by all the suppliers and subcontractors from whom you have received this
notice. If they cannot obtain lien releases because you have not paid them, you
may use the dual payee check method to protect yourself.
YOU SHOULD TAKE APPROPIATE STEPS TO PROTECT YOUR
PROPERTY FROM LIENS.
YOUR PRIME CONTRACTOR AND YOUR CONSTRUCTION
LENDER ARE REQUIRED BY LAW TO GIVE YOU WRITTEN
INFORMATION ABOUT LIEN CLAIMS. IF YOU HAVE NOT
RECEIVED IT, ASK THEM FOR IT.