HomeMy WebLinkAboutT-433403PIAZZA LIGHTING SEQUENCE OF OPERATIONS SPACE TYPE �O �QG `O� �� JQ �� BOG O�� �' O�� O�' DESCRIPTION O� �Q GG �O G �yJ �0 ��� O� G�� O��C, 0���GO EXTERIOR LIGHTING PHOTOCELL TURNS LIGHTS ON/OFF. TIMECLOCK PROVIDES ADDITIONAL AFTER HOURS CONTROL. PIAZZA X 50 fc T1 X L1 X MANUAL CONTROLS TO ALLOW FOR MANUAL OVERRIDE. SCENE CONTROL FOR GOBO PROJECTOR FIXTURE HEADS. LOGAN STREET CATENARY X 50 fc T1 X L1 PHOTOCELL TURNS LIGHTS ON/OFF. TIMECLOCK PROVIDES ADDITIONAL AFTER HOURS CONTROL. MANUAL CONTROLS TO ALLOW FOR MANUAL OVERRIDE. SEE SPECIFICATION SECTION 26 0993 FOR DEFINITIONS & OTHER REQUIREMENTS LIGHTING SEQUENCE OF OPERATIONS NOTES 1. ALL LIGHTING CONTROLS WHICH REDUCE LIGHTING POWER SHALL MAINTAIN A REASONABLY UNIFORM ILLUMINATION PATTERN. 2. BUILDING IS DESIGNATED LIGHTING ZONE '2' FOR THE PURPOSES OF EXTERIOR LIGHTING CONTROL, AS DESCRIBED IN WSEC TABLE 405.5.3(1). DIMMING REQUIRED LUMINAIRES IN THIS SPACE SHALL BE PROVIDED WITH DIMMABLE DRIVERS. DAYLIGHT RESPONSE AUTOMATICALLY RAISE OR LOWER LIGHT OUTPUT TO THE MAXIMUM LIGHT LEVELS LISTED IN THE DAYLIGHT ZONES UNTIL LIGHT FIXTURES ARE EITHER TURNED 'ON' TO 100% LIGHT OUTPUT OR 'OFF'. DAYLIGHT CONTROLS ARE TO BE PROGRAMMED SUCH THAT MANUAL OVERRIDE CAPABILITIES WILL NOT BE PERMITTED OTHER THAN A REDUCTION OF LIGHT OUTPUT FROM THE LEVEL ESTABLISHED BY THE DAYLIGHT RESPONSE CONTROLS. FOR EXTERIOR LIGHTING, PHOTOCELLS SHALL BE PROGRAMMED TO AUTOMATICALLY TURN LUMINAIRES 'ON' TO 100% LIGHT OUTPUT AT DUSK, AND AUTOMATICALLY TURN LUMINAIRES 'OFF' AT DAWN. TIMECLOCK T1 BUSINESS + EVENING AFTER HOURS PHOTOCELL CONTROLS LUMINAIRES DURING THIS TIME. AUTOMATICALLY TURN LUMINAIRES'OFF.' LOCAL CONTROLS L1 TURN LUMINAIRES'ON' TO 100% LIGHT OUTPUT (UNLESS OTHERWISE NOTED) AND TURN LUMINAIRES'OFF'. SCENE CONTROL LUMINAIRES IN THIS SPACE HAVE SET SCENES. VERIFY ALL SCENE SETTINGS WITH OWNER PRIOR TO PROGRAMMING. TIMECLOCK HOURS SCHEDULE 1 DAY OF WEEK BUSINESS HOURS EVENING HOURS AFTER HOURS MONDAY - FRIDAY 7:00 AM - 6:59 PM 7:00 PM - 10:59 PM 11:00 PM - 6:59 AM SATURDAY - SUNDAY 8:00 AM - 3:39 PM 4:00 PM - 11:59 PM 12:00 AM - 7:59 AM TIMECLOCK HOURS SCHEDULE NOTES 1. VERIFY ALL TIMECLOCK SCHEDULES AND SCENE SETTINGS WITH OWNER PRIOR TO PROGRAMMING. LOAD CLASSIFICATIONS AS LISTED IN THE LOAD SUMMARY ON PANELBOARD SCHEDULES CLASSIFICATION DESCRIPTION CONTINUOUS LOADS WHICH ARE LIKELY TO RUN CONTINUOUSLY FOR OVER 3 HOURS LIGHTING 125% MOTOR 125% OF LARGEST MOTOR, PLUS 100% OF ALL OTHER MOTORS NON -CONTINUOUS 100% RECEPTACLE 100% OF FIRST 10kVA, PLUS 50% OF ALL LOAD ABOVE 10kVA (NEC 220.44) EXAMPLES HEAT TRACE INTERIOR LIGHTING EXTERIOR LIGHTING PUMPS FANS CONVENIENCE RECEPTACLES CODES 2021 INTERNATIONAL BUILDING CODE - WAC 51-50 2023 NATIONAL ELECTRICAL CODE (NFPA 70) 2021 INTERNATIONAL EXISTING BUILDING CODE - WAC 51-50-4800 2021 WASHINGTON STATE ENERGY CODE (WSEC) ENERGY CODE EXISTING LIGHTING CONTROLS TO REMAIN. CONTROLS FOR ALL NEW EXTERIOR FIXTURES SHALL MEET WASHINGTON STATE ENERGY CODE