HomeMy WebLinkAboutW-433505WATER UTILITY NOTES & SPECIFICATIONS
L/
M
1
N
1
1♦
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS
APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE
KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN
WRITING BY THE PUBLIC WORKS DEPARTMENT AT (425) 430-7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24
HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE
AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48-HOUR LOCATORS 800-424-5555.
4. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE -CONSTRUCTION MEETING.
5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR HORIZONTAL CONTROL SHALL BE NORTH
AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE
BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS
52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE PUSH -ON OR
MECHANICAL JOINT. BEDDING TO BE CLASS C.
7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA
C110/A21.10-87. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/421/4-90. IF FITTINGS ARE 3 TO 12 INCHES IN DIAMETER AND HAVE
MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI/AWWA C110-A21.10-87 OR ANSI/AWWA C153/A21.53-94. THREE (3) INCH
TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS, SHALL BE IN ACCORDANCE WITH ANSI/AWWA
C110/A21.10.87 OR A COMBINATION OF ANSI/AWWA C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT THE PORTION OF THE FITTING WITH A
MECHANICAL JOINT(S) MAY BE WITH ANSI/AWWA C153/A21.53-94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN
ACCORDANCE WITH AWWA C11O/A21.10-87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA SECTION 10-4.3 OF
ANSI/AWWA C11O/A21.10-87 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER.
8. GATE VALVES SHALL BE IRON BODY, BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O-RING STUFFING BOX (AWWA C500)
OR OF RESILIENT SEATED TYPE (AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI. GATE
VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380, M & H, OR APPROVED EQUAL.
9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE) CONFORMING TO
AWWA C-502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2-1/2 INCH HOSE NOZZLES WITH
NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN 6 THREADS PER
INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER 4.6263. HYDRANTS SHALL HAVE A 1-1/4 INCH
PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
10. THE TWO 2-1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN AND
PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER
TEST PRESSURES.
11. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH STORZ. STORZ ADAPTER SHALL BE
FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND TWO SET
SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET,
AND SHALL BE ATTACHED TO HYDRANT ADAPTER WITH 1/8 INCH, COATED, STAINLESS STEEL, AIRCRAFT CABLE.
12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43-655 SAFETY YELLOW OR APPROVED EQUAL.
13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS,LATEST REVISION.
15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12 INCHES AND
LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE LOWERED TO
CLEAR.
16. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS"
SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER
COATING ON THE REAR OF "PIG" ONLY.
17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION.
18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN
ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING
SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT
EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS & SPECIFICATIONS 7-11.3(11). THE LOSS IN
PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD.
19. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER SOLUTION.
DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED/INJECTED IN ACCORDANCE WITH
SECTION 7-11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED ABOVE.
20. A PRE -CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS REQUIRED
FOR SCHEDULING.
21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION.
23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER
APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON.
24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY APPROVED
WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION AND MATERIALS ARE TO
BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS.
25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR, AS WELL AS
THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN.
27. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF
COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL
SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2)
INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT.
29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE
PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH. *
30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC
PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS.
Know what's below.
Call before you dig.
t+ T . kr
@�
46972sv�
GISTVV�
�SSIONAL
07/21 /2025
T A C O M A SEATTLE
S P O K A N E T R I- C I T I E S
2215 North 30th Street, Suite 300 Tacoma, WA 98403
253.383.2422 TEL 253.383.2572 FAX www.ahbl.com WEB
CITY OWNED
AND MAINTAINED
O
O
z
a
W
r
W
z
3
J
}
U
H
W
W
a.
d
PRIVATELY OWNED AND MAINTAINED
MAXIMUM PIPE LENGTH FROM PROPERTY LINE
TO DDCVA MUST NOT EXCEED 50 FEET
•�4 4 CONCRETE BOLLARDS
•'� 03 10
a
z
0.l
z
W
f
W
a
C3
O
FT. MAX.
13 12 11
DDCVA MUST BE INSTALLED IMMEDIATELY AFTER
PIPE
PIPE PENETRATION THROUGH BUILDING FLOOR SLAB.
