Conditions for Permit C25000233
Engineering
1 ADD NOTE: POLE WILL NEED ASSET NUMBER. ASSET NUMBERS WILL BE PROVIDED BY
TRANSPORTATION MAINTENANCE ONCE INSTALLED. CONTRATOR SHALL INSTALL ASSET NUMBER PER
DETAIL 139.
Not Satisfied
2 REPEAT COMMENT: 1" DCVA REQUIRED FOR BACKFLOW PREVENTION. ADD DCVA TO PLANS.
Not Satisfied
3 REMOVE NOTE: PROVIDE NEW 3/4" CONDUIT TO CANTENARY POLES WITH (1) NEW CIRCUT FOR
RECEPTACLES, CIRCUITS FROM PANEL (E) E1 IN BUILDING ELECTRICAL ROOM, PLUS (2) 1" CONDUITS
FOR LOW VOLTAGE EQUIPMENT, ROUTING TBD
Not Satisfied
4 ADD NOTE TO PLANS: TIME CLOCK FOR CANTENARY LIGHTS SHALL BE ATTACHED TO SERVICE
CABINET AND MAINTAINED BY TRANSPORTATION MAINTENANCE.
Not Satisfied
5 NEW SPRINKLER AND IRRIGATION SHALL BE INSTALLED DOWNSTREAM OF THE EXISTING AND/OR
PROPOSED DCVA
Not Satisfied
6 ADD NOTE: 1" DCVA REQUIRED FOR BACKFLOW PREVENTION. SEE IRRIGATION PLANS.
Not Satisfied
7 ADD STANDARD DETAILS 119, 120, 124, 139 AND J013 TO PLANSET.
Not Satisfied
8 REVISE PLANS: 2" LIGHTING CONDUIT SHALL RUN FROM J BOX TO J BOX NEXT TO EACH POLE. 2"
CONDUIT WILL GO FROM J BOX TO EACH POLE. #8 WIRE SHALL BE INSTALLED FOR LIGHTING CIRCUT,
STANDARD PLANS 119, 120, J013 AND 124 WILL NEED TO BE FOLLOWED FOR LIGHTING SYSTEM.
Not Satisfied
9 ADD NOTE: EXISTING 1-INCH IRRIGATION METER PER CITY RECORDS
Not Satisfied
Page 1 of 2
10 VERIFY THAT DRINKING FOUNTAIN IS CONNECTING TO DOMESTIC WATER SUPPLY AND NOT TO
LANDSCAPE IRRIGATION LINE. REVISE AS NECESSARY.
Not Satisfied
11 ADD NOTE TO PLANS: USE THE SAME 2 INCH CONDUIT THAT THE LIGHTING RUNS IN.
Not Satisfied