Loading...
HomeMy WebLinkAboutRSD Trasportation Expansion - Contech No. 825125 Filterra MemoContech Engineered Solutions LLC 9025 Centre Pointe Drive, Suite 400 West Chester, OH 45069 Phone: (513) 645-7000 www.ContechES.com Sascha Eastman Jacobson Consulting Engineers sascha@jacobsonengineers.com Re: RSD Transportation Expansion, Contech No. 825125 Dear Sascha Eastman: This correspondence provides information relating to the Filterra System sequence number 10 in the above referenced project. Due to existing site conditions, the outlet pipe does not connect with the current Filterra elevations. To adjust, the proposed solution is to raise the outlet on the Filterra unit 4”, leaving 4” of standing water within the Filterra unit. Raising the outlet pipe up 4” will not affect the flow of water through the Filterra media as the standing water elevation is below the media layer, within the underdrain stone. The Filterra media’s ability to meet water quality standards will not be affected by raising the outlet elevation. This acknowledgement expressly incorporates by reference Contech’s standard terms and conditions of sale. A copy of which can be viewed here https://www.conteches.com/cos. If there are any questions, please feel free to contact me. Regards, Dan Dodson, Biofiltration Product Manager Contech Engineered Solutions, LLC