ROOM IN WHICH DDCVA IS LOCATED SHALL:
A. HAVE FLOOR DRAIN CONNECTED TO THE SANITARY SEWER SYSTEM.
B. HAVE A HEATING SYSTEM (40• F MIN. TEMP.) NO HEAT TAPE
C. NOT BE USED FOR STORAGE AROUND THE DDCVA
D. HAVE CLEARLY DELINEATED ACCESS WAYS TO DDCVA AND PIVs.
A RIGHT -OF -ENTRY AGREEMENT MUST BE GRANTED TO THE
CITY OF RENTON FOR INSPECTION OF THE DDCVA
AND METER.
SEPARATE FIRE SPRINKLER PLANS INCLUDING INSTALLATION OF DDCVA
MUST BE SUBMITTED TO RENTON REGIONAL FIRE AUTHORITY FOR
REVIEW AND APPROVAL.
A SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED.
1. MAIN LINE TEE (MJ x FL) WITH CONCRETE BLOCKING (WATER MAIN
LOCATED IN EASEMENT ON PRIVATE PROPERTY SHALL NOT BE MORE
THAN 50 FEET TO BUILDING)
2. BRANCH VALVE (FL x MJ) WITH VALVE BOX AND COVER
3. CLASS 52 DUCTILE IRON PIPE (4 INCH MINIMUM) ALL PIPE AND
FITTINGS SHALL BE RESTRAINED WITH SHACKLE RODS AND CONCRETE
THRUST BLOCKS PER NFPA AND AWWA STANDARDS.
4. POST -INDICATOR VALVE (MJ) WITH TAMPER SWITCH
5. 2-90• BENDS (FL x FL) WITH FLANGED DUCTILE IRON PIPE SPOOL
6. 18" LONG SPOOL (FL x PE)
7. FLANGE COUPLING ADAPTOR
8. APPROVED DDCVA ON MAIN LINE IN HORIZONTAL POSITION ONLY. (PER
LATEST DEPT. OF HEALTH APPROVED LIST OF BACKFLOW PREVENTION
DEVICES) BOTTOM OF DDCVA SHALL BE A MINIMUM OF 24 INCH ABOVE
FLOOR LEVEL AND NOT HIGHER THAN 3 FEET MAXIMUM. INSTALL 3
CONCRETE PADS OR ADJUSTABLE PIPE SUPPORT COLUMNS UNDER
DDCVA
9. 0 ' S & Y VALVES TO BE RESILIENT SEATED WITH TAMPER SWITCHES.
ADD WIRING IN ACCORDANcE WITH L & I
10. METERED 3/4 INCH BY-PASS DCVA - BY-PASS METER SHALL BE A
3/4 INCH "SENSUS-ECR" SR POSITIVE DISPLACEMENT METER EQUIPPED
ICE REGISTER WITH A REMOTE READ SENSOR PLATE MOUNTED ON THE
OUTSIDE OF THE BUILDING WALL (WALL MOUNT TYPE).
11. SWING TYPE GRAVITY CHECK VALVE, FLANGE WITH BALL DRIP IN VAULT
OR OUTSIDE BUILDING
12. 4"x 4" x 6" BULL, ELBOW, THREADED
13. UL LISTED FIRE DEPT. CONNECTION, UL LISTED BREAK AWAY CAPS,
LOCATE WITHIN 50 FEET MAXIMUM OF A PUBLIC FIRE HYDRANT.
AFTER FIELD INSTALLATION, MAIN DDCVA AND BY-PASS DCVA
MUST BE TESTED SATISFACTORILY BY A DEPARTMENT OF HEALTH
CERTIFIED BACKFLOW ASSEMBLY TESTER. TEST REPORT MUST BE
SUBMITTED TO CITY OF RENTON WATER UTILITY ENGINEERING
DEPARTMENT PRIOR TO ACTIVATION OF NEW LINE. INSTALL
BRASS Y4" FLARE TEST COCKS WITH Y4" FLARE CAPS
BUILDING WALL
U
to
N
I� a 10
0 8
Y
i 0
J
J
O
m
F
O 0
z
0
z_
0
J_
4 INCH
N 48 INCH
M
m
of
J
Y
W
0 w
z H
o N
s r
m N
2 W
w
W J
`L
L�
oa
F (n
PERIMETERS OF MINIMUM CLEARANCES
TO BE PAINTED ON FLOOR IN WHITE
ENAMEL PAINT STRIPE, WITH 2 INCH
STENCILED BLACK LETTERS TO SAY:
"DO NOT BLOCK ACCESS"
STANCHIONS BOLTED TO FLOOR.
Y STD. PLAN -360.5
INSIDE BUILDING INSTALL FOR 3" AND APPROVED:
PUBLIC WORKS
+ + DEPARTMENT LARGER DETECTOR DOUBLE CHECK
-� �FNSo� VALVE ASSEMBLY 6/28/2023MartinPastucha
P.blir W.,ksAdmi.istn l,.r DATE
3-INCH AND LARGER DETECTOR DCVA
INSIDE BUILDING INSTALL
2-1/2" FDC INLET WITH TWO-WAY FREE STANDING CHROME -
LOCKING FDIC CAPS PLATED FIRE DEPARTMENT CONNECTION
MANUFACTURED BY WITH 1" MIN. HIGH LETTERS "AUTO SPKR"
KNOX PRODUCTS
0 0 METAL ADDRESS PLATE WELDED ON POST OR
ATTACHED BY U-BOLT AND CHAIN, 24" MIN.
N ABOVE GRADE AND 1" MIN. HIGH LETTERS.
M 18" X 18" X 8"
CONC. BLOCK
GRADE
FIRE DEPARTMENT CONNECTION
NOT TO SCALE
CUT
FILL
3LOCK
T MIN RADIUS
jUNOBSTRUCTED WORKING AREA
AROUND OUTSIDE OF FIRE HYDRANT
TE SHEAR BLOCK
NOTE:
4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT WITH EXPANSION JOINT AT BACK OF SIDEWALK, FINISH TO MATCH SIDEWALK, ALL
CONCRETE SHALL BE MINIMUM 3,000 PSI AND SHALL BE MECHANICALLY MIXED - JOB SITE MIXING, HAND -MIXED CONCRETE, AND MOBILE
CONCRETE MIXERS ARE NOT ALLOWED.
`�T Y 0"
+ +
:FNT0P
FIRE HYDRANT ASSEMBLY
SHEAR BLOCK
FIRE HYDRANT SHEAR BLOCK
NOT TO SCALE
STD. PLAN - 310.2
Martin Pastucha
Public Works Administrator
FIRE PROTECTION NOTES
DATE
THE FIRE PROTECTION SYSTEM INCLUDING MATERIALS, SIZING, AND CONFIGURATION IS
SUBJECT TO A CONTRACTOR PROVIDED DESIGN BY A FIRE PROTECTION ENGINEER, AND AS
SUCH, THE FINAL DESIGN OF THE FIRE PROTECTION SYSTEM MAY DEVIATE FROM THE SYSTEM
SHOWN. THE FIRE PROTECTION SYSTEM AS SHOWN FROM THE MAIN LINE TO THE
CONNECTION AT THE BUILDING SPRINKLER IS INTENDED FOR LOCATION OF THE FIRE
HYDRANTS AND FIRE DEPARTMENT CONNECTION ONLY. CONTRACTOR'S BID SHALL REFLECT
THE CONDITIONS OF THE FIRE PROTECTION ENGINEER'S DESIGN. CONTRACTOR SHALL
COMPLY WITH ALL NATIONAL FIRE PROTECTION ASSOCIATION REQUIREMENTS AS SET FORTH
BY "NFPA 13", ITS AMENDMENTS, AND LOCAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO
ACQUISITION OF ALL PERMITS.
FIRE SPRINKLER NOTE
WHERE THE UNDERGROUND WATER SUPPLY TEES OFF TO SERVE ONLY A FIRE SPRINKLER
SYSTEM AND/OR FIRE HYDRANTS, A SEPARATE DETAILED PLAN MUST BE SUBMITTED AND
APPROVED BY THE FIRE MARSHAL PRIOR TO INSTALLATION.