HomeMy WebLinkAbout202140_004-008_5309-122_5309-123_Pre-Main_12 1 2011Customer Name
City of Renton, WA
Job Name
Sanitary Sewer
Rehabilitation
2011
Job No.
202140
Map #City
Renton, WA
Surveyed By (Operator)
Bravo Environmental
Location - Road Name
Sunset Blvd
Date
12/1/2011
Size (dia) x
8
Length
361
Shot-Seg Number
004-008
Start Manhole No.
5309-122
Finish Manhole No.
5309-123
Depth
0
Direction
Downstream
Media Number
01
Comments - General Material
Concrete
Job Type
Pre-Main
DOC ID: ITI/FRM-OPR-04 EFF.DATE: 12/01/03 APPROVAL: COMPANY MGT. REP.: ON-FILE
Dist. (ft.)Code Description Clock Remarks (Diameter, Intrusion, etc.)
0.0 MH Manhole 5309-122
28.0 CN Connection 10 Abandoned
55.0 CN Connection 10 Abandoned
55.0 RM Roots mass … % cross-sectional area loss 9 to 10 Lateral
85.0 RF Roots, Fine 9 to 3
91.0 RF Roots, Fine 9 to 3
108.0 DEG Debris, Grease 10 to 11
112.0 RF Roots, Fine 9 to 3
116.0 CN Connection 10 Abandoned
116.0 RF Roots, Fine 9 to 10 Lateral
118.0 RF Roots, Fine 8 to 4 Lateral
136.0 CC Circumferential Crack 3 to 9
140.0 RF Roots, Fine 4
147.0 CN Connection 10 Abandoned
147.0 RM Roots mass … % cross-sectional area loss 8 to 10 15%
161.0 RF Roots, Fine 9 to 3
179.0 RF Roots, Fine 8 to 4
183.0 DEG Debris, Grease 10 to 2 5%
188.0 RF Roots, Fine 8 to 9
214.0 CN Connection 10 Abandoned, root ball
216.0 RF Roots, Fine 10 to 4
216.0 CC Circumferential Crack 6 to 9
222.0 RF Roots, Fine 8 to 4
240.0 RF Roots, Fine 8 to 4
244.0 CN Connection 10 Abandoned, root ball lateral
279.0 RF Roots, Fine 8 to 4
288.0 RF Roots, Fine 9 to 3
292.0 DEG Debris, Grease 10 to 2
297.0 RF Roots, Fine 10 to 3
298.0 CN Connection 10 Abandoned, root ball
324.0 RF Roots, Fine 9 to 3
358.0 SWM Surface damage, wear medium 8 to 4 Surface aggregate visible, Finish
continuous defect 01
358.0 MH Manhole 5309-123
Page 1 of 1 Generated on 1/23/2012 at 3:02 PM by the PipeTech® TV inspection system.