REQUIREMENTS FOR EXTERIOR LIGHTING POWER ALLOWANCES AND CONTROLS: - PHOTOCELL FOR AUTOMATIC SHUTOFF WHEN DAYLIGHT IS PRESENT - TIMECLOCK PROGRAMMED FOR BUSINESS HOURS, AFTER HOURS, AND EVENING. PER WSEC FOR EXISTING BUILDINGS (C503.6.1) "ALTERATIONS THAT REPLACE 20 PERCENT OR MORE OF THE TOTAL INSTALLED WATTAGE OF EXTERIOR LUMINAIRES SHALL COMPLY WITH SECTIONS WITH SECTIONS C405.4 and C405.5. WHERE ... LESS THAN 20 PERCENT OF THE INSTALLED EXTERIOR WATTAGE IS REPLACED, THE INSTALLED LIGHTING WATTAGE SHALL BE MAINTAINED OR REDUCED." FINAL LOAD CALCULATIONS INDICATE TOTAL ADDED FIXTURE WATTAGE IS LESS THAN 20 PERCENT OF THE TOTAL SITE LIGHTING POWER, AND REDUCES THE TOTAL SITE LIGHTING POWER: - EXISTING EXTERIOR LIGHTING POWER (PRIOR TO ALTERATION): 7160 VA - PROPOSED NEW EXTERIOR LIGHTING ADDITION: 1419 VA (19.8%) - TOTAL PROPOSED NEW EXTERIOR LIGHTING POWER: 3319 VA SITE EXTERIOR LIGHTING ZONE: ZONE 2 PIAZZA LIGHTING DESIGN CRITERIA NORMAL LIGHTING: CRITERIA COORDINATED WITH ARCHITECT ON 11/22/2024. SPACE E (AVG HORIZONTAL ILLUMINATION AT FLOOR) PIAZZA 2 FC LOGAN ST CATENARY 3.8 FC EGRESS AND EMERGENCY LIGHTING: EXISTING INSTALLATION DOES NOT INCLUDE ANY BACKUP POWER FOR SITE LIGHTING. PIAZZA LIGHTING FIXTURE SCHEDULE FIXTURE LUMEN NUMBERED DESCRIPTION VOLTAGE LOAD LAMP COLOR MOUNTING MANUFACTURER MODEL TYPE OUTPUT - NOTES 1 (E) A2 DOUBLE HEAD POLE MOUNTED LIGHT (12') 240 V 200 W METAL POLE MOUNTED HALIDE - 1 (E) A3 DOUBLE HEAD POLE MOUNTED LIGHT (16') 240 V 200 W METAL POLE MOUNTED LINEAR LIGHT TUBE 120 V 300 W HALIDE METAL RECESSED - 1 (E) C - - HALIDE (N) F1 MAST POLE MOUNTED FIXTURE 120 V 39 W LED 4500 3000K POLE MOUNTED SELUX OLIVIO GRANDE 2 (N) F1A MAST POLE MOUNTED PROJECTOR 120 V 49 W LED - 6500K POLE MOUNTED SELUX OLIVIO GRANDE GOBO PROJECTOR 2 (N) F2 CATENARY FIXTURE 240 V 43 W LED 3645 3000k CATENARY HESS PEN380X 30K DIM UNV T5 3 NUMBERED NOTES: 1. EXISTING LIGHT FIXTURE DATA BASED ON PIAZZA AS-BUILTS DATED 11/7/2000. 2. FIXTURES MOUNTED ON 18' POLE. EACH POLE HAS (3) FIXTURE HEADS + (2) PROJECTOR HEADS. 3. 240V SINGLE PHASE CONNECTION REQUIRED FOR POWER FROM UTILITY SERVICE CABINET. PROVIDE CIRCUITS IN SCHEDULE 80 PVC, 2" MINIMUM, PER CITY OF RENTON. COORDINATE ALL CIRCUITING AND INSTALLATION REQUIREMENTS WITH CITY OF RENTON AND WORLD CUP LEGACY SQUARE PROJECT DESIGNERS. UP SURVEYED: SCALE: VERTICAL: NAVD 1988 DESIGNED: NTS HORIZONTAL: NAD 1983/1991 1Arup191 US, Inc. Call 811 DRAWN: 1191 Second Avenue Suite 400 � oNE INCH DATU M Seattle A 981258 F + 1 206 749 0665 • two business days IF NOT L SC LE CHECKED: before you digINCH N O. REVISION BY DATE I AP P R I APPROVED: SCALE ACCORDINGLY q 0 CITY OF RENTON Planning/Building/Public Works Dept. T-433403 IN COMPLIANCE WITH CITY OF RENTON STANDARDS DEVELOPMENT ENGINEERING % �IL TRANSPORTATION OPERATION msippo 08/13/2025 CBarnes 08/15/2025 RENTON MARKET & PIAZZA CIVIL CONSTRUCTION PERMIT ELECTRICAL - DESIGN CRITERIA AND LOAD CALCULATIONS - PIAZZA 7 / 16 / 2025 PAGE DRAWING NO: E0.03 SHEET: 5OF: 4